and Maintenance
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
December 2015
RT-SVX49B-EN
Introduction
Read this manual thoroughly before operating or servicing
this unit.
WARNING
NOTICE
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being undertaken
could result in death or serious injury. Technicians, in
order to protect themselves from potential electrical,
mechanical, and chemical hazards, MUST follow
precautions in this manual and on the tags, stickers,
and labels, as well as the instructions below:
Before installing/servicing this unit, technicians
MUST put on all Personal Protective Equipment (PPE)
recommended for the work being undertaken.
ALWAYS refer to appropriate MSDS sheets and OSHA
guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.
RT-SVX49B-EN
Introduction
Copyright
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
RT-SVX49B-EN (3 Dec 2015)
RT-SVX49B-EN
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warnings, Cautions, and Notices . . . . . . . . 2
Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Creating a Custom Graph . . . . . . . . . . . . . . .24
Standard Graphs . . . . . . . . . . . . . . . . . . . . . .27
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Communication . . . . . . . . . . . . . . . . . . . . . 5
Screen characteristics . . . . . . . . . . . . . . . . 5
Touchscreen Guidelines . . . . . . . . . . . . . . . . 5
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Supported Languages . . . . . . . . . . . . . . . . . . 7
Screen Overview . . . . . . . . . . . . . . . . . . . . . . 8
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Display Settings Screen . . . . . . . . . . . . . . . .31
Language . . . . . . . . . . . . . . . . . . . . . . . . . .35
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Active Alarms . . . . . . . . . . . . . . . . . . . . . . . .
Historic Alarms . . . . . . . . . . . . . . . . . . . . . . .
Viewing Active and Historic Alarms . . . . .
Alarm Icons . . . . . . . . . . . . . . . . . . . . . . . . . .
Sorting Alarms . . . . . . . . . . . . . . . . . . . . . . .
11
11
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . .37
Identifying and Diagnosing Issues . . . . . . .37
12
12
13
13
Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Custom Reports . . . . . . . . . . . . . . . . . . . . . . 14
Creating a Custom Report . . . . . . . . . . . . 14
Editing a Custom Report . . . . . . . . . . . . . 16
About . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
System Report . . . . . . . . . . . . . . . . . . . . . . . 18
Economizer/Ventilation Report . . . . . . . . . 19
4
RT-SVX49B-EN
Do NOT use:
Voyager
Precedent
a screwdriver
a pen
a pencil point
Hardware
TheTracerTD-5 is a durable touchscreen display that is
designed to operate in both indoor and outdoor
environments.TheTD-5 display utilizes a standard 75mm
VESA mounting pattern for installation. Alternatively, it
can be installed with a user-supplied VESA mount.
Power
TheTracerTD-5 display is powered by 24 VAC or 24 VDC
and requires 21 VA power, which it receives through a
power cable.The display is typically connected to J10 of
the RTRM Module, but it can also be powered from an
alternate power source.
Communication
RS-485 communication is provided to theTD-5 through
the RTRM J10 connector.
Screen characteristics
The 5-inch WVGA 800 x 480 resolution touch-sensitive
color screen is LED backlit, which enables viewing in poor
light conditions including outdoor usage (with the
exception of direct sunlight).
NOTICE:
TD-5 Damage!
TD-5 does NOT have a UV-resistant touchscreen and
must be mounted out of direct sunlight. Failure to
follow instructions could result in TD-5 damage.
Touchscreen Guidelines
The touch screen registers the downward pressure of a
touch. Light, quick, yet deliberate touches are most
effective.Touching with more pressure has no effect.
Recommended tools to use:
finger
thumb
pencil eraser
RT-SVX49B-EN
Dimensions
147,0
[5 . 8 ]
42,1
[1 . 7 ]
32,0
[1 . 3 ]
154,0
[6 . 1 ]
115,3
[4 . 5 ]
106,4
[4 . 2 ]
RT-SVX49B-EN
Storage
temperature:
Operating
temperature:
Mounting weight:
Environmental
rating
(enclosure):
Display color
Agency Compliance
Supported Languages
TheTD-5 display supports 26 built-in languages. For help
on how to select a specific language for the display, see
Language, p. 35.
