Anda di halaman 1dari 50

SWITCHRACKS

Custom designed, switchracks, panel


boards, motor starters

Explosion Proof Electrical Equipment

Ex Enclosures

www.feam-ex.com

SWITCHRACKS

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 /22 (Dusts)


Classification: Group II - Category 2G 2D

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
(

( II 2 G) Ex db IIB+H2 T6T3
II 2 G) Ex db [ia/ib] IIB+H2 T6T3
( II 2 D) Ex tb IIIC T85CT150C

II 2 G Ex d IIC T6...T3
II 2(1) GD Ex d [ia/ib IIA or IIB or IIC Ga] IIC T6...T3
II 2 D Ex tb IIIC T85C...T200C
II 2 D Ex tb [ia Da/ib] IIIC T85C

EXECUTION

II 2 G Ex d e ia/ib ia mb IIC T6, T5 or T4 Gb


II 2 D Ex tb IIIC T85C or T100C Db
RULES OF COMPLIANCE

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-11; EN/IEC 60079-31

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +60C

OTHER AVAILABLE CERTIFICATES

IECEx
INMETRO
EAC
RINA
RUSSIAN MARINE CERTIFICATE (RMRS)
UL NEC 505

NEC - NEMA 4, 7, 9
Class I - Groups B, C, e D
Class II - Groups E, F, e G
Class III

INSTALLATION
PROTECTION

4 , 7 BCD , 9 EFG

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE
CERTIFICATION AND COMPLIANCES

-20C +40C
UL Standard 1203 - 4 Ed. (15 Sett. 2006)
Explosion-Proof / Dust-Ignition-Proof
Electrical Equipment for Use in Hazardous (Classified) Locations

Mechanical characteristics
Boxes
Painting
Screws
Gaskets
Pipes and fittings
Supporting rack

marine grade copper free aluminum - stainless steel AISI 316L


external epoxy powders grey RAL-9006 colour (standard)
external stainless steel
silicon rubber
galvanized steel (standard) - stainless steel (optional)
hot dip galvanized steel - stainless steel

On request accessories:
Stainless steel pipes and fittings
Galvanized steel epoxy painted supporting rack
Stainless steel supporting rack

Internal anticondensate painting orange RAL-2004


External colours different from standard

Bartec Feam Catalogue 04 I 95

Switchracks
panel boards - general information

Explosion Proof Electrical Equipment

Ex Enclosures

www.feam-ex.com

SWITCHRACKS

Description:
SWITCH-RACK is a word usually adopted to indicate an ensemble of control units, signaling units, motor starters, switching units, and so on.
Switch-racks are mechanically assembled on robust frame with various fixing solutions (ground, wall, etc.), electrically wired up on purpose.
BARTEC-FEAM since over 50 years, designs and manufacturers switch-racks according to its own diagram or according to customers specifications,
in full compliance with European CENELEC standards.

INFORMATIONS:
Test and inspections:
All components and documents are tested and checked at the various working stages , according to BARTEC-FEAMs Quality Pans.
The above mentioned Plans call for all test and checks necessary to ensure an execution on purpose. Whenever a strict, documented quality
control execution is required please advise BARTEC-FEAM Sales Department. When the switchrack is completed ,an effective working inspection
is carried out, and an inspection report is written. Customers inspectors are allowed in BARTEC-FEAMs workshop to survey working evolution
and to witness final inspection.

Standard Tests and Checks:


Visual and dimensional control
Working control
Equipment control

Mechanical running control


Hydrostatic test
Insulation test

Grinding check
Insulation resistance measuring
Insulation test / Electrical running test

Ordering:
The following technical information are needed to work out a switchrack. A direct consult with BARTEC-FEAM Sales Department is however advisable,
especially when problems of space arise.
A) Area classification and mode of protection.
B) Applicable standards
C) Power and auxiliary wiring diagrams or full, detailed description of switchracks work
D) Maximum overall dimensions.
Possibility of double front execution
E) Location of incoming and outgoing cable entries
F) Threading, size and number of hubs
G) Type of cable entries
H) Painting cycle, type and color
I) Switchracks location (indoor or outdoor)
L) Request of protective canopy(if needed)
N) Vendor List of components to be respected (if any)

Responsibility:
Once acknowledged the order, BARTEC-FEAM Technical Dept. issues electrical and mechanical manufacturing drawings.
These drawings are sent to customer for approval and whichever change has to be advised as soon as possible.
We take full responsibility for engineering, purchasing and assembling of components ,wiring and erection of the ensemble ready for
installation.

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this
bulletin can be considered as binding on our confirmation only.

96 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

EJB Enclosures

Ex Enclosures

www.feam-ex.com

EJB

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II - Category 2G 2D

Certificate
NEMA Type 4X

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
EXECUTION

RULES OF COMPLIANCE

( II 2 G) Ex db IIB+H2 T6T3
II 2 G) Ex db [ia/ib] IIB+H2 T6T3
( II 2 D) Ex tb IIIC T85CT150C

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-11; EN/IEC 60079-31

EC Type-Examination Certificate

INERIS 13 ATEX 0022X

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +60C

OTHER AVAILABLE CERTIFICATES

Component: INERIS 13 ATEX 9019U


IECEx: IECEx INE 13_0070X
INMETRO: CEPEL 12.2139
EAC: TC RU C-IT.08..01499
RINA: ELE18111CS_012
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
NEC 505: UL 20141204-E302348 - Type rating NEMA 1, 12, 4 and 4X

Mechanical characteristics
Body/cover

marine grade copper free aluminium light alloy

Screws

stainless steel

Internal mounting plate

hot dip galvanized steel / aluminum

Fixing

fixing lugs AL UNI EN 1706:1999 - galvanized steel stirrups sp. 10mm (EJB71/73-91/93)

Hinges

On the long side - cast on enclosure body and cover

On Request Accessories:
External epoxy painting with colour on request

Drain and breather valves

Internal anticondensate painting orange RAL-2004

Galvanized steel body & cover

O-Ring gaskets on cover

Cast iron body & cover

Glass windows on cover

Bartec Feam Catalogue 04 I 97

Explosion Proof Electrical Equipment

Ex Enclosures

CODE

A [mm]

B [mm]

C [mm]

D [mm]

E [mm]

F [mm]

G [mm]

H [mm]

I [mm]

L [mm]

M [mm]

INT. PLATE
X - Y [mm]

WEIGHT
[Kg]

DETAIL

EJB-08

380

170

188

126

136

270

156

11

91

315

105

305 - 85

8,2

EJB-11

175

175

197

122

132

78

171

11

90

113

113

100 - 100

4,00

EJB-21

284

245

267

169

179

160

241

11

121

216

176

180 - 140

11,20

EJB-22

300

200

221

222

232

195

186

11

174

229

129

180 - 100

11,30

EJB-23

310

260

281

197

207

195

251

11

152

245

195

200 - 160

13,30

EJB-30

415

315

337

164

174

294

299

11

113

345

245

300 - 200

19,50

EJB-31

415

315

337

246

256

294

299

11

195

345

245

300 - 200

24,20

EJB-51

566

366

388

256

268

360

337

13

200

487

287

450 - 250

36,10

EJB-61

670

470

491

361

373

500

443

13

307

580

380

530 - 330

68,10

EJB-63

670

470

491

236

248

500

443

13

182

580

380

530 - 330

50,50

EJB-71

742

542

572

429

439

520

580

16

331

632

432

590 - 390

110,40

EJB-73

742

542

572

311

321

520

580

16

213

632

432

590 - 390

95,60

EJB-91

960

660

697

462

472

700

650

16

350

825

525

750 - 440

188,50

EJB-93

960

660

697

305

315

700

650

16

193

825

525

750 - 440

166,50

Reference details

C
B

LxM

www.feam-ex.com

EJB

EJB Technical features

EJB Glass windows on cover


ENCLOSURE CODE

DIMENSIONS

WINDOW
CODE

EJB-08

EJB-11

EJB-21

EJB-22

EJB-23

EJB-30/31

EJB-51

F1

F2

F3

F4

F5

F6

F7

F8

F9

DETAIL

A [mm]

B [mm]

60

60

75

75

110

75

150

75

150

150

300

75

300

150

300

300

450

300

98 I Bartec Feam Catalogue 04

EJB-61/63 EJB-71/73 EJB-91/93

Explosion Proof Electrical Equipment

EJB Glass windows on cover

Ex Enclosures

Reference details

Reference details

PLATES

EJB

PLATE X-Y

CUSTODIA tipo
ENCLOSURE type
Via M. Pagano, 3
I-20090 Trezzano s/N
ITALY
www.feam-ex.com

0722

II2 GD

year s/n

BKI 08 ATEX 019


V

Hz

Ex d IIB+H

Ta

A
2

Ex tD A21 IP66 T

VA

NON APRIRE SOTTO TENSIONE


DO NOT OPEN WHILE ENERGIZED
Ad ogni apertura del coperchio
ripristinare il grasso ai siliconi.
accertarsi che le valvole di respirazione
e drenaggio siano sempre chiuse
Renew silicone grease every tyme
cover is opened. and make sure
that the drain and breather valves
are always closed.

