Abstract
This application note describes how to test directional distance protection when it is used as a backup
protection for a power transformer. This test can be carried out in an easy and comfortable way using the
corresponding OMICRON RelaySimTest test template.
RelaySimTest offers simulation based system testing methods. To perform a test, a fault scenario is
calculated based on the simulation of the power system network. The voltages and currents for the relay
location can be used to test the correct behavior of the distance protection when the fault is located before or
after the power transformer.
OMICRON
Page 1 of 22
General information
OMICRON electronics GmbH including all international branch offices is henceforth referred to as
OMICRON.
The product information, specifications, and technical data embodied in this application note represent the
technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this application note is useful, accurate and
entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be
present.
OMICRON translates this application note from the source language English into a number of other
languages. Any translation of this document is done for local requirements, and in the event of a dispute
between the English and a non-English version, the English version of this note shall govern.
All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming,
optical character recognition and/or storage in electronic data processing systems, requires the explicit
consent of OMICRON. Reprinting, wholly or partly, is not permitted.
OMICRON 2015. All rights reserved. This application note is a publication of OMICRON.
OMICRON 2015
Page 2 of 22
Content
1
1.2
General Requirements....................................................................................................................6
2.2
2.3
3.2
4.2
4.2.2
OMICRON 2015
Page 3 of 22
Safety instructions
Only experienced and competent professionals that are trained for working in high voltage or high current
environments may perform this application note. Additional the following qualifications are required:
OMICRON 2015
Page 4 of 22
NOTICE
Equipment damage or loss of data possible.
Do not use (or even turn on) any electrical equipment without understanding
the information in its manual.
Always turn off each system involved to the test process before wiring up or
rewiring the equipment.
General Requirements
To use this application note it is necessary to read the Getting started manual [1] of RelaySimTest before
and it is essential to have a good knowledge about the CMC test system.
OMICRON 2015
Page 5 of 22
Impedance is transformed with the square of the power transformers voltage ratio.
On star/delta transformers there is a phase rotation corresponding to the power transformers vector
group. The fault current distribution changes from one side of the transformer to the other. For
instance, a two-phase short circuit on one side may appears as a three-phase fault with asymmetric
current distribution on the other side.
OMICRON 2015
Page 6 of 22
The zero-sequence system cannot be converted by a start/delta transformer. That means that earthfaults are not measured correctly by the distance relay through a star/delta transformer. In isolated
or compensated systems, this is usually not a problem. Depending on the system characteristics, a
separate earth-fault protection may be required.
Usually in the distance scheme, Zone 1 doesnt protect the complete line adjacent to the power transformer.
The instantaneous tripping is only possible for around 80% to 90% of the line. Zone 2 reaches into, but not
beyond the transformer and Zone 3 protects the cable connected to the secondary side of the transformer.
Z3
Z2
Z1
D1
OMICRON 2015
Page 7 of 22
Cable Data
50 Hz
10 kV
2500 A
0,5 km
R1 = 23 mOhm/km
X1 = 48 mOhm/km
R0 = 261,93 mOhm/km
X0 = 84,5 mOhm/km
C1= 1,206 F/km
C0= 1,206 F/km
80% transf.
80% line
Z3
Z2
Z1
CT A
200 A / 1 A
Y
2
Relay
A
VT A
110 kV / 100 V
d5
S= 40 MVA
Xcc= 12 %
Rcc= 0,5%
Figure 4 presents the time grading of the distance protection. Relay A has three forward zones.
The first zone is instantaneous which means the nominal trip time is 0 seconds. The second zones nominal
trip time is 400 ms and the third zone trips with an 800 ms delay.
OMICRON 2015
Page 8 of 22
Z3
0.8 s
Z2
0.4 s
0s
Z1
A
OMICRON 2015
Page 9 of 22
OMICRON 2015
Page 10 of 22
Test cases
Figure 8 shows the Test cases menu. It contains the grid topology (1), the test scenarios (2), the test steps
(3) and the test properties (4). The next sections describe this menus referring to the test template of the
application note.
OMICRON 2015
Page 11 of 22
L1-N
L2-L3
L1-L2-L3
Depending on the relay under test, on the relays parameters and on the grid where the protection system is
used, it may be necessary to add more fault types.
The Initial state of a fault is inactive to get transients when the fault is applied. To get particularly high fault
currents with DC components the fault inception angle is set to 0.
The RelaySimTest template includes two test cases. One simulates faults before the transformer, in the
overhead line, and the second simulates faults after the transformer, in the cable connected to the
transformer low-voltage side.
In the isolated system at the low-voltage side of the transformer, single L-N faults do not characterize shortcircuits. Therefore they are not added as Test steps.
The nominal trip time of the protection is between 0 and 0,8 s, therefore the simulation time after a fault or
switching event is at least 1,2 s. Hence the protection system has enough time to show its reaction on the
event.
The following sections describe in detail the template test cases.
OMICRON 2015
Page 12 of 22
OMICRON 2015
Page 13 of 22
The start measuring event is the beginning of the corresponding fault, if the fault leads to a trip.
The start measuring event is the beginning of the simulation (0s) or the beginning of the
corresponding fault for tests where the relay is not allowed to trip.
In both cases the trip command is observed. Therefore the trip signal activation is the stop
measuring event.
The Set assessment condition menu (next to the Define measurements menu) defines the assessment of
the test steps. For test points where the relay has to trip, the min/max values have to be entered (option
Custom min/max values, see Figure 14). For those test points where the relay is not allowed to trip, the
option No stop event occurs is the required assessment condition.
OMICRON 2015
Page 14 of 22
This section assumes that the setup in the scheme above is complete:
The Test sets configuration menu defines the CMC and the configuration used for the tests.
The test template includes a general CMC as shown in Figure 16.
After a click on the Choose test set button on the right side of the CMC icon, a new window opens and
offers the CMC that is connected to the PC. A click on the CMC selects it.
OMICRON 2015
Page 15 of 22
The Getting Started manual of RelaySimTest [1] describes how the wiring between the CMCs and the relays
can be configured in the Test sets configuration menu.
To perform the tests of this application note the following signals have to be configured:
Three test voltages
Three test currents
Start and trip signals
OMICRON 2015
Page 16 of 22
The zones in the TransView Circle Diagrams are displayed in the next four figures.
OMICRON 2015
Page 17 of 22
When a Test Step is executed, the fault trajectories are visible in the TransView Circle Diagrams and it
allows to double check that the relay trips in the correct zone.
The next examples can be found in the RelaySimTest sample:
L1-N fault before transformer: fault location 25% of overhead line
The Trip A1 occurs at 19.8 ms. According to the zones time grading this means Zone 1. On the right hand
side, the phase 1 fault trajectory ends in Zone 1 in the LE Circle Diagram.
Note that you may have to zoom on the Zone 1 because it is very small compared with the other zones.
Page 18 of 22
Page 19 of 22
If a test case is open a click on the Execute selected button executes only the selected test step. A
click on the Execute all button runs all test steps of the test case sequentially.
However, in the Test Manager menu the Execute selected button runs all selected test cases,
while Execute all runs all test cases.
OMICRON 2015
Page 20 of 22
List of Literature
[1] Getting started with RelaySimTest; OMICRON electronics GmbH; 2014
[2] Numerical Distance Protection: Principles and Applications; 4th edition; Gerhard Ziegler; PUBLICIS;
2011
[3] SIPROTEC Distance Protection 7SA6 V4.70 Manual, SIEMENS
OMICRON 2015
Page 21 of 22
Support
When you are working with our products we want to provide you with the greatest possible
benefits. If you need any support, we are here to assist you.
+1 800-OMICRON
Additionally, on our website you can find our Service Center or Sales Partner closest
to you.