Arabic
Chinese (Simplified)
Chinese (Traditional)
Czech
Dutch
English
French
French Canadian
German
RT-SVX49B-EN
Greek
Hebrew
Hungarian
Indonesian
Italian
Japanese
Korean
Norwegian
Polish
Portuguese (Brazil)
Portuguese (Portugal)
Romanian
Russian
Spanish (Mexico)
Spanish (Spain)
Swedish
Thai
Screen Overview
There are three distinct areas on theTD-5 screens:
Figure 1.
Main display
area
Bottom display
area
RT-SVX49B-EN
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury. Disconnect all electric
power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized.
Packaged Contents
Power cables
RT-SVX49B-EN
10
RT-SVX49B-EN
Alarms
Active Alarms
Figure 3.
Sortable
columns
Alarm severity
Active Alarms
button
RT-SVX49B-EN
11
Alarms
Historic Alarms
On the Alarms screen, touch the Historic Alarms button to
view all alarms, commonly referred to as the event log (see
Figure 4, p. 12).
Figure 4.
Number of historic
alarms
Sortable
columns
Alarm severity
Sortable Alarms
You can sort active alarms by touching one of the column
headers. Choose to sort by severity, date and time, or
description.
Alarm Severity
A color-code icon representing the severity of each alarm
is shown under the severity (!) column. For a description
of the five alarm icons, see Table 1, p. 13.
12
RT-SVX49B-EN
Alarms
Alarm Icons
Table 2.
Alarm icons
Active
Alarm Icons
Notification Class
Critical
Service Required
Advisory
Sorting Alarms
Information
Table 2.
Smoke Detector
Heat Failure
Dirty Filter
Emergency Stop
Frostat Trip
Freezestat Tripped
RT-SVX49B-EN
List of alarms
13
Reports
You can use theTracerTD-5 Display to view a variety of
reports and create and edit custom reports.
Touch the Reports button in the bottom display area to
view the Reports screen.The Reports screen contains the
following buttons:
Table 3.
Custom Report 1
System Report
About
Custom Report 2
Compressor Report
Sensor Report
Custom Report 3
Operating Modes
Configuration Report
Economizer/
Ventilation Report
Heating Report
Figure 5.
Reports screen
Custom Reports
You can create up to three custom reports using the
TracerTD-5 Display
14
RT-SVX49B-EN
Reports
Figure 6.
RT-SVX49B-EN
15
Reports
Category
Selector
Buttons that
re-order your
custom
report list
Scroll buttons
to navigate
through the
data list
Scroll buttons
to navigate
through the
data list
Figure 9.
Custom Report
1
16
RT-SVX49B-EN
Reports
About
Data Area
Display Kernal
6200-0630-01.00
RT-SVX49B-EN
17
Reports
System Report
Touch the System Report button to view the System
Report screen.Touch the arrow buttons to move between
screens.
Figure 11.
Data Area
The following data appears in the System Report screen.
Unit Application
VAV,CV,SZVAV
Setpoint Source
Remote, Local
Occupancy
Occupied, Unoccupied
Economizing
Enabled, Disabled
Ventilation Control
Fixed/DCV
(*DCV = Demand Control Ventilation)
Heating Type
None, Electric, Gas, Hydronic
Space Pressure
X.XX iwc/mm(H20)
Thermostat Y1 Input
Open, Closed
Thermostat G Input
Open, Closed
Thermostat W2 Input
Open, Closed
Thermostat Y2 Input
Open, Closed
Thermostat X2 Input
Open, Closed
18
RT-SVX49B-EN
Reports
Frostat Input
Open, Closed
Economizer/Ventilation Report
Touch the Economizer/Ventilation Report button to view
the Economizer/Ventilation Report screen.Touch the arrow
buttons to move between screens.
Data Area
The following data appears in the Economizer/Ventilation
Report screen.
Economizing
Enabled, Disabled
Ventilation Control
Fixed, DCV
Space CO2
XXXX PPM
Design Min OA Damper Pos Setpoint 100% Fan Design Min OA Damper Pos Setpoint Mid Fan
XXX%
XXX%
Space Pressure
XX.XX IWC /cmWC
Compressor Report
Data Area
Dehumidification Status
Inactive, Active Reheat, Active Enhanced
RT-SVX49B-EN
19
Reports
Table 4.