11.00.88

S.r.l.

www.feam-ex.com

EJB Indicative quantity of terminals and relevant section


CODE

SECT. 2,5
[sq/mm]

SECT. 6,0
[sq/mm]

SECT. 10,0
[sq/mm]

SECT. 16,0
[sq/mm]

SECT. 35,0
[sq/mm]

SECT. 50,0
[sq/mm]

SECT. 70,0
[sq/mm]

SECT. 240,0
[sq/mm]

INT. PLATE X - Y
[mm]

EJB-08

24 x 1

18 x 1

10 x 1

305 - 85

EJB-11

12 x 1

8x1

6x1

100 - 100

EJB-21

30 x 1

20 x 1

14 x 1

12 x 1

9x1

7x1

5x1

1x1

180 - 140

EJB-22

30 x 1

20 x 1

14 x 1

12 x 1

9x1

7x1

5x1

1x1

180 - 100

EJB-23

35 x 1

22 x 1

16 x 1

14 x 1

11 x 1

9x1

7x1

2x1

200 - 160

EJB-30

52 x 2

32 x 2

24 x 2

20 x 2

14 x 2

12 x 1

8x1

4x1

300 - 200

EJB-31

52 x 2

32 x 2

24 x 2

20 x 2

14 x 2

12 x 1

8x1

4x1

300 - 200

EJB-51

80 x 2

46 x 2

36 x 2

30 x 2

22 x 2

18 x 2

16 x 1

6x1

450 - 250
530 - 330

EJB-61/63

92 x 3

58 x 3

46 x 3

38 x 3

28 x 3

26 x 2

22 x 2

12 x 1

EJB-71/73

110 x 3

70 x 3

56 x 3

46 x 3

34 x 3

28 x 2

24 x 2

12 x 1

590 - 390

EJB-91/93

140 x 3

90 x 3

70 x 3

60 x 3

44 x 3

36 x 3

32 x 2

14 x 2

750 - 440

EJB Body and cover enclosures drilling layout


ENCLOSURE
CODE

DRILLING AREA
A-B [mm]

EJB-08

300x60

QUANTITY ALLOWED ENTRIES FOR SIZE


(from 1 to size 8)

DRILLING AREA
C-D [mm]

QUANTITY ALLOWED ENTRIES FOR SIZE


(from 1 to size 8)

95x60

EJB-11

100x60

100x60

EJB-21

200x90

10

160x90

EJB-22

215x130

15

11

110x130

EJB-23

215x105

11

165x105

EJB-30

320x65

13

225x65

EJB-31

320x150

28

18

14

11

225x150

20

12

EJB-51

460x155

44

27

24

20

12

10

255x155

24

15

12

11

EJB-61

550x250

72

50

36

32

21

21

14

350x250

48

30

24

20

12

12

EJB-63

550x130

36

29

18

16

14

350x130

24

17

12

10

EJB-71

570x270

90

55

46

39

32

21

15

10

370x270

59

35

28

25

21

12

10

EJB-73

570x160

40

26

22

18

14

12

370x160

26

18

14

12

11

EJB-91

745x290

112

84

65

55

40

28

23

14

440x290

70

42

35

35

24

18

13

EJB-93

745x145

48

42

29

22

10

11

440x145

30

24

21

14

12

Bartec Feam Catalogue 04 I 99

EJB
Body and cover enclosures drilling layout
Reference details

SIZE

UNI 6125

ISO 228/1

ASA B2.1

ISO 965/I

GK 1/2

G 1/2

1/2 NPT

M20

GK 3/4

G 3/4

3/4 NPT

M25

GK 1

G 1

1 NPT

M32

GK 1-1/4

G 1-1/4

1-1/4 NPT

M40

GK 1-1/2

G 1-1/2

1-1/2 NPT

M50

GK 2

G 2

2 NPT

M63

GK 2-1/2

G 2-1/2

2-1/2 NPT

M75

GK 3

G 3

3 NPT

M85

EJB

Ex Enclosures

EJB Threads comparation table

WALL DRILLING AREA

Max allowed quantity of push button and pilot light


ENCLOSURE
CODE

DRILLING AREA
E-F [mm]

MAX OPERATORS
PERMITTED

EJB-08

300x90

10

EJB-11

120x120

EJB-21

200x155

12

EJB-22

200x100

12

EJB-23

215x165

16

EJB-30

305x205

30

EJB-31

305x205

30

EJB-51

465x265

54

EJB-61

575x370

56

EJB-63

575x370

56

EJB-71

590x390

48

EJB-73

590x390

48

EJB-91

800x500

54

EJB-93

800x500

54

Reference details

COVER DRILLING AREA


F

www.feam-ex.com

Explosion Proof Electrical Equipment

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this
bulletin can be considered as binding on our confirmation only.

100 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

EJB INX Enclosures

Ex Enclosures

www.feam-ex.com

EJB INX

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II - Category 2G 2D

Certificate
NEMA Type 4X

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
(II 2 G) Ex db IIB+H2 T6T3
(II 2 G) Ex db [ia/ib] IIB+H2 T6T3
(II 2 D) Ex tb IIIC T85CT150C

EXECUTION
RULES OF COMPLIANCE

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-11; EN/IEC 60079-31

EC Type-Examination Certificate

INERIS 13 ATEX 0022X

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +60C

OTHER AVAILABLE CERTIFICATES

Component: INERIS 13 ATEX 9019U


IECEx: IECEx INE 13_0070X
INMETRO: CEPEL 12.2139
EAC: TC RU C-IT.08..01499
RINA: ELE18111CS_012
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
NEC 505: UL 20141204-E302348 - Type rating NEMA 1, 12, 4 and 4X

Mechanical characteristics
Body & cover

stainless steel AISI-316 L

Screws

stainless steel AISI-316 L

Internal mounting plate

stainless steel AISI-316 L

Fixing

fixing lugs stainless steel AISI-316 L - stainless steel stirrups sp.10mm (EJB71/73 and EJB91/93)

Hinges

welded on cover and body

Opening handle

insulating material fixed on cover by stainless steel screws

On request accessories:
External epoxy painting (any colours)
Internal anticondensate painting orange RAL-2004
O-Ring gaskets on cover

Glass windows on cover


Drain and breather valves

Bartec Feam Catalogue 04 I 101

Explosion Proof Electrical Equipment

EJB INX Technical features

EJB-11 INX
EJB-21 INX
EJB-22 INX
EJB-23 INX
EJB-30 INX
EJB-31 INX
EJB-51 INX
EJB-61 INX
EJB-63 INX
EJB-71 INX
EJB-73 INX
EJB-91 INX
EJB-93 INX

A
[mm]

B
[mm]

C
[mm]

D
[mm]

E
[mm]

F
[mm]

G
[mm]

H
[mm]

I
[mm]

L
[mm]

M
[mm]

INT. PLATE
X - Y [mm]

WEIGHT
[Kg]

DETAIL

175
284
300
310
415
415
566
670
670
742
742
960
960

175
245
200
260
315
315
366
470
470
542
542
660
660

197
267
221
281
337
337
388
491
491
572
572
697
697

122
169
222
197
164
246
256
361
236
429
311
462
305

132
179
232
207
174
256
268
373
248
439
321
472
315

78
160
195
195
294
294
360
500
500
520
520
700
700

171
241
186
251
299
299
337
443
443
580
580
650
650

11
11
11
11
11
11
13
13
13
16
16
16
16

90
121
174
152
113
195
200
307
182
331
213
350
193

113
216
229
245
345
345
487
580
580
632
632
825
825

113
176
129
195
245
245
287
380
380
432
432
525
525

100 - 100
180 - 140
180 - 100
200 - 160
300 - 200
300 - 200
450 - 250
530 - 330
530 - 330
590 - 390
590 - 390
750 - 440
750 - 440

11,00
32,00
38,00
40,00
53,00
62,00
110,00
152,00
140,00
280,00
200,00
618,00
573,00

A
A
A
A
A
A
A
A
A
A
A
A
A

Reference details

A
C

E
D

L xM

www.feam-ex.com

EJB INX

CODICE

Ex Enclosures

EJB INX Indicative quantity of terminals and relevant section


SEZ. 2,5
[sq/mm]

SEZ. 6,0
[sq/mm]

SEZ. 10,0
[sq/mm]

SEZ. 16,0
[sq/mm]

SEZ. 35,0
[sq/mm]

SEZ. 50,0
[sq/mm]

SEZ. 70,0
[sq/mm]

SEZ. 240,0
[sq/mm]

INT. PLATE
X - Y [mm]

EJB-11 INX

12 x 1

8x1

6x1

4x1

2x1

100 - 100

EJB-21 INX

30 x 1

20 x 1

14 x 1

12 x 1

9x1

7x1

5x1

1x1

180 - 140

EJB-22 INX

30 x 1

20 x 1

14 x 1

12 x 1

9x1

7x1

5x1

1x1

180 - 100

EJB-23 INX

35 x 1

22 x 1

16 x 1

14 x 1

11 x 1

9x1

7x1

2x1

200 - 160

EJB-30 INX

52 x 2

32 x 2

24 x 2

20 x 2

14 x 2

12 x 1

8x1

4x1

300 - 200

CODE

EJB-31 INX

52 x 2

32 x 2

24 x 2

20 x 2

14 x 2

12 x 1

8x1

4x1

300 - 200

EJB-51 INX

80 x 2

46 x 2

36 x 2

30 x 2

22 x 2

18 x 2

16 x 1

6x1

450 - 250
530 - 330

EJB-61/63 INX

92 x 3

58 x 3

46 x 3

38 x 3

28 x 3

26 x 2

22 x 2

12 x 1

EJB-71/73 INX

110 x 3

70 x 3

56 x 3

46 x 3

34 x 3

28 x 2

24 x 2

12 x 1

590 - 390

EJB-91/93 INX

140 x 3

90 x 3

70 x 3

60 x 3

44 x 3

36 x 3

32 x 2

14 x 2

750 - 440

102 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

EJB INX Glass Windows on Cover

Ex Enclosures

EJB-21
INX

EJB-22
INX

EJB-23
INX

EJB-30/31
INX

EJB-51
INX

EJB-61/63 EJB-71/73 EJB-91/93


INX
INX
INX

A
[mm]

B
[mm]

DETAIL

F1

60

60

F2

75

75

F3

110

75

F4

150

75

F5

150

150

F6

300

75

F7

300

150

F8

300

300

F9

450

300

Reference details

EJB INX

EJB-11
INX

DIMENSIONS

www.feam-ex.com

ENCLOSURE CODE

WINDOW
CODE

Reference details

PLATE
B

S.r.l.

