relates the overall heat transfer coefficient, heat transfer surface area, and log
mean temperature difference to the rate of heat transfer. This heat exchanger
design equation is used to find the area needed for heat exchangers.
Introduction
The heat exchanger design equation can be used to calculate the required
heat transfer surface area for a variety of specified fluids, inlet and outlet
temperatures
and
types
and
configurations
of
heat
exchangers,
including
counterflow or parallel flow. A value is needed for the overall heat transfer
coefficient for the given heat exchanger, fluids, and temperatures. Heat exchanger
calculations could be made for the required heat transfer area, or the rate of heat
transfer for a heat exchanger of given area.
Q=UA T lm
WhereQ is the rate of heat transfer between the two fluids in the heat
exchanger in But/hr,
U is the overall heat transfer coefficient in Btu/hr-ft2-oF,
A is the heat transfer surface area in ft2,
Tlm is the log mean temperature difference in oF, calculated from the
inlet and outlet
temperatures of both fluids.
For design of heat exchangers, the basic heat exchanger design equation can
be used to calculate the required heat exchanger area for known or estimated
values of the other three parameters, Q, U, and T lm.
showing that the log mean temperature difference is the right average temperature
to use for heat exchanger calculations. That log mean temperature is defined in
terms of the temperature differences as shown in the equation at the right. T Hin and
THout are the inlet and outlet temperatures of the hot fluid and T Cin and TCout are the
inlet and outlet temperatures of the cold fluid. Those four temperatures are shown
in the diagram at the left for a straight tube, two pass shell and tube heat
exchanger with the cold fluid as the shell side fluid and the hot fluid as the tube side
fluid.
Q=m hot c p hot ( T Hin T Hout )=m cold c p cold (T CoutT cin )
Wheremhot = mass flow rate of hot fluid, slugs/hr,
Cp hot = heat capacity of the hot fluid, Btu/slug-oF
Mcold = mass flow rate of cold fluid, slugs/hr,
Cp cold = heat capacity of the cold fluid, Btu/slug-oF,
The required heat transfer rate can be determined from known flow rate, heat
capacity and temperature change for either the hot fluid or the cold fluid. Then
either the flow rate of the other fluid for a specified temperature change, or the
outlet temperature for known flow rate and inlet temperature can be calculated.
Figure A1. Basic Components of a Plate Fin Exchanger (Shah & Webb, 1983)
Function/Working Principle:
The concept is shown in Figure A2. Corrugated metal fins are placed between
flat plates. The structure is joined together by brazing. The fins have the dual
purpose of holding the plates together, thus containing pressure, and of forming a
secondary (fin) surface for heat transfer. At the edges of the plates are bars, which
contain each fluid within the space between adjacent plates. The heights of
corrugations and bars may vary between plates, as shown. For a liquid stream we
can use a low height corrugation, matching high heat transfer coefficient with lesser
surface area while for a low pressure stream we can use a high corrugation height,
matching low coefficient with higher surface area but also giving larger through
area to achieve lower pressure drop. An industrial unit contains about 1000 m2 of
surface per cubic meter.
Figure A2. Basic Construction of Plate Fin Exchanger (source: Martson, Ltd.)
Corrugations are also made with heat transfer enhancement devices.
Plain corrugation is the basic form and is used normally for low pressure drop
streams.
Perforated corrugation shows a slight increase in performance over plain
corrugation, but this is reduced by the loss of area due to perforation. The main
use is to permit migration of fluid across fin channels, usually in boiling duties.
Serrated corrugation is made by cutting the fins every 3.2 mm and displacing
the second fin to a point half way between the preceding fins. This gives a
dramatic increase in heat transfer.
Herringbone corrugation is made by displacing the fins sideways every 9.5
mm to give a zig-zag path. Performance is intermediate between the plain and
serrated forms. The friction factor continues to fall at high Reynolds numbers,
unlike the serrated, showing advantages at higher velocities and pressures.
The designer can, therefore, vary fin heights, fin pitch and fin thickness together
with four standard fin types giving great versatility of design.
Figure A3b. Types of Plate Fin Surface (a. Plain Triangular, b. Plain Rectangular, c.
Wavy Fin, d. Offset Strip Fin, e. Multiouver Fin, f. Perforated Fin, Talukdar n.d)
Plate-fin units are normally arranged for counterflow heat exchange. Cross
flow units are used for vehicle radiators and cross counterflow is used for liquid
subcoolers.
Characterization of which corrugation will be used is determinded by Figure
A4:
Type of Material:
It is used for rapid cooling or heating of heat sensitive materials and others
such as:
Clear Fluids
Low Viscosity Fluids
Tight Temp. Control
Slurry with Fine Particles
Consideration/Limitation:
Plate and fin heat exchangers are usually made of aluminum alloys, which
provide high heat transfer efficiency. The material enables the system to operate at
a lower temperature difference and reduce the weight of the equipment. The brazed
aluminum construction is limited to pressures up to around 60 bar and
temperatures up to 150C. The units cannot be mechanically cleaned, so their use is
restricted to clean process and service steams.
Aluminum units use material AS3003 in the exchanger block. Braze material
is AS3003 + silicon. Plates are purchased with a thin film of braze metal on both
sides. The unit is built and placed in a vacuum furnace. The braze takes place under
vacuum and at a temperature of 580C. The parts of the block are then firmly
attached together. Stainless steel units are made of AISI type 321. Braze material is
essentially nickel and can be applied to the plates by spraying. Brazing takes place
under vacuum at temperatures up to 1050C.
Industry Application:
Plate and fin heat exchangers are mostly used for low temperature services
such as natural gas, helium and oxygen liquefaction plants, air separation plants
and transport industries such as motor and aircraft engines.
These are called as extended surface exchangers it is used in the conditions
where when a process fluid is having very low heat transfer coefficient when
compared to other fluids because the overall heat transfer coefficient decreases
which affect the capacity of heat transfer by the available surface area so the area
of contact is to be increase. We come across this type of problem when heat
transfer is dealt with heating of air or gas streams and for cooling viscous liquids
like engine oil.
The cost of plate-fin heat exchangers is generally higher than conventional
heat exchangers due to a higher level of detail required during manufacture.
