Quotation No.: 1Q0179 R.

0
Date: 03-May-1999

QUOTATION NUMBER
1Q0179
REVISION NUMBER
0

DATE
03-May-1999
REVISION DATE
-

CUSTOMER
P.T. ALAM MAKMUR CONTOH
REFERENCE
SPECIFICATION NUMBER 1/34455/ADF899/99
PROJECT
STANDARD PROJECT
PLANT
ECDF SWITCHBOARD
SCOPE OF SUPPLY
20KV METAL ENCLOSED SWITCHGEAR UNISWITCH

Contacts:
Mr. Setiadi Budiman Tel. +62 21 590 9955 / Fax. +62 21 590 0116

Page: 1 of 7

Quotation No.: 1Q0179 R. 0


Date: 03-May-1999

AIS MV SWITCHBOARDS GENERAL DESCRIPTION

The UniSwitch system is an Air Insulated metal enclosed compartmented


Switchgear. The system consitsts of a range of prefabricated standardized
panels which can either be delivered as completed switchgear or as single
panel. By using standardized components as circuitbreakers (SF6 of Vacuum),
SF6 switch disconnectors, earthing switchs and fuse bases the system covers
almost any configuration. The UniSwitch system is basically designed to be
used in public and industrial secondary distribution network.
The panel is built up of 2mm AlZn-coated steel plates which are bolted
together. All panels are designed with two overpressure reliefs at the rear
side, one for the cable compartment and one for switch/busbar compartment.
The system is designed to meet the requirement according to IEC Standard:
56, 129, 265, 298, 420, 529, 694, 932. It has been also tested by the:
PT. PLN (Pesero)
JASA TEKNIK KELISTRIKAN LMK
UNIT LABORATORIUM LISTRIK
as per the following technical reports:
No. 890.ULL.214A.96
SDC-type
No. 891.ULL.214A.96
SDF-type
No. 105.ULL.179A.98
CBW-type
No. 909.ULL.214A.96
CBC-type
No. 128.ULL.043A.98
SDC&DBC-type
2

THE MAIN RATED VALUES

Rated Voltage

kV

12

17.5

24

Rated lightning impulse withstand voltage between phases and


to earth

kV

75

95

125

Rated 1 min. power-frequency withstand voltage between


phases and to earth

kV

28

38

50

Rated frequency

Hz

50-60

50-60

50-60

Rated normal current

630

630

630

Rated busbar current

630(1250)

630

630

Rated short-time withstand current Ith/1S

kA

25

25

20

Rated peak withstand and making current, Idyn, Ima

kA

62.5

50

50

Ambient air temperature limits (cubicle and SFL Siwtch)

-40 +40

-40 +40

-40 +40

Degree of protection by enclosure

IP2XC

IP2XC

IP2XC

Busbar material

Copper

Copper

Copper

Max. moisture content


90 %
Surface treatment
*
Unpainted parts
*
Painted parts

Aluzinked steel plate


RAL7032, grey

Page: 2 of 7

Quotation No.: 1Q0179 R. 0


Date: 03-May-1999

3
3.1

DESCRIPTION OF TYPICAL UNITS


CBC1-TYPE

3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.1.6
3.1.7
3.1.8
3.1.9
3.1.10
3.1.11
3.1.12
3.1.13
3.1.14
3.1.15
3.1.16
3.1.17
3.1.18
3.1.19
3.1.20
3.2

Circuit Breaker Cubicle CBC1, W750mmH1895mmD1180mm including:


Load Break Switch with SF6 extinguishing medium SFL-K 24kV 630A
20kA/1S.
SF6 Circuit Breaker HAD-US 24kV 630A 20kA/1S with charging-motor.
Upper Earthing Switch type EL-210 24kV 50kA.
Down-Stream Earthing Switch type EM-210 24kV 50kA.
Capacitive Voltage Indication to indicate the presence of voltage in
power cable.
Three DIN-type current transformers with ratio 400/5/5A cl. 1.0 15VA
for metering and cl. 5P10 15VA for protection.
Three-phase Overcurrent Protection type SPAJ 140 C or
Three-phase Overcurrent Protection type PR511 (self-powered).
One Ampere-meter (90, 96mm96mm) and Selector Switch.
Three DIN-type voltage transformers with ratio 20kV:3 / 110:3 cl.
1.0 15VA.
One Volt-meter (90, 96mm96mm) and Selector Switch.
One Zero current transformer with ratio 100/5A cl. 5P10 15VA for
earth-fault protection.
Three Surge-Arresters type MWD-16 for 20kV rated voltage.
Watt-meter (90, 96mm96mm)
VAR-meter (90, 96mm96mm)
PF-meter (90, 96mm96mm)
Frequency-meter (90, 96mm96mm)
Digital multi-display meter GOSSEN A2000 or RECDIGIT 1600E
(144mm144mm) to indicate kWh, Volt, Ampere, kW, KVAR, PF, Freq.
Additional on-top low voltage compartment.

CUBICLE SDC1-TYPE

3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.2.6
3.2.7
3.2.8
3.2.9
3.2.10
3.2.11
3.2.12
3.2.13
3.2.14
3.2.15
3.2.16
3.2.17

Switch Disconnetor Cubicle SDC1, W500mmH1895mmD1180mm including:


Load Break Switch with SF6 extinguishing medium SFL-K 24kV 630A
20kA/1S.
Upper Earthing Switch type EL-210 24kV 50kA.
Capacitive Voltage Indication to indicate the presence of voltage in
power cable.
Three DIN-type current transformers with ratio 400/5A cl. 1.0 15VA.
Three cable core current transformers with ratio 400/5A cl. 1.0
15VA.
One Zero current transformer with ratio 100/5A cl. 1.0 15VA.
One Ampere-meter (90, 96mm96mm) and Selector Switch.
Three DIN-type voltage transformers with ratio 20kV:3 / 110:3 cl.
1.0 15VA.
One Volt-meter (90, 96mm96mm) and Selector Switch.
Three Surge-Arresters type MWD-16 for 20kV rated voltage.
Watt-meter (90, 96mm96mm)
VAR-meter (90, 96mm96mm)
PF-meter (90, 96mm96mm)
Frequency-meter (90, 96mm96mm)
Digital multi-display meter GOSSEN A2000 or RECDIGIT 1600E
(144mm144mm) to indicate kWh, Volt, Ampere, kW, KVAR, PF, Freq.
Additional on-top low voltage compartment.
Page: 3 of 7

Quotation No.: 1Q0179 R. 0


Date: 03-May-1999

3.3

CUBICLE SDF1-TYPE

3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
3.3.6
3.3.7
3.3.8
3.3.9
3.3.10
3.3.11
3.3.12
3.3.13
3.3.14
3.3.15
3.3.16
3.3.17
3.4

Switch Disconnetor w/fuse Cubicle SDF1, W500mmH1895mmD1180mm


including:
Load Break Switch with SF6 extinguishing medium SFL-A 24kV 630A
20kA/1S.
HRC fuse 24kV 63A
Upper Earthing Switch type EL-210 24kV 50kA.
Down-Stream Earthing Switch type EF24-210 24kV 4kA.
Capacitive Voltage Indication to indicate the presence of voltage in
power cable.
Three cable core current transformers with ratio 100/5A cl. 1.0
15VA.
One Zero current transformer with ratio 100/5A cl. 1.0 15VA.
One Ampere-meter (90, 96mm96mm) and Selector Switch.
Three DIN-type voltage transformers with ratio 20kV:3 / 110:3 cl.
1.0 15VA.
One Volt-meter (90, 96mm96mm) and Selector Switch.
Watt-meter (90, 96mm96mm)
VAR-meter (90, 96mm96mm)
PF-meter (90, 96mm96mm)
Frequency-meter (90, 96mm96mm)
Digital multi-display meter GOSSEN A2000 or RECDIGIT 1600E
(144mm144mm) to indicate kWh, Volt, Ampere, kW, KVAR, PF, Freq.
Additional on-top low voltage compartment.

CUBICLE BUS RISER BRC-TYPE

3.4.1
3.4.2

Bus Rise Cubicle BRC1, W500mmH1895mmD1180mm including:


Capacitive Voltage Indication to indicate the presence of voltage in
power cable.
3.4.3 Three DIN-type current transformers with ratio 100/5A cl. 1.0 15VA.
3.4.4 One Ampere-meter (90, 96mm96mm) and Selector Switch.
3.4.5 Three DIN-type voltage transformers with ratio 20kV:3 / 110:3 cl.
1.0 15VA.
3.4.6 One Volt-meter (90, 96mm96mm) and Selector Switch.
3.4.7 Watt-meter (90, 96mm96mm)
3.4.8 VAR-meter (90, 96mm96mm)
3.4.9 PF-meter (90, 96mm96mm)
3.4.10 Frequency-meter (90, 96mm96mm)
3.4.11 Digital multi-display meter GOSSEN A2000 or RECDIGIT 1600E
(144mm144mm) to indicate kWh, Volt, Ampere, kW, KVAR, PF, Freq.
3.4.12 Additional on-top low voltage compartment.
3.5

CUBICLE DBC-TYPE

3.5.1
3.5.2
3.5.3
3.5.4
3.5.5
3.5.6
3.5.7
3.5.8
3.5.9

Direct Busbar Cubicle DBC1, W500mmH1895mmD1180mm including:


Capacitive Voltage Indication to indicate the presence of voltage in
power cable.
Three DIN-type current transformers with ratio 100/5A cl. 1.0 15VA.
One Ampere-meter (90, 96mm96mm) and Selector Switch.
Three DIN-type voltage transformers with ratio 20kV:3 / 110:3 cl.
1.0 15VA.
One Volt-meter (90, 96mm96mm) and Selector Switch.
Watt-meter (90, 96mm96mm)
VAR-meter (90, 96mm96mm)
PF-meter (90, 96mm96mm)
Page: 4 of 7

Quotation No.: 1Q0179 R. 0


Date: 03-May-1999

3.5.10 Frequency-meter (90, 96mm96mm)


3.5.11 Digital multi-display meter GOSSEN A2000 or RECDIGIT 1600E
(144mm144mm) to indicate kWh, Volt, Ampere, kW, KVAR, PF, Freq.
3.5.12 Additional on-top low voltage compartment.
3.6

CUBICLE SECTIONALIZER SEC-TYPE

3.6.1
3.6.2
3.6.3
3.6.4
3.6.5
3.6.6
3.6.7
3.6.8
3.6.9
3.6.10
3.6.11
3.6.12
3.6.13
3.6.14
3.7

Sectionalizing Cubicle SEC1, W500mmH1895mmD1180mm including:


Load Break Switch with SF6 extinguishing medium SFL-K 24kV 630A
20kA/1S.
Upper Earthing Switch type EL-210 24kV 50kA.
Capacitive Voltage Indication to indicate the presence of voltage in
power cable.
Three DIN-type current transformers with ratio 100/5A cl. 1.0 15VA.
One Ampere-meter (90, 96mm96mm) and Selector Switch.
Three DIN-type voltage transformers with ratio 20kV:3 / 110:3 cl.
1.0 15VA.
One Volt-meter (90, 96mm96mm) and Selector Switch.
Watt-meter (90, 96mm96mm)
VAR-meter (90, 96mm96mm)
PF-meter (90, 96mm96mm)
Frequency-meter (90, 96mm96mm)
Digital multi-display meter GOSSEN A2000 or RECDIGIT 1600E
(144mm144mm) to indicate kWh, Volt, Ampere, kW, KVAR, PF, Freq.
Additional on-top low voltage compartment

CUBICLE COUPLER SEB-TYPE

3.7.1
3.7.2
3.7.3
3.7.4
3.7.5
3.7.6
3.7.7
3.7.8
3.7.9
3.7.10
3.7.11
3.7.12
3.7.13
3.7.14
3.7.15
3.7.16
3.7.17
3.7.18
3.7.19
3.7.20

Sectionalizing
with
Circuit
Breaker
Cubicle
SEB1,
W750mmH1895mmD1180mm including:
Load Break Switch with SF6 extinguishing medium SFL-K 24kV 630A
20kA/1S.
SF6 Circuit Breaker HAD-US 24kV 630A 20kA/1S with charging-motor.
Upper Earthing Switch type EL-210 24kV 50kA.
Down-Stream Earthing Switch type EM-210 24kV 50kA.
Capacitive Voltage Indication to indicate the presence of voltage in
power cable.
Three DIN-type current transformers with ratio 400/5/5A cl. 1.0 15VA
for metering and cl. 5P10 15VA for protection.
Three-phase Overcurrent Protection type SPAJ 140 C or
Three-phase Overcurrent Protection type PR511 (self-powered).
One Ampere-meter (90, 96mm96mm) and Selector Switch.
Three DIN-type voltage transformers with ratio 20kV:3 / 110:3 cl.
1.0 15VA.
One Volt-meter (90, 96mm96mm) and Selector Switch.
One Zero current transformer with ratio 100/5A cl. 5P10 15VA for
earth-fault protection.
Three Surge-Arresters type MWD-16 for 20kV rated voltage.
Watt-meter (90, 96mm96mm)
VAR-meter (90, 96mm96mm)
PF-meter (90, 96mm96mm)
Frequency-meter (90, 96mm96mm)
Digital
multi-display
meter
GOSSEN
A2000
RECDIGIT
1600E
(144mm144mm) to indicate kWh, Volt, Ampere, kW, KVAR, PF, Freq.
Additional on-top low voltage compartment.

Page: 5 of 7

Quotation No.: 1Q0179 R. 0


Date: 03-May-1999

COMPOSITION OF MV SWITCHBOARD

Illustration below is the sample of switchboard arrangement:


Total width is 3500mm plus 40mm for end covers.
5

Remarks to Major accesories

5.1.1

5.1.2

5.1.3

5.1.4
5.1.5
5.1.6
5.1.7

DIN-Type CT
The standard price cover the spec of
Primary current:
50A, 100A, 200A, 630A
Secondary current:
1A or/and 5A
Number of cores:
1 or 2
Metering core:
cl. 0.5 or 1.0 or 1.5
Burden for metering:
10VA, 30VA
Protection core:
cl. 5P10 or 10P10
Thermal current:
20kA
Double primary is also covered by the standard price.
Example:
10-20/5/1A
cl. 0.5 7.5VA
cl. 5P10 10VA
Ith = 16kA
DIN-type VT
The standard price cover the spec of
Primary voltage:
24kV/3
Secondary voltage:
100V/3 or 110V/3
Open-delta voltage:
100V/3 or 110V/3
Class:
0.5 or 1.0 or 1.5
Burden:
15VA, 50VA or (100VA for cl. 1)
Double pole primary is also covered by the standard price.
Example:
22000:3/110:3/110:3
cl. 0.5
50VA
Zero CT
The standard price cover the spec of
Primary current:
100A
Secondary current:
1A
Protection core:
cl. 5P10 or 10P10
Surge-Arresters
The standard price cover the spec of
Voltage up to 24 kV
All analog meter
The standard price cover the spec of
Class same as instrument trafo above
Fuse
The standard price cover the spec of
Voltage up to 24 kV and rating up to 80A
Additional on-top low voltage compartment.
The standard price cover the spec of
Height:
450mm
Depth:
250mm
Width:
375mm or 500mm or 750mm

PRECISATIONS AND CLARIFICATION


The switchboard offered are in full accordance with IEC standards,
accordance with other standards are not guaranteed.
The main busbars of our switchboard are copper and isolate with brown
heat-shrinkable tube.
Page: 6 of 7

Quotation No.: 1Q0179 R. 0


Date: 03-May-1999

All internal wiring are black and there are identified with numbered
ferrules at both ends.
Wiring for controls and signals are 1.5mm
Wiring for current circuits are 2.5mm
Documentation of as built drawings and equipment manuals will be
supplied for one copy.
Delivery time is 3 months after approval drawings have been approved by
the customer.
Exclusions in this offer:
Power cables
Control wiring between cubicles
Interlockings between cubicles
Erection and commissioning
GENERAL REMARKS
Every single cubicle shall be tested in the ABB workshop according to
the normal tests for acceptance consisting of:
visual inspection
dielectric test at power frequency
mechanical operations
sequence of operations.

Page: 7 of 7