CUSTODIA tipo
ENCLOSURE type
Via M. Pagano, 3
I-20090 Trezzano s/N
ITALY
www.feam-ex.com

0722

II2 GD

year s/n

BKI 08 ATEX 019 Ta

Ex d IIB+H

Hz

A
2

Ex tD A21 IP66 T

VA

NON APRIRE SOTTO TENSIONE


DO NOT OPEN WHILE ENERGIZED
Ad ogni apertura del coperchio
ripristinare il grasso ai siliconi.
accertarsi che le valvole di respirazione
e drenaggio siano sempre chiuse
Renew silicone grease every tyme
cover is opened. and make sure
that the drain and breather valves
are always closed.

11.00.88

PLATE X-Y

EJB INX Body and cover enclosures drilling layout


ENCLOSURE
CODE
EJB-11 INX
EJB-21 INX
EJB-22 INX
EJB-23 INX
EJB-30 INX
EJB-31 INX
EJB-51 INX
EJB-61 INX
EJB-63 INX
EJB-71 INX
EJB-73 INX
EJB-91 INX
EJB-93 INX

DRILLING AREA
A-B [mm]
100x60
200x90
215x130
215x105
320x65
320x150
460x155
550x250
550x130
570x270
570x160
745x290
745x145

QUANTITY ALLOWED ENTRIES FOR SIZE


(from 1 to size 8)
1
3
10
15
11
13
28
44
72
36
90
40
112
48

2
2
7
11
8
7
18
27
50
29
55
26
84
42

3
2
5
8
6
5
14
24
36
18
46
22
65
29

4
1
3
6
4
5
11
20
32
16
39
18
55
22

5
1
2
6
3
4
8
12
21
14
32
14
40
10

6
2
3
3
3
6
10
21
7
21
12
28
11

7
1
2
2
3
6
14
5
15
7
23
9

DRILLING AREA
C-D [mm]

100x60
160x90
110x130
165x105
225x65
225x150
255x155
350x250
350x130
370x270
370x160
440x290
440x145

1
1
2
3
8
4
10
4
14
5

QUANTITY ALLOWED ENTRIES FOR SIZE


(from 1 to size 8)
1

3
8
9
9
9
20
24
48
24
59
26
70
30

2
5
5
6
5
12
15
30
17
35
18
42
24

2
4
5
6
4
9
12
24
12
28
14
35
21

1
3
4
5
3
8
11
20
10
25
12
35
14

1
2
2
2
3
6
6
12
8
21
8
24
12

1
1
2
2
5
6
12
4
12
11
18
7

1
1
1
2
3
8
3
10
4
13
5

1
1
1
2
6
3
6
2
8
3

Reference details

WALL DRILLING AREA

Bartec Feam Catalogue 04 I 103

EJB INX
Body and cover enclosures drilling layout

www.feam-ex.com

ENCLOSURE
CODE

DRILLING AREA
E-F [mm]

MAX OPERATORS
PERMITTED

EJB-11 INX

120x120

EJB-21 INX

200x155

12

EJB-22 INX

200x100

12

EJB-23 INX

215x165

16

EJB-30 INX

305x205

30

EJB-31 INX

305x205

30

EJB-51 INX

465x265

54

EJB-61 INX

575x370

56

EJB-63 INX

575x370

56

EJB-71 INX

590x390

48

EJB-73 INX

590x390

48

EJB-91 INX

800x500

54

EJB-93 INX

800x500

54

Ex Enclosures

Reference details

COVER DRILLING AREA


F

EJB INX

Max allowed q.ty of push button and pilot light

Explosion Proof Electrical Equipment

EJB INX Threads comparation table


SIZE

UNI 6125

ISO 228/1

ASA B2.1

ISO 965/I

GK 1/2

G 1/2

1/2 NPT

M20

GK 3/4

G 3/4

3/4 NPT

M25

GK 1

G 1

1 NPT

M32

GK 1-1/4

G 1-1/4

1-1/4 NPT

M40

GK 1-1/2

G 1-1/2

1-1/2 NPT

M50

GK 2

G 2

2 NPT

M63

GK 2-1/2

G 2-1/2

2-1/2 NPT

M75

GK 3

G 3

3 NPT

M85

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this
bulletin can be considered as binding on our confirmation only.

104 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

EJC Enclosures

Ex Enclosures

www.feam-ex.com

EJC

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 /22 (Dusts)


Classification: Group II - Category 2G 2D

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex db IIC T6...T3
II 2 G Ex db [ia/ib] IIC T6
II 2 D Ex tb IIIC T85CT150C
II 2 D Ex tb [ia/ib] IIIC T85C

EXECUTION

RULES OF COMPLIANCE

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-11; EN/IEC 60079-31

EC Type-Examination Certificate

BKI 11 ATEX 0019

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +80C

OTHER AVAILABLE CERTIFICATES

IECEx: IECEx BKI 11.0010


INMETRO: CEPEL 12.2137
EAC: TC RU C-IT.08..01499 (-60C +60C)
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315

Mechanical characteristics
Body/cover

marine grade copper free aluminium light alloy

Screws

stainless steel

Internal mounting plate

hot dip galvanized steel

Fixing

fixing lugs al uni 4514

Opening handle

insulating material fixed on cover by stainless steel screws

Valves

Drain and breather stainless steel AISI-316L

On Request Accessories:
External epoxy painting (any colours)
Internal anticondensate painting orange RAL-2004

O-Ring gaskets on cover


Glass windows on cover

Bartec Feam Catalogue 04 I 105

Explosion Proof Electrical Equipment

Ex Enclosures

CODE

A
[mm]

B
[mm]

C
[mm]

D
[mm]

E
[mm]

F
[mm]

G
[mm]

H
[mm]

I
[mm]

L
[mm]

M
[mm]

INT. PLATE
X-Y [mm]

WEIGHT
[Kg]

DETAIL

EJC-21

285

245

267

171

161

170

221

11

113

216

176

180 x 140

12,00

EJC-30

415

315

338

156

146

294

285

11

94

344

244

300 x 200

21,00

EJC-31

415

315

338

238

228

294

285

11

176

344

244

300 x 200

25,00

EJC-51

566

366

388

252

240

360

337

13

185

487

287

450 x 250

40,00

EJC-61

668

468

490

355

343

500

443

13

277

580

380

530 x 330

80,00

EJC-63

668

468

490

229

217

500

443

13

151

580

380

530 x 330

66,00

Reference details

C
B

LxM

www.feam-ex.com

EJC

EJC Technical features

EJC Glass windows on cover


WINDOW
CODE

ENCLOSURE CODE

WINDOW DIMENSIONS

DETAIL

EJC-21

EJC-30/31

EJC-51

EJC-61/63

A [mm]

B [mm]

F1

60

60

F2

75

75

F3

110

75

F4

150

75

F5

150

150

F6

300

75

F7

300

150

F8

300

300

F9

450

300

106 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

EJC Glass windows on cover


Reference details

Ex Enclosures

Reference details

PLATE

EJC

PLATE X-Y

www.feam-ex.com

EJC Body and cover enclosures drilling layout


Reference details

QUANTITY ALLOWED ENTRIES FOR SIZE


(from 1 to size 8)
1
2
3
4
5
6
7 8

ENCLOSURE
CODE

DRILLING AREA
A-B [mm]

EJC-21

200 x 75

EJC-30

320 x 50

EJC-31

320 x 145

21

18

14

11

EJC-51

460 x 140

33

26

16

14

12

EJC-61

550 x 230

60

40

27

24

14

14

10

EJC-63

550 x 110

35

20

18

15

10

ENCLOSURE
CODE

DRILLING AREA
C-D [mm]

EJC-21

160 x 75

EJC-30

225 x 50

EJC-31

225 x 145

15

12

EJC-51

255 x 140

18

14

EJC-61

350 x 230

40

24

18

15

EJC-63

350 x 110

23

12

12

QUANTITY ALLOWED ENTRIES FOR SIZE


(from 1 to size 8)
1
2
3
4
5
6
7 8

ENCLOSURE
CODE

DRILLING AREA
E-F [mm]

MAX OPERATORS
PERMITTED

EJC-21

200 x 155

12

EJC-30

305 x 205

30

EJC-31

305 x 205

30

EJC-51

460 x 260

54

EJC-61

540 x 360

56

EJC-63

540 x 360

56

Bartec Feam Catalogue 04 I 107

EJC Indicative quantity of terminals


and relevant section

EJC
www.feam-ex.com

SECT. 16,0
[sq/mm]

SECT.35,0
[sq/mm]

Ex Enclosures

SECT. 50,0
[sq/mm]

SECT. 70,0
[sq/mm]

SECT. 240,0
[sq/mm]

INT. PLATE X - Y

SECT. 2,5
[sq/mm]

SECT. 6,0
[sq/mm]

EJC-21

30 x 1

20 x 1

14 x 1

12 x 1

8x1

6x1

2x1

1x1

180 x 140

EJC-30

52 x 2

32 x 2

24 x 2

20 x 2

14 x 2

12 x 1

8x1

4x1

300 x 200

EJC-31

52 x 2

32 x 2

24 x 2

20 x 2

14 x 2

12 x 1

8x1

4x1

300 x 200

EJC-51

80 x 2

46 x 2

36 x 2

30 x 2

22 x 2

18 x 2

16 x 1

6x1

450 x 250

EJC-61

92 x 3

58 x 3

46 x 3

38 x 3

28 x 3

26 x 2

22 x 2

12 x 1

530 x 330

EJC-63

92 x 3

58 x 3

46 x 3

38 x 3

28 x 3

26 x 2

22 x 2

12 x 1

530 - 330

CODE

SECT. 10,0
[sq/mm]

Explosion Proof Electrical Equipment

[mm]

EJC Flamepath detail

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this
bulletin can be considered as binding on our confirmation only.

