Hasil Pengamatan
Tabel 4.1. Data Hasil Pengamatan
Mv
(kW)
(g/s)
(mmH2O)
Temperatur (C)
20
30
0,5
20
40
20
30
1,0
20
40
T1
T2
T3
T4
T5
T6
31,0
28,0
37,0
33,0
43,0
34,5
30,9
27,9
36,5
32,9
43,0
34,9
30,7
27,5
36,3
32,8
43,0
34,2
30,5
27,3
36,2
33,0
53,0
39,5
31,0
27,8
35,9
32,8
53,0
38,5
30,3
27,9
36,0
32,9
53,0
38,9
Dimana:
T1 = Temperatur dry bulb masuk
T2 = Temperatur wet bulb masuk
T3 = Temperatur dry bulb keluar
T4 = Temperatur wet bulb keluar
T5 = Temperatur air masuk
T6 = Temperatur air keluar
4.2.
Pengolahan Data
1)
Konstanta Orifice
= 0,137
Keterangan:
!
!!
Vb =
Volume spesifik campuran steam dan uap yang lepas dari atas
kolom (m3/kg)
2)
3)
Dimensi Kolom
P
(4.1)
= 0,15 m
14
L
4)
15
= 0,15 m
Data Packing
= B-200 m-1
Jumlah dek
= 8
= 18
= 2,16 m2
Tinggi packing
= 0,48 m
Densitas packing
area
,
volume
= 200 m-1
= 20 mmH2O
= 34,5 oC
= (34,5 28) oC
= 6,5 oC
= 0,137
x
Vb
!"
!,!"#
= 0,6377 kg/ s
Air volume flowrate (V)
= m x Vb
= 0,6377 kg/ s x 0,923 m3/ kg
= 0,5886 m3/ s
=
=
V
A
!,!""#
!,!""#
16
= 26,16 m/ s
4.2.2.
= 20 mmH2O
= 27,9 oC
= 34,9 oC
= (34,9 27,9) oC
= 7 oC
=0,137
x
Vb
!"
!,!"#
= 0,6384 kg/ s
Air volume flowrate (V)
= m x Vb
= 0,6384 kg/ s x 0,921 m3/ kg
= 0,588 m3/ s
V
A
!,!""
= !,!""#
= 26,13 m/ s
4.2.3. Untuk Cooling Load P 0,5 kW, Laju Alir 40 gr/ s
Untuk Orifice Differential (x)
= 20 mmH2O
= 34,2 oC
= (34,2 27,5) oC
17
= 6,7 oC
Spesifikasi volumetric udara keluar dengan menggunakan cara plot temperatur
dry bulb udara keluar T3 = 36,3 oC dan temperatur wet bulb keluar T4 = 32,8 oC
pada physcometric chart (gambar 4.3), maka diperoleh Vb= 0,9207 m3/ kg.
= 0,137
x
Vb
!"
= 0,137
!,!"#$
= 0,6385 kg/ s
Air volume flowrate (V)
= m x Vb
= 0,6385 kg/ s x 0,9207 m3/ kg
= 0,5879 m3/s
V
A
!,!"#$
= !,!""#
= 26,129 m/ s
4.2.4.
= 20 mmH2O
= 39,5 oC
= (39,5 27,3) oC
= 12,2 oC
x
Vb
18
!"
=0,137
!,!"#$
= 0,6386 kg/s
Air volume flowrate (V)
= m x Vb
= 0,6386 kg/ s x 0,9206 m3/ kg
= 0,5879 m3/s
V
A
!,!"#$
= !,!""#
= 26,129 m/s
4.2.5.
= 20 mmH2O
= 38,5 oC
= (38,5 27,8) oC
= 10,7 oC
=0,137
x
Vb
!"
!,!"#$
= 0,6387 kg/ s
Air volume flowrate (V)
= m x Vb
= 0,6387 kg/ s x 0,9201 m3/ kg
= 0,5877 m3/s
= 0,15 m x 0,15 m
19
= 0,0225 m2
Kecepatan udara
V
A
!,!"##
=!,!""#
= 26,12 m/ s
4.2.6.
= 20 mmH2O
= 38,9 oC
= (38,9 27,9) oC
= 11 oC
= 0,137
x
Vb
!"
!,!"#"
= 0,6387 kg/ s
Air volume flowrate (V)
= m x Vb
= 0,6387 kg/ s x 0,9202 m3/ kg
= 0,5877 m3/s
= 0,15 m x 0,15 m
= 0,0225 m2
Kecepatan udara
V
A
!,!"##
= !,!""#
= 26,12 m/ s
Tabel 4.2. Specific Volume (dari Humidity Chart) Udara-Air Tipe B-200 m-1
P, kW
x, mmH2O
T3 , o C
T4 , o C
0,5
1,0
20
20
20
37
33
0,923
36,5
32,9
0,921
36,3
32,8
0,9207
36,2
33
0,9206
35,9
32,8
0,9201
36
32,9
0,9202
P
T5 T6
0,5
43 34,5
= 0,0588 kW/oC
Cooling Range
=T5 T6
= 43 34,5
= 8,5 oC
P
T5 T6
0,5
43 34,9
=0.0617 kW/oC
Cooling Range
= T5 T6
= 43 34,9
= 8,1 oC
P
T5 T6
0,5
43 34,2
21
= 0.0568 kW/oC
Cooling Range
=T5 T6
= 43 34,2
= 8,8 oC
4.2.8.
P
T5 T6
1,0
53 39,5
= 0.0741 kW/oC
Cooling Range
=T5 T6
= 53 39,5
= 13,5 oC
P
T5 T6
1,0
53 38,5
= 0.069 kW/oC
Cooling Range
= T5 T6
= 53 38,5
= 14,5 oC
P
T5 T6
1.0
53 38,9
= 0.0709 kW/oC
Cooling Range
22
=T5 T6
= 53 38,9
= 14,1 oC
Tabel 4.3. Kecepatan Udara, Approach To Wet Bulb dan Cooling Range
P
(kW)
Mv
(g/s)
Kecepatan Udara
(m/s)
Approach To Wet
Bulb
(C)
Cooling
Range
(C)
20
26,16
6,5
8,5
30
26,13
8,1
40
26,129
6,7
8,8
20
26,129
12,2
13,5
30
26,12
10,7
14,5
40
26,12
11
14,1
0.5
4.3.
7.1
Mv = 30 g/s
7
6.9
6.8
6.7
Mv = 40 g/s
6.6
Mv = 20 g/s
6.5
6.4
26.125
26.13
26.135
26.14
26.145
26.15
26.155
26.16
26.165
23
8.8
Mv = 40 g/s
8.7
8.6
Mv = 20 g/s
8.5
8.4
8.3
8.2
Mv = 30 g/s
8.1
8
26.125
26.13
26.135
26.14
26.145
26.15
26.155
26.16
26.165
12.4
Mv = 20 g/s
12.2
12
11.8
11.6
11.4
11.2
Mv = 40 g/s
11
10.8
10.6
26.118
Mv = 30 g/s
26.12
26.122
26.124
26.126
26.128
26.13
24
Mv = 30 g/s
14.4
14.2
14
Mv = 40 g/s
13.8
Mv = 20 g/s
13.6
13.4
26.118
26.12
26.122
26.124
26.126
26.128
26.13