However, these costs can often be outweighed by the cost saving produced by the
added heat transfer. Plate-fin heat exchangers are generally applied in industries
where the fluids have little chances of fouling. The delicate design, as well as the
thin channels in the plate-fin heat exchanger, makes cleaning difficult or impossible.
Applications of plate-fin heat exchangers include:
Design Calculation:
1. Number of Passes (source: Design of Compact Plate Fin Heat Exchanger by
Dewatwal, 2009)
where:
b = fin thickness
L3 = heat exchanger height
w = distance between the plate and fin
L1 N
pf
N
nf =
L2 ( p+1)
pf
Where:
Th = Hot Fluid, Tc = Cold Fluid
12
pressure) up to 10 mm. This means relatively thick material separates the two fluids
compared to tubing of conventional exchangers.
The concept of a spiral heat exchanger is as simple as it is sophisticated. Two
or four long metal strips, onto which spacer studs are welded, are wound around a
core, thus creating two or four equally spaced single passage channels. The
concentric shape of the flow passages and the studs yield turbulence already at low
Reynolds numbers. By optimizing the flow pattern heat transfer is enhanced, whilst
fouling is reduced.
The main feature of this exchanger type is that there is a single passage for
each fluid.
The main advantage of the SHE is its highly efficient use of space. This
attribute is often leveraged and partially reallocated to gain other improvements in
performance, according to well known tradeoffs in heat exchanger design. A
compact SHE may be used to have a smaller footprint and thus lower all-around
capital costs, or an over-sized SHE may be used to have less pressure drop, less
pumping energy, higher thermal efficiency, and lower energy costs.
The most fascinating feature of SHE is that due to its geometry, there is very
limited fouling. As the fluid flows in a spiral, deposition on the walls f the heat
exchanger is negligible. This means lower down time as compared to the
conventional Shell and Tube heat exchangers.
13
14
One fluid enters the centre of the unit and flows towards the periphery. The
other fluid enters the unit at the periphery and moves towards the centre. The
channels are curved and have a uniform cross section. The product channel is
normally open on one side and closed on the other. The heating/cooling medium
channel can sometimes be closed on both sides, depending on the cleanliness of
the heating/cooling medium. Each channel has one connection in the centre and
one on the periphery of the heat exchanger.
Spiral heat exchangers have high waste heat recovery. The secret is the true
counter-current flow. It enables crossing temperature situations where the cold fluid
can be heated to temperatures very close to those of the hot fluid. The closer the
temperature approach between two fluids, the more heat is recovered. This effect is
enhanced by the high turbulence in the unit due to the single channel geometry and
the arrangement of the studs.
The heat transfer capacity of the exchanger was dictated by the width of the
channels. Right up until the 1960s, this effectively meant a maximum capacity of
200 m2 since steel strip was only available in relatively narrow widths. Attempts to
increase capacity by fabricating larger areas met with only limited success, since
they resulted in long, thin channels with excessively high pressure drops. Once
wider materials became available and wider channels could be formed, however,
heat transfer capacity was progressively increased. Today, practical maximum
capacity of a standard Spiral Heat Exchanger is 400-600 m 2. Currently the spiral is
manufactured in a winding process using a D-shaped mandrel with the two strips
being welded to a central plate and distance studs have replaced the steel bars.
Alternatively tubular centers are becoming more common.
Usually, alternate edges of the passages are closed and covers fitted to both
sides of the spiral assembly.
Type of Material:
Sludges
Liquids in Suspension
Clear Fluids
15
Fluids
Slurry with Coarse Particles
Refrigerants
Thermal Fluids
Tight Temp. Control
High Scaling Material
Consideration/Limitation:
Spiral Heat Exchanger is almost always a liquid/liquid heat exchanger.
In most cases it is mounted horizontally and can be opened at each end. Each
channel circuit is seal welded on one side and open on the other. The open channel
is sealed by the gasket face of the end cover. The flid in the two channels always
follows the spiral direction, from the outside towards the centre, or the centre to the
outside. The flow arrangement is counter-current. The unit is preferably mounted
horizontally. In the vertical position there is a risk of solid material settling by
gravity to the bottom of the channel. Also, for cleaning it needs to be rotated to the
horizontal position.
Performance data
usage of stainless steel tubing, it offers the unique ability to provide a welded 304
stainless steel spiral tube bundle. Additionally, we specialize in spiral tube heat
exchangers with 316L stainless steel and a variety of exotic alloy materials
including Hastelloy, Inconel, Incoly and specialty stainless steels to name just
a few.
Industry Application:
16
heating, heat recovery, pre-heating and effluent cooling. Spiral heat exchangers are
particularly effective for handling sludges, liquids in suspension including slurries,
and a wide range of viscous fluids. Their design and fabrication make them well
suited for controlling viscosity, a vital parameter when abrasive or corrosive fluids
must be handled. The spiral heat exchanger is also used as a condenser and
evaporator.
Petrochemical
Refinery
Steel making
Pulp and paper
Mineral processing (metals, ore)
Wastewater
treatment
17
Design Calculation:
Where:
where:
P = Pumping Power
p = Pressure Drop
= density
= Efficiency
Heat Exchange
Equipment
Double Pipe Heat
Exchanger
Double
pipe
heat exchangers are the
simplest exchangers used in
industries. These are also
known as hairpin, jacketed
pipe, jacketed U-tube and
concentric pipe. In its simplest
form, it is just one pipe inside
another larger pipe. The inner
pipe can be plain or have
longitudinal fins attached to
increase the surface area
available for heat transfer.
Fins can be attached to the
pipe by welding, soldering, by
mechanical
insertion
into
grooves or can be integral with
the piping. One fluid flows
through the inside pipe and
the other flows through the
annulus between the two
pipes. The wall of the inner
pipe is the heat transfer
surface. The pipes are usually
doubled back multiple times in
order to make the overall unit
Industrial
Application
Double Pipe
Heat
Exchanger is
used
in
Petroleum
industry,
Chemical
industry,
Food
industry and
Pharmaceuti
cal industry
for
the
following
operations/pr
ocesses:
Pasteurization
Digester
Heating
Heat Recovery
Pre-heating
Effluent cooling
more compact.
The
most
widely used double pipe heat
exchanger is the hair pin. The
high stresses produced by
differential thermal expansion
between outer and inner pipes
are more easily handled.