108 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

EJB UL Enclosures

Ex Enclosures

www.feam-ex.com

EJB UL

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 /22 (Dusts)


Classification: Group II - Category 2G 2D

Certificate
NEMA Type 4X

REFERENCE STANDARDS
TERMINAL BOARD / POWER UNITS CONTROL AND SIGNALLING UNITS
NEC - NEMA 4, 7, 9
Class I - Groups B, C, e D
Class II - Groups E, F, e G
Class III

INSTALLATION
PROTECTION

4 , 7 BCD , 9 EFG

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-20C +40C
UL Standard 1203 - 4 Ed. (15 Sett. 2006)
Explosion-Proof / Dust-Ignition-Proof
Electrical Equipment for Use in Hazardous (Classified) Locations

CERTIFICATION AND COMPLIANCES

Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
EXECUTION

RULES OF COMPLIANCE

( II 2 G) Ex db IIB+H2 T6T3
II 2 G) Ex db [ia/ib] IIB+H2 T6T3
( II 2 D) Ex tb IIIC T85CT150C

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-11; EN/IEC 60079-31

EC Type-Examination Certificate

INERIS 13 ATEX 0022X

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +60C

OTHER AVAILABLE CERTIFICATES

IECEx: IECEx INE 13_0070X


NEC 505: UL 20141204-E302348 - Type rating NEMA 1, 12, 4 and 4X

Mechanical characteristics
Body and cover
Screws
Internal plate
Fixing
Gaskets

marine grade copper free aluminium light alloy


stainless steel - internal / external
hot dip galvanized steel / aluminium
galvanized steel stirrups th.10mm
O-RING silicon rubber on cover

On Request Accessories:
External epoxy painting (any colours)
Internal anticondensate painting orange RAL-2004
O-Ring gaskets on cover

Glass windows on cover


Drain and breather valves
Stainless steel AISI-316L hinges

Bartec Feam Catalogue 04 I 109

Explosion Proof Electrical Equipment

Ex Enclosures

CODE

A
[mm]

B
[mm]

C
[mm]

D
[mm]

E
[mm]

F
[mm]

G
[mm]

H
[mm]

I
[mm]

L
[mm]

INT. PLATE
X-Y [mm]

WEIGHT
[Kg]

DETAIL

EJB-21UL

320

280

177

189

180

233

121

214

174

13

180 - 140

13,50

EJB-31UL

450

350

248

260

294

287

191

341

241

13

325 - 225

27,00

EJB-51UL

600

400

266

278

360

333

195

481

281

13

460 - 260

52,50

EJB-61UL

710

500

389

397

500

460

277

566

356

12

560 - 360

114,00

EJB-63UL

710

500

259

267

500

460

147

571

362

12

560 - 360

92,00

CODE

A
[mm]

B
[mm]

C
[mm]

D
[mm]

E
[mm]

F
[mm]

G
[mm]

H
[mm]

I
[mm]

L
[mm]

INT. PLATE
X-Y [mm]

WEIGHT
[Kg]

DETAIL

EJB-21UL

12,60

11,10

7,00

7,50

7,10

9,20

4,80

8,50

6,90

0,60

7.10 - 5.60

31,00

EJB-31UL

17,80

13,80

9,80

10,30

11,60

11,30

7,60

13,50

9,50

0,60

12.80 - 8.90

62,00

EJB-51UL

23,70

15,80

10,50

11,00

14,20

13,20

7,70

19,00

11,10

0,60

18.20 - 10.30

121,00

EJB-61UL

28,00

19,70

15,40

15,70

19,70

18,20

11,00

22,30

14,10

0,50

22.10 - 14.20

262,00

EJB-63UL

28,00

19,70

10,20

10,60

19,70

18,20

5,80

22,50

14,30

0,50

22.10 - 14.20

212,00

Reference details

D
B

HxI

www.feam-ex.com

EJB UL

EJB UL Technical features

EJB UL Body enclosures drilling layout


ENCLOSURE
CODE

AREA FOR ENTRY INSTALLATION (LONG WALL SIDES)

AREA FOR ENTRY INSTALLATION (SHORT WALL SIDES)

A
[mm]

B
[mm]

A
[inch.]

B
[inch.]

C
[mm]

D
[mm]

C
[inch.]

D
[inch.]

EJB-21 UL

190

80

7,50

3,20

150

80

6,00

3,20

EJB-31 UL

320

140

12,60

5,60

230

140

9,10

5,60

EJB-51 UL

450

120

17,80

4,80

250

120

9,90

4,80

EJB-61 UL

550

260

21,70

10,30

350

260

13,80

10,30

EJB-63 UL

550

150

21,70

6,00

350

150

13,80

6,00

110 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

EJB UL Body enclosures drilling layout

Ex Enclosures

139
(5.47)

3
M90

115
(4.53)

126
(4.96)

2 1/2
M75

101
(3.98)

108
(4.25)

120
(4.72)

2
M63

88
(3.46)

94
(3.70)

102
(4.02)

112
(4.41)

1 1/2
M50

75
(2.95)

82
(3.23)

88
(3.46)

95
(3.74)

106
(4.17)

1 1/4
M40

67
(2.64)

70
(2.76)

77
(3.03)

84
(3.31)

91
(3.58)

103
(4.06)

1
M32

58
(2.28)

63
(2.48)

66
(2.60)

73
(2.87)

80
(3.15)

86
(3.39)

99
(3.90)

3/4
M25

52
(2.05)

55
(2.17)

59
(2.32)

63
(2.48)

69
(2.72)

79
(2.99)

83
(3.27)

95
(3.74)

1/2
M20

46
(1.81)

49
(1.93)

52
(2.05)

57
(2.24)

60
(2.36)

67
(2.64)

73
(2.87)

80
(3.15)

93
(3.66)

NPT
Metric

1/2
M20

3/4
M25

1
M32

1 1/4
M40

1 1/2
M50

2
M63

2 1/2
M75

3
M90

4
-

Reference details

WALL DRILLING AREA


C

EJB UL Cover enclosures drilling layout


MINUMUM DISTANCE
BETWEEN OPENINGS
(CENTER TO CENTER)

E
[mm]

F
[mm]

E
[inch.]

F
[inch.]

[mm]

[inch.]

EJB-21 UL

200

150

7,90

6,00

50

2,00

EJB-31 UL

300

200

11,90

7,90

50

2,00

EJB-51 UL

460

260

18,20

10,30

50

2,00

EJB-61 UL

570

370

22,50

14,60

50

2,00

EJB-63 UL

570

370

22,50

14,60

50

2,00

COVER DRILLING AREA


F

ENCLOSURE
CODE

AREA FOR OPERATORS


INSTALLATION ENCLOSURE COVER

Bartec Feam Catalogue 04 I 111

www.feam-ex.com

4
-

EJB UL

MINIMUM DISTANCE BETWEEN WALL ENTRIES (CENTER TO CENTER)


1st ROW [mm] - 2nd ROW [inch.]

www.feam-ex.com

EJB UL

EJB UL Indicative quantity of


terminals and relevant section

Explosion Proof Electrical Equipment

Ex Enclosures

INT. PLATE X - Y

CODE

SEZ. 2,5
[sq/mm]

SEZ. 6,0
[sq/mm]

SEZ. 10,0
[sq/mm]

SEZ. 16,0
[sq/mm]

SEZ. 35,0
[sq/mm]

SEZ. 50,0
[sq/mm]

SEZ. 70,0
[sq/mm]

SEZ. 240,0
[sq/mm]

[mm]

[inch.]

