27 Aug 2016
Submitted to: First NatGas Power Corp (FNPC)
Submitted by: WSP | Parsons Brinckerhoff
www.wsp-pb.com
Test run 2
100CC-GAS
100CC-GAS
75CC-GAS
75CC-GAS
25-Aug-16
25-Aug-16
25-Aug-16
25-Aug-16
2.00 PM
3.00 PM
5.00 PM
6.00 PM
3.00 PM
4.00 PM
6.00 PM
7.00 PM
6,200.0
6,200.0
[kW]
421,267.5
421,240.6
[kJ/kWh]
5,786.4
5,849.2
[kW]
[kJ/kWh]
421,254.1
5,817.8
6,200.0
Performance Guarantee
Net Electrical Output
414,100
[kW]
[kJ/kWh]
[kJ/kWh]
6,096
6,281
6,152
[%]
96%
[kW]
397,536
[%]
104%
[kJ/kWh]
6,398
[kW]
421,254
[kJ/kWh]
5,932
[kW]
7,154
Differences
of Net Electrical Output
of Net Weighted Heat Rate
[kJ/kWh]
Confidential
219
1 of 7
Test run 2
100CC-GAS
100CC-GAS
75CC-GAS
75CC-GAS
25-Aug-16
25-Aug-16
25-Aug-16
25-Aug-16
2.00 PM
4.00 PM
6.00 PM
7.00 PM
3.00 PM
5.00 PM
7.00 PM
8.00 PM
Electrical measurements
Net active power
7016_P
801
[kW]
406,101.1
405,472.9
314,105.0
314,009.4
Net voltage
7016_U
802
[V]
230,324.7
231,000.9
231,890.3
232,643.8
Net current
7016_I
803
[A]
1,037.0
1,028.8
801.4
793.8
Generator speed
7038_f
810
[1/s]
3,599.4
3,599.1
3,600.3
3,600.7
7038_P
811
[kW]
413,567.3
412,828.9
320,087.8
319,903.3
Gross voltage
7038_U
812
[V]
22,903.2
22,902.4
22,903.5
22,903.7
Gross current
7038_I
813
[A]
11,012.4
10,922.9
8,524.0
8,439.7
SPPA-T3000
814
[A]
2,539.1
2,495.9
2,144.1
2,068.8
Excitation current
Gas turbine measurements
Compressor inlet P
3006100
300_1
[mbar]
20.559
20.521
14.033
14.093
Compressor inlet P
3006103
300_2
[mbar]
20.764
20.719
14.166
14.224
Compressor inlet P
3006101
300_3
[mbar]
20.832
20.791
14.231
14.290
Compressor inlet P
GT inlet DBT (GT filer house)
3006094
300_4
[mbar]
20.586
20.538
14.106
14.168
5K150-0151
302
[C]
30.25
30.35
29.14
28.81
5K150-0121
303
[C]
30.21
30.37
29.16
28.83
5K150-0153
304
[C]
30.21
30.36
29.15
28.81
5K150-0119
305
[C]
30.29
30.35
29.20
28.83
5K150-0150
306
[C]
30.37
30.51
29.29
28.93
5K150-0115
307
[C]
30.29
30.44
29.22
28.85
5K150-0154
308
[C]
30.09
30.15
28.99
28.60
5K150-0122
309
[C]
30.37
30.43
29.29
28.89
5K150-0099
310
[C]
30.37
30.45
29.25
28.89
5UK150-0037
311
[C]
30.29
30.42
29.25
28.91
5UK150-0038
312
[C]
30.24
30.37
29.22
28.89
5UK150-0039
313
[C]
30.28
30.42
29.22
28.88
5UK150-0041
314
[C]
30.36
30.49
29.29
28.94
5UK150-0042
315
[C]
30.44
30.58
29.44
29.08
5UK150-0043
316
[C]
30.49
30.66
29.41
29.04
5UK150-0044
317
[C]
30.56
30.65
29.46
29.07
5UK150-0045
318
[C]
30.53
30.63
29.44
29.05
5UK150-0046
319
[C]
30.53
30.64
29.46
29.10
SPPA-T3000
[hr]
1,142.0
1,144.0
1,146.0
1,147.0
[C]
28.56
28.53
28.35
28.29
5K150-0104
191
Ambient conditions
Ambient pressure
2002065
350
[bar]
1.0034
1.0030
1.0041
1.0046
Ambient pressure
2002059
351
[bar]
1.0035
1.0031
1.0040
1.0046
2002063
352
[bar]
1.0030
1.0028
1.0037
1.0042
Ambient DBT
Ambient pressure
5K100-0030
353
[C]
30.70
30.99
29.54
29.10
Ambient WBT
5K100-0029
354
[C]
26.45
25.66
25.76
26.04
Ambient DBT
5K100-0034
355
[C]
30.61
30.82
29.42
29.01
Ambient WBT
5K100-0033
356
[C]
26.36
25.54
25.67
25.96
252
[Hz]
1,155.38
1,151.30
907.15
908.41
1050030
253
[bar]
40.00
39.98
40.14
40.15
5EX150-0028
256
[C]
43.29
42.60
40.76
40.93
4KUK650-0030
257
[C]
217.60
217.60
217.90
217.80
0.01770
DCS
259
[kg/s]
0.02263
0.02293
0.01748
DCS
260
[C]
28.29
28.2
23.6
23.1
DCS
261
[bar]
3.06
3.06
3.07
3.07
Confidential
2 of 7
Test run 2
100CC-GAS
100CC-GAS
75CC-GAS
75CC-GAS
25-Aug-16
25-Aug-16
25-Aug-16
25-Aug-16
2.00 PM
4.00 PM
6.00 PM
7.00 PM
3.00 PM
5.00 PM
7.00 PM
8.00 PM
C/H ratio
[C]
30.27
30.38
29.19
28.83
[mbar]
1.0033
1.0030
1.0039
1.0045
[%]
71.89
65.73
74.35
78.67
[-]
3.1061
3.1062
3.1074
3.1074
[Hz]
59.99
59.99
60.01
60.01
[mbar]
20.685
20.642
14.134
14.194
[EOH]
1142.037
1144.037
1146.037
1147.037
[C]
28.56
28.53
28.35
28.29
[-]
OFF
OFF
OFF
OFF
30
1.006
C/H ratio
[C]
0.27
0.38
-0.81
-1.17
[mbar]
-2.700
-3.033
-2.067
-1.533
70
[%]
1.89
-4.27
4.35
8.67
3.118
[-]
3.1061
3.1062
3.1074
3.1074
60
[%]
-0.018
-0.025
0.009
0.019
11.8/7.6
[mbar]
9.085
9.042
6.534
6.594
1320
[EBH]
28.0
[C]
0.56
0.53
0.35
0.29
[-]
OFF
OFF
OFF
OFF
Evaporative cooler
Summary of Correction factors to plant power output
Ambient temperature (external)
1]
[-]
1.00145
1.00202
0.99637
0.99478
2]
[-]
1.00264
1.00296
1.00199
1.00148
3]
[-]
0.99980
1.00043
1.00286
1.00562
5]
[-]
0.99983
0.99982
0.99983
0.99984
[KP,1 grid]
[-]
1.00031
1.00043
0.99989
0.99977
[-]
1.01027
1.01022
1.01116
1.01126
[KP,2 inlet P]
[KP,3 deg]
[-]
1.00000
1.00000
1.00000
1.00000
Evaporative cooler
[-]
1.02378
1.02378
2]
[-]
-706.292
-740.434
-371.271
-424.365
[kW]
189.268
178.796
86.257
71.189
[-]
f 1]
[-]
1.00000
1.00000
1.00007
1.00010
f 2]
[-]
1.00003
1.00004
0.99998
0.99999
f 3]
[KHR,1 grid]
[-]
1.00002
0.99995
0.99948
0.99899
[-]
0.99998
0.99998
1.00000
1.00001
[-]
0.99896
0.99896
0.99803
0.99801
[KHR,2 inlet P]
[KHR,3 deg]
[-]
1.00000
1.00000
1.00000
1.00000
Evaporative cooler
[-]
1.00047
1.00047
Confidential
3 of 7
Test run 2
100CC-GAS
100CC-GAS
75CC-GAS
75CC-GAS
25-Aug-16
25-Aug-16
25-Aug-16
25-Aug-16
2.00 PM
4.00 PM
6.00 PM
7.00 PM
3.00 PM
5.00 PM
7.00 PM
8.00 PM
Gross power
P'gross,meas
[kW]
413,567
412,829
320,088
319,903
Gross voltage
U'gross,meas
[V]
22,903
22,902
22,904
22,904
Gross current
I'gross,meas
[A]
11,012
10,923
8,524
8,440
pf'
[-]
0.95
0.95
0.95
0.96
[kW]
406,101
405,473
314,105
314,009
Net voltage
[V]
230,325
231,001
231,890
232,644
Net current
[A]
1,037
1,029
801
794
Excitation current
[A]
2,539
2,496
2,144
2,069
[A]
12,213.5
12,191.7
9,452.8
9,447.4
[kVA]
486,550
485,681
376,574
376,357
Igross, pfN
Sgross
If
[A}
3,083
3,077
2,470
2,469
PL,FR,N
[kW]
1,500.00
1,500.00
1,500.00
1,500.00
558.57
PL,FE,N
[kW]
558.54
558.49
558.56
PL,SC,N
[kW]
6.17
6.15
4.94
4.94
PL,Exc,pfN
[kW]
1,383.04
1,378.33
887.74
886.94
PL,SC,pfN
[kW]
415.08
413.60
248.64
248.36
PL,pfN
[kW]
3,862.82
3,856.57
3,199.88
3,198.81
P'L,FR
[kW]
1,500.00
1,500.00
1,500.00
1,500.00
P'L,FE
[kW]
558.54
558.49
558.56
558.57
P'L,SC
[kW]
5.08
4.99
4.29
4.14
P'L,Exc
[kW]
938.29
906.68
669.04
622.88
P'L,Sc
[kW]
337.45
331.99
202.18
198.20
P'L
[kW]
3,339.37
3,302.16
2,934.07
2,883.80
PGen
[kW]
-523.46
-554.42
-265.81
-315.01
369,423
Snet,pfN
[kVA]
477,766
477,027
369,535
Psc,Tra,pfN
[kW]
730.71
728.45
437.15
436.88
PL,tra,pfN
[kW]
730.71
728.45
437.15
436.88
319,863
S'net
[kVA]
413,698
411,639
321,888
P'sc,Tra
[kW]
547.88
542.44
331.68
327.53
P'L,tra
[kW]
547.88
542.44
331.68
327.53
PTra
-182.84
-186.02
-105.46
-109.36
-706.29
-740.43
-371.27
-424.36
Confidential
4 of 7
Test run 2
100CC-GAS
100CC-GAS
75CC-GAS
75CC-GAS
25-Aug-16
25-Aug-16
25-Aug-16
25-Aug-16
2.00 PM
4.00 PM
6.00 PM
7.00 PM
3.00 PM
5.00 PM
7.00 PM
8.00 PM
Generator serial no
Apparent power nominal
SN
[kVA]
pfN
[-]
0.85
Ugross,N
[V]
23,000
[ ]
[%]
0.11247357
100%
75%
50%
25%
Apparent power
Sgross
[kVA]
521,000
390,750
260,500
130,250
Stator current
Igross
[A]
13,078
9,809
6,539
3,270
Active power
[kW]
442,850
332,138
221,425
110,713
Voltage
Rotor winding R20
Load point
521,000
Field current
If,pfN
[A]
3,296
2,543
1,926
1,423
Friction losses
PL,FR
[kW]
1,500
1,500
1,500
1,500
565
Core losses
PL,FE
[kW]
565
565
565
Short-circuit losses
PL,SC
[kW]
1,472
828
368
92
PL,Exc
[kW]
1,581
941
540
295
PL,Add
[kW]
147
122
107
97
PL,C
[kW]
PL
[kW]
5,272
3,961
3,084
2,552
[%]
98.82%
98.82%
98.63%
97.75%
Total losses
Efficiency
BAT Transformer Shop Test Results
2014-220-94
[kVA]
555,000
[kW]
202.294
[kW]
986.057
[V]
23,000
Transformer LV voltage
Confidential
5 of 7
Test run 2
100CC-GAS
100CC-GAS
75CC-GAS
75CC-GAS
25-Aug-16
25-Aug-16
25-Aug-16
25-Aug-16
2.00 PM
4.00 PM
6.00 PM
7.00 PM
3.00 PM
5.00 PM
7.00 PM
8.00 PM
Cables losses
Cable losses at at nominal power
Nominal current of the cable
Net current measured
Total cable losses
[kW]
116.0
116.0
116.0
116.0
[A]
1,223.0
1,223.0
1,223.0
1,223.0
[A]
1037.0
1028.8
801.4
793.8
[kW]
83.40
82.09
49.81
48.87
314,154.8
314,058.3
317,665.7
317,683.0
317,700.3
Pnet,pfn
[kW]
406,184.5
405,554.9
Pcorr
[kW]
421,267.5
421,254.1
421,240.6
HRCorr
Pcorr
HRCorr
[kJ/kWh]
[kW]
5786.35
5,817.8
5849.21
[kJ/kWh]
Confidential
6 of 7
Test run 2
100CC-GAS
100CC-GAS
75CC-GAS
75CC-GAS
25-Aug-16
25-Aug-16
25-Aug-16
25-Aug-16
2.00 PM
4.00 PM
6.00 PM
7.00 PM
3.00 PM
5.00 PM
7.00 PM
8.00 PM
90.3585
CH5
[% mol]
90.3951
90.3815
90.3499
Ethane
C2H6
[% mol]
2.8844
2.8852
2.8864
2.8822
Propane
C3H8
[% mol]
1.2255
1.2262
1.2301
1.2288
n-Butane
nC4H10
[% mol]
0.3809
0.3819
0.3865
0.3869
Iso-Butane
iC4H10
[% mol]
0.2918
0.2919
0.2941
0.2940
n-Pentane
nC5H12
[% mol]
0.0798
0.0803
0.0830
0.0833
Iso-Pentane
iC5H12
[% mol]
0.1092
0.1098
0.1128
0.1131
neo-Pentane
neoC5H12
[% mol]
0.0000
0.0000
0.0000
0.0000
C6H14+
[% mol]
0.0773
0.0776
0.0837
0.0842
0.6058
N2
[% mol]
0.6073
0.6092
0.6061
CO2
[% mol]
3.9488
3.9563
3.9674
3.9632
H2
[% mol]
0.0000
0.0000
0.0000
0.0000
Helium
He
[% mol]
0.0000
0.0000
0.0000
0.0000
Oxygen
O2
[% mol]
0.0000
0.0000
0.0000
0.0000
Water
H2O
[% mol]
0.0000
0.0000
0.0000
0.0000
[% mol]
100.0000
100.0000
100.0000
100.0000
Total
Fuel gas pressure
[bar]
40.00
39.98
40.14
40.15
[C]
43.29
42.60
40.76
40.93
[kJ/kg]
44,476.9
44,467.1
44,456.7
44,461.6
[kg/m ]
[-]
29.603
30.0353
30.4227
30.4039
3.1061
3.1062
3.1074
3.1074
Elster-Istromet
Elster-Istromet
Elster-Istromet
Elster-Istromet
10521012
10521012
10521012
10521012
200
200
200
200
PIGSAR
PIGSAR
PIGSAR
PIGSAR
23-Sep-14
[DN]
Calibration laboratory
Calibration date
Impulse / m3
Fuel gas pressure
Fuel gas temperature
Fuel gas density
Measured frequency
23-Sep-14
23-Sep-14
23-Sep-14
[1/m3]
2250
2250
2250
2250
[bar]
40.00
39.98
40.14
40.15
[C]
43.29
42.60
40.76
40.93
[kg/m3]
29.603
30.0353
30.4227
30.4039
[1/s]
1,155.38
1,151.30
907.15
908.41
[kg/s]
15.2013
15.3687
12.2658
12.2753
[kg/s]
0.0226
0.0229
0.0175
0.0177
[kg/s]
15.2239
15.3917
12.2833
12.2930
[KJ/s]
677,111.7
684,423.3
546,072.9
546,564.5
Confidential
7 of 7