Manifolding of a multiple hairpin
setup
is
easily
accommodated. When using
multiple hair-pin double pipe
heat exchangers all the
exchangers do not have the
same dimension.
Double
pipe
exchangers
can
either be single-tube
or multiple-tube. The
single-tube consists
of a single tube or
pipe, either finned or
bare, inside a shell.
Multiple tube double
pipe
sections
consist of 7 to 64
tubes,
bare
or
longitudinally finned
with the outer pipe
shell.
Exchanger
In this type of
exchanger,
round
and
rectangular
tubes are the most
common, although
elliptical tubes are
also used. Fins are
generally used on
the outside, but they
may be used on the
inside of the tubes
in
some
applications. They
Operating
pressures
and
Individually finned tubes
temperatures are somewhat limited
These
exchangers
are
extensively
used
as
condensers
and
evaporators
in
airconditioning
and
refrigeration
applications,
as
condensers
in
electric
exchanger
flat
compared
to
shell-and-tube
exchangers due to joining of the
fins to plates or tubes such as
brazing and mechanical expansion
power
plants, as oil
coolers
in
propulsive
power
plants, and
as air-cooled
exchangers
(also
referred
to
as a fin-fan
exchanger)
in
process.and
power industries.
(continuous) fins on
tubes has been
variously referred to
as a plate-fin and
tube,
plate-finned
tube,and tube in
plate-fin exchanger
in the literature. In
order
to
avoid
confusion with a
plate-fin exchanger
defined above, we
will refer to this type
as
a
tube-fin
exchanger
having
flat (plain, wavy, or
interrupted)
fins.
Individually finned
tubes are probably
more rugged and
practical in large
tube-fin exchangers.
Shell-and-tube
exchangers
sometimes employ
low finned tubes to
increase the surface
area
on
the
shellside when the
shellside
heat
transfer coefficient is
low compared to the
tubeside coefficient.
The exchanger with
Studded Tube
flexibility
in
distributing surface
area on the hot and
cold
sides
as
warranted by design
considerations; and
(3) there is generally
substantial
cost,
weight, or volume
savings.
R
d
R
1
1
1
1
=
+ fo +
ln( i , o )+ fi +
U A A o ho A o 2 kl
d i , i Ai A i h i
Where:
T LM =
( T o , iT i ,o ) (T o , oT i, i)
( T o ,i T i , o )
ln
(T o ,o T i , i)
Where:
T i , a=
T i , o +T i , i
2
T o ,a=
T o ,o +T o ,i
2
Where:
Association,
or
lumped
together
and
determined
i=
di , i m
i
i ai
Where:
In the inner pipe if the Reynolds is less than 2000 this is considered to
be laminar flow and the Nusselt number is equal to 4.36. If the Reynolds
number is greater than 10,000, the Nusselt number is given by
Where:
Where:
Where:
Design Problem
1. Benzene(hot stream)
To,i= 75C
To,o=50C
o
o
o
ID = 41 mm
OD = 48 mm
Thermal conductivity =
0.154 W/m-K
2.Water(cold stream)
Ti,i= 30C
Ti,o=40C
Specific heat capacity = 4.186
Viscosity=0.8cP
Wall thickness=2.2mm
o
kJ/kg C
ID =21mm
OD =25.4mm
Thermal conductivity of
wall= 74.5 W/m K
4. No phase change occurs; both fluids are single phase and are unmixed.
Design Considerations
2. Water will be taken in the tube side to cause lesser damageto the heat
exchanger since it causes a lot of fouling and corrosion.
Design Requirements
5. Tube Length
6. Pressure Drop
Design Calculations
T LM =
( T o , iT i ,o ) (T o , oT i, i)
( T o ,i T i , o )
ln
(T o ,o T i , i)
( 7540 )(5030)
( 7540 )
ln
(5030)
= 26.80
m
C p dT
Q=
2. Heat Duty
Q benzene=Qwater
= 47,000 kJ/h
=1122.79 kg/h
= 0.9 m/s
Reynolds number, Re = Dv /
=23,625
Prandtl number, Pr = Cp /k
= 5.38
Nu = hiDi/k = 0.023(Re)0.8(Pr)0.3
Thus, hi = Nu(k/Di)
= 120.13(0.623 W/mC)/(0.021 m)
= 3563.86 W/m2-C
Flow area =
IDo2
OD i2
4
4
= 0.00081355 m2
Wetted Perimeter =
( ID o +ODi )
( 0.041 m+0.0254 m )
= 0.2086 m
= 4(0.00081355 m2/0.2086 m)
= 0.0156 m
= 0.397 m/s
= 14395.01
Prandtl number,Pr = Cp /k
= 4.52
Nu = hoDH/k = 0.023(Re)0.8(Pr)0.4
=(0.023)(14395.01)0.8(4.52)0.4 = 89.2
ho= Nu(k/DH)
= 89.2(0.154 W/m-oC/0.0156 m)
880.54 W/m2oC
(0.0254)(L)
(0.021)(L)
Am=(A0 - Ai)/ln(OD/ID)
A0/Am = 1.098
A0/Ai = 1.21
1
1 A r r A 1
= + o o i+ o
U o ho Am k w
A i hi
1
0.0022
1.21
+1.098
+
880.54
74.5 3563.86
= 663.30 W/m2-oC
Q = UoAoTLM
Ao = Q/UoTLM
= 0.73 m2
Use: 0.75 m2
5. Tube Length
Ao =
L=
A o / OD
ODL
= 9.40 m
Design
Function
H
a
i
r
p
i
View
P
a
c
k
i
n
g
g
l
a
n
d
R
e
t
u
r
n
b
e
n
d
S
u
p
p
o
r
t
l
u
g
s
F
l
a
n
g
e
U
n
i
o
n
j
o
i
n
t
N
o
z
z
l
e
s
G
a
s
k
e
t
s
Design Dimensions
1. Process Fluid
Flowrate
2. Heating Fluid
Flowrate
3. Heat Duty
11
22
.7
9
kg
/h
10
00
kg
/h
47
,0
00
kJ/
h
0.75
Inside
Diameter
Outside
Diameter
m2
5. Inside
Diameter
6. Outside Diameter
7. Length
8. BWG
Schedule
21
m
m
25
.4
m
m
9.
4
m
1
B
W
G
16
Ma
41mm
48
mm
Ma
Acc
Inlet
Temperat
ure
Outlet
Temperat
ure
Tube Dimensions
Pipe Dimensions
30 oC
40 oC
75oC
Outlet
Temperat
ure
50 oC
Introduction
Shell and Tube Heat Exchanger (STHE) is the most commonly used
type of heat exchanger in the chemical and allied industries. Its flexibility
in design allows its operation for a wide range of pressures and
temperatures.
Function
Type of Material
STHE can handle a broad range of process fluids due to its versatility
on its construction. It can handle process fluids at a wide range of
temperature and pressure; fluids that are corrosive, viscous, toxic and
lethal fluids.
Design Consideration/Limitation
44
Design Standards
Tubular
Exchanger
Manufacturers
Association
(TEMA)
standards are followed in most countries of the world for the design of shell
and tube heat exchangers. TEMA published a widely accepted standard of
designing a STHE. This standard is intended to supplement the American
Society of Mechanical Engineers (ASME) as well as other boiler and
pressure vessel codes. The TEMA standards are applicable to unfired shell
and tube heat exchangers with inside diameters not exceeding 60 in. (1524
mm). Each section is identified by an uppercase letter symbol, which
precedes the paragraph numbers of the section and identifies the subject
matter.
45
divided into four major parts: front header, shell, tube bundle, and rear
header.
Front header this is where the fluid enters the tube-side of the
exchanger.
Shell this contains the tube bundle
Tube Bundle this is made up of the tubes, tube sheets, baffles,
tie rods, etc. It holds the bundle together.
Rear Header this is where the tube-side fluid leaves the
exchanger; or in the case of a multiple tube-side passes, this is
where it is returned to the front header.
46
1. Shell
2. Shell cover
47
30.
Liquid
connection
level
Types
TEMA provides a
summarized in the table below:
standard
designation
system
that
48
is
49
U-Bend STHE
50
STH
E
Typ
e
Fix
edTub
esh
eet
Typic
al
TEMA
Code
BEM,
AEM,
NEN
Utub
e
BEU,
AEU
Advantages
Disadvantages
Provides
maximum
heat
transfer area for
a given shell and
tube diameter;
Outer part
of
tubes
are
inaccessible for
mechanical
cleaning;
Provides
for
single
and
multiple
tube
asses to assure
proper velocity;
Allows
differential
thermal
expansion
between
the
shell and tube
bundle as well as
for
individual
tubes;
Both the tube
bundle and the
shell side can be
inspected
and
cleaned
mechanically;
No provision to
allow
for
differential
thermal
expansion
developed
between
the
tube
and
the
shell side. This
can
be
taken
care by providing
expansion
joint
on the shell side.
Some tubes are
omitted at the
center
of
the
tube bundle;
Tubes can be
only cleaned by
chemical
methods;
Individual tube is
difficult
to
replace;
No single
pass
or
51
tube
true
countercurrent
flow is possible;
Flo
atin
g
Hea
d
AEW,
BEW,
BEP,
AEP,
AES,
BES
Allows
differential
thermal
expansion
between
shell and
bundle;
for
the
tube
Tube
wall
thickness at the
U-bend is thinner
than at straight
portion of the
tubes;
Draining of tube
circuit is difficult
when positioned
with the vertical
position with the
head
side
upward.
To provide the
floating
head
cover,
it
is
necessary to bolt
it
to
the
tubesheet.
The
bolt
circle
requires the use
of space where it
would
be
possible to place
a large number
of tubes;
Tubes
cannot
expand
independently so
that
huge
thermal
shock
applications
should
be
avoided;
Packing
materials
produce limits on
design pressure
and temperature
52
Materials of Construction
Materials
of
construction
Allowable
fluid
temperature, C (F)
Carbon steel
540 (1004)
C-Mo steel
590 (1094)
Cr-Mo steel
650 (1202)
590 (1094)
590 (1094)
650 (1202)
(< 6 % Cr)
Alloy
steel
(<17 % Cr)
Austenitic
Cr-
Ni steel
Cast iron
200 (392)
Brass
200 (392)
53
Tubes
Tubes of circular cross section are exclusively used in STHE.
Since the desired heat transfer in the exchanger takes place across the tube
surface, the selection of tube geometric variables is important from the
performance point of view. Important tube geometrical variables include
tube size and tube arrangement. Also, tubes must be able to withstand
the following: (1) operating temperature and pressure on both sides; (2)
thermal stresses due to the differential thermal expansion between the shell
and the tube bundle; and (3) corrosive nature of both the shellside and
tubeside fluids.
Tube Size
Tube size is specified by its outside diameter and wall thickness.
In line with the principles of heat transfer, the smaller diameter tubes
yield higher heat transfer coefficients and result in a more compact
exchanger and cheaper exchanger. The smaller diameters that are
preferably used in most duties are from 5/8 to 1 in. (16 25 mm). However,
larger tubes are easier to clean, more rugged, and they are used
when the allowable pressure drop in the tubeside is small.
steel and alloy set by TEMA is given in Table 4. The sizes presented in Table 4
gives the best performance and are most economical in most applications.
The most used sizes are the 3/8-in. and 4/3-in. For clean fluids, use -in. If
the tubes are subjected to mechanical cleaning, use -in. When fouling is
expected, use 1-in. Falling film exchangers and vaporizers generally use 1.5in. and 2-in. tubes.
54
The
tube
wall
thickness
is
generally
identified
by
the
Birmingham wire gauge (BWG). The BWG and its corresponding tube wall
thickness is given in Table 5. Tube wall thickness must be checked against the
55
Bir
min
gha
m
Wir
e
Ga
ge
BW
G
12
13
14
15
16
17
18
19
(in
ch
es
)
(
m
m
)
0.
10
9
2.
76
9
0.
09
5
2.
41
3
0.
08
3
2.
10
8
0.
07
2
1.
82
9
0.
06
5
1.
65
1
0.
05
8
1.
47
3
0.
04
9
1.
24
5
0.
1.
56
04
2
20
21
22
23
24
25
26
27
06
7
0.
03
5
0.
88
9
0.
03
2
0.
81
3
0.
02
8
0.
71
1
0.
02
5
0.
63
5
0.
02
2
0.
55
9
0.
02
0
0.
50
8
0.
01
8
0.
01
6
possible with a small shell diameter and long tubes, consistent with the
space. However, for offshore applications, long exchangers, especially with
removable bundles are very difficult to maintain and install because of their
space limitations. The preferred lengths of tubes for heat exchangers are 6 ft
(1.83 m), 8 ft (2.44 m), 12 ft (3.66 m), 16 ft (4.88 m), 20 ft (6.10 m), and 24 ft
(7.32 m). The optimum tube length to shell diameter ratio will usually fall
within the range of 5 to 10.
Tube Arrangements
57
as possible within the shell to achieve maximum heat transfer area. Another
factor of selecting a tube layout pattern is the cleaning requirement.
Tube Pitch
The recommended tube pitch (distance between tube centers) is
1.25 times the tube outside diameter; this will normally be used unless
process requirements dictate otherwise. Where a square pattern is used for
58
Tube-Side Passes
The fluid in the tube is usually directed to flow back and forth in
59
Shells
The TEMA standards cover exchangers up to 60 in. (1520 mm)
diameter. Up to about 24 in. (610 mm), shells are normally constructed from
standard, close tolerance pipe; above 24 in. (610 mm) they are rolled from
plate. For high-pressure applications the shell thickness would be sized
according to the pressure vessel design standards. The minimum allowable
shell thickness is given in the TEMA standards, found in Table 6.
but also on the number of tube passes, as spaces must be left in the pattern
of tubes on the tube sheet to accommodate the pass partition plates.
60
designate the various types. The E shell is the most commonly used
arrangement. Two shell passes (F shell) are occasionally used where the shelland tube-side temperature differences are unsuitable for a single pass;
however, it is difficult to obtain a satisfactory seal with a shell-side baffle and
the same flow arrangement can be achieved by using two shells in series.
The divided flow and split-flow arrangements (G and J shells) are used to
reduce the shell-side pressure drop where pressure drop, rather than heat
transfer, is the controlling factor in the design.
Others
Baffles
Baffles are used in the shell to direct the fluid stream across the
tubes, to increase the fluid velocity and to improve the rate of heat transfer.
There are three types of baffle: single segmental, double segmental and
doughnut or disc baffle. The most commonly used type of baffle is the single
segmental baffle.
61
segmental baffle. The baffle cut is the height of the segment removed to form
the baffle, expressed as a percentage of the baffle disc diameter. Baffle cuts
from 15% to 45% are used. Generally, a baffle cut of 20% to 25% will be the
optimum, giving good heat-transfer rates, without excessive pressure drop.
There will be some leakage of fluid around the baffle as a clearance must be
allowed for assembly.
The baffle spacings used range from 0.2 to 1.0 shell diameters.
A close baffle spacing will give higher heat-transfer coefficients, but at the
expense of higher pressure drop. The optimum spacing will usually be
between 0.3 to 0.5 times the shell diameter.
Design Calculations
Step
#1. Obtain
the
required
thermophysical
properties
(viscosity,
1
Arithmetic Mean Temperature= (T 2T 1)
2
Step #2. Calculate heat duty (Q) of the exchanger assuming that there is
no heat loss to the surrounding.
62
63
64
LMTD=
T hi T co
)
t hot ci
A=
Q
U est x LMTD x FT
Step #6. Select tube material, decide the tubes inside (d i) and outside
(do) diameter, its wall thickness (t) and tube length (L). Calculate the
number of tubes (nt) required to provide the taken heat transfer area
calculated:
nt =
A
d o L
np
)
nt
u=
d 2i
4 m(
where m, and are mass flow rate, density and viscosity of tube side
fluid.
If u <1 m/s, fix np so that the Reynolds number, Re, be greater than or
equal to 104. ,
65
np
)
nt
=
d i
4 m(
However, this is subject to allowable pressure drop in the tube side of the
heat exchanger.
Step #7. Decide type of shell and tube exchanger (fixed tubesheet, Utube, floating head). Select the tube pitch (PT), determine inside shell
diameter (Ds) that can accommodate the calculated number of tubes (nt).
Use the standard tube counts table given in table 8.
66
67
Step #9 . Assign fluid to shell side or tube side. Select the type of baffle
(segmental, doughnut etc.), its size (i.e. percentage cut, 25% baffles are
widely used), spacing (B) and number. The baffle spacing is usually chosen
to be within 0.2Ds to Ds.
68
Step #10 . Determine the tube side film heat transfer coefficient (hi) using
the suitable form of Sieder-Tate equation in laminar and turbulent flow
regimes.
Select the outside tube (shell side) dirt factor (Rdo) and inside tube
(tube side) dirt factor (Rdi) in Table 9.
69
Step #11 . If
to step #5, calculate heat transfer area ( A ) required using Uo,cal and
repeat the calculations starting from step #5 .
If the calculated shell side heat transfer coefficient (ho) is too low, assume
closer baffle spacing (B) close to 0.2 Ds and recalculate shell side heat
transfer coefficient. However, this is subject to allowable pressure drop
across the heat exchanger
Step #13 . Calculate the tube-side pressure drop (PT ): (i) pressure drop
in the straight section of the tube (frictional loss) (Pt) and (ii) return loss
(Prt) due to change of direction of fluid in a multi-pass exchanger'.
70
Step #14 . Calculate shell side pressure drop (PS): (i) pressure drop for
flow across the tube bundle (frictional loss) (Ps) and (ii) return loss (Prs)
due to change of direction of fluid.
Total
shell
side
pressure
(1.9)
If the tube-side pressure drop exceeds the allowable pressure drop for the
process system, decrease the number of tube passes or increase number
of tubes per pass. Go back to step #6 and repeat the calculations steps.
Sample Problem
Viscosity, lb/ft-hr
Density, lb/ft3
Thermal
Conductivity,
Btu/hr-ft-deg-F
Specific Heat Capacity,
Btu/lb-ft
Specific Gravity
Keros
ene
3.872
49.8
0.083
0.48
0.80
Gasol
ine
0.2
42.7
0.075
0.57
0.685
Given data :
71
Hot
fluid
inlet
Hot
fluid
outlet
Cold
fluid
inlet
Cold
fluid
outlet
) = 150000 lb.h-1
=3240000 Btu/h
mg = 142105 lb h-1
Iteration #1:
The first iteration is started assuming 1 shell pass and 2 tube passes shell
and tube exchanger with following dimensions and considerations.
72
Tube ID ( di ) = 0.834''
The log mean temperature correction factor (FT) for 1-2 shell and tube
exchanger :
where,
73
= 42.75F
-1
is assumed to initiate the design calculation for the kerosene and gasoline
heat exchanger.
= 1586.36 ft
74
= 502
As Re<<10
= 2740.2<10
Iteration #2:
Assumptions:
75
Tube ID=0.834
No. of tubes:
nt = 335
Fluid velocity:
76
= 1.04 m/s (so the design velocity is within the acceptable range)
Assumptions:
77
(for square
pitch)
=0.082ft
C = Tube clearance
C = PT - d0
C = 1 -1=0.25
= 0.675 ft
Mass velocity,
-2
78
=35668
jH =110 for the shell side fluid at Re=35668 with 25% cut segmental baffles
( [3] page 838 )
ho = 155.3 Btu h
ft
-2
-1
Fouling
0.0005 h ft 2 F Btu
-1
-1
for
kerosene
and Rdg =
(1.6)
79
Let
select,
Admirality
brass
-1
as
tube
material
with
thermal
ft-1 F-1 .
-1
ft
-2
F-1
Now,
Friction factor f = 0.00028 x 144 for Re = 0.04032 ft2 /ft2 for Re=11571.4
= 0.232 ft
80
= 5.81 psi
Return loss Prt : (due to change in flow direction of the tube side fluid)
= 0.73 psi
=5.81+0.73
Therefore the tube side pressure drop is within the maximum allowable
pressure drop of 10 psi.
81
Spacing, B =15.5
as = 0.444 ft2
Re = 35668
No of baffles,
Friction factor, f = 0.0017 X 144= 0.2448 ft2 / ft2 with 25% cut segmental
baffles ( [3] page 839 )
= 1.4 psi
82
Therefore the shell side pressure drop is within the maximum allowable
pressure drop of 7 psi.
Over surface =
% Over surface =
=20% (acceptable)
Over design:
24368=2312 ft2
83
24335=2105 ft2
Equipme
nt
Shelland-Tube
Heat
Exchang
er
Function
Allows two
fluids
to
exchange
heat;
a
fluid flows
over the
outside of
the tubes
while the
other fluid
flows
inside the
tubes.
Can
function
as: chiller,
condenser
,
partial
condenser
,
final
condenser
,
cooler,
exchanger
, heater,
reboiler,
thermosip
hon
reboiler,
forcedcirculation
reboiler,
Type of
Material
Consideration/L
imitation
It
can
handle
process
fluids at a
wide
range of
temperatu
re
and
pressure;
fluids that
are
corrosive,
viscous,
toxic and
lethal
fluids.
Construction
Details
and
Standards
Follow ASME Code
or
TEMA
standards
Selection
of
Flow Path
Tubeside fluids
that
are
corrosive, dirtier,
at high pressure
Shellside fluids
that are more
viscous or gases
84
steam
generator
85
Function
fresh air supply to indoor. It is one important equipment and key technology
in the field of construction energy saving.
Design Consideration/Limitation
1.
2.
3.
4.
by the
Introduction:
Heat transfer in the fluidized bed is, apart from the particle and gas
mixing, the most important process contributing to the intensity of the physical and
chemical processes. In fact, several different processes can be distinguished:
particle-gas heat transfer, heat transfer between different points in the bed, heat
transfer between the fluidized bed particles and the larger particles floating in the
bed and the heat transfer to the submerged surfaces in contact with the bed. All of
these heat transfer processes are very intensive in fluidized beds.
points in the bed does not exceed 2-5C, with mean bed temperatures of several
hundred, even 1000C. Gas temperature, when leaving the bed, is practically the
same as the particle temperature. These facts tell us of the great capability of the
solid particles to exchange heat with the fluidizing gas. Intensive heat transfer is,
first of all, a consequence of the large specific heat transfer surface (3000 to 45000
m2/m3), although heat transfer coefficients to the particles in the bed are relatively
small, 6-25 W/m2C. The large heat capacity of the solid particles also makes the
temperature difference between gas and particles small. Gas temperature follows
the particle temperature.
Fluidized beds are used as a technical process which has the ability to
promote high levels of contact between gases and solids. In a fluidized bed a
characteristic set of basic properties can be utilised, indispensable to modern
process and chemical engineering, these properties include:
Extremely high surface area contact between fluid and solid per unit bed
volume
High relative velocities between the fluid and the dispersed solid phase.
High levels of intermixing of the particulate phase.
Frequent particle-particle and particle-wall collisions.
fluidized bed heat exchanger is in the particle convection. Gas convection and
radiation also form a significant part of the total heat transfer.
Function/Working Principle:
brought into a chamber, in which they are fluidised with air or re-circulated flue gas
as a slowly bubbling fluidised bed. Heat exchanger elements, often in the form of
tube coils, are located inside this fluidised bed, see Figure C1.
The hot particles colliding with the heat transfer surfaces effectively
release their thermal energy, thus increasing significantly the external heat transfer
coefficient. At the same time, the continuous collisions slightly erode the surface,
thus preventing deposition of harmful ashes. The benefits of such heat exchanger
are clear:
more efficient heat transfer than in the gas channel => smaller heat transfer
area is required
possibility to control the heat transfer, both by the bed temperature in the
immersed in a bed of finely divided solid material, such as a tube bundle immersed
in a bed of sand or coal particles. If the upward fluid velocity on the bed side is low,
the solid particles will remain fixed in position in the bed and the fluid will flow
through the interstices of the bed. If the upward fluid velocity is high, the solid
particles will be carried away with the fluid. At a proper value of the fluid velocity,
the upward drag force is slightly higher than the weight of the bed particles. As a
result, the solid particles will float with an increase in bed volume, and the bed
behaves as a liquid. This characteristic of the bed is referred to as a fluidized
condition. Under this condition, the fluid pressure drop through the bed remains
almost constant, independent of the flow rate, and a strong mixing of the solid
particles occurs. This results in a uniform temperature for the total bed (gas and
particles) with an apparent thermal conductivity of the solid particles as infinity.
Very high heat transfer coefficients are achieved on the fluidized side compared to
particle-free or dilute-phase particle gas flows.
Type of Material:
Due to the high thermal load and the special environment, the
Reductions
Pyrolysis
FBHE have been designed and built for many different materials,
Consideration/Limitation:
Industry Application:
gaseous fuels, drying, adsorption, cooling, heating, freezing, conveying, storing and
thermal treating of various particulate solid materials. Chemical reaction is common
on the fluidized side in many process applications, and combustion takes place in
coal combustion fluidized beds. The common applications of the fluidized-bed heat
exchanger are drying, mixing, adsorption, reactor engineering, coal combustion,
and waste heat recovery.
Design Calculation:
The factor with the greatest influence on the heat transfer, apart from the
fluidization velocity, is the particle size. Particle size influences the change of
the relative contribution of various mechanisms in the overall heat transfer. In
the fluidized bed with small (< 0.1 mm) particles, convection by particles
account for 90% of the overall heat transfer, while in the beds of large
particles (> 1 mm) only 20% of the heat transfer is done by particle
convection. Particle heat capacity is also important for the amount of heat
transfered by particle convection. The maximum heat transfer coefficient is
often calculated from the Zabrodski relation:
= 35.80.20.6/d0.36
where:
uniform bed temperature at x position (Tb,x) and plug flow for the solid material,
the energy balance for a control volume of length x provides:
Where:
Air cooled heat exchangers are used to transfer heat from a process
fluid to ambient air. The process fluid is contained within heat conducting
tubes. Atmospheric air, which serves as the coolant, is caused to flow
perpendicularly across the tubes in order to remove heat. In a typical air
cooled heat exchanger, the ambient air is either forced or induced by a fan or
fans to flow vertically across a horizontal section of tubes. For condensing
applications, the bundle may be sloped or vertical. Similarly, for relatively
small air cooled heat exchangers, the air flow may be horizontal across
vertical tube bundles.
In order to improve the heat transfer characteristics of air cooled
exchangers, the tubes are provided with external fins. These fins can result in
a substantial increase in heat transfer surface. Parameters such as bundle
length, width and number of tube rows vary with the particular application as
well as the particular finned tube design.
Air-cooled heat exchangers are generally arranged in banks with
several exchangers installed side by side. The height of the bundle
aboveground must be one-half of the tube length to produce an inlet velocity
equal to the face velocity. This requirement applies both to ground-mounted
exchangers and to those pipe-rack-installed exchangers which have a fire
deck above the pipe rack. (Perrys)
Advantage
Disadvantage
1. Since air has relatively poor thermal transport properties when compared
to water, the air cooled heat exchanger could have considerably more heat
transfer surface area. A large space requirement may result
The forced-draft unit, which is illustrated in Figure 4.1 pushes air across the
finned tube surface. The fans are located below the tube bundles. The
induced-draft design has the fan above the bundle, and the air is pulled
across the finned tube surface. In theory, a primary advantage of the forceddraft unit is that less power is required. This is true when the air-temperature
rise exceeds 30C (54F).
The forced-draft design offers better accessibility to the fan for onstream
maintenance and fan-blade adjustment. The design also provides a fan and Vbelt assembly, which are not exposed to the hot-air stream that exits from
the unit. Structural costs are less, and mechanical life is longer.
Induced-draft units are less likely to recirculate the hot exhaust air, since the
exit air velocity is several times that of the forced-draft unit. Induced-draft
design more readily permits the installation of the air cooled equipment
above other mechanical equipment such as pipe racks or shell-and-tube
exchangers. In a service in which sudden temperature change would cause
upset and loss of product, the induced-draft unit gives more protection in that
only a fraction of the surface (as compared with the forced draft unit) is
exposed to rainfall, sleet, or snow.
Induced Draft coolers utilize fans located on the topside of the tube bundle.
These fans draw cooling air up through the tube bundle to provide a more
efficient distribution of airflow. The advantages of this induced design include
greater protection to the tube bundle as a result of the plenum positioning
above the bundle, reduced potential for recirculation of hot air and reduced
noise levels at ground level.
FINNED TUBES
Common to all air cooled heat exchangers is the tube, through which the
process fluid flows. To compensate for the poor heat transfer properties of air,
which flows across the outside of the tube, and to reduce the overall
dimensions of the heat exchanger, external fins are added to the outside of
the tube. A wide variety of finned tube types are available for use in air
cooled exchangers. These vary in geometry, materials, and the methods of
construction, which affect both air side thermal performance and air side
pressure drop. In addition, particular combinations of materials and/or fin
bonding methods may determine maximum design temperature limitations
for the tube and limit environments, in which the tube might be used. The
use of a particular fin tube is essentially a matter of agreement between the
air cooled heat exchanger manufacturer and the user.
permit any number of tube side passes for the process fluid. For multipass
tube bundles, the headers contain partition plates, which divide the bundle
into separate passes. However, these may be limited by the operating
temperature conditions. If there is a large temperature difference per pass,
then the hotter tubes may expand lengthwise to a much greater extent than
the tubes in succeeding passes. This could result in high stresses on the tube
joint, resulting in leakage at the joint. If differential expansion between
passes is excessive, split headers may be necessary. The tube bundle is
normally permitted to float independently of the supporting structure due to
overall bundle expansion.
Figure 4.4. Typical tube bundle (two pass) using box headers with tube
plugs opposite each tube end. Key: (1) Tube; (2) Tube Sheet; (3) Inlet/Outlet
Nozzles; (4) Vent; (5) Drain; (6) Tube Plugs; (7) Side Frame; (8) Pass Rib
End plates on the tube side headers frequently include removable plugs.
These can be pipe tap plugs or straight threads with gasket seals. The plugs
are located opposite each tube end to permit access for each tube for rerolling of the tube to tubesheet joint, should leaks, occur and for cleaning the
tubes if this should be necessary. If the tubes are welded into the tubesheets
and the process fluid conditions are non-fouling, these plugs are not
necessary.
tube spacing and prevent meshing or deformation of the fins; and across the
top row of tubes to keep the tubes in proper position. The supports are
spaced evenly along the bundle length at intervals, not exceeding about 1.5
meters.
Tube bundles are designed to be rigid and self-contained and are mounted so
that they expand independently of the supporting structure. The face area of
the tube bundle is its length times width. The net free area for air flow
through the bundle is about 50 percent of the face area of the bundle.
The standard air face velocity (FV) is the velocity of standard air passing
through the tube bundle and generally ranges from 1.5 to 3.6 m/s (300 to
700 ft/min).
TUBING
The 25.4-mm (1-in) outside-diameter tube is most commonly used. Fin
heights vary from 12.7 to 15.9 mm (0.5 to 0.625 in), fin spacing from 3.6 to
2.3 mm (7 to 11 per linear inch), and tube triangular pitch from 50.8 to 63.5
mm (2.0 to 2.5 in). Ratio of extended surface to bare-tube outside surface
varies from about 7 to 20. The 38-mm (1a-in) tube has been used for flue-gas
and viscous-oil service.
Tube size, fin heights, and fin spacing can be further varied. Tube lengths vary
and may be as great as 18.3 m (60 ft). When tube length exceeds 12.2 m (40
ft), three fans are generally installed in each bay. Frequently used tube
lengths vary from 6.1 to 12.2 m (20 to 40 ft).
FANS
Axial-flow fans are large-volume, low-pressure devices. Fan diameters are
selected to give velocity pressures of approximately 2.5 mm (0.1 in) of water.
Total fan efficiency (fan, driver, and transmission device) is about 75 percent,
and fan drives usually have a minimum of 95 percent mechanical efficiency.
Usually fans are provided with four or six blades. Larger fans may have more
blades. Fan diameter is generally slightly less than the width of the bay.
band-center frequencies: 63, 125, 250, 1000, 2000, 4000, 8000, and also the
dBa value (the dBa is a weighted single-value sound-pressure level).
Reducing the fan-tip speed results in a straight-line reduction in air flow while
the noise level decreases. The API Standard limits fan-tip speed to 61 m/s
(12,000 ft/min) for typical constructions. Fan-design changes which reduce
noise include increasing the number of fan blades, increasing the width of the
fan blades, and reducing the clearance between fan tip and fan ring.
Both the quantity of air and the developed static pressure of fans in air-cooled
heat exchangers are lower than indicated by fan manufacturers test data,
which are applicable to testing-facility tolerances and not to heat-exchanger
constructions.
The axial-flow fan is inherently a device for moving a consistent volume of air
when blade setting and speed of rotation are constant. Variation in the
amount of air flow can be obtained by adjusting the blade angle of the fan
and the speed of rotation. The blade angle can be either (1) permanently
fixed, (2) hand-adjustable, or (3) automatically adjusted. Air delivery and
power are a direct function of blade pitch angle.
Fan mounting should provide a minimum of one-half to three fourths diameter
between fan and ground on a forced-draft heat exchanger and one-half
diameter between tubes and fan on an induced-draft cooler. Fan blades can
be made of aluminum, molded plastic, laminated plastic, carbon steel,
stainless steel, and Monel.
FAN DRIVERS
Electric motors or steam turbines are most commonly used. These connect
with gears or V belts. (Gas engines connected through gears and hydraulic
motors either direct-connected or connected through gears are in use. Fans
may be driven by a prime mover such as a compressor with a V-belt takeoff
from the flywheel to a jack shaft and then through a gear or V belt to the fan.
Direct motor drive is generally limited to small-diameter fans.
V-belt drive assemblies are generally used with fans 3 m (10 ft) and less in
diameter and motors of 22.4 kW (30 hp) and less.
Right-angle gear drive is preferred for fans over 3 m (10 ft) in diameter, for
electric motors over 22.4 kW (30 hp), and with steam-turbine drives.
DESIGN CONSIDERATIONS
1. Design dry-bulb temperature. The typically selected value is the
temperature which is equaled or exceeded 2a percent of the time during the
warmest consecutive 4 months. Since air temperatures at industrial sites are
frequently higher than those used for these weather-data reports, it is good
practice to add 1 to 3C (2 to 6F) to the tabulated value.
2. Air recirculation. Prevailing winds and the locations and elevations of
buildings, equipment, fired heaters, etc., require consideration. All air-cooled
heat exchangers in a bank are of one type, i.e., all forced-draft or all induceddraft. Banks of air-cooled exchangers must be placed far enough apart to
minimize air recirculation.
3. Wintertime operations. In addition to the previously discussed problems of
winterization, provision must be made for heavy rain, strong winds, freezing
of moisture upon the fins, etc.
4. Noise. Two identical fans have a noise level 3 dBa higher than one fan,
while eight identical fans have a noise level 9 dBa higher than a single fan.
Noise level at the plant site is affected by the exchanger position, the
reflective surfaces near the fan, the hardness of these surfaces, and noise
from adjacent equipment. The extensive use of aircooled heat exchangers
contributes significantly to plant noise level.
5. Ground area and space requirements. Comparisons of the overall space
requirements for plants using air cooling versus water cooling are not
consistent. Some air-cooled units are installed above other equipmentpipe
racks, shell-and-tube exchangers, etc. Some plants avoid such installations
because of safety considerations, as discussed later.
6. Safety. Leaks in air-cooled units are directly to the atmosphere and can
cause fire hazards or toxic-fume hazards. However, the large air flow through
an air-cooled exchanger greatly reduces any concentration of toxic fluids.
Segal [Pet. Refiner, 38, 106 (April 1959)] reports that air-fin coolers are not
located over pumps, compressors, electrical switchgear, control houses and,
in general, the amount of equipment such as drums and shell-and-tube
exchangers located beneath them are minimized. Pipe-rack-mounted aircooled heat exchangers with flammable fluids generally have concrete fire
decks which isolate the exchangers from the piping.
7. Atmospheric corrosion. Air-cooled heat exchangers should not be located
where corrosive vapors and fumes from vent stacks will pass through them.
9. Process-side cleaning. Either chemical or mechanical cleaning on the inside
of the tubes can readily be accomplished.
controllable pitch of fan blades, annual power required has been found to be
22, 36, and 54 percent respectively of that needed at the design condition for
three process services. Alternatively, when fans have two-speed motors,
these deliver one-half of the design flow of air at half speed and use only oneeighth of the power of the full-speed condition.