EJB-21 UL

30 x 1

20 x 1

14 x 1

12 x 1

8x1

6x1

2x1

1x1

180 - 140

7.10 - 5.60

EJB-31UL

52 x 2

32 x 2

24 x 2

20 x 2

14 x 2

12 x 1

8x1

4x1

325 - 225

12.80 - 8.90

EJB-51 UL

80 x 2

46 x 2

36 x 2

30 x 2

22 x 2

18 x 2

16 x 1

6x1

460 - 260

18.20 - 10.30

EJB-61 UL

92 x 3

58 x 3

46 x 3

38 x 3

28 x 3

26 x 2

22 x 2

12 x 1

560 - 350

22.10 - 14.20

EJB-63 UL

92 x 3

58 x 3

46 x 3

38 x 3

28 x 3

26 x 2

22 x 2

12 x 1

560 - 350

22.10 - 14.20

EJB UL Additional Technical features for NEC 500 only


PRODUCT COVERED
Explosion-proof enclosures for use in Hazardous Locations, Class I, Groups B, C, and D; Class II, Groups E, F, and G; Class III.
These enclosures are Classified as to explosion and fire hazards only in according to Standard UL1203 4 ed.
The explosion-proof enclosures are suitable for Class I, Group B Hazardous Locations only when provided with from M20 to M90, 1/2 in. to 3 in., supply
connection openings. If other supply connection openings are provided, then the enclosures are suitable for Class I, Groups C & D Hazardous Locations only.
The 1/2 in. NPSM operator openings are only suitable for enclosures marked for Class I, Groups B, C & D Hazardous Locations
The enclosures covered by this Certification may have electrical components installed inside. The installation of electrical components shall not reduce the
mechanical integrity of the enclosures.
The enclosures may or may not be provided with hinges for service of the enclosures only.
PROTECTION AGAINST CORROSION
All ferrous-metal other than stainless steel shall be protected against corrosion, except at joint surfaces and conduit threads There shall be no materials
applied to joint surfaces.
GROUNDING
Internal Ground Screw Hexagon head screw M6 x 10 with a stainless steel flat and lock washer provided on the base of the enclosure body.
External Ground Terminal colored green, marked with the letter or word G, GROUND, or marked with a grounding symbol.
SUPPLY CONNECTIONS
NPT and Metric Supply Connections - The side walls of the enclosure are provided with conduit openings or none may be supplied, in which case field drilling
and tapping instructions are provided with each enclosure. The entry is drilled and tapped completely through the enclosure wall, and the inside edge is
smoothed and well-rounded such that the conductor insulation will not be damaged when installed. All unused openings are closed with plated steel, plated
cast iron or aluminum close-up plugs which are threaded to match the opening. Closer-up Plugs have to be Listed for the same Class, Group and Division as
marked on Enclosure nameplate.
OPERATOR OPENINGS
The cover of the enclosure may be provided with operator openings in the cover only and located only as given in drilling and tapping instructions provided
with each Classified enclosure. All unused openings are closed with plated steel, plated cast iron or aluminum close-up plugs which are threaded to match
the opening. Closer-up Plugs have to be Listed for the same Class, Group and Division as marked on Enclosure nameplate.

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this
bulletin can be considered as binding on our confirmation only.

112 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

GUB Enclosures

Ex Enclosures

www.feam-ex.com

GUB

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II - Category 2G 2D

Certificate
NEMA Type 4X

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex d IIC T6...T3
II 2(1) GD Ex d [ia/ib IIA or IIB or IIC Ga] IIC T6...T3
II 2 D Ex tb IIIC T85C...T200C
II 2 D Ex tb [ia Da/ib] IIIC T85C

EXECUTION

RULES OF COMPLIANCE

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-11; EN/IEC 60079-31

EC Type-Examination Certificate

INERIS 13 ATEX 0021X

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +80C

OTHER AVAILABLE CERTIFICATES

Component: INERIS 13 ATEX 9018U


IECEx: IECEx INE13.0069X
Component: IECEx INE 13.0082U
INMETRO: CEPEL 12 2141
EAC: TC RU C-IT.08..01499
RINA: ELE18111CS_017
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
UL NEC-505: 20141112-E465037 - Type rating NEMA 1, 12, 4 and 4X

Mechanical characteristics
Body

marine grade copper free aluminium light alloy

Cover

marine grade copper free aluminium light alloy

Screws

stainless sttel

Internal plate

hot dip galvanized steel / aluminium

Fixing

fixing lugs AL UNI 4514 casting on enclosure body

On request accessories:
External epoxy painting with colour on request
Internal anticondensate painting orange RAL-2004
O-Ring gaskets on cover
Glass windows on cover

Drain and breather valves


Galvanized steel body & cover
Cast iron body & cover

Bartec Feam Catalogue 04 I 113

Explosion Proof Electrical Equipment

Ex Enclosures

CODE

A
[mm]

B
[mm]

C
[mm]

D
[mm]

E
[mm]

F
[mm]

G
[mm]

H
[mm]

I
[mm]

L
[mm]

M
[mm]

N
[mm]

INT.PLATE
X - Y [mm]

WEIGHT
[Kg]

DETAIL

GUE1

135

135

111

96

110

150

113

50

110

110

90

2,00

GUB0

168

168

145

125

172

172

154

97

137

137

110 - 110

4,00

GUB1

198

198

152

134

200

200

176

88

170

170

150 - 150

5,00

GUB03

280

305

228

202

270

308

13

275

133

248

270

220 - 200

13,50

GUB23

270

310

174

152

315

275

12

244

100

243

283

180 - 180

9,80

GUB4

420

420

281

230

380

460

14

410

147

384

384

280 - 280

31,70

GUB5

600

600

382

313

545

460

14

580

208

550

550

490 - 490

105,60

GUBW1

198

198

152

134

200

200

176

88

170

170

90

150 - 150

5,10

GUBW03

280

305

228

202

270

308

13

275

133

248

270

195

220 - 200

14,20

GUBW23

270

310

174

152

315

275

12

244

100

243

283

150

180 - 180

10,30

GUBW4

420

420

281

230

380

460

14

410

147

384

384

230

280 - 280

30,00

Reference details

B
A

L-M

L-M

C
C

D
A

114 I Bartec Feam Catalogue 04

L-M

L-M

www.feam-ex.com

GUB

GUB Technical features

Explosion Proof Electrical Equipment

GUB Body Enclosures Drilling Layout

GUE1

QUANTITY ALLOWED ENTRIES FOR size (from


1 to size 8)
1

102x50

GUB0

128x80

GUB1

148x87

GUB03

263x120

15

11

GUB23

270x97

11

10

GUB4

350x140

23

18

14

GUB5

550x195

45

36

GUBW1

148x87

GUBW03

263x120

GUBW23
GUBW4

DRILLING AREA
C-D [mm]

QUANTITY ALLOWED ENTRIES FOR size (from


1 to size 8)
1

102x50

128x80

148x87

238x120

12

230x97

11

10

350x140

23

18

14

11

10

27

24

18

12

550x195

45

36

27

24

18

12

148x87

15

11

238x120

12

270x97

11

10

230x97

350x140

23

18

14

11

10

350x140

23

18

14

11

10

Reference details

WALL DRILLING AREA

plate

PLATE X-Y

PLATE X-Y

Bartec Feam Catalogue 04 I 115

GUB

DRILLING AREA
A-B [mm]

www.feam-ex.com

ENCLOSURE
CODE

Ex Enclosures

www.feam-ex.com

GUB

GUB Indicative quantity of terminals and


relevant section

Explosion Proof Electrical Equipment

Ex Enclosures

CODE
ENCLOSURE

SECT. 2,5
[sq/mm]

SECT. 6,0
[sq/mm]

SECT. 10,0
[sq/mm]

SECT. 16,0
[sq/mm]

SECT. 35,0
[sq/mm]

SECT. 50,0
[sq/mm]

SECT. 70,0
[sq/mm]

SECT. 240,0
[sq/mm]

INT.PLATE X - Y
[mm]

GUE1

8x1

4x1

4x1

2x1

2x1

90

GUB0

12x1

6x1

6x1

4x1

4x1

2x1

1x1

110 - 110

GUB1

20x1

10x1

10x1

6x1

6x1

4x1

2x1

1x1

150 - 150

GUB03

34x1

20x1

18x1

14x1

10x1

8x1

6x1

4x1

220 - 200

GUB23

26x1

16x1

14x1

12x1

8x1

6x1

4x1

1x1

180 -180

GUB4

48x2

28x2

24x2

20x2

12x2

10x2

8x1

4x1

280 - 280

GUB5

64x3

40x3

36x3

30x3

11x3

16x3

16x1

6x2

490 - 490

GUBW1

20x1

10x1

10x1

6x1

6x1

4x1

2x1

1x1

150 - 150

GUBW3

34x1

20x1

18x1

14x1

10x1

8x1

6x1

4x1

220 - 200

GUBW23

26x1

16x1

14x1

12x1

8x1

6x1

4x1

1x1

180 -180

GUBW4

48x2

28x2

24x2

20x2

12x2

10x2

8x1

4x1

280 - 280

GUB Threads comparation table


SIZE

UNI 6125

ISO 228/1

ASA B2.1

ISO 965/I

GK 1/2

G 1/2

1/2 NPT

M20

GK 3/4

G 3/4

3/4 NPT

M25

GK 1

G 1

1 NPT

M32

GK 1-1/4

G 1-1/4

1-1/4 NPT

M40

GK 1-1/2

G 1-1/2

1-1/2 NPT

M50

GK 2

G 2

2 NPT

M63

GK 2-1/2

G 2-1/2

2-1/2 NPT

M75

GK 3

G 3

3 NPT

M85

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this
bulletin can be considered as binding on our confirmation only.