SOV 1 Output
Heating, Cooling
SOV 2 Output
Heating, Cooling
Compressor 1 Starts
XXXXX
Compressor 2 Starts
XXXXX
Compressor 3 Starts
XXXXX
Heating Report
Data Area
Heating Type
None, Electric, Gas, Hydronic
*Config definition needed here for Dual Bank
Mod staged heat.
Heating Configuration
Staged /Modulating
Freezestat Input
Open, Closed
Freeze Avoidance
ACtive, Inactive
20
RT-SVX49B-EN
Reports
Configuration Report
Data Area
Unit Application
CV, VAV, SZVAV
Refrigeration Type
Cooling Only, Heat Pump
Product Type
Voyager 3, Commercial, Precedent/
Voyager 2/Odyssey, Precedent 17 Plus
Dehumidification
None, Hot Gas Reheat, Enhanced
Economizer
Installed, Not Installed
Dehumidification Type
Staged, Modulating
Heating Type
None, Electric, Gas, Hydronic
CV Control Type
Zone, Thermostat
Windmill Prevention
Disable, Enable
Cabinet Type
Horizontal, Downflow
Sensor Report
Data Area
Space CO2
XXXX PPM
Space Humidity
XXX%
Space Pressure
X.XX in(H2O)/mm(H20)
RT-SVX49B-EN
21
Reports
Data Area
RTRM
Occupancy
Occupied, Unoccupied
RTRM
Thermostat Y1 Input
Open, Closed
Thermostat G Input
Open, Closed
RTRM
Thermostat W2 Input
Open, Closed
Thermostat Y2 Input
Open, Closed
Thermostat X2 Input
Open, Closed
RTRM
RTRM
RTOM
RTOM
RTOM
Frostat Input
Open, Closed
RTOM
Freezestat Input
Open, Closed
RTOM
VSM
RTVM
IGN
Data Area
RTRM
Compressor 1 Output
Off, On
Compressor 2 Output
Off, On
RTRM
SOV 1 Output
Active, Inactive
RTRM
SOV 2 Output
Active, Inactive
RTOM/RTAM/RTVM/
RTEM/RTDM
RTOM/RTAM/RTVM/
RTEM/RTDM
IGN
22
RT-SVX49B-EN
Reports
Figure 12. Operating modes report details screen
RT-SVX49B-EN
23
Graphs
Graphs allow users to view data in graphical format on the
Display. Four custom graphs and eight standard graphs
are available. Graphs can be created with a maximum of
four lines per graph. Custom graphs are user-defined and
can be edited by changing the scale on the left and rightYaxis and choosing the line color.
24
RT-SVX49B-EN
Graphs
3. Touch the Add/Remove button to add values to the
custom data graph.
The Add/Remove screen appears.
4. Use the arrow buttons to select a value.
7.
Figure 16. Edit graph screen (after values have been added)
25
Graphs
Figure 17.
Graphs
11. Touch the Manually Select Range box for either the left
or rightY-axis.
12. Touch the edit button next to one of the two value
ranges.
Standard Graphs
There shall be 8 standard graphs.The standard graphs are
below:
Table 10.
Standard graphs
Space Temperature
Economizer
Compressor
VAV
Humidity
Heat Pump
CO2
Space Temperature:
The table below describes the data in the System Status
graph:
Data Point
Line Color
Blue
Axis
Left
Green
Left
Black
Left
Red
Left
Data Point
Line Color
Axis
Pink
Left
Green
Left
Black
Left
Blue
Right
Compressor Graph:
The table below describes the data in the graph:
RT-SVX49B-EN
27
Graphs
VAV System:
The table below describes the data in the System Status
graph:
Data Point
Line Color
Axis
Pink
Left
Green
Left
Black
Left
Red
Left
Economizer Graph:
The table below describes the data in the graph:
Data Point
Line Color
Purple
Axis
Left
Grey
Left
Pink
Right
Yellow
Right
Data Point
Line Color
Axis
Black
Left
Pink
Left
Yellow
Right
Purple
Right
CO2 Graph:
The table below describes the data in the graph:
Data Point
Line Color
Axis
Red
Left
Black
Left
Space CO2
Green
Left
Yellow
Right
Data Point
Line Color
Axis
Yellow
Left
Red
Left
Humidity Graph:
The table below describes the data in the graph:
Black
Left
Space Humidity
Green
Left
Data Point
Line Color
Axis
Green
Left
Blue
Left
Purple
Left
Grey
Left
28
RT-SVX49B-EN
Settings
The Settings screen provides options for display settings,
language, overrides and security.Touch the Settings
button in the bottom display area to view the Settings
screen.
