E s ko m D i s t r i b u t i o n h a s e x p e r i e n c e d
substation shut-downs caused by
spurious AC signals superimposed on the
substation's main DC supply. In one case,
commissioning staff mistakenly connected
a 230 V AC mains supply to the positive leg
of the DC supply. In another, an AC signal
was coupled to the DC circuitry during
earth fault conditions on the HV network as
a result of irregularities with the substation
earthing. Both cases led to the complete
shutdown of the MV (secondar y-side)
busbars at the affected substations, with
all HV/MV transformer MV circuit-breakers
tripping spuriously. Both incidents were
subsequently found to have been caused
by the same circuit of the specific type of
transformer protection scheme used.
The two incidents of maltripping due to
AC coupling onto DC circuits were found
to involve the same circuit in the same
type of transformer protection scheme
(see Fig. 1).
The circuit in Fig. 1 operates as follows:
VTest
Vrms
C1
nF
C2
nF
R1
R2
IEC 6025522-7
150
100
100
100
100
ESKASAAO4
250
100
N/A
N/A
N/A
Plant Description
IEC
ESK
Max C @
250V AC
Cable
length
1a
Fail
Fail
5 nF
12 m
1b
Pass
Pass
300 nF
800 m
2a
Pass
Pass
150 nF
400 m
2b
Pass
Pass
>800 nF
>2100 m
Fail
Fail 15 nF
40 m
Fail
Pass 110 nF
270 m
Pass
Pass 570 nF
1500 m
Pass
Pass
230 nF
600 m
Pass
Pass
360 nF
900 m