of operation
This infosheet gives information about:
> selection criteria of chillers
> energy performance of different types of chillers
> description of chilled water systems.
Introduction
Water chiller is a broad term describing an overall package which includes refrigeration plant, water
chiller and air or water cooled condenser. This name infers that the compressor, condenser and chiller
with internal piping and controls are combined into a single unit.
Water chiller plant may range in size from small capacity reciprocating compressor units with air or water
cooled condensers up to large units incorporating centrifugal or screw compressors. Large water chillers
are normally water cooled using the recirculated water from a cooling tower.
Central chilled water units are used in air conditioning systems comprising of air handling units each
fitted with chilled water coils. These air handling units can be either located in a central plant room or
distributed throughout the building.
The type of compressor used would vary depending upon the capacity of the individual units. Generally,
reciprocating compressors are used for small to medium-sized water chillers whilst larger capacity water
chillers incorporate centrifugal or screw compressors.
Selection criteria
When selecting water chillers it is essential that the following be carefully considered:
> Performance characteristics at both maximum and part load operation. To achieve efficient operation it
is necessary that the water chiller be able to reduce the refrigeration capacity as the cooling load of the
building decreases.
> Selection of the type of water chiller must also take into account the minimum load that the chiller may
be required to operate down to. As an example, reciprocating compressors can unload to between 12
15%, centrifugal chillers down to 2025% and screw compressors down to 1015%. Should this turn
down ratio be insufficient to meet the minimum cooling requirement on the building, then multiple
chillers will be necessary in order to achieve energy efficient operation.
> For water cooled equipment to achieve maximum energy efficiency, it is important that the cooling
tower water system operate at the lowest possible temperature. Data from the water chiller
manufacturers can be obtained in order to determine the minimum acceptable condenser water
temperature. As a guide, for each 1C reduction in the water temperature entering the condenser,
power reduction of the chiller is reduced by approximately 2%. Most water chillers can operate
satisfactorily with condenser water temperature down to 24C.
> The chilled water temperature should be maintained as high as possible to reduce the energy
consumption of the compressor. Typically, a 1C increase in chilled water temperature can reduce the
compressor energy input by approximately 2%.
> The temperature differentials across both the condenser and chiller heat exchangers should optimized
to be as high as possible. High temperature differentials will result in lower water flow rate with a
consequential reduction of pumping energy.
1 of 6
> Adequate water treatment should be provided in order to maintain the heat exchange surfaces in a
clean condition to achieve maximum heat transfer efficiency.
Efficiency of water chillers is generally measured by the energy efficiency ratio (EER). This is the ratio of
the electrical energy input (kWe) to the refrigeration output (kWr). Information concerning the EER at
varying operating conditions can be obtained from the water chiller manufacturers and assessment of
this data should form part of the selection criteria for water chilling equipment.
As a guide, the following are considered to be typical values at full load operation:
> Reciprocating: 0.270.29 kWe/kWr
> Centrifugal: 0.180.22 kWe/kWr
> Screw: 0.180.22 kWe/Kwr
Typical energy consumption curves are included later.
Water chiller unitreciprocating compressor
A water chiller of this type incorporates either single or multiple centrifugal compressors. Reciprocating
compressors are limited in size generally to between 3501000 kWr for economic reasons. A water
chiller which incorporates multiple compressors can provide good staging in reduction of capacity. The
following is typical energy consumption curve.
0.3
kWe/kWr
0.25
0.2
0.15
10
20
30
40
50
60
70
80
90
100
% LOAD
2 of 6
0.40
0.35
kWe/kWr
0.30
0.25
0.20
0.15
0.10
0.05
0.00
10
20
30
40
50
60
70
80
90
100
% LOAD
kWe/kWr
0.60
0.50
0.40
0.30
0.20
0.10
10
20
30
40
50
60
70
80
90
100
% LOAD
3 of 6
Constant flow
It is usual for small to medium water chilling systems to operate as constant flow systems. This means
that the same quantity of water is circulated at all times regardless of the load. It is essential that the flow
to the water chillers be maintained at a relatively constant value in order to avoid the possibility of water
freezing within the tubes.
Constant flow chilled water systems can be energy inefficient as it is often necessary for the water to
continue to circulate through the equipment to maintain flow even though at light load the temperature
difference between supply and return water may be only 1C or 2C.
The following diagram illustrates a constant flow water chiller system.
4 of 6
5 of 6
An alternative scheme is to measure the chilled water quantity together with flow and return
temperatures and use this to calculate the cooling load. Having calculated the cooling load it is then
possible to stage the chilled water equipment to achieve minimum energy consumption. It is important
that the load profile for each chiller be considered and that the sequencing be carried out by operating
the water chillers at their most efficient operating point to achieve minimum energy consumption.
In this way, the water chilling unit which has the capacity closest to the actual requirement can be
energised to operate at peak efficiency. Variable speed drives on centrifugal chilled water units will allow
a more economic operation of the equipment at lower capacity operation.
Conclusion
Selecting the correct chiller for the appropriate application can lead to significant energy savings, reduce
maintenance costs and greenhouse gas emissions.
The information in this document is derived from various sources and is understood to be correct at the time of publication. However, the
information may not be error free and may not be appropriate for a particular purpose. The Sustainable Energy Authority accepts no liability
whatsoever to any person for an injury, loss or damage that may arise in connection with any use or reliance on the information.
6 of 6