754 N Currier St, Pomona, CA 91768


Inspection prepared for: Lucero & Alvero Veronica
Real Estate Agent: Carmen Magallon Date of Inspection: 5/26/2016 Time: 2:00 PM
Age of Home: 1952 Size: 2122
Weather: Sunny, warm, dry
Order ID: 87106
Elite Basic Home Inspection
Check permits for any alterations/remodels
Inspector: Jason Solano
Certified Master Inspector
Phone: (800)494-8998
Email: timmaher@eliteinspections.com

The Elite Group

754 N Currier St, Pomona, CA

Summary Page

Summary Page
The summary below consists of potentially significant findings. These findings can be a safety hazard, a
deficiency requiring a major expenses to correct or items I would like to draw extra attention to. The
summary is not a complete listing of all the findings in the report, and reflects the opinion of the inspector.
Please review all of the pages of the report as the summary alone does not explain all the issues.
INTERIOR
Page 6 Item: 4
Walls
Large cracks/holes present larger than typical - needs to be
further evaluated/serviced
Page 7 Item: 8
Floors
Uneven areas- needs to be serviced - hidden damage may exist
Damaged- needs to be serviced
Page 7 Item: 10
Windows
Stuck in position- needs to be serviced
Page 8 Item: 11
Doors
Gap at top- needs to be serviced
Page 8 Item: 14
Electrical
Outlet hot wired in reverse with neutral - needs to be serviced
Outlets missing covers/loose - needs to be serviced Large
amount of metal conduit visible - needs to be serviced
Page 9 Item: 15
Stairs & Handrails
Missing rails- unsafe - needs to be serviced
Page 9 Item: 18
Smoke Detector/s
Did not operate - needs to be serviced or replaced up/downstairs
BEDROOM/S
Page 11 Item: 3
Walls
Large cracks/holes present larger than typical - needs to be
further evaluated/serviced - upstairs
Page 11 Item: 5
Ceilings
Cracking/holes larger than typical - needs to be
evaluated/serviced - upstairs
Page 11 Item: 6
Ceiling Fan/s
Did not operate - needs to be serviced or replaced - upstairs
north west
Page 12 Item: 8
Floors
No flooring present - upstairs east
Page 12 Item: 10 Windows
Missing hardware- needs to be serviced - upstairs Did not
lock/latch- needs to be serviced - upstairs Deteriorated window
frames - needs to be serviced
Page 12 Item: 11 Doors
Damaged- needs to be serviced - upstairs Missing door knob needs to be serviced
Page 13 Item: 12 Electrical
Outlet/switch cover missing - needs to be serviced/repaired for
safety - various locations upstairs Non-energized (dead) outlets needs to be serviced - north east
Page 13 Item: 14 Smoke Detector/s
Missing - needs to be installed - all
BATHROOM/S
Page 14 Item: 3
Walls
Large holes in areas, recommend patching - upstairs
Page 15 Item: 7
Floors
Heavily torn- needs to be serviced - downstairs
Page 15 Item: 9
Windows
Did not lock/latch- needs to be serviced - downstairs
Page 16 Item: 17 Shower Walls
Heavily cracked tile - needs to be serviced/repaired - downstairs
Page 17 Item: 19 Toilet/s
Toilet loose at floor - needs to be serviced - upstairs
KITCHEN
Page 20 Item: 19 Electrical
Exposed connections - potential hazard needs to be serviced under counter near sink in cabinet Outlet/switch cover
damaged/missing - needs to be repaired for safety
HEATING/AIR CONDITIONING
Page 1 of 52

The Elite Group

754 N Currier St, Pomona, CA

Page 22 Item: 7
Page 23 Item: 9

Thermostat/s
Registers

Page 23 Item: 10

Heater Enclosure/s

Page 24 Item: 12
Page 24 Item: 13

Refrigerant Line/s
Air Conditioning
Compressor/s

WATERHEATER/S
Page 25 Item: 2
Venting
Page 25 Item: 5
Page 26 Item: 6

Overflow Line/s
Water Heater
Temperature

Page 26 Item: 11

Enclosure/s

ELECTRICAL/GAS SERVICE
Page 27 Item: 1
Main Panel

Page 27 Item: 3

Breakers

ATTIC AREA
Page 29 Item: 1

Structure

GARAGE AND/OR CARPORT


Page 31 Item: 2
Rafters & Ceilings
Page 31 Item: 5
Page 31 Item: 9

Garage Door
Opener/s
Fire Door/s

Page 32 Item: 10

Firewall/s

Page 32 Item: 16

Electrical

Damaged - needs to be serviced


Missing register cover(s) and return air grills - needs to be
serviced
Attic unit does not have proper catch pan below coil box - needs
to be serviced
Missing insulation at compressor unit - needs to be serviced
Service disconnect was pulled out upon arrival, inspector insert it
to test compressor, took out upon completion on inspection needs to be serviced
Missing screws at vent connections - needs to be serviced, three
screws are recommended at all vent connections
None - needs to be serviced/installed
Temperature was above 120 F at one or more fixtures within the
structure, this a potential scald hazard - needs to be
serviced/adjusted - consult a plumber
Holes in walls/ceiling areas - needs to be serviced Combustion
air vent screens damaged/missing - needs to be serviced Heavily
stains in subfloor from upstairs - needs to be serviced
Sharp-pointed metal screws hold panel cover in place. These are
a potential hazard as they may puncture wire insulation and
electrify panel box, becoming a shock or electrocution hazard.
These screws should be replaced with approved, flat-tipped screws.
Lights would dim periodically - needs to be further evaluated
No visible labeling for breakers on panel cover - needs to be
serviced
Framing has been altered or modified and is not original to the
structure - check all building permits to ensure that all framing was
installed to code Ridge beam/ rafters cut - needs to be serviced
Large stains- needs to be serviced and further evaluated for
possible leak
Large stains - needs to be serviced Not fire rating material at
ceiling - needs to be serviced
Did not operate - needs to be serviced
Emergency Egress Concern. Exterior door(s) have a double-sided
keyed dead bolt lock set. This type of lock requires a key to unlock
the door from the inside and can present an obstacle to anyone
trying to evacuate the home in the event of a fire. Window in
door not fire- resistive - needs to be serviced
Holes present - needs to be serviced to retain integrity of fire
separation
Open junction boxes - safety concern - recommend installing
proper covers, as needed, for safety Non-energized (dead) outlets
- needs to be serviced

EXTERIOR AREAS
Page 2 of 52

The Elite Group

754 N Currier St, Pomona, CA

Page 34 Item: 2

Siding

Page 34 Item: 3

Wood Trim

Page 34 Item: 5

Eaves & Facia

Page 35 Item: 6
Page 35 Item: 8

Exterior Paint
Exterior Window/s

RAISED FOUNDATION
Page 37 Item: 3
Sub Flooring
Page 38 Item: 10 Plumbing
GROUNDS
Page 39 Item: 1

Driveway/s and
Walkway/s

Page 39 Item: 3

Balcony/s

Page 39 Item: 4

Balcony and Deck


Railing

Page 40 Item: 5

Patio and Porch


Deck/s
Exterior Electrical

Page 40 Item: 6

Page 41 Item: 7
Page 41 Item: 8
Page 42 Item: 13

GFCI/s
Exterior Plumbing
and Faucet/s
Fencing and Walls

Page 42 Item: 15
ROOF
Page 43 Item: 1

Planter/s

Page 43 Item: 2
Page 44 Item: 3
Page 44 Item: 5

Flashing/s
Gutters and Down
Spout/s
Chimney/s

Page 44 Item: 6

Spark Arrestor/s

Condition

Deteriorated wood - needs to be serviced - consult termite


inspection
Deteriorated wood - needs to be serviced - consult termite
report
Deteriorated in areas - needs to be serviced - consult the termite
report
Blistered and peeling in areas - needs to be serviced
Deteriorating wood present - consult termite report - needs to be
serviced
Large stains - needs to be serviced - hidden damage may exist
Cast-iron drain pipes rusted and cysts at bottom - needs to be
serviced
Driveway displacement/lifting/uneven areas - trip hazard - needs
to be serviced Walkway displacement/uplifted/uneven areas potential trip hazard - needs to be serviced Cracking/chipping
large - needs to be serviced
Deteriorated wood - consult termite report - needs to be
serviced Cracked more than typical - needs to be serviced
Staircase and structure is loose - needs to be serviced Flooring
damaged - needs to be serviced
Railing weak - needs to be serviced Deteriorated wood - needs
to be serviced - consult termite report Heavily damaged - needs
to be serviced
Cracking/chipping large - needs to be serviced
Displaced/lifted/uneven areas trip hazard - needs to be serviced
Unsecured or loose wiring/conduit/electrical - needs to be
serviced
Recommend licensed electrician to further evaluate and repair to
assure the system is safe and operating properly
Exterior outlet/switch covers are missing or not of proper
exterior weather proof type - needs to be serviced
Test did not operate- needs to be serviced
Galvanized water piping present - recommend complete water
distribution system evaluation
Loose/leaning areas of fencing/walls needs to be serviced
Missing/damaged bricks - needs to be serviced
Heavily damaged due to tree roots - needs to be serviced
Wavy areas present - needs further evaluation by licensed roofer
Tree branches rub roof - needs to be serviced Heavily
weathered areas - needs to be replaced
Missing at roof to wall juncture - needs to be serviced
Heavily clogged/restricted by debris - needs to be serviced
Chimney has wooden structure built on it covering top - heavily
deteriorated - needs to be serviced
No spark arrestor/rain cap present - recommend installation
Page 3 of 52

The Elite Group

754 N Currier St, Pomona, CA

POOL AND/OR SPA


Page 45 Item: 1
Plumbing
Page 45 Item: 2
Pumps
Page 45 Item: 3
Jets
Page 45 Item: 6
Electrical
Page 46 Item: 7
GFCI/s
Page 46 Item: 11 Heater
Page 46 Item: 12
Page 46 Item: 13
Page 47 Item: 14
Page 47 Item: 15

Tile
Coping
Decking
Gate/s & fencing

Page 47 Item: 16
Page 47 Item: 17

Structure/s
Water Condition

Main drain cover not anti- vortex type - recommend upgrade


Corroded - needs to be serviced
Not functional - needs to be serviced
Exposed wires - potential hazard needs to be serviced
Tested did not operate - needs to be serviced
Burner chamber corroded/rusted - needs to be serviced Burner
chamber full of debris - needs to be serviced
Missing - needs to be serviced
Missing sections - needs to be serviced
Uneven/lifted/lipage in areas trip hazards present
No safety latches, self closers or alarms at doors (includes
screens) from house accessing pool area - needs to be serviced
Gate not self closing and latching properly - needs to be serviced
Multiple rough areas present - needs further evaluation
Dirty pool, debris present in areas - needs to be serviced/cleaned
Cloudy - needs to be serviced Completely discolored - needs to
be serviced