Control Settings
Display Settings
Security Settings
Setpoints
Touch the Setpoints button to view the Setpoints screen.
Touch the arrow buttons to move between screens.
Figure 21.
Setpoints screen
RT-SVX49B-EN
29
Settings
Data Area
The following data appears in the Setpoints screen.
Front Panel Occupied Space Cooling Setpoint
XXX.X F/C
Front Panel Unoccupied Space Heating Setpoint Supply Air Reheat Setpoint
XXX.X F/C
XXX.X F/C
Design Min OA Damper Pos Setpoint 100% Fan Design Min OA Damper Pos Setpoint Mid Fan
XX%
XX%
Compressor 1 Starts
XXXXXX
Compressor 2 Starts
XXXXXX
Compressor 3 Starts
XXXXXX
Setup
Touch the Setup button to view the Setpoints screen.
Touch the arrow buttons to move between screens.
30
RT-SVX49B-EN
Settings
Display Preferences
Touch the Display Preferences button to open the
associated screen (Figure 23, p. 32). On this screen, all
available options to display information on theTD-5
screens are available.There are two pages on this screen,
accessed by using the arrow button at the bottom of the
screen.
RT-SVX49B-EN
31
Settings
Figure 23. Display preferences screen
Date Format
Touch the Date Format button to open the associated
screen.Three options are available to display the current
date: MMDDYYYY, DDMMYYYY, andYYYYMMDD.
Date Separator
Touch the Date Separator button to open the associated
screen.Three options are available to display separators
in the date format: None, Hyphen (-), or Slash (/).
Time Format
Unit System
Touch the Unit System button to open the associated
screen.Two options are available: SI (system
international) or IP (Inch-Pound).
Brightness
Touch the Brightness button, or the brightness icon
(
)located at the bottom left of each screen, to open the
associated screen. Screen brightness is measured in
percentage. Use the keypad to enter a new brightness
number.
Backlight Time-out
Touch the Backlight Time-out button to open the
associated screen.This value is measured in minutes, with
30 being the maximum limit. Use the keypad to enter a
backlight time-out value.This value is the amount of time
that the display will remain lit without activity. When the
32
RT-SVX49B-EN
Settings
Figure 24. Setting the header data point
Header data
point
Touchscreen Calibration
RT-SVX49B-EN
33
Settings
Figure 25. Touchscreen Calibration
Collection Frequency
Collection frequency sets the time interval that the Graph
Data is saved, and displayed on the graph.The faster the
Home Page
Use the arrow button on the Display Preferences screen to
advance to page 2.Touch the Home Page button to open
the associated screen.This function allows you to choose
what will display when the home button is touched.
34
RT-SVX49B-EN
Settings
Figure 27.
Language
Touch the Language button, or the language icon (
)
located at the bottom right of each screen, to open the
35
Settings
tap the digit twice which opens the keypad screen where
you can make date and time entries. When finished, touch
Clean Touchscreen
Touch the CleanTouchscreen button to safely clean theTD5 touchscreen using any brand of common household
glass cleaner. When this button is touched, the screen
background color becomes black, allowing dirt and
fingerprints to become more visible. It also displays a
countdown timer (five to zero seconds).Touch the screen
36
RT-SVX49B-EN
Troubleshooting
This section describes the possible error messages and
other issues that you may encounter while using the
TracerTD-5 display.
Possible Cause
Possible Solution
No power.
Blank display
RT-SVX49B-EN
37
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments,the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
2015Trane All rights reserved
RT-SVX49B-EN 3 Dec 2015