116 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

GUB INX Enclosures

Ex Enclosures

www.feam-ex.com

GUB INX

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II - Category 2G 2D

Certificate
NEMA Type 4X

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex d IIC T6...T3
II 2(1) GD Ex d [ia/ib IIA or IIB or IIC Ga] IIC T6...T3
II 2 D Ex tb IIIC T85C...T200C
II 2 D Ex tb [ia Da/ib] IIIC T85C

EXECUTION

RULES OF COMPLIANCE

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-11; EN/IEC 60079-31

EC Type-Examination Certificate

INERIS 13 ATEX 0021X

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +80C

OTHER AVAILABLE CERTIFICATES

Component: INERIS 13 ATEX 9018U


IECEx: IECEx INE13.0069X
Component: IECEx INE 13.0082U
INMETRO: CEPEL 12 2141
EAC: TC RU C-IT.08..01499
RINA: ELE18111CS_017
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
UL NEC-505: 20141112-E465037 - Type rating NEMA 1, 12, 4 and 4X

Mechanical characteristics
Body

stainless steel AISI-316L

Cover

stainless steel AISI-316L

Internal plate

stainless steel AISI-316L

Fixing

fixing lugs stainless steel AISI-316L welded on enclosure body

On Request Accessories:
External epoxy painting with colour on request
Internal anticondensate painting orange RAL-2004
O-Ring gaskets on cover

Glass windows on cover


Drain and breather valves

Bartec Feam Catalogue 04 I 117

Explosion Proof Electrical Equipment

GUB INX Technical features


CODE

A
[mm]

B
[mm]

C
[mm]

D
[mm]

E
[mm]

F
[mm]

G
[mm]

H
[mm]

I
[mm]

L
[mm]

M
[mm]

N
[mm

INT.PLATE
X - Y [mm]

WEIGHT [Kg]

DETAIL

GUE1

135

135

100

92

152

105

113

47

111

111

7,00

GUB0

170

170

141

133

185

145

154

82

140

140

110 - 110

13,00

GUB1

200

200

160

152

216

170

177

98

170

170

150 - 150

19,00

GUB03

280

310

219

209

260

310

13

275

152

250

280

220 - 220

50,00

GUB23

310

270

165

157

235

350

12

224

110

290

250

180 - 180

32,00

GUB4

420

420

234

226

380

460

13

405

148

390

390

280 - 280

83,00

GUB5

600

600

320

310

550

630

13

600

203

550

550

490 - 490

280,00

GUBW1

200

200

160

152

216

170

177

98

170

170

90

150 - 150

19,00

GUBW03

280

310

219

209

260

310

13

275

152

250

280

195

220 - 220

50,00

GUBW23

310

270

165

157

235

350

12

224

110

290

250

150

180 - 180

32,00

GUBW4

420

420

234

226

380

460

13

405

148

390

390

230

280 - 280

83,00

GUB INX

Reference details

B
A

LxM

LxM

D
A
A

C
F

118 I Bartec Feam Catalogue 04

LxM

LxM

www.feam-ex.com

Ex Enclosures

Explosion Proof Electrical Equipment

GUB INX Body enclosures drilling layout

GUE1 INX

QUANTITY ALLOWED ENTRIES FOR size


(from 1 to size 8)
1

102x50

GUB0 INX

128x80

GUB1 INX

148x87

GUB03 INX

263x120

15

11

GUB23 INX

270x97

11

10

GUB4 INX

350x140

23

18

14

GUB5 INX

550x195

45

36

GUBW1 INX

148x87

GUBW03 INX

263x120

GUBW23 INX
GUBW4 INX

DRILLING AREA
C-D [mm]

QUANTITY ALLOWED ENTRIES FOR size


(from 1 to size 8)
1

102x50

128x80

148x87

238x120

12

230x97

11

10

350x140

23

18

14

11

10

27

24

18

12

550x195

45

36

27

24

18

12

148x87

15

11

238x120

12

270x97

11

10

230x97

350x140

23

18

14

11

10

350x140

23

18

14

11

10

Reference details

Reference details

WALL DRILLING AREA

PLATE

PLATE
X-Y

PLATE
X-Y

PLATE
X-Y

PLATE
X-Y

Bartec Feam Catalogue 04 I 119

GUB INX

DRILLING AREA
A-B [mm]

www.feam-ex.com

ENCLOSURE
CODE

Ex Enclosures

www.feam-ex.com

GUB INX

GUB INX Indicative quantity of terminals


and relevant section

Explosion Proof Electrical Equipment

Ex Enclosures

CODE
ENCLOSURE

SECT. 2,5
[sq/mm]

SECT. 6,0
[sq/mm]

SECT. 10,0
[sq/mm]

SECT. 16,0
[sq/mm]

SECT. 35,0
[sq/mm]

SECT. 50,0
[sq/mm]

SECT. 70,0
[sq/mm]

SECT. 240,0
[sq/mm]

INT.PLATE X - Y
[mm]

GUE1 INX

8x1

4x1

4x1

2x1

2x1

90

GUB0 INX

12x1

6x1

6x1

4x1

4x1

2x1

1x1

110 - 110

GUB1 INX

20x1

10x1

10x1

6x1

6x1

4x1

2x1

1x1

150 - 150

GUB03 INX

34x1

20x1

18x1

14x1

10x1

8x1

6x1

4x1

220 - 200

GUB23 INX

26x1

16x1

14x1

12x1

8x1

6x1

4x1

1x1

180 -180

GUB4 INX

48x2

28x2

24x2

20x2

12x2

10x2

8x1

4x1

280 - 280

GUB5 INX

64x3

40x3

36x3

30x3

11x3

16x3

16x1

6x2

490 - 490

GUBW1 INX

20x1

10x1

10x1

6x1

6x1

4x1

2x1

1x1

150 - 150

GUBW3 INX

34x1

20x1

18x1

14x1

10x1

8x1

6x1

4x1

220 - 200

GUBW23 INX

26x1

16x1

14x1

12x1

8x1

6x1

4x1

1x1

180 -180

GUBW4 INX

48x2

28x2

24x2

20x2

12x2

10x2

8x1

4x1

280 - 280

GUB INX Threads comparation table


SIZE

UNI 6125

ISO 228/1

ASA B2.1

ISO 965/I

GK 1/2

G 1/2

1/2 NPT

M20

GK 3/4

G 3/4

3/4 NPT

M25

GK 1

G 1

1 NPT

M32

GK 1-1/4

G 1-1/4

1-1/4 NPT

M40

GK 1-1/2

G 1-1/2

1-1/2 NPT

M50

GK 2

G 2

2 NPT

M63

GK 2-1/2

G 2-1/2

2-1/2 NPT

M75

GK 3

G 3

3 NPT

M85

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this
bulletin can be considered as binding on our confirmation only.

120 I Bartec Feam Catalogue 04

GUA - EAHF
Junction and pulling boxes

Explosion Proof Electrical Equipment

Ex Enclosures

GUA INOX

www.feam-ex.com

EAHF

GUA

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex d IIC T6...T3 Gb
II 2 G Ex e IIC T6...T3 Gb
II 2 D Ex tb IIIC T85C...T200C Db

EXECUTION
RULES OF COMPLIANCE

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-7; EN/IEC 60079-31

EC Type-Examination Certificate
PROTECTION DEGREE

INERIS 03 ATEX 0048X


IP66

AMBIENT TEMPERATURE

-60C +130C

OTHER AVAILABLE CERTIFICATES

GUA - EAHF

Installation: hazardous areas: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II - Category 2G 2D

Component: INERIS 10 ATEX 9005U


IECEx: IECEx INE 12.0021X
Component: IECEx INE 12.0023U
INMETRO: CEPEL 12.2193
Component INMETRO: CEPEL 12.2191U
EAC: TC RU C-IT.08..01499
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
UL NEC-505: 20131030-E365676

Mechanical characteristics
Body

marine grade copper free aluminum - stainless steel AISI316L (size 17/27/37 only)

Cover

marine grade copper free aluminum - stainless steel AISI316L (size 17/27/37 only)

Screws

esterna in acciaio inossidabile

Gasket

O-Ring sealing NBR

On Request Accessories:
External epoxy painting with colour on request
Internal anticondensate painting orange RAL-2004

Bartec Feam Catalogue 04 I 121

POSIZIONE
IMBOCCHI
Explosion Proof Electrical Equipment
POSIZIONE
IMBOCCHI
POSIZIONE
POSIZIONE IMBOCCHI
IMBOCCHI
POSIZIONE IMBOCCHI

CODE

A [mm]

B [mm]

C
[mm]

D
[mm]

E
[mm]

F
[mm]

G
[mm]

H
[mm]

GUA16

87

77

100

75

40

70

70

FIGURA
GUAB...
WEIGHT [Kg]
GUAB...
GUAB...
GUAB...
0,60

DETAIL
A

GUA17

113

100

130

79

50

95

82

GUAB...
0,90

GUA26

87

77

100

75

40

70

70

0,60

GUA27

113

100

130

79

50

95

82

0,90

87

77

100

75

40

70

70

GUAL...
0,60
GUAL...
GUAL...
0,90
GUAL...

GUA36

1,30

GUAL...

1,30

1,30

GUA37

113

100

130

79

50

95

82

GUA59

154

135

169

110

75

100

130

7,5

GUA69

154

135

169

110

75

100

130

7,5

GUAY59

154

135

169

110

75

155

80

EAHF26

87

77

110

76

50

26

85

EAHF - Reference details

GUA - Reference details

C
A
G

GUAB16
GUAB...
GUAB17
GUAB...
GUAB26
GUAB...
GUAB27
GUAB36
GUAB...
GUAB37
GUAB59
GUAB69
GUAL16
GUAL17
GUAL26
GUAL27
GUAL36
GUAL37
GUAL59
GUAL69
GUAC16
GUAC17
GUAC26
GUAC27
GUAC36
GUAC37
GUAC59
GUAC69
GUAT16
GUAT17
GUAT26
GUAT27
GUAT36
GUAT37
GUAT59
GUAT69
EAHF26
GUAX16
GUAX17
GUAX26
GUAX27
GUAX36
GUAX37
GUAX59
GUAX69

GUAL...
GUAL...
GUAL...
GUAL...
GUAC...
GUAC...
GUAC...
GUAC...

