3. The one-line diagram for a three phase distribution feeder is shown below. Neglect exciting branch
of transformer. The three phase load consists of WYE connected series R-L elements with the values
given.
(a) Sketch per unit, per phase diagram for the system. Use a VA base of 200 kVA and a high side
voltage base of 2400V line-to-line.
(b) Determine V1 line-to-line if the load sees a voltage of 235V line-to-line.
2400:240V
150 kVA
X = 10%
LOAD
V1
R = 0.44
3 phase, high voltage feeder.
Series impedance of
Series impedance of
X = 0.33