Page 4 of 52

The Elite Group

754 N Currier St, Pomona, CA

ABOUT YOUR INSPECTION


In order for you to receive the full value of this inspection, please read the information we have provided.
ALL ITEMS IN RED PRINT ARE OF IMMEDIATE CONCERN TO THIS STRUCTURE AND SHOULD BE FURTHER
EVALUATED BEFORE THE CLOSE IN ESCROW. HOWEVER, THE ENTIRE REPORT MUST BE READ FOR FULL
DISCLOSURE
During this inspection your inspector did not dismantle equipment, dismantle any structural items, apply
stress or destructive testing. Areas that are hidden and/or not readily visible are not covered in this report.
Our report is not a guarantee or warranty on the condition of your property or its contents. This report
provides an unbiased visual inspection only. The Elite Group inspections are performed with consideration
given to the age of the structure. Defects will be indicated and marked as such regardless if the condition is
normal for the age. These defects should be inspected by the appropriate licensed contractor. Opinions vary
from person to person and this report is the opinion of the inspector and must be considered as such. Your
report does not include all items covered in the REAL ESTATE TRANSFER DISCLOSURE FORM.
An attorney and/or real estate broker should be consulted on additional items not included in this report.
Mold spores, asbestos , formaldehyde, radon, lead paint, Chinese drywall, poria and all other toxic items of
concern cannot be identified as toxic and/or dangerous with this inspection report. Your inspector is not
certified to identify any of these toxic or dangerous items. It's recommended the client have the property
tested by a certified expert in these areas, in all cases.
PHOTO DOCUMENTATION
Your report also includes digitally imaged photos of certain problem areas (should they exist). Also included
are pictures (General Views) to establish location and identification.
Please carefully read your entire Inspection Report. Call your inspector after you have reviewed your report,
so we can go over any questions you may have. Remember, when the inspection is completed and the report
is delivered, we are still available to you for any questions you may have, throughout the entire closing
process. Properties being inspected do not "Pass" or "Fail. - The following report is based on an inspection
of the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending
upon the age of the property, some items like GFCI outlets may not be installed; this report will focus on
safety and function, not current code. This report identifies specific non-code, non-cosmetic concerns that
the inspector feels may need further investigation or repair.
For your safety and liability purposes, we recommend that licensed contractors evaluate and repair any and
all concerns and defects noted in the report.
Note that this report is a snapshot in time. We recommend that you or your representative carry out a final
walk-through inspection immediately before closing to check the condition of the property, using this
report as a guide. Conditions change during escrow time periods.
THIS REPORT IS NON-TRANSFERABLE TO ANOTHER PARTY, NO EXCEPTIONS.
THANK YOU FOR USING THE ELITE GROUP PROPERTY INSPECTION SERVICE, INC.

Page 5 of 52

The Elite Group

754 N Currier St, Pomona, CA


INTERIOR

See bedrooms, bathrooms, kitchen, and laundry area pages of the report for additional interior information. INSP = Inspected,
NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed contractor, NONE = Not
present at time of inspection

1. Notes
Evidence of alterations, remodels or additions at this property - We advise you to check
all building permits for all areas of the structures present, a home inspection is NOT a
building code violation inspection. If the proper building permits have not been
obtained and/or do not have final inspection signatures, then you cannot assume that
these areas were installed to proper building codes...further investigation beyond the
scope of the home inspection may be needed.
2. Utilities / General Comments
All Utilities are ON
Occupied structure - personal items throughout the structure may prevent access or
view to some areas
Multiple people are present at (arrived or left during) this inspection and may have
entered areas or operated appliances or fixtures after they have already been inspected
or reported on by the home inspector. The home inspector is not responsible for the
condition of these items or areas after they are inspected; the home inspector does not
go back an re-inspect the items/areas during this limited time inspection.
Buyer present during inspection Buyer's agent present during inspection Seller's
agent not present during inspection Owner present during inspection
3. Walls Constructed of/Coverings
Plaster
4. Walls
INSP

NINSP

NFE

NONE

Areas under construction/remodel/workers present - not inspected - check permits


Occupied structure some areas not accessible due to personal items Small
cracks/holes/chipped/dirty areas/cosmetic blemishes observed - typical for age of
structure Small cracking may be found throughout the structure, this is normal for
California construction and generally caused by settling, earthquake, and wind
conditions. Patched/partial painted areas present - consult seller regarding patched
areas Large cracks/holes present larger than typical - needs to be further
evaluated/serviced

5. Ceilings Constructed of/Coverings


Drywall Plaster Cork
6. Ceilings
INSP

NINSP

NFE

NONE

Some areas not fully visible due to height/angle/natural lighting/shadowing - N/A Small
cracks/holes/chipped/dirty areas/cosmetic blemishes observed - normal for age Small
cracking may be found throughout the structure, this is normal for California
construction and generally caused by settling, earthquake, and wind conditions.
Patched/partial painted areas present - consult seller regarding patched areas

7. Floor Coverings
Vinyl Hardwood Floating laminate

Page 6 of 52

The Elite Group

754 N Currier St, Pomona, CA

8. Floors
INSP

NINSP

NFE

NONE

Personal items prevent complete inspection in areas Under construction- not


inspected (areas upstairs) Uneven areas- needs to be serviced - hidden damage may
exist
Damaged- needs to be serviced

Damaged- needs to be serviced

Damaged- needs to be serviced

Uneven areas- needs to be serviced


- hidden damage may exist

9. Windows Constructed of
Single pane Aluminum framed Stationary Note: Vertical operating windows are
known to have sash cable/spring problems, although the problem may not exist at the
time of the inspection, we recommend that you check them often and repair these
windows upon discovery of any sash cable or spring problems.
10. Windows
INSP

NINSP

NFE

NONE

Note: Tint/film over windows is not inspected and often is


bubbled/loose/peeling/scratched - tint/film prevent an accurate inspection of the
window glass areas Note: Interior window shutters/blinds/coverings are not tested or
inspected as part of this home inspection (this includes all windows at the structure)
Only accessible windows were tested during this inspection Operated at time of
inspection Visible/accessible windows have worn frames/hardware/sills/tracks - typical
for age Recommend general window maintenance/lubrication and weather tight
service Could not access some areas due to furnishings - not inspected Could not
access some areas due to height - not inspected Could not access some areas due to
window coverings - not inspected Stuck in position- needs to be serviced

Stuck in position- needs to be serviced

Page 7 of 52

The Elite Group

754 N Currier St, Pomona, CA

11. Doors
INSP

NINSP

NFE

NONE

Note: Only accessible doors were tested during this inspection, personal items were not
disturbed or moved to test all doors. Operated at time of inspection Loose/worn
hardware needs minor service - typical for age Weathered/worn door(s) Gap at topneeds to be serviced

Gap at top- needs to be serviced


12. Screen Doors
INSP

NINSP

NFE

NONE

Security screen present Operated at time of inspection Rusted - aesthetic

13. Fireplace/s
INSP

NINSP

NFE

NONE

Location/s: Living room


Masonry
Could not access - not inspected Recommend evaluation by licensed masonry
contractor due to age

14. Electrical
INSP

NINSP

NFE

NONE

Note: Only the visible and accessible switches/outlets are testing during this inspection,
personal items are not moved to access any outlets/switches behind them.
Representative number of receptacles and switches tested and operational at time of
inspection Some outlets not accessible - not inspected Some switches not accessible
- not inspected Some switches have unknown function - not inspected inquire with
seller regarding operation Loose/worn outlets/switches - typical for age consider
replacement Outlet hot wired in reverse with neutral - needs to be serviced Outlets
missing covers/loose - needs to be serviced Large amount of metal conduit visible needs to be serviced

Outlet hot wired in reverse with


neutral - needs to be serviced

Large amount of metal conduit


visible - needs to be serviced

Outlets missing covers/loose needs to be serviced

Page 8 of 52

The Elite Group

754 N Currier St, Pomona, CA

Outlets missing covers/loose - needs to be serviced


15. Stairs & Handrails
INSP NINSP NFE NONE
Functional at time of inspection Weak steps - aesthetic Missing rails- unsafe - needs
X
X
to be serviced

Missing rails- unsafe - needs to be serviced


16. Closet/s
INSP

NINSP

NFE

NONE

Some closet areas not visible for inspection due to personal storage Worn closets with
loose/worn hardware - typical for age Doors/drawers did not close properly - normal
for age of materials Patched areas throughout inquire with seller Cracking small aesthetic

17. Door Bell/s


INSP

NINSP

NFE

NONE

Did not operate front - needs to be serviced

18. Smoke Detector/s


INSP NINSP NFE NONE
Note: Smoke detectors that are out of reach are not tested for functionality, all battery
X
X
operated smoke detectors should be within reach for testing and maintenance. For
safety purposes we recommend that smoke detectors be placed in all hallways outside
of sleeping areas (bedrooms) and on all levels of multi-level dwellings. For longer
hallways and/or oddly located bedrooms, multiple smoke detectors are suggested and
should be placed at each end of the hallways to ensure optimum safety alert. Did not
operate - needs to be serviced or replaced - up/downstairs

Page 9 of 52

The Elite Group

754 N Currier St, Pomona, CA

Did not operate - needs to be serviced or replaced - up/downstairs


19. Carbon Monoxide Detector/s
INSP NINSP NFE NONE
Note: Carbon monoxide detectors that are out of reach are not tested for functionality,
X
X
all battery operated and some plug-in model carbon monoxide detectors should be
within reach for testing and maintenance. Note: Carbon monoxide detectors are
tested via the accessible test button only, they are not tested/measured/evaluated per
manufacturer specifications for installation height or suggested locations. For safety
purposes we recommend that carbon monoxide detectors be placed in all hallways
outside of sleeping areas (bedrooms) and on all levels of multi-level dwellings. For
longer hallways and/or oddly located bedrooms, multiple carbon monoxide detectors
are suggested and should be placed at each end of the hallways to ensure optimum
safety alert. Operational at time of inspection via factory installed test button up/downstairs Not permanently mounted - needs to be serviced - downstairs

Not permanently mounted - needs to be serviced - downstairs

Page 10 of 52

The Elite Group

754 N Currier St, Pomona, CA


BEDROOM/S

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Location/s
Upstairs east Upstairs south east Upstairs south west Upstairs north west
Downstairs north Downstairs south
2. Walls Constructed of/Coverings
Drywall Plaster
3. Walls
INSP

NINSP

NFE

NONE

Occupied structure some areas not accessible due to personal items Small
cracks/holes/chipped/dirty areas/cosmetic blemishes observed - typical for age of
structure Small cracking may be found throughout the structure, this is normal for
California construction and generally caused by settling, earthquake, and wind
conditions. Areas under construction/remodel/workers present - not inspected - check
permits Large cracks/holes present larger than typical - needs to be further
evaluated/serviced - upstairs