GUAT...

GUAT...
GUAT...
GUAT...
GUAT...
GUAX...

GUAX...
GUAX...
GUAX...
GUAX...
122 I Bartec Feam Catalogue 04

GUAT...
F

2 x 1/2"
2 x 1/2"
2 x 3/4"
2 x 3/4"
2 x 1"
2 x 1"
2 x 1-1/2"
2 x 2"
2 x 1/2"
2 x 1/2"
2 x 3/4"
2 x 3/4"
2 x 1"
2 x 1"
2 x 1-1/2"
2 x 2"
2 x 1/2"
2 x 1/2"
2 x 3/4"
2 x 3/4"
2 x 1"
2 x 1"
2 x 1-1/2"
2 x 2"
3 x 1/2"
3 x 1/2"
3 x 3/4"
3 x 3/4"
3 x 1"
3 x 1"
3 x 1-1/2"
3 x 2"
3 x 3/4"
4 x 1/2"
4 x 1/2"
4 x 3/4"
4 x 3/4"
4 x 1"
4 x 1"
4 x 1-1/2"
4 x 2"

GUAT...
GUAT...
GUAT...
GUAT...

A
G
D

H
GUAX...
B
GUAX...
GUAX...
GUAX...

GUAX...
REFERENCE DETAILS

CODE

GUAC...

POSIZIONE IMBOCCHI
FIGURA
POSIZIONE IMBOCCHI
FIGURA
GUA
- EAHF
Hubs arrangement
POSIZIONE
IMBOCCHI
FIGURA
COMPLETE
POSIZIONE
IMBOCCHI
FIGURA HUBS SIZE
REFERENCE DETAILS

GUAL...

GUAB...

GUAC...

C
B

95

0,50
GUAC...
GUAC...
GUAY - Reference
details
GUAC...
GUAC...
7

www.feam-ex.com

GUA - EAHF

GUA - EAHF Technical features

FIGURA
FIGURA
FIGURA
FIGURA Ex Enclosures

GUAW...

COMPLETE
CODE

HUBS SIZE

GUAW16
GUAW17
GUAW26
GUAW27
GUAW36
GUAW37
GUAW59
GUAW69
GUAD16
GUAD17
GUAD26
GUAD27
GUAD36
GUAD37
GUAD59
GUAD69

4 x 1/2"
4 x 1/2"
4 x 3/4"
4 x 3/4"
4 x 1"
4 x 1"
4 x 1-1/2"
4 x 2"
3 x 1/2"
3 x 1/2"
3 x 3/4"
3 x 3/4"
3 x 1"
3 x 1"
3 x 1-1/2"
3 x 2"

GUAW...
GUAW...
GUAW...
GUAW...
GUAW...

GUAD...

GUAD...
GUAD...
GUAD...
GUAD...
GUAD...

GUAY...

GUAY...
GUAY...
GUAY59
GUAY...
GUAY...

3 x 1-1/2

GUAY...
GUAM...

GUAM16
GUAM17
GUAM26
GUAM27
GUAM36
GUAM37
GUAM59
GUAM69
GUAJ16
GUAJ17
GUAJ26
GUAJ27
GUAJ36
GUAJ37
GUAJ59
GUAJ69

GUAM...
GUAM...
GUAM...
GUAM...

GUAJ...

GUAM...
GUAJ...
GUAJ...
GUAJ...
GUAJ...
GUAJ...

3 x 1/2"
3 x 1/2"
3 x 3/4"
3 x 3/4"
3 x 1"
3 x 1"
3 x 1-1/2"
3 x 2"
5 x 1/2"
5 x 1/2"
5 x 3/4"
5 x 3/4"
5 x 1"
5 x 1"
5 x 1-1/2"
5 x 2"

HANDLES-D Operators (PILOT


LIGHTS - PUSH BUTTONS - HANDLES)

Explosion Proof Electrical Equipment

Ex Enclosures

HANDLES-D

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II - Category 2G 2D

EFP2#
EFL1P#

www.feam-ex.com

EFISL

EFI-RL
EFP2FSR#

EFLP3#

EFP2F#

EFP2FSC#

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex d IIB+H2 Gb or IIC Gb
II 2 D Ex tb IIIC Db

EXECUTION
RULES OF COMPLIANCE

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-31

EC Type-Examination Certificate

INERIS 13 ATEX 9017U

PROTECTION DEGREE

IP66
-60C +200C
-60C +95C (pilot lights)

AMBIENT TEMPERATURE
OTHER AVAILABLE CERTIFICATES

IECEx: IECEx INE 13_0073U


INMETRO: CEPEL 13.2257U
EAC: TC RU C-IT.08..01323 (-60C +60C)
NEC 505: UL 20140220-E466537

Mechanical characteristics
PILOT LIGHTS
Body
Diffuser

HANDLES
polycarbonate
polycarbonate

Body

marine grade copper free aluminium light alloy

Transmission parts

stainless steel

ILLUMINATED PUSH BUTTONS

PUSH BUTTONS

Body

stainless steel

Body

stainless steel

Protection ring

nickel plated brass

Protection ring

nickel plated brass

Diffuser

polycarbonate

Button

aluminium light alloy / polycarbonate

Transmission

stainless steel

Transmission

stainless steel

Bartec Feam Catalogue 04 I 123

Explosion Proof Electrical Equipment

HANDLES-D Technical data


HANDLES-D

CODE

Ex Enclosures

CONTACTS

PUSH BUTTON COLOUR

THREAD SIZE

EFP2#AZ1

1 NO

LIGHT BLUE

ISO-ISO-M25

EFP2#AZ2

1 NC

LIGHT BLUE

ISO-M25

HANDLES-D

EFP2#AZ3

1 NO + 1 NC

LIGHT BLUE

ISO-M25

EFP2#AZ4

2 NO

LIGHT BLUE

ISO-M25

EFP2#AZ5

2 NC

LIGHT BLUE

ISO-M25

EFP2#BI1

1 NO

WHITE

ISO-M25

EFP2#BI2

1 NC

WHITE

ISO-M25

www.feam-ex.com

SPRING RETURN PUSH BUTTON - CONTACTS 10AMP

EFP2#BI3

1 NO + 1 NC

WHITE

ISO-M25

EFP2#BI4

2 NO

WHITE

ISO-M25

EFP2#BI5

2 NC

WHITE

ISO-M25

EFP2#BL1

1 NO

BLUE

ISO-M25

EFP2#BL2

1 NC

BLUE

ISO-M25

EFP2#BL3

1 NO + 1 NC

BLUE

ISO-M25

EFP2#BL4

2 NO

BLUE

ISO-M25

EFP2#BL5

2 NC

BLUE

ISO-M25

EFP2#GI1

1 NO

YELLOW

ISO-M25

EFP2#GI2

1 NC

YELLOW

ISO-M25

EFP2#GI3

1 NO + 1 NC

YELLOW

ISO-M25

EFP2#GI4

2 NO

YELLOW

ISO-M25

EFP2#GI5

2 NC

YELLOW

ISO-M25

EFP2#NE1

1 NO

BLACK

ISO-M25

EFP2#NE2

1 NC

BLACK

ISO-M25

EFP2#NE3

1 NO + 1 NC

BLACK

ISO-M25

EFP2#NE4

2 NO

BLACK

ISO-M25

EFP2#NE5

2 NC

BLACK

ISO-M25

EFP2#RO1

1 NO

RED

ISO-M25

EFP2#RO2

1 NC

RED

ISO-M25

EFP2#RO3

1 NO + 1 NC

RED

ISO-M25

EFP2#RO4

2 NO

RED

ISO-M25

EFP2#RO5

2 NC

RED

ISO-M25

EFP2#VE1

1 NO

GREEN

ISO-M25

EFP2#VE2

1 NC

GREEN

ISO-M25

EFP2#VE3

1 NO + 1 NC

GREEN

ISO-M25

EFP2#VE4

2 NO

GREEN

ISO-M25

EFP2#VE5

2 NC

GREEN

ISO-M25

EFP2#VE

EFP2#RO

MILANO S.r.l.

xxx
VER/APPR.
CHKD/APPR.

DIS.N.
DWG.N.

Forniture Elettriche
Apparecchiature Materiali
FG.
SH.

