Project : __________________________________
Location : ___________________________________________
ATTRIBUTE
Raceways, Fittings and Support
1. Conduit size, type and make as indicated on plans and specifications.
2. Limitations on use of each type of conduit being observed.
3. Required type of fittings provided and compatible with conduit type.
4. Conduits run parallel or perpendicular to walls and to similar structures. Vertical runs are plumb.
5. Conduit runs properly and coordinated with other trades.
6. Proper bending are made based on code requirements.
7. No more than four quarter bends (360 degrees total) between pull points.
8. Bonding jumpers installed on cable trays as shown on plans and where required by code.
9. Areas verified where exposed conduit is allowed and conditions are understood.
10. Raceway support of approved type and based on plans and specifications.
11. Properly and rigidly supported at an interval of approximately 1500mm and within 900mm of boxes
except on areas not permitted by the structural members.
12. Coatings and surface treatment as required.
Junction and Pull Boxes
1. Junction, pull, and outlet boxes are of approved type and make as shown on plans and
specifications.
2. Junction and pull boxes are located on strategic locations for ease of cable pulling.
3. Boxes shall be of sufficient size to provide free space for all conductors.
4. Pull boxes for straight pull and angle or u-pull shall be sized respectively in accordance with code
requirements.
5. Boxes securely and rigidly supported.
6. Boxes are accessible and covered.
7. Unused openings are sealed.
Wires and Cables
1. Conductor material, size, stranding, insulation and make as specified on plans and specifications.
2. Cable type and make as specified on plans and specifications.
3. Applicable to its use and application.
4. Use of suitable equipment and methods for pulling of cables and conductors.
5. Proper color coding of conductors.
6. Cables routed properly to avoid interference by separating power and data.
7. Cable splices not used (i.e. UTP, STP, etc.).
8. Cables properly harnessed and bundled.
9. Cables with proper labeling and tagging.
10. Test(s) required conducted (i.e. Insulation Resistance Test of 220VAC power supply).
Closed Circuit Television (CCTV)
1. Camera, DVR, monitor, keyboard, and other components as specified on plans and specifications.
2. DVR's, cameras and other devices located as per approved plans and drawings, coordinated with
other trades, in accordance with codes and standards, and as per manufacturer's recommendation.
3. Camera and other components applicable to its use and location.
4. Dedicated power supply tapped to correct tapping point and mechanically protected. UPS supplied
tapping point highly recommended.
5. Back-up power supply (battery) available in case primary power supply shuts down. Back-up time
as per specification or code requirement.
6. Protection from lightning installed if required.
7. Camera in focus and clear of obstruction.
8. Camera installed in location that cannot be tampered.
9. Camera not facing bright light.
10. Camera clean, properly and rigidly supported.
11. Test(s) required conducted (i.e. Functional Test of CCTV)
Access Control
DATE
CHECKED /
INSPECTED
FORM /
REPORT
NO.
REMARKS
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
QA-EE02,
QA-EE03
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
QA-AUX101
1 of 3
Page 1 of 5
1.
2.
3.
4.
5.
6.
7.
8.
Access controller, expansion module, emergency break glass, exit push button, proximity/biometric
reader, electromagnetic lock, sounder and other components as per plan and specification.
Access controller and other devices located as per approved plans and drawings, coordinated with
other trades, in accordance with codes and standards, and as per manufacturer's recommendation.
Devices applicable to its use and location.
Dedicated power supply tapped to correct tapping point and mechanically protected. UPS supplied
tapping point highly recommended.
Back-up power supply (battery) available in case primary power supply shuts down. Back-up time as
per specification or code requirement.
Protection from lightning installed if required.
Interfacing with other systems like FDAS and FM 200 already connected.
Test(s) required conducted (i.e. Functional Test of Access Control)
FIR
FIR
FIR
FIR
FIR
FIR
FIR
QA-AUX201
to 207
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
QA-AUX301
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
2 of 3
Page 1 of 5
measured at right angle, from all walls or partitions extending to within 460mm (18in) of the ceiling.
17. Smoke and heat detectors properly located, unobstructed, securely mounted and operational.
18. Smoke detectors installed to prevent nuisance alarm or improper operation.
19. Smoke detectors not installed where air velocity exceeds 1.5m/s (300ft/min) unless specifically
designed.
20. Smoke detectors installed under raised floors orientated to minimize dust contamination and for which
they have been listed.
21. Smoke detectors installed after the construction cleanup of all trades are final unless protected.
22. Manual fire alarm boxes securely mounted and free from physical damage.
23. Manual fire alarm boxes located throughout the protected area so that they are conspicuous,
unobstructed and accessible.
24. Manual fire alarm box located within 1.5m (5ft) of the exit doorway opening at each exit on each floor.
25. The operable part of the manual alarm box not less than 1.1m (3 1/2ft) and not more than 1.37m
(4 1/2ft) above floor level.
26. Manual fire alarm boxes mounted on both sides of grouped openings over 12.2 m (40 ft) in width, and
within 1.5 m (5 ft) of each side of the opening.
27. Additional manual fire alarm boxes provided so that the travel distance to the nearest fire alarm box will
not be in excess of 30 m (100 ft) measured horizontally on the same floor.
28. Protection from lightning installed if required.
29. Interfacing with other systems like Access Control System, FM 200, PACU, AHU, etc. already
connected.
30. Test(s) required conducted (i.e. Functional Test of FDAS)
Background Music and Public Address (BGM/PA)
1. Equipments, microphone, speaker and other components as specified on plans and specifications.
2. Equipments, speakers and other components installed as per approved plans and drawings and in
coordination with other trades. All works comply with standards and manufacturer's recommendation.
3. Speakers applicable to its use and location.
4. Dedicated power supply tapped to correct tapping point if required.
5. Speakers clean, properly and rigidly supported.
6. Test(s) required conducted (i.e. Functional Test of BGM/PA, Sound Level Measurement)
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
FIR
QA-AUX401
FIR
FIR
FIR
FIR
FIR
QA-AUX501
Prepared by:
___________________
QA Engineer
Noted by:
___________________
QA Supervisor
3 of 3