4. Ceilings Constructed of/Coverings


Drywall Plaster
5. Ceilings
INSP

NINSP

NFE

NONE

Some areas not fully visible due to height/angle/natural lighting/shadowing - N/A Small
cracks/holes/chipped/dirty areas/cosmetic blemishes observed - typical for age of
structure Small cracking may be found throughout the structure, this is normal for
California construction and generally caused by settling, earthquake, and wind
conditions. Areas under construction/remodel/workers present - not inspected - check
permits Cracking/holes larger than typical - needs to be evaluated/serviced - upstairs

Cracking/holes larger than typical - needs to be evaluated/serviced - upstairs


6. Ceiling Fan/s
INSP

NINSP

NFE

NONE

Note: It is not possible to determine the method of attachment to the ceiling. These
units are heavy and due to the designed movement, must have the proper style
mounting boxes for correct and safe attachment. Recommend confirming the method
of attachment prior to use. This may require the removal of the fan or insulation to
visually verify proper support. Operated at time of inspection Worn unit Did not
operate - needs to be serviced or replaced - upstairs north west

7. Floor Coverings
Hardwood
Page 11 of 52

The Elite Group

754 N Currier St, Pomona, CA

8. Floors
INSP

NINSP

NFE

NONE

Scratched/chipped/worn areas Scratched heavily in areas Consult termite report for


wood floors Personal items prevent complete inspection in areas Under
construction- not inspected
No flooring present - upstairs east

9. Windows Constructed of
Single pane Double pane Aluminum framed Wood framed Crank style wood
framed Stationary Note: Vertical operating windows are known to have sash
cable/spring problems, although the problem may not exist at the time of the
inspection, we recommend that you check them often and repair these windows upon
discovery of any sash cable or spring problems.
10. Windows
INSP

NINSP

NFE

NONE

Operated at time of inspection Visible/accessible windows have worn


frames/hardware/sills/tracks - typical for age Recommend general window
maintenance/lubrication and weather tight service Could not access some areas due to
furnishings - not inspected Could not access some areas due to height - not inspected
Could not access some areas due to window coverings - not inspected Missing
hardware- needs to be serviced - upstairs Did not lock/latch- needs to be serviced upstairs Deteriorated window frames - needs to be serviced

Deteriorated window frames - needs to be serviced

Missing hardware- needs to be serviced - upstairs

11. Doors
INSP

NINSP

NFE

NONE

Note: Only accessible doors were tested during this inspection, personal items were not
disturbed or moved to test all doors. Operated at time of inspection Loose/worn
hardware needs minor service - typical for age Under construction - not tested or
inspected Damaged- needs to be serviced - upstairs Missing door knob - needs to be
serviced

Damaged- needs to be serviced - upstairs

Page 12 of 52

The Elite Group

754 N Currier St, Pomona, CA

12. Electrical
INSP

NINSP

NFE

NONE

Note: Only the visible and accessible switches/outlets are testing during this inspection,
personal items are not moved to access any outlets/switches behind them.
Representative number of receptacles and switches tested and operational at time of
inspection Loose/worn outlets/switches - typical for age, consider upgrading Bulb
defective/missing/light(s) did not function - check bulbs/consult electrician to further
evaluate Outlet/switch cover missing - needs to be serviced/repaired for safety various locations upstairs Non-energized (dead) outlets - needs to be serviced - north
east

Outlet/switch cover missing - needs to be


serviced/repaired for safety - various locations
upstairs

Non-energized (dead) outlets - needs to be serviced north east

13. Closet/s
INSP

NINSP

NFE

NONE

Some closet areas not visible for inspection due to personal storage Worn closets with
loose/worn hardware - typical for age Doors/drawers do not open/close properly normal for the age of the structure Closet doors missing - needs to be serviced

14. Smoke Detector/s


INSP NINSP NFE NONE
Missing - needs to be installed - all
X X

Page 13 of 52

The Elite Group

754 N Currier St, Pomona, CA


BATHROOM/S

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Location/s
Upstairs Downstairs
2. Walls Constructed of/Coverings
Plaster
3. Walls
INSP

NINSP

NFE

NONE

No visible mold found at the time of the inspection Remodeled bathroom - check
permits for all remodeled areas Small cracks/holes/chipped/dirty areas/cosmetic
blemishes observed - normal for age of structure Small cracking may be found
throughout the structure, this is normal for California construction and generally caused
by settling, earthquake, and wind conditions. Patched/partial painted areas present consult seller regarding patched areas Large holes in areas, recommend patching upstairs

Large holes in areas, recommend patching - upstairs


4. Ceilings Constructed of/Coverings
Drywall Plaster
5. Ceilings
INSP

NINSP

NFE

NONE

Some areas not fully visible due to height/angle/natural lighting/shadowing - N/A


Recently painted throughout structure Small cracks/holes/chipped/dirty areas - normal
for age Small cracking may be found throughout the structure, this is normal for
California construction and generally caused by settling, earthquake, and wind
conditions. Patched/partial painted areas present - consult seller regarding patched
areas Stains/blistered areas present - tested dry with moisture meter - downstairs

Stains/blistered areas present - tested dry with moisture meter - downstairs


Page 14 of 52

The Elite Group

754 N Currier St, Pomona, CA

6. Floor Coverings
Vinyl Vinyl tile
7. Floors
INSP

NINSP

NFE

NONE

Personal items prevent complete inspection in areas Worn and stained areas- typical
for age of the material Heavily torn- needs to be serviced - downstairs

Heavily torn- needs to be serviced - downstairs


8. Windows Constructed of
Single pane Aluminum framed Louver type aluminum framed
9. Windows
INSP

NINSP

NFE

NONE

Only accessible windows were tested during this inspection Operated at time of
inspection Visible/accessible windows have worn frames/hardware/sills/tracks - typical
for age Worn windows/frames/hardware/tracks - typical for age of material Did not
lock/latch- needs to be serviced - downstairs

Did not lock/latch- needs to be serviced - downstairs


10. Doors
INSP

NINSP

NFE

NONE

Operated at time of inspection Loose/worn hardware needs minor service - typical for
age

11. Counter/s
INSP

NINSP

NFE

NONE

Some counter areas not visible for inspection due to personal storage Counter is
worn/scratched/older - typical wear for age

Page 15 of 52

The Elite Group

754 N Currier St, Pomona, CA

12. Cabinet/s
INSP

NINSP

NFE

NONE

NFE

NONE

Some interior cabinet areas not visible for inspection due to personal storage Worn
cabinets with loose/worn hardware - typical for age Stained and worn areas below
sink/s - dry at the time of the inspection Loose/worn hardware No visible mold found
at the time of the inspection

13. Sink/s
INSP

NINSP

Some areas not visible/accessible due to personal items Worn fixture/sink - typical for
the age

14. Mirror/s
INSP

NINSP

NFE

NONE

Mirror functional at time of inspection Worn/older - typical wear for age

15. Bath Tub/s


INSP

NINSP

NFE

NONE

Note - tubs are not filled to overflow opening to test Some areas not visible due to
personal items Fixture was tested and operating at the time of the inspection Fixture
was in a worn/older condition at the time of the inspection - typical for age Tub is
worn/older/stained/scratched/chipped - typical for the age

16. Shower/s
INSP

NINSP

NFE

NONE

Note: Shower drains are not plugged and the pan long-term tested - consult termite
report Some areas not visible due to personal items Tub/Shower combo present see tub notes for additional information Fixture was tested and operating at time of
inspection via normal fixture controls Fixture was in a worn and older condition typical for the age

17. Shower Walls


INSP

NINSP

NFE

NONE

Some areas not visible/accessible for inspection due to personal items present Shower
pans are not long-term water tested - consult the termite report Tile and grout present
Worn tile/grout Recommend grout and sealer maintenence Grout/caulking is dirty
or stained - recommend cleaning and drying all surfaces that may accumulate moisture
Cracked/loose/missing grout in areas - recommend grout and sealer Heavily cracked
tile - needs to be serviced/repaired - downstairs

Heavily cracked tile - needs to be serviced/repaired - downstairs


18. Enclosures / Shower doors
INSP NINSP NFE NONE
Some areas not visible due to personal items present Operational at time of inspection
X
Cannot determine if tempered Enclosure door(s) in a worn/older condition with
loose/worn hardware - typical for the age Corrosion present in areas - signs of wear
and moisture accumulation Shower curtain - N/A
Page 16 of 52

The Elite Group

754 N Currier St, Pomona, CA

19. Toilet/s
INSP

NINSP

NFE

NONE

Tested and operational at time of inspection via normal fixture controls, flush test
performed Toilet is in a worn and older condition at the time of the inspection - typical
for age No visible leaking at the time of inspection Stained/worn bowl Toilet loose
at floor - needs to be serviced - upstairs

Toilet loose at floor - needs to be serviced - upstairs


20. Plumbing
INSP

NINSP

NFE

NONE

Note: The plumbing supply valves are visually inspected only and are not tested for
functionality due to the potential for leakage - valves that are not used often will seize or
freeze and are likely to leak when operated (opened/closed). Some areas not visible
due to personal items Operational at time of inspection via normal fixture controls - no
visible leaks observed Angle stops/hoses/drain pipes are worn/older - recommend
upgrading these areas with new fixtures No visible leaks found at the time of the
inspection Trap not visible and could not be inspected

21. Electrical
INSP

NINSP

NFE

NONE

NFE

NONE

Representative number of receptacles and switches tested and operational at time of


inspection Loose/worn outlets/switches - typical for age consider replacement Bulb
defective/light did not function - check bulb/consult an electrician to evaluate

22. GFCI/s
INSP

NINSP

Tested and operational at time of inspection via normal control GFCI not grounded typical for old ungrounded system pre-1965 GFCI and light/fans on same circuit;
upgrade for more convenient use

23. Exhaust Fan/s


INSP

NINSP

NFE

NONE

Operated at time of inspection Worn/older fan

24. Heating
INSP

NINSP

NFE

NONE

See HVAC page for more information about this section Central unit

Page 17 of 52

The Elite Group

754 N Currier St, Pomona, CA


KITCHEN

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Walls Constructed of/Coverings


Drywall Granite
2. Walls
INSP

NINSP

NFE

NONE

Occupied structure some areas not accessible due to personal items/appliances


Appliances present and are not moved for inspection - limited inspection of walls, floors,
cabinet areas covered by appliances Small cracks/holes/chipped/cosmetic blemishes
observed - normal for age of structure Small cracking may be found throughout the
structure, this is normal for California construction and generally caused by settling,
earthquake, and wind conditions. No visible mold found at the time of the inspection

3. Ceilings Constructed of/Coverings


Drywall
4. Ceilings
INSP

NINSP

NFE

NONE

Some areas not fully visible due to height/angle/natural lighting/shadowing - N/A


Some ceiling areas not accessible/inspected due to personal dcor Small
cracks/holes/chipped/dirty areas - normal for age Small cracking may be found
throughout the structure, this is normal for California construction and generally caused
by settling, earthquake, and wind conditions.

5. Floor Coverings
Floating laminate
6. Floors
INSP

NINSP

NFE

NONE

Personal items prevent complete inspection in areas Worn and stained areas- typical
for age of the material

7. Counters
INSP

NINSP

NFE

NONE

Some counter areas not visible for inspection due to personal storage Counter is
worn/cracked/scratched/etc. - typical for age

8. Cabinet/s
INSP

NINSP

NFE

NONE

NFE

NONE

Some interior cabinet areas not visible for inspection due to personal storage Worn
cabinets - loose/worn hardware - typical for age Stained areas below sink - dry at time
of inspection Doors and drawers did not close properly - typical for age No visible
mold found at the time of this inspection

9. Sink/s
INSP

NINSP

Some areas not visible due to personal items Worn fixtures/sink - typical for age

10. Spray Wand/s


INSP

NINSP

NFE

NONE

Sprayer not operating properly - needs to be serviced

Page 18 of 52

The Elite Group

754 N Currier St, Pomona, CA

Sprayer not operating properly - needs to be serviced


11. Soap Dispenser/s
INSP NINSP NFE NONE
No soap present - not inspected or tested
X
12. Dishwasher/s
INSP

NINSP

NFE

NONE

None installed

13. Garbage Disposal/s


INSP NINSP NFE NONE
None installed
X
14. Plumbing
INSP

NINSP

NFE

NONE

Note: The plumbing supply valves are visually inspected only and are not tested for
functionality due to the potential for leakage - valves that are not used often will seize or
freeze and are likely to leak when operated (opened/closed). Some areas not
visible/accessible due to personal items present Operational at time of inspection via
normal fixture controls - no visible leaks observed Angle stops/hoses are worn/older recommend upgrading these areas with new fixtures Trap not visible - N/A

15. Range/s
INSP

NINSP

NFE

NONE

Note: The range or cooktop has a limited inspection, the Inspector cannot predict the
remaining life of the unit nor determine the BTUs output by each burner or if/how well
the burners will cook food. Gas - tested and operational at time of inspection via
normal controls Normal wear for age - no major visible defects

16. Oven/s
INSP

NINSP

NFE

NONE

Note: The "Bake" feature is the only feature operated during a home inspection;
convection, browning, rotisserie, warming drawers and other features are not tested
during the oven inspection. Ovens are tested for basic heating element functionality.
The oven cannot be tested to each incremental temperature setting or determine if
adequate cooking temperatures can be achieved, nor if temperatures are calibrated with
oven settings. We cannot determine if or how well the oven cooks food nor can we
predict the remaining life left for the unit. Personal storage/pots/pans inside - unit was
not tested Anti-tip device is not visible/not tested - we recommend that an anti-tip
device be installed to prevent a possible tip hazard

17. Microwave/s
INSP

NINSP

NFE

NONE

Portable (non built-in type) unit present - not tested

Page 19 of 52

The Elite Group

754 N Currier St, Pomona, CA

18. Exhaust Vent/s


INSP

NINSP

NFE

NONE

Hood with fan


Note: The exhaust fan/vent is testing using the normal controls only. No smoke testing
or other testing is done to determine the CFMs or how well the unit evacuates air. The
home inspector cannot predict the remaining life left in the unit. Tested and
operational at time of inspection via normal controls Unit is worn/older replacement/repairs/maintenance will be required in the near future Worn/dirty
filters, recommend cleaning Greasy/dirty unit - recommend cleaning Missing buttons
- needs to be serviced

19. Electrical
INSP

NINSP

NFE

NONE

Representative number of receptacles and switches tested and operational at time of


inspection Some outlets not accessible - not inspected Some switches not accessible
- not inspected Some switches have unknown function - not inspected inquire with
seller regarding operation Loose/worn outlets/switches - typical for age, consider
replacement Bulb defective/light did not function - check bulb/consult an electrician to
further evaluate Exposed connections - potential hazard needs to be serviced - under
counter near sink in cabinet Outlet/switch cover damaged/missing - needs to be
repaired for safety

Exposed connections - potential hazard needs to be serviced - under counter near sink in cabinet
20. GFCI/s
INSP

NINSP

NFE

NONE

None installed recommend upgrade for increased safety

Page 20 of 52

The Elite Group

754 N Currier St, Pomona, CA


LAUNDRY AREA

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Laundry Area Location


NOTE: The laundry area receives a limited inspection: washer and dryer units (if
present) are not operated or tested for functionality nor are they moved to inspect
walls/ceilings/floors/etc beneath or around them. The interior areas of the dryer vent
are not inspected for obstructions. The laundry plumbing supply valves are not
operated. Water is not run through the laundry drain during this inspection. Interior
hall area
2. Dryer Vent/s
INSP

NINSP

NFE

NONE

Note: Dryer vent should be cleaned periodically to prevent lint fire hazards Some
exterior areas of the structure are not visible due to personal storage/vegetation in
areas Could not fully inspect the dryer vent in the laundry area, it is obscured by
cabinetry/washer/dryer Worn exterior cover - typical for age

3. Plumbing
INSP

NINSP

NFE

NONE

Note: The plumbing supply valves are visually inspected only and are not tested for
functionality due to the potential for leakage - valves that are not used often will seize or
freeze and are likely to leak when operated (opened/closed). The laundry drain cannot
be tested at this inspection. The washer and dryer (if present) are not tested or
inspected. Washer/dryer unit(s) present during inspection and obstruct the view of the
wall/plumbing areas Visible fixtures were worn/old - typical wear for age No visible
leaks at time of inspection Drain trap is not visible at the time of the inspection - n/a note: laundry drains are not water or pressure tested during this inspection

4. Gas Valve/s
INSP

NINSP

NFE

NONE

Note: The inspector does not check for gas leaks, consult the Gas Company to evaluate
all gas areas prior to occupancy Worn valve - recommend upgrading to newer style
valve

5. Electrical
INSP

NINSP

NFE

NONE

NFE

NONE

Washer/dryer unit(s) present during inspection and obstruct the view of the
wall/electrical areas Some outlets/switches not accessible - not inspected
Representative number of receptacles and switches tested and operational at time of
inspection Loose/worn outlets/switches - typical for age consider replacement

6. GFCI/s
INSP

NINSP

None installed recommend upgrade for increased safety

7. Exhaust Fan/s
INSP

NINSP

NFE

NONE

None

Page 21 of 52

The Elite Group

754 N Currier St, Pomona, CA


HEATING/AIR CONDITIONING

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Heater/s
INSP

NINSP

NFE

NONE

Location: Attic
Type: Gas fired forced hot air Split system
Note: Inspector does not examine heat exchanger or determine the presence of a
cracked heat exchanger - this is not a complete evaluation of the internal areas of the
heater - consult an HVAC contractor for further evaluation if you have concerns about
the heat exchanger Operated at time of inspection Unit has normal wear for age at
the time of the inspection - no major visible defects This unit is a newer unit/not
original to the structure - check all installation permits to ensure that this unit was
installed to code Recommend regular service/maintenence to extend the life of the
unit

2. A/C Evaporator Coil Box


INSP NINSP NFE NONE
Note: The a/c coil box is only examined on the exterior - an internal inspection is not
X
completed on the coil box - consult a HVAC contractor to further evaluate as needed
Note: This inspection does not determine if the evaporator coil BTU size is the same as
condensing unit size - consult a HVAC contractor for further evaluation as needed The
visible areas of the coil box are worn/dirty/deteriorated and typical for the age of this
older unit Condensation lines cannot be traced to all locations by the inspector, often
times there are several areas of the condensate lines that are not visible to the inspector
- consult a HVAC contractor to further evaluate as needed Unable to determine the
output of the condensation drain line(s) - consult a HVAC contractor to evaluate
3. Venting
INSP

NINSP

NFE

NONE

Some areas not visible due to personal items/storage/etc. and cannot be viewed for
inspection The visible areas of the vent are worn and deteriorated - typical for the age
of the material

4. Air Supply
INSP

NINSP

NFE

NONE

Recommend seasonal service and maintenance to ensure that all areas are
sealed/cleaned/dry and functioning normally at all times Some areas not visible due to
personal items/storage/duct work/ insulation outer wrapping Normal at time of
inspection - no major visible defects

5. Gas Supply Valve/s and Pipe/s


INSP NINSP NFE NONE
Normal wear at time of inspection - no major visible defects No sediment trap at gas
X
supply - may have not been required at time of original installation, but is recommended
6. Electrical
INSP

NINSP

NFE

NONE

Operating properly at the time of the inspection - no major visible defects

7. Thermostat/s
INSP

NINSP

NFE

NONE

Standard mechanical type present - functional day of the inspection Damaged - needs
to be serviced

Page 22 of 52

The Elite Group

754 N Currier St, Pomona, CA

Damaged - needs to be serviced


8. Filter/s
INSP

NINSP

NFE

NONE

Located on the side of the heater


A seasonal HVAC service contract is recommended to ensure that all filters
changed/cleaned regularly or as needed We recommend that the filters be change or
cleaned every 3 to 6 months depending on the usage of the heating and air conditioning
systems Filter is worn/dirty and will likely need changing soon

9. Registers
INSP

NINSP

NFE

NONE

No heat source in multiple rooms - needs to be serviced Heater Temperature at


Registers: 110 degrees A/C Temperature at Registers: 52 degrees Temperature at Air
Return:80 degrees Representative number tested and functional day of the inspection
Note: The inspector cannot determine if asbestos exists in any part of the HVAC
system - consult an asbestos testing company if you have concerns about asbestos
Note: Adjustable louvers in registers are not tested for functionality - those closed for
long periods of time may not operate properly Note: Not all registers are tested for air
flow due to location, access, etc. Visible register covers are worn and older - consider
upgrading to newer style registers Missing register cover(s) and return air grills - needs
to be serviced

Heater Temperature

A/C Temperature

10. Heater Enclosure/s


INSP NINSP NFE NONE
Attic unit does not have proper catch pan below coil box - needs to be serviced
X
X
11. Platform/Base/s
INSP NINSP NFE NONE
Not applicable
X

Page 23 of 52

The Elite Group

754 N Currier St, Pomona, CA

12. Refrigerant Line/s


INSP NINSP NFE NONE
Missing insulation at compressor unit - needs to be serviced
X
X

Missing insulation at compressor unit - needs to be serviced


13. Air Conditioning Compressor/s
INSP NINSP NFE NONE
Location: Electric unit - exterior south
X
X
Worn/weathered unit recommend seasonal service/maintenance Operated at the
time of inspection Recommend regular service/maintenence to extend the life of the
unit Service disconnect was pulled out upon arrival, inspector insert it to test
compressor, took out upon completion on inspection - needs to be serviced

Page 24 of 52

The Elite Group

754 N Currier St, Pomona, CA


WATERHEATER/S

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Water Heater/s Condition


INSP NINSP NFE NONE
Number of gallons: Personal items/storage prevent access/view of unit - limited
X
inspection
Location/s: Hall coset Gas
Note: The water heater is visually inspected only, the combustion/pilot doors are not
removed for flame or burner condition inspection due to the potential for draft to burn
out the pilot flame. The Inspector cannot predict the remaining life of the unit.
Operated at the time of the inspection The unit is worn/older - consult a plumber for
general maintenance recommendations to extend the life of the unit
2. Venting
INSP

NINSP

NFE

NONE

Missing screws at vent connections - needs to be serviced, three screws are


recommended at all vent connections

Missing screws at vent connections - needs to be serviced, three screws are recommended at all vent
connections
3. Plumbing
INSP

NINSP

NFE

NONE

Material type: Copper has been added/upgraded (not original) - check all installation
permits
Worn valve/piping/connections - typical for age

4. Temperature Pressure Release Valve/s


INSP NINSP NFE NONE
Note: The inspector visually inspects the TPRV only - this valve is not opened or tested
X
during the inspection Worn/older valve present - consider upgrading
5. Overflow Line/s
INSP

NINSP

NFE

NONE

None - needs to be serviced/installed

Page 25 of 52

The Elite Group

754 N Currier St, Pomona, CA

None - needs to be serviced/installed


6. Water Heater Temperature
INSP NINSP NFE NONE
Note: Temperature can be taken at the exhaust draft diverter location, but may not
X
X
represent the actual temperature at the interior fixtures within the structure - see all
photos attached to the report 100 F
Temperature was above 120 F at one or more fixtures within the structure, this a
potential scald hazard - needs to be serviced/adjusted - consult a plumber
7. Strapping
INSP

NINSP

NFE

NONE

Standard metal type straps present - normal wear on the day of the inspection - no
major visible defects Recommend blocking in areas where the water heater is not
touching the walls

8. Gas Valve/s
INSP

NINSP

NFE

NONE

Worn valve - consider upgrading to newer style No sediment trap at gas supply sediment trap is recommended

9. Combustion Air
INSP

NINSP

NFE

NONE

Combustion air appears to be adequate at the time of the inspection

10. Platform/Base/s
INSP NINSP NFE NONE
None/not applicable - unit is sitting on concrete
X
11. Enclosure/s
INSP

NINSP

NFE

NONE

Holes in walls/ceiling areas - needs to be serviced Combustion air vent screens


damaged/missing - needs to be serviced Heavily stains in subfloor from upstairs needs to be serviced

Heavily stains in subfloor from upstairs - needs to be serviced


Page 26 of 52

The Elite Group

754 N Currier St, Pomona, CA


ELECTRICAL/GAS SERVICE

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Main Panel
INSP

NINSP

NFE

NONE

Location/s: East side of the structure


Note: Panels are visually inspected only, the inspector does not perform a load
calculation to determine service capacity adequacy Worn/older panel - consider
upgrading services Sharp-pointed metal screws hold panel cover in place. These are a
potential hazard as they may puncture wire insulation and electrify panel box, becoming
a shock or electrocution hazard. These screws should be replaced with approved, flattipped screws. Lights would dim periodically - needs to be further evaluated

Sharp-pointed metal screws hold panel cover in place. These are a potential hazard as they may puncture
wire insulation and electrify panel box, becoming a shock or electrocution hazard. These screws should be
replaced with approved, flat-tipped screws.
2. Sub Panel/s
INSP

NINSP

NFE

NONE

Location: Interior wall


Panel cover is painted over and cannot be removed without damage to the paint/walls wiring was not inspected Worn/older panel - consider upgrading services

General view
3. Breakers
INSP

NINSP

NFE

NONE

Type of wiring: Copper Panel cover was not removable due to painted over/stripped
screws/etc. interior wiring and breakers could not be inspected N/A
Note: Breakers are visually inspected only - the inspector does not perform any
electrical stress tests on the system to determine if a breaker trips properly (consult an
electrician for further evaluation, if this is a concern) Worn/old breakers - may require
replacement at any time No visible labeling for breakers on panel cover - needs to be
serviced

Page 27 of 52

The Elite Group

754 N Currier St, Pomona, CA

4. Panel Wiring
INSP

NINSP

NFE

NONE

Note: Some wire types cannot be determined due to wire casings cover wires entering
the breakers. Wiring type: copper - main Note: Ungrounded outlets may be present
in older structures (pre-1965) even if the main or sub panels have been upgraded. The
inspector cannot determine if all wiring has been updated. Expect to find ungrounded
outlets in older homes (pre-1965) Note: Inspector does not perform a load calculation
to determine service capacity adequacy Panel cover is painted over and cannot be
removed without damage to the paint/walls - wiring was not inspected

5. Cable Feeds
INSP

NINSP

NFE

NONE

Overhead - worn/weathered - needs service/maintenance

6. Main Gas Valve


INSP

NINSP

NFE

NONE

Location: West side of the structure


Natural gas present
Worn valve - typical for age Minor rusting - typical for exterior weathering recommend rust treatment No seismic safety valve present - recommend installation
for increased safety

General view
7. Gas Pipe/s and Valve/s
INSP NINSP NFE NONE
Note: We recommend the gas supplier be contacted to safety check all fuel gas
X
systems/appliances prior to occupancy, the inspector cannot determine if gas lines are
properly protected in the ground. Note: Exterior gas lines, fire pits, BBQs, etc. are not
included as part of this inspection - consult your gas supplier company to further
evaluate these areas and check permits for any added gas lines, fire pits, BBQs, etc.
Worn meter/piping - typical for age and exterior weathering

Page 28 of 52

The Elite Group

754 N Currier St, Pomona, CA


ATTIC AREA

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Structure
INSP

NINSP

NFE

NONE

Limited attic inspection - many areas are not accessible to to limited space, lack of
proper walk boards, electrical, plumbing, ductwork, etc. Cracking small at wood
members - typical for age Framing has been altered or modified and is not original to
the structure - check all building permits to ensure that all framing was installed to code
Ridge beam/ rafters cut - needs to be serviced Large stains- needs to be serviced and
further evaluated for possible leak

Ridge beam/ rafters cut - needs to be serviced

Large stains- needs to be serviced and further


evaluated for possible leak

2. Insulation
INSP

NINSP

NFE

NONE

Material type: Loose fill


Approximate depth: 8 inches
Note: The inspector does not determine the presence of asbestos or any other
hazardous materials in the building Note: The inspector does not determine R-value of
the insulation Note: Insulation generally blocks visible inspection access to framing
below level of insulation Limited access/access hindrances prevent visible inspection of
areas of insulation All visible insulation is worn/older/dirty - typical for the age of the
structure

3. Ventilation
INSP

NINSP

NFE

NONE

Note: Temperature sensors or operation of mechanical fans not tested/inspected


Some areas not visible due to personal storage/insulation/access hindrances Existing
ventilation appeared to be functional on the day of the inspection

4. Vent Screens
INSP

NINSP

NFE

NONE

Some areas not visible due to personal storage/insulation/access hindrances Visible


ventilation screens appeared to be functional at time of inspection

5. Exhaust Vent/s
INSP

NINSP

NFE

NONE

Some areas not visible due to personal storage/insulation/access hindrances Some


vents are not visible or accessible and cannot be inspected - N/A All visible vents
appear to be in normal condition where visible - no major visible defects

Page 29 of 52

The Elite Group

754 N Currier St, Pomona, CA

6. Duct Work
INSP

NINSP

NFE

NONE

Note: The inspector does not determine the presence of asbestos or any other
hazardous materials in the duct work - if there is any concern about asbestos in the duct
work we recommend that the client have the ducts tested as needed. Note: The
inspector cannot determine efficiency or effectiveness of the duct layout - check all
installation permits Some areas not visible due to personal storage/insulation/access
hindrances Limited inspection/access due to structure and duct layout Older/worn
ducts present - recommend routine maintenance and cleaning to extend the life of the
existing ducts

7. Electrical
INSP

NINSP

NFE

NONE

Evidence of electrical alterations in the attic - check all permits for electrical alterations
to ensure that all electrical was installed to city/county electrical code Most electrical
not accessible and not inspected Attic light operated via normal fixture control

8. Plumbing
INSP

NINSP

NFE

NONE

Some areas not visible due to personal storage/insulation/access hindrances Vents


only - no other plumbing/piping is visible for inspection

9. Access Entry/s
INSP

NINSP

NFE

NONE

Access door is dirty with cosmetic blemishes present

10. Chimney/s
INSP

NINSP

NFE

NONE

Not visible/accessible for inspection

Page 30 of 52

The Elite Group

754 N Currier St, Pomona, CA


GARAGE AND/OR CARPORT

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Roof Condition
INSP

NINSP

NFE

NONE

Living space above entire garage area

2. Rafters & Ceilings


INSP NINSP NFE NONE
Garage has alterations to ceiling and walls - check permits Patched areas- inquire with
X
X
seller regarding reason for repairs Large stains - needs to be serviced Not fire rating
material at ceiling - needs to be serviced
3. Main Automotive Door/s
INSP NINSP NFE NONE
Type: Metal sectional
X
Recommend weather tight service/maintenance to prevent moisture intrusion around
main door area Worn/weathered door - typical for age and exposure to weather
4. Hardware/Springs
INSP NINSP NFE NONE
Door did not operate - could not test
X
5. Garage Door Opener/s
INSP NINSP NFE NONE
Worn/older model - suggest upgrading to modern unit Missing cover Did not
X
X
operate - needs to be serviced
6. Garage Door/s Reverse Safety Status
INSP NINSP NFE NONE
Could not test due to door opener not operating
X
7. Exterior Door/s
INSP

NINSP

NFE

NONE

Operated at the time of inspection Worn/weathered door - typical for age


Loose/worn hardware - needs minor service Recommend weather tight
service/maintenance to prevent moisture intrusion

8. Exterior Door Screen/s


INSP NINSP NFE NONE
Security screen present - operated at the time of inspection Rusted - aesthetic
X
9. Fire Door/s
INSP

NINSP

NFE

NONE

Door locked - not tested or inspected Emergency Egress Concern. Exterior door(s) have
a double-sided keyed dead bolt lock set. This type of lock requires a key to unlock the
door from the inside and can present an obstacle to anyone trying to evacuate the home
in the event of a fire. Window in door not fire- resistive - needs to be serviced

Page 31 of 52

The Elite Group

754 N Currier St, Pomona, CA

Emergency Egress Concern. Exterior door(s) have a double-sided keyed dead bolt lock set. This type of lock
requires a key to unlock the door from the inside and can present an obstacle to anyone trying to evacuate
the home in the event of a fire.
10. Firewall/s
INSP

NINSP

NFE

NONE

Personal items/storage/etc. are present and prevent a complete inspection of firewall


areas Recommend sealing any holes/gaps/cracks/loose tape all areas of the firewall
should be properly sealed with the correct fire-rated materials Holes present - needs to
be serviced to retain integrity of fire separation

11. Walls
INSP

NINSP

NFE

NONE

Personal items/storage/etc. are present and prevent a complete inspection of wall areas
Small cracks/holes/chipped/dirty areas/cosmetic blemishes observed - typical for age
of structure

12. Anchor Bolts


INSP

NINSP

NFE

NONE

Could not access - not inspected

13. Cabinet/s
INSP

NINSP

NFE

NONE

Not accessible for inspection

14. Counter/s
INSP

NINSP

NFE

NONE

NFE

NONE

Not accessible for inspection

15. Slab
INSP

NINSP

Personal items/storage/vehicles prevent complete inspection of floor areas Small


cracks/chipped areas - typical for the age of the materials

16. Electrical
INSP

NINSP

NFE

NONE

Personal items/storage prevents access and complete inspection to some electrical


areas Lighting did not function - check bulb/consult an electrician for further
evaluation The accessible outlets were tested and operating at the time of the
inspection The accessible switches and lighting was tested and operating at the time of
the inspection Open junction boxes - safety concern - recommend installing proper
covers, as needed, for safety Non-energized (dead) outlets - needs to be serviced

Page 32 of 52

The Elite Group

754 N Currier St, Pomona, CA

Non-energized (dead) outlets - needs to be serviced

Open junction boxes - safety concern - recommend


installing proper covers, as needed, for safety

17. GFCI/s
INSP

NINSP

NFE

NONE

None visible - recommend upgrade for increased safety

18. 240 Volt Receptacle


INSP NINSP NFE NONE
Not present/visible - not inspected or tested
X
19. Ventilation
INSP

NINSP

NFE

NONE

None recommend ventilation for garage

Page 33 of 52

The Elite Group

754 N Currier St, Pomona, CA


EXTERIOR AREAS

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Stucco
INSP

NINSP

NFE

NONE

None present - siding only (see siding notes)

2. Siding
INSP

NINSP

NFE

NONE

Constructed of: Wood Stone


Note: Siding requires periodic seasonal maintenance, consult an exterior finish
contractor for maintenance tips/schedules/suggestions Some not accessible for
inspection due to vegetation/personal items/height/limited access - these areas cannot
be visibly inspected
Deteriorated wood - needs to be serviced - consult termite inspection

Deteriorated wood - needs to be serviced - consult termite inspection


3. Wood Trim
INSP

NINSP

NFE

NONE

Note: For damaged wooden areas and moisture problems (mold/mildew) always obtain
a structural pest control inspection; Inspector does not determine wood destroying
organism presence or damage - always obtain a structural pest control inspection;
Inspector does not use specialized instruments to detect moisture, if any, under
siding/trim surface
Some not accessible for inspection due to vegetation/personal items/height/limited
access - not visible for inspection
Deteriorated wood - needs to be serviced - consult termite report

4. Weep Screeds
INSP

NINSP

NFE

NONE

No weep screeds present - typical for age

5. Eaves & Facia


INSP

NINSP

NFE

NONE

Note: Inspector does not determine wood destroying organism presence or damage always obtain a structural pest control inspection
Some not accessible or visible for inspection due to vegetation/personal
items/height/angle Consult termite report for all wood areas at the structure
Deteriorated in areas - needs to be serviced - consult the termite report

Page 34 of 52

The Elite Group

754 N Currier St, Pomona, CA

Deteriorated in areas - needs to be serviced - consult the termite report


6. Exterior Paint
INSP

NINSP

NFE

NONE

Paint is recommended to help maintain and seal the exterior areas of the structure
Blistered and peeling in areas - needs to be serviced

7. Exterior Doors
INSP

NINSP

NFE

NONE

Note: Exterior doors require seasonal maintenance to extend lifespan and maintain
weather tight seals All visible and accessible doors were tested during this inspection
Loose/worn hardware and hinges - typical for age Worn/weathered recommend
weather tight service/maintenance Maintain weather tight seals at all doors Consult
the termite report for all wood doors/frames at this structure

8. Exterior Window/s
INSP NINSP NFE NONE
Note: Exterior windows require seasonal maintenance to extend lifespan and maintain
X
X
weather tight seals See interior section for additional information - some exterior
window areas may not be visible due to height/limited access/vegetation/etc. Worn
windows/screens - typical for age Recommend weather tight service/maintenance
Missing screens - screens are recommended at all openable windows Consult the
termite report for all wood window/frames at this structure (if wood is present)
Deteriorating wood present - consult termite report - needs to be serviced

Page 35 of 52

The Elite Group

754 N Currier St, Pomona, CA


CONCRETE SLAB FOUNDATION

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Slab Foundation
INSP

NINSP

NFE

NONE

Raised foundation only

2. Foundation Perimeter
INSP NINSP NFE NONE
Vegetation/storage present - some areas of foundation perimeter not visible for
X
inspection Personal items prevented complete inspection Large
trees/bushes/vegetation around the structure areas may have a long term affect on the
slab areas/perimeter and the underground plumbing (recommend a sewer scope
inspection for underground plumbing). Worn and cracked - typical for the age of the
structure

Page 36 of 52

The Elite Group

754 N Currier St, Pomona, CA


RAISED FOUNDATION

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Foundation Walls
INSP NINSP NFE NONE
All accessible areas of foundation walls were visibly inspected during this inspection
X
(some areas my not be accessible due to limited space/plumbing piping/duct work
obstructions) Cracks minor (less than 1/8-inch) Constructed of: concrete masonry
blocks Recommend foundation contractor to evaluate this foundation due the age of
the structure
2. Cripple Walls
INSP

NINSP

NFE

NONE

None/not applicable

3. Sub Flooring
INSP

NINSP

NFE

NONE

Structure inspection limited due to access hindrances such as


insulation/ductwork/pipes/wires Some areas of the sub floor are not visible or
inspected Large stains - needs to be serviced - hidden damage may exist

Large stains - needs to be serviced - hidden damage may exist


4. Post and Girders
INSP

NINSP

NFE

NONE

Structure inspection limited due to access hindrances such as


insulation/ductwork/pipes/wires Consult termite report for all wood
deterioration/moisture damage under structure Stained and worn areas

5. Anchor Bolts
INSP

NINSP

NFE

NONE

No visible anchor bolts present recommend adding bolts or earthquake retrofit steel
plates

6. Ventilation
INSP

NINSP

NFE

NONE

Note: Inspector does not perform calculations to determine exact square-feet of


ventilation required at time of construction Adequate ventilation

7. Vent Screens
INSP

NINSP

NFE

NONE

Worn/bent/small holes recommend maintenance and repairs to prevent pest intrusion

Page 37 of 52

The Elite Group

754 N Currier St, Pomona, CA

8. Access Panel/s
INSP

NINSP

NFE

NONE

heavily worn/weathered, deteriorated wood present recommend service/repair to


prevent pest access to under structure Limited inspection - some areas under the
structure are not accessible/visible due to piping/electrical/duct work, insulation or
inadequate service space N/A

9. Electrical
INSP

NINSP

NFE

NONE

Structure inspection limited due to access hindrances such as


insulation/ductwork/pipes/wires All wiring should be properly secured to the framing.

10. Plumbing
INSP

NINSP

NFE

NONE

Check permits for all plumbing under structure to ensure plumbing was installed to city
code - plumbing upgrades are present Recommend a main drain sewer camera
inspection due to age Cast-iron drain pipes rusted and cysts at bottom - needs to be
serviced

Cast-iron drain pipes rusted and cysts at bottom - needs to be serviced


11. Duct Work
INSP

NINSP

NFE

NONE

None present

12. Basement
INSP

NINSP

NFE

NONE

None present

Page 38 of 52

The Elite Group

754 N Currier St, Pomona, CA


GROUNDS

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Driveway/s and Walkway/s


INSP NINSP NFE NONE
Constructed of: Personal items/automobiles/vegetation/debris prevent complete
X
X
inspection in areas Concrete Asphalt
Driveway stained heavily in areas Driveway displacement/lifting/uneven areas - trip
hazard - needs to be serviced Walkway displacement/uplifted/uneven areas potential trip hazard - needs to be serviced Cracking/chipping large - needs to be
serviced
2. Patio and Porch Roof/s
INSP NINSP NFE NONE
Constructed of: Same as main structure - porch Same as main structure - patio
X
See main roof page for porch/patio areas
3. Balcony/s
INSP

NINSP

NFE

NONE

Note: Inspector cannot determine if balcony is/are watertight, no water testing is


performed, we recommend weather tight service and maintenance to all necessary
areas to prevent water intrusion Deteriorated wood - consult termite report - needs to
be serviced Cracked more than typical - needs to be serviced Staircase and structure
is loose - needs to be serviced Flooring damaged - needs to be serviced

Staircase and structure is loose - needs to be serviced Deteriorated wood - consult termite report - needs to
be serviced
4. Balcony and Deck Railing
INSP NINSP NFE NONE
Railing weak - needs to be serviced Deteriorated wood - needs to be serviced - consult
X
X
termite report Heavily damaged - needs to be serviced

Deteriorated wood - needs to be serviced - consult termite report

Page 39 of 52

The Elite Group

754 N Currier St, Pomona, CA

5. Patio and Porch Deck/s


INSP NINSP NFE NONE
Personal items present - some areas not visible for inspection
X
X
Cracking/chipping large - needs to be serviced
Displaced/lifted/uneven areas trip hazard - needs to be serviced

Displaced/lifted/uneven areas trip hazard - needs to be serviced


6. Exterior Electrical
INSP NINSP NFE NONE
Note: The Inspector does not perform and stress or destructive testing of the electrical
X
X
system; Yard area electrical that is not readily visible and accessible may not be seen or
inspected; Low voltage lighting/electrical systems, motion detectors, intercom,
video/audio/security systems are not inspected. Generally, it is typical for older homes
not to have exterior outlets or switches.
Accessible lights/switches/outlets were tested on the day of the inspection
The visible and tested fixtures/switches/outlets were in a loose/worn condition typical for age
Electrical fixtures should be caulked/sealed to wall attachments to help prevent
moisture entry
Some light(s) did not function (some may be on sensors or timers) - check bulbs first,
then consult an electrician to further evaluate as needed Unsecured or loose
wiring/conduit/electrical - needs to be serviced
Recommend licensed electrician to further evaluate and repair to assure the system is
safe and operating properly
Exterior outlet/switch covers are missing or not of proper exterior weather proof type
- needs to be serviced

Unsecured or loose wiring/conduit/electrical - needs to be serviced


7. GFCI/s
INSP

NINSP

NFE

NONE

Test did not operate- needs to be serviced

Page 40 of 52

The Elite Group

754 N Currier St, Pomona, CA

Test did not operate- needs to be serviced


8. Exterior Plumbing and Faucet/s
INSP NINSP NFE NONE
Note: Sump pumps, septic tanks and associated piping and sewer drain pipes from
X
X
structure to street are excluded from this inspection
Note: We recommend adding anti-siphon/backflow preventers (if not already
present) on all exterior hose bibs for optimum potable water protection Exterior
faucets operated/worn at time of inspection via normal fixture controls
Some areas not visible due to personal items/vegetation obstructing view/access
Galvanized water piping present - recommend complete water distribution system
evaluation
9. Main Water Valve
INSP NINSP NFE NONE
Type of plumbing: Note: This section includes a percentage approximation of the
X
plumbing type, it is not a guarantee of the plumbing type in all areas. The inspector
cannot see plumbing type inside walls, floor or other areas that may be covered.
Copper 90% and galvanized 10% (approximate) - recommend complete water
distribution system evaluation due to galvanized plumbing present
Note: We recommend adding anti-siphon/backflow preventers (if not already present)
on all exterior hose bibs for optimum potable water protection Main water shutoff is
visibly inspected only - they are not tested for operation due to the potential for leakage
No visible leaking found at the time of the inspection Main ball valve is worn - typical
for age
10. Water Pressure
INSP

NINSP

NFE

NONE

Note: Recommended water pressure is between 55 to 80 pounds per square inch (psi)
Note: Water Pressure can fluctuate depending upon time of day and municipal service
adjustments Approximate pounds per square inch: 60

General view

Page 41 of 52

The Elite Group

754 N Currier St, Pomona, CA

11. Pressure Regulator


INSP NINSP NFE NONE
None installed - a pressure regulator is recommended to allow for water pressure
X adjustments as needed
12. Sprinklers
INSP

NINSP

NFE

NONE

None present/visible

13. Fencing and Walls


INSP NINSP NFE NONE
Constructed of: Note: Fence or wall enclosures are not evaluated for security adequacy
X
X
or design
Block Wood Brick Wrought iron Chain link
Some wall/fence areas not visible for inspection due to vegetation/personal items
Visible fencing/wall areas are worn and weathered - typical for the age of the materials
Cracking small and typical for age - monitor for further cracking and repair as needed
Loose/leaning areas of fencing/walls needs to be serviced
Missing/damaged bricks - needs to be serviced
14. Gate/s
INSP

NINSP

NFE

NONE

Constructed of: Note: Gates are not evaluated for security adequacy Wrought iron
Gate(s) locked - not tested Loose/worn hardware Weathered and worn materials
Operated on the day of the inspection

15. Planter/s
INSP

NINSP

NFE

NONE

Note: The Inspector cannot determine if planter areas are leaking into the structure,
consult seller disclosures or obtain further evaluation of these areas for any moisture
intrusion issues Not completely visible for inspection due to soil/plants/vegetation
Recommend adding drainage in planter areas to direct moisture away from the structure
Heavily damaged due to tree roots - needs to be serviced

Heavily damaged due to tree roots - needs to be serviced


16. Grading
INSP

NINSP

NFE

NONE

Note: This inspection cannot determine adequate drainage needs, the addition of drains
may be needed in areas to help divert water away from the structure Note: Steep
hillsides, fire safety study and inaccessible areas on the grounds are excluded from this
inspection. Underground drains present - not tested for performance. Note
underground drains will require periodic maintenance

Page 42 of 52

The Elite Group

754 N Currier St, Pomona, CA


ROOF

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Condition
INSP

NINSP

NFE

NONE

Disclaimer: The inspector cannot determine if a roof (or any part of the roof system)
leaks at any time or under any weather conditions, no water or hose testing is
performed during this inspection. If there are concerns of possible roof leaks, please
contact a licensed roofer to perform an additional inspection. Remaining roof life can
only be determined by a licensed roofer. This applies to all roof areas evaluated during
this inspection. Inspection method - roof was walked
Constructed of: Asphalt shingles Rolled composition
Worn and weathered materials present - roof needs maintenance Shingles exhibited
moderate granule loss - normal for age of material Multiple layers roof material
present - unable to determine how many layers or added weight Rolled composition
roofing not considered a long-term material Material appears to be pre-1980 may
contain asbestos - testing required to confirm Wavy areas present - needs further
evaluation by licensed roofer Tree branches rub roof - needs to be serviced Heavily
weathered areas - needs to be replaced

Tree branches rub roof - needs to be serviced


2. Flashing/s
INSP

NINSP

NFE

NONE

Worn/weathered/rusted/bent - typical for age Missing at roof to wall juncture - needs


to be serviced

Missing at roof to wall juncture - needs to be serviced


3. Gutters and Down Spout/s
INSP NINSP NFE NONE
Gutters are present at the structure Recommend cleaning and routine maintenence on
X
X
gutter system to maintain good drainage Existing gutters area worn/older - consider
upgrading/replacing as needed Heavily clogged/restricted by debris - needs to be
serviced
Page 43 of 52

The Elite Group

754 N Currier St, Pomona, CA

Heavily clogged/restricted by debris - needs to be serviced


4. Vents and Vent Cap/s
INSP NINSP NFE NONE
Worn/weathered recommend seasonal maintenance to ensure that caps do not
X
become loose or develop other defects
5. Chimney/s
INSP

NINSP

NFE

NONE

Common area/roof - Maintained by Homeowner's Association - Not Inspected Note:


Chimney inspection includes all exterior accessible areas of chimney - interior cavity/flue
is not inspected, consult a licensed chimney sweep contractor for further investigation
and inspection of the internal areas of the chimney. Worn/weathered chimney
recommend seasonal maintenance and care
Cracks in bricks - aesthetic but monitor Minor deterioration Recommend chimney
inspection due to age Chimney has wooden structure built on it covering top - heavily
deteriorated - needs to be serviced

Chimney has wooden structure built on it covering top - heavily deteriorated - needs to be serviced
6. Spark Arrestor/s
INSP

NINSP

NFE

NONE

No spark arrestor/rain cap present - recommend installation

7. Sky Light/s
INSP

NINSP

NFE

NONE

None present

Page 44 of 52

The Elite Group

754 N Currier St, Pomona, CA


POOL AND/OR SPA

INSP = Inspected, NINSP = NOT inspected, NFE = Needs further evaluation, repaired or replaced by appropriate licensed
contractor, NONE = Not present at time of inspection

1. Plumbing
INSP

NINSP

NFE

NONE

Inspection disclaimer: This is a limited inspection of the pool/spa and associated


equipment. Underground piping is excluded from this inspection, the inspector cannot
determine if a pool structure or plumbing leaks underground. If there is any concern of
a pool leak, consult a pool contractor to perform a leak dye test. The inspector cannot
determine the remaining life of any of the pool equipment. Worn/older type piping
present - expect repairs to be necessary in the near future Some equipment not
accessible due to enclosure Main drain cover not anti- vortex type - recommend
upgrade

Main drain cover not anti- vortex type - recommend upgrade


2. Pumps
INSP

NINSP

NFE

NONE

Operated on the day of the inspection - one pump Not functional/did not operate needs to be serviced - 2nd pump Worn pump(s), recommend servicing Inspector
cannot determine the remaining life left in the pool pump(s) Some equipment not
accessible due to enclosure Corroded - needs to be serviced

3. Jets
INSP

NINSP

NFE

NONE

Not functional - needs to be serviced

4. Pressure Gauge/s
INSP NINSP NFE NONE
Operated on the day of the inspection Normal wear for age at the time of the
X
inspection - no major visible defects
5. Pool Fill Valve/s
INSP

NINSP

NFE

NONE

Not applicable - none present

6. Electrical
INSP

NINSP

NFE

NONE

Exterior conduit is worn/weathered may need future repair Exposed wires - potential
hazard needs to be serviced

7. GFCI/s
INSP

NINSP

NFE

NONE

Tested did not operate - needs to be serviced

Page 45 of 52

The Elite Group

754 N Currier St, Pomona, CA

8. Light/s
INSP

NINSP

NFE

NONE

NFE

NONE

Tested and functional at time of inspection

9. Filter/s
INSP

NINSP

Filter is worn/weathered - recommend service/maintenance to be performed by a pool


contractor

10. Skimmer and Basket/s


INSP NINSP NFE NONE
Worn - needs service/maintenance by a licensed pool contractor
X
11. Heater
INSP

NINSP

NFE

NONE

Type: Natural gas type present


Note: Safety pressure relief valves (if present) are not operated and are excluded from
inspection; an internal evaluation of the heater parts is beyond the scope of this
inspection. Operated on the day of the inspection Burner chamber corroded/rusted needs to be serviced Burner chamber full of debris - needs to be serviced

12. Tile
INSP

NINSP

NFE

NONE

Worn tile/grout present Recommend regular grout and sealer maintenance Missing needs to be serviced

Missing - needs to be serviced


13. Coping
INSP

NINSP

NFE

NONE

Missing sections - needs to be serviced

Missing sections - needs to be serviced

Page 46 of 52

The Elite Group

754 N Currier St, Pomona, CA

14. Decking
INSP

NINSP

NFE

NONE

Uneven/lifted/lipage in areas trip hazards present

15. Gate/s & fencing


INSP NINSP NFE NONE
Constructed of: See grounds fencing for additional fencing information
X
X
No safety latches, self closers or alarms at doors (includes screens) from house accessing
pool area - needs to be serviced Gate not self closing and latching properly - needs to
be serviced
16. Structure/s
INSP

NINSP

NFE

NONE

Type: Below ground pool and spa


Constructed of: Gunite
Note: Some areas of the structure are not visible due to water/weather conditions; sun
glare and wind can often affect the visible areas of the structure Limited inspection
only from outside of the pool - this is not an underwater inspection of all areas of the
pool structure Worn/stained/rough surface areas - typical of age Recommend
licensed pool contractor for evaluation due to age/conditions/inspection limitations
Multiple rough areas present - needs further evaluation

Multiple rough areas present - needs further evaluation


17. Water Condition
INSP NINSP NFE NONE
Note: water chemistry is not tested or included with this inspection Note: Ultraviolet
X
X
light and/or salt chlorine generator type water treatment systems not included in this
inspection (if present) Dirty pool, debris present in areas - needs to be
serviced/cleaned
Cloudy - needs to be serviced Completely discolored - needs to be serviced

Page 47 of 52

The Elite Group

754 N Currier St, Pomona, CA

INSPECTION AGREEMENT
BY ACCEPTANCE OF OUR INSPECTION REPORT YOU AGREE TO THE TERMS OF THIS AGREEMENT AND THE
TERMS AND CONDITIONS OF THE CONTRACT
SCOPE OF THE INSPECTION / REPORT
We will perform a non-invasive physical examination designed to identify material defects in the systems,
structures, and components of buildings located on the property to be inspected, as they exist at the time of
the inspection. Our inspection will be limited to those specific systems, structures and components that are
present and visually accessible. We will only operate components and systems with normal user controls and
as conditions permit. Unless we agree otherwise, we will only inspect the primary building, and its associated
primary parking structure, on the property. We will also provide you with a report that describes and
identifies the inspected systems, structures and components and identifies material defects. We may amend
the report within twenty-four (24) hours after completing the inspection.
Unless we agree otherwise, we will perform the inspection, and issue the report, in accordance with the
mandatory parts of the current Standards of Practice (Residential Standards - Four or Less Units) of the
International Association of Certified Home Inspectors ("the InterNACHI Standards") and subject to the
Definitions, Scope, Limitations, Exceptions and Exclusions in the InterNACHI
Standards. Terms in this Agreement have the same meaning as the defined terms in the InterNACHI
Standards. The InterNACHI Standards are available from InterNACHI's website: http://www.nachi.org/
IF YOU DISCOVER A DEFECT FOR WHICH WE MAY BE LIABLE TO YOU, YOU MUST NOTIFY US AND GIVE US A
REASONABLE OPPORTUNITY TO RE-INSPECT THE PROPERTY BEFORE YOU REPAIR THE DEFECT. YOUR NOTICE
MUST BE IN WRITING, INCLUDE A SIGNED COPY OF THIS AGREEMENT, AND BE MAILED TO:
Corporate Office
The Elite Group Property Inspection Service, Inc
Attn: Inspector Supervisor
21700 E Copley Suite 390 Diamond Bar, CA 91765
1(800) 494 - 8998
OUR LIABILITY TO YOU FOR CLAIMS ARISING FROM OUR INSPECTION OR OUR REPORT, WHETHER SOUNDING
IN TORT OR CONTRACT, WILL NOT BE MORE THAN THE LESSER OF ACTUAL DAMAGES OR TEN (10) TIMES THE
INSPECTION FEE.
TEGPIS AND CLIENT AGREE THAT CLIENT CANNOT FILE A LEGAL ACTION AGAINST TEGPIS OR ITS EMPLOYEES,
WHETHER SOUNDING IN TORT OR CONTRACT, MORE THAN ONE YEAR AFTER THE CLIENT DISCOVERS, OR
WITH THE EXERCISE OF REASONABLE DILIGENCE SHOULD HAVE DISCOVERED THE BREACH OR MATERIAL
DEFECT.
Our report is NOT a warranty of the items inspected. Contact your home warranty company.
CONFLICT OF INTEREST DISCLOSURE AND STATEMENT OF COMMITMENT
Our goal is to provide valuable and unbiased information that helps consumers make informed decisions. A
portion of our business may be based on relationships with other professions- real estate sales professionals,
lawyers, lenders, vendors, etc., and our reports sometimes conflict with the business interests of these
parties. We do not allow these relationships to compromise the integrity of our service. However, they do
enable us to deliver more value to our clients. Our reports are intended to accurately reflect our impartial
professional opinion, without exception.
YOU MUST PAY THE INSPECTION FEE BEFORE WE CAN DELIVER THE REPORT TO YOU.

Page 48 of 52

The Elite Group

754 N Currier St, Pomona, CA

DISCLAIMER
Interior: Limited inspection on all occupied/staged structures, personal property, furniture and moving boxes prevent a complete
inspection. Recommend checking for permits on all additional construction including windows, patio roofs, out structures, garage
and attic conversions, etc. performed on the property after original construction. Built-in central vacuum systems are not inspected.
Bathrooms: Leaking bathtub and sink overflow drains and spa tub jet hoses cannot be detected with this inspection. Shower pans
are not leak tested consult the termite report. Exterior access panels are only inspected if readily accessible and operable (not
sealed or painted or screwed shut).
Kitchen: This inspection cannot determine how well the dishwasher cleans the dishes. Disposal blades are not inspected. Water
purifying systems and water softeners are not inspected. Non built-in appliances and built-in refrigerators are excluded from this
report.
Laundry: Water supply valves that are left in the on position for a long period of time tend to leak when turned off or do not shut
off completely. Supply valves cannot be tested whether a washing machine is present or not. Washer and dryer units not inspected.
Attic: The inspector cannot determine or test if asbestos materials exist throughout the structure. When attic insulation is covering
ceiling joists, we cannot completely inspect due to inspector safety concerns. Most attics are not completely accessible due to
limited space. Attic insulation and limited space prevent the inspector from performing a complete inspection of the attic area, not
all areas are accessible and will be determined by the inspector discretion. Temperature sensors and fans for attic exhaust systems
are not tested. Rodents: If there is visible evidence of rodents, it will be noted as such. Most rodent infestation exists under attic
insulation, in walls or in areas not visible to the inspector and cannot be identified with this inspection. Its recommended a pest
inspection be preformed whether or not evidence exists.
Heating &Air Conditioning: This report does not indicate if the heater is on recall, a follow up report will be emailed via RecallChek.
Electronic air filters are not inspected. Inspector cannot determine a crack in the firebox. Not all registers can be tested for pressure
flow, due to location, condition and operation of the heating &Air Conditioning system. Missing labels prevent RecallChek.
Water Heater: Circulating pumps, TPR Valves and pressure tanks cannot be tested with inspection. Solar water heaters are not
inspected. Tankless units that are not original to the structure should be further evaluated by a qualified tankless technician as
there are many aspects that are out of the scope of a general home inspection.
Roof: Chimney cavities are excluded from this inspection, recommend a chimney scope inspection be performed. Solar panels and
tube globes are excluded from this report. The inspector cannot determine whether a roof is water tight or not, under any
condition.
Electrical: Electrical and gas fires due to poor installation of wiring and faulty gas pipes cannot be determined by the inspector.
Exterior Areas: For damaged wooden areas and moisture problems (mold/mildew), consult the termite inspection report. See
interior section of the report for additional window and door information. Gas leaks or carbon monoxide poisoning cannot be
detected with this inspection, including all gas and propane systems interior and exterior of the structure. The operation of gas
appliance ventilation exhaust pipes cannot be detected. Recommend Gas Company to evaluate all gas areas before occupying the
property. Fire pits and exterior BBQ's are excluded from this inspection. Recommend mold and moisture damaged areas be further
evaluated by the appropriate licensed contractor throughout the structure.
Grounds: This report cannot determine if patio and porch roofs or patio enclosures are water tight. Low voltage lighting and
motion-detected sensors on light fixtures are not inspected. Sprinklers on timers are not inspected consult seller/association. Above
ground pools, ponds, waterfalls, birdbaths, and pumps used for these items, are excluded from this report. Steep hillsides and
inaccessible areas on the grounds are excluded from this report. It is highly recommend that all structures built on hillsides and
slopes have a geological inspection performed to determine if the structure is stable. This inspection cannot determine ground
movement or drainage issues.
Foundation: Sump pumps, septic tanks and sewer drain pipes from structure to street are excluded from this inspection. Soil levels
and stem walls prevent complete inspection of the under house area. Drain scope inspections are recommended whether a defect
is detected or not. Slab foundations are often covered and not visible; this is a limited inspection.
Pool: Solar panels are excluded from report. Valves that are not labeled for the pool and/or spa jets are excluded from this report.
Automatic pool fill float valves and electronic chlorine dispensers are excluded from this report. Portable spas have a limited
inspection. The inspector cannot determine pool or spa leaks. It is the buyer's full responsibility to ensure the pool area is in full
compliance with the safety laws and codes. If there is no self containing fence around the pool, all doors from the structure leading
to the pool and spa must be equipped with safety alarms and secondary latches above the reach of children. All gates leading to the
pool must self close and be equipped with a latch five feet or higher from the ground. The fencing in all cases must be five feet tall.
SEE CONTRACT FOR A COMPLETE DISCLAIMER OF ITEMS EXCLUDED FROM THIS INSPECTION

Page 49 of 52

The Elite Group

754 N Currier St, Pomona, CA

RECALLCHEK
RecallChek - The inspector will only provide photos of stickers visible at time of inspection.
You will get an email from RecallChek where you can enter in the following model numbers.

Page 50 of 52

The Elite Group

754 N Currier St, Pomona, CA

Residential Earthquake Hazards Report


Yes

No

N/A

Don't
Know

1. Is the water heater braced, strapped, or anchored to resist falling during an


earthquake?

X
Yes

No

N/A

Don't
Know

X
Yes

No

N/A

Don't
Know

X
Yes

No

N/A

No

N/A

b. If the exterior foundation consists of unconnected concrete piers and


posts, have they been strengthened?
Don't
Know

4. If the exterior foundation, or part of it, is made of unreinforced masonry, has


it been strengthened?

X
Yes

No

N/A

Don't
Know

X
Yes

No

N/A

No

N/A

b. Were the tall posts or columns either built to resist earthquakes or have
they been strengthened?
Don't
Know

6. If the exterior walls of the house, or part of them, are made of unreinforced
masonry, have they been strengthened?

X
Yes

No

N/A

Don't
Know

X
Yes

No

No

7. If the house has a living area over the garage, was the wall around the
garage dooropening either built to resist earthquakes or has it been
strengthened?

Don't
Know

X
Yes

5. If the house is built on a hillside:


a. Are the exterior tall foundation walls braced?

Don't
Know

X
Yes

3. If the house has cripple walls:


a. Are the exterior cripple walls braced?

Don't
Know

X
Yes

2. Is the house anchored or bolted to the foundation?

8. Is the house outside an Alquist-Priolo Earthquake Fault Zone (zones


immediately surrounding known earthquake faults)?

Don't
Know

9. Is the house outside a Seismic Hazard Zone (zone identified as susceptible


to liquefication or landsliding)?

EXECUTED BY:
___________________________
(Seller)

___________________________
(Seller)

__________
Date

I acknowledge receipt of this form, completed and signed by the seller. I understand that if the seller has answered No
to one or more questions, or if seller has indicated a lack of knowledge, there may be one or more earthquake
weaknesses in this house.

___________________________
(Buyer)

___________________________
(Buyer)

__________
Date

Page 51 of 52

The Elite Group

754 N Currier St, Pomona, CA

Glossary

Glossary
Term

Definition

A/C
Combustion Air

Abbreviation for air conditioner and air conditioning


The ductwork installed to bring fresh outside air to the furnace
and/or hot water heater. Normally, two separate supplies of air
are brought in: one high and one low.
A special device that is intended for the protection of personnel
by de-energizing a circuit, capable of opening the circuit when
even a small amount of current is flowing through the grounding
system.
Not accessible, not inspected

GFCI

N/A

Page 52 of 52