EFP2

DI
OF

SPRING RETURN MUSHROOM PUSH BUTTON - CONTACTS 10AMP


1 NO

RED

ISO-M25

EFP2F#2

1 NC

RED

ISO-M25

1 NO + 1 NC

RED

ISO-M25

2 NO

RED

ISO-M25

2 NC

RED

ISO-M25

EFP2F#3
EFP2F#4
EFP2F#5

124 I Bartec Feam Catalogue 04

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPOR


.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREP

EFP2F#1

Explosion Proof Electrical Equipment

HANDLES-D Technical data


HANDLES-D

Ex Enclosures

CODE

CONTACTS

PUSH BUTTON COLOUR

THREAD SIZE

1 NO

BLACK

ISO-M25

EFP2FSC#NE2

1 NC

BLACK

ISO-M25

EFP2FSC#NE3

1 NO + 1 NC

BLACK

ISO-M25

EFP2FSC#NE4

2 NO

BLACK

ISO-M25

EFP2FSC#NE5

2 NC

BLACK

ISO-M25

1 NO

RED

ISO-M25

1 NC

RED

ISO-M25

EFP2FSC#RO3

1 NO + 1 NC

RED

ISO-M25

EFP2FSC#RO4

2 NO

RED

ISO-M25

EFP2FSC#RO5

2 NC

RED

ISO-M25

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

EFP2FSC#RO1
EFP2FSC#RO2

www.feam-ex.com

EFP2FSC#NE1

HANDLES-D

RELEASE BY KEY STAY-PUT MUSHROOM PUSH BUTTON - CONTACTS 10AMP

TURN TO RELEASE STAY-PUT MUSHROOM PUSH BUTTON - CONTACTS 10AMP


EFP2FSR#GI1
xxx
PA/REV
PA/DKHC

xxx

xxx

xxx

xxx

SID
NWARD

NOITPIRCSED/ENOIZIRCSED

FO/LED

.VER

1 NC

YELLOW

ISO-M25

1 NO + 1 NC

YELLOW

ISO-M25

EFP2FSR#GI4

2 NO

YELLOW

ISO-M25

EFP2FSR#GI5

2 NC

YELLOW

ISO-M25

EFP2FSR#NE1

1 NO

BLACK

ISO-M25

EFP2FSR#NE2

1 NC

BLACK

ISO-M25

EFP2FSR#NE3

1 NO + 1 NC

BLACK

ISO-M25

EFP2FSR#NE4

2 NO

BLACK

ISO-M25

BLACK

ISO-M25

RED

ISO-M25

RED

ISO-M25

RED

ISO-M25

RED

ISO-M25

RED

ISO-M25

EFP2FSR#NE5

2 NC

EFP2FSR#RO1

1 NO

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

D
O

ISO-M25

EFP2FSR#GI2

EFP2FSR#RO2

ehcirttelE erutinroF
taM erutaihccerappA

YELLOW

EFP2FSR#GI3

1 NC

EN#RSF2PFE
EFP2FSR#RO3

OR#RSF2PFE

1 NO

IG#RSF2PFE
1 NO + 1 NC

EFP2FSR#RO4

2 NO

EFP2FSR#RO5

2 NC

.l.r.S ONA LIM

.N.SID
.N.GWD

.G F
.HS

RSF2PFE

xxx

xxx

xxx

xxx

xxx

.RPPA/REV
.RPPA/DKHC

SID
NWARD

NOITPIRCSED/ENOIZIRCSED

FO/LED

.VER

LB#P1LFE

IB#P1LFE

CODE

HANDLES-D

CONTACTS DIAGRAM

RA#P1LFE

SUPPLY

LAMPHOLDER

LAMP COLOUR

SIZE

LIGHT BLUE

ISO-M25

WHITE

ISO-M25

BLUE

ISO-M25

YELLOW

ISO-M25

RED

ISO-M25

GREEN

ISO-M25

BLUE

ISO-M32

BLUE

ISO-M32

Ba-9s

YELLOW

ISO-M32

Ba-9s

YELLOW

ISO-M32

Ba-9s

RED

ISO-M32

Ba-9s

RED

ISO-M32

Ba-9s

RED

ISO-M32

Ba-9s

GREEN

ISO-M32

Ba-9s

GREEN

ISO-M32

PILOT LIGHT FOR BACK COVER INSTALLATION


12V 380V ac/dc

Ba-9s

EFL1P#BI

12V 380V ac/dc

Ba-9s

EFL1P#BL

12V 380V ac/dc

Ba-9s

EFL1P#GI

12V 380V ac/dc

Ba-9s

EFL1P#RO

12V 380V ac/dc

Ba-9s

EFL1P#VE

12V 380V ac/dc

R#P1LFE
#P1LFEBACK COVER INSTALLATION
SPRINGORETURN
ILLUMINATED PUSH BUTTONIGFOR

EV#P1LFE

LB#3PLFE
cirttelE erutinroF
erutaihccerappA
1

IB#3PLFE

.l.r.S ONA LIM

.N.SID
.N.GWD

.GF
.HS

P1LFE

xxx

xxx

xxx

.RPPA/REV
.RPPA/DKHC

SID
NWARD

NOITPIRCSED/ENOIZIRCSED

LB#3PLFE

EFLP3#BL1

1NO

EFLP3#BL3

1NO + 1NC

12V 380V ac/dc

EFLP3#GI2

1NC

12V 380V ac/dc

EFLP3#GI3

1NO + 1NC

12V 380V ac/dc

EFLP3#RO1

1NO

12V 380V ac/dc

EFLP3#RO2

1NC

12V 380V ac/dc

EFLP3#RO3

1NO + 1NC

12V 380V ac/dc

EFLP3#VE1

1NO

12V 380V ac/dc

xxx

xxx

FO/LED

.VER

IB#3PLFE

.N.SID
.N.GWD

ZA#3PLFE 12V 380V ac/dc

IG#3PLFE
1NO + 1NC

EFLP3#VE3

.l.r.S ONA LIM

PFE

Ba-9s

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

EFL1P#AZ

xxx

xxx

xxx

xxx

xxx

.RPPA/REV
.RPPA/DKHC

SID
NWARD

NOITPIRCSED/ENOIZIRCSED

FO/LED

.VER

12V 380V ac/dc

Ba-9s
Ba-9s

Bartec Feam Catalogue 04 I 125

Explosion Proof Electrical Equipment

HANDLES-D Technical data

Ex Enclosures

LR-IFE N TRAP

HCTIWS GREBELE ROF ELDNAH ELBAKCOLDAP HTIW NOISSIMSNART FOORP .LPXE IFE

CODE

HANDLES-D

HANDLE COLOUR

SIZE

BACK COVER INSTALLATION PADLOCKABLE HANDLE (for selector switch only)

EFI-RL

BLACK

1/2" ISO-228

EFI-RC

BLACK

1" ISO-228

2040.00093

BLACK

1/2 ISO-228

CR-IFE N TRAP

39000.0402 N TRAP

ELDNAH ELBAKCOLDAP HTIW NOISSIMSNART FOORP .LPXE IFE

26

HANDLES-D

HCTIWS GREBELE ROF RELLORTNOC YEK HTIW NOISSIMSNART FOORP .LPXE IFE

221

822-OSI "1

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP E.H
OCDCS
CO
UR
TVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT
HE
TNGENMID
WTALSIOT
AID

53n

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

822-OSI "2/1

HCTIWS

.l.r.S ONALIM

.N.SID
.N.GWD

.G F
.HS

www.feam-ex.com

with keys
hcirttelE erutinroF
erutaihccerappA

CR-IFE

MS

BM

NOITAMROFNI ROF

41.21.01

.RPPA/REV
.RPPA/DKHC

SID
NWARD

NOITPIRCSED/ENOIZIRCSED

FO/LED

.VER

CS-IFE N TRAP
REVOC RAER NO BCM ROF ELDNAH ELBAKCOLDAP HTIW NOISSIMSNART FOORP .LPXE IFE

BACK COVER INSTALLATION PADLOCKABLE HANDLE (for MCB only)

822-OSI "2/1

5,5
3

5,4

EFI-SC

BLACK

1/2" ISO-228

87500.0402 N TRAP
.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

BCM ROF ELDNAH ELBAKCOLDAP HTIW NOISSIMSNART FOORP .LPXE IFE

0
.VER

PADLOCKABLE HANDLE FOR MCB (ALL POSITION)

1BUG-IFE N TRAP

REVOC

BCM ROF ELDNAH ELBAKCOLDAP HTIW NOISSIMSNART FOORP .LPXE IFE

822-OSI "2/1

85200.0402 N TRAP

822-OSI "2/1

2040.00578

BLACK

1/2" ISO-228

EFI-GUB1

BLACK

1/2" ISO-228

.XAM A052/061 BCCM ROF ELDNAH ELBAKCOLDAP HTIW NOISSIMSNART FOORP .LPXE IFE

OF

41.10.21

2-OSI "2/1

IRCSED

FO/LED

.VER

MAEF
NOISSIMSNART
5,41

LSIFE N TRAP
BCCM ROF ELDNAH ELBAKCOLDAP HTIW NOISSIMSNART FOORP .LPXE IFE

822-OSI "2/1
0

FO/LED

.VER

37

41.21.01

PART N 2040.00578

PADLOCKABLE HANDLE FOR MCCB 63A MAX (ALL POSITION)

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

031

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

92

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

REDIENHCS
NOISSIMSNART

2040.00258

BLACK

1/2" ISO-228

63400A SIZE PADLOCKABLE HANDLE (ALL POSITIONS)

.VER

86
n

EFI-SL

1/2" ISO-228

BLACK

65

1/2 ISO-228

58

CODE

FO/LED

.VER

ROTARY DEVICE FOR SCHNEIDER MCB


43

8,42

2,54

62

SCHNEIDER
TRANSMISSION

29
FEAM
TRANSMISSION

2010.00260

14,5

51.10.51

QUESTO DOCUMENTO E' DI PROPRIETA' DI FEAM S.r.l. - OGNI DIRITTO E' RISERVATO A TERMINE DI LEGGE.
THIS DOCUMENT IS THE PROPERTY OF FEAM S.r.l. - ALL RIGHTS ARE RESERVED ACCORDING TO LAