12.2
11.02
Via RS-232
NCK (complete)
--
PLC (complete)
--
HMI (with option of saving only partial areas of the HMI data)
S Area-specific archiving: Backup or reimport of individual data areas (softkeys Data In, Data Out and Data Selection).
Error, operating
message texts and
cycle alarm texts
These texts are part of the operating panel system software. They must be reloaded after hardware component replacement or software upgrading. The
messages must be in the correct format (see Chapter 13 Upgrading PCU 20
software). The texts cannot be read out of the control.
Operating
procedure
(data backup)
12
Device type:
RTS/CTS
Baud rate:
9600 baud
Parity:
None
Data bits:
Stop bits:
12-270
--
--
12 Data Backup
12.2 Data backup via PCU 20
11.02
Saving changed
values
MD 11210
UPLOAD_MD_CHANGES_ONLY
11210
MD Number
MD backup of changed MD only
Default presets: 0
min. input limit: 0
max. input limit: 1
Change effective: immediately
Protection level: 2/4
Unit: -Data type BYTE
valid as of SW release: 1 or 4
Meaning:
Selects a differential MD upload:
Bit 0 (LSB)
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
corresponds to ....
Note
12-271
12
12 Data Backup
12.2 Data backup via PCU 20
11.02
Recommendation
MD 11210 UPLOAD_MD_CHANGES_ONLY should be set to 1 or the corresponding bits set to 1. With this setting, the transferred files contain only those
data which deviate from the default. This is of advantage with respect to future
SW upgrades.
Series
start-up
(data backup)
Area-specific
archiving
5. HMI interface configuration (see above, select tape format for all data except
for drive data).
6. Start PCIN data transmission program (Data In) on PC/PG, specify file
name.
7. Select data area to be output on HMI (HMI Services operating area, data
output Data Out).
8. Select the heading Data and then select the following areas in the order
given from the list that is then displayed:
12
--
Machine data
--
Setting data
--
Option data
--
--
--
Protection areas
--
R parameters
--
Zero offsets
--
Drive data
--
Compensation data
--
--
--
--
When the areas are output, the internal area identifier used in each case
appears on the top line of the display.
12-272
12 Data Backup
12.2 Data backup via PCU 20
11.02
9. Start the read-out process (Start softkey) and acknowledge any related input requests on the operator panel.
Note
For the PLC, data backup can be executed with the SIMATIC tools HiGraph.
Note filter setting for SDBs!
References:
/S7HT/ Manual, Application of Tools
These tools are useful in ensuring portability of the PLC programs.
Loading archiving
data
Retrieving
series start-up files
4. Select the HMI interface configuration RS-232-PG/PC as above (punchedtape format deselected).
5. Start the PCIN data transmission program on the PG/PC. Select the NCK
series start-up file to be read into control under Data Out for transmission.
Go to the Services, Data In area on the HMI and start the import process
(Start softkey). Acknowledge any input requests displayed on the HMI.
6. Follow the same procedure for the PLC series start-up file after executing an
NCK reset and a PLC general reset.
7. After another NCK reset, the control powers up with the imported data sets.
12
Note
The NCK series start-up file must always be imported before the PLC series
start-up file.
Retrieving
individual
archive files
4. Select the HMI interface configuration RS-232 PG/PC as above and set
tape format (except for drive data).
--
Start the PCIN data transmission program on the PG/PC. Select the
archive file to be read into control under Data Out for transmission.
--
Select the Services, Data In area in the HMI and initiate the reading-in
process (Start softkey). The file is automatically detected and loaded
accordingly.
12-273
12 Data Backup
12.2 Data backup via PCU 20
11.02
6. Load the machine data file (COMPLETE_TEA_INI) and actuate NCK reset.
If you then receive messages about a reconfiguration of the memory or restandardization of machine data, then you must read in the machine data file
again and press NCK Reset. Generally speaking, this process must be
carried out two to three times because the first time the file is loaded the
memory allocation is changed or a rotary axis is defined.
7. If global user data must be activated, then the so-called %_N_INITIAL_INI
file (Table 12-1) must be read out. It is read out through selection of the setting All data as for area-specific archiving.
8. Read in archive file for global user data (MAC.DEF and GUD.DEF).
9. Read the save %_N_INITIAL_INI file back in to activate the global user
data.
10. Then load the other areas.
11. The PLC area must be loaded last after a PLC general reset.
Note
When you are loading drive data, deselect the tape format as well as all special
functions on the right of the display of interface settings.
Do not actuate softkey Back up boot file in the drive data menu until you have
reset the control once after loading the drive archive data.
Note
Check/correct the interface settings after display of a message regarding memory reconfiguration.
12
Error during
transmission
12-274
12 Data Backup
12.3 Data backup via PCU 50
11.02
Table 12-1
File _N_INITIAL_INI
S Option data
S Machine data
S Setting data
---
S Tool offsets
Leadscrew error
compensation
Quadrant error compensation
Sag compensation
S Zero offsets
S Global user data
S Workpieces
S R parameters
Part programs
S Subroutines
S User cycles
S Standard cycles
S Definitions and macros
12.3
Via RS-232
To archive or read in data via the RS-232 interface, proceed in exactly the same
way described in Section 12.2:
12
NCK (complete)
--
PLC (complete)
--
HMI (with option of saving only partial areas of the HMI data)
You can redirect the data backup to archive files on the PCU 50 hard disk.
Via disk
Via NC card
You can save data also on the NC card, see Operators Guide, Services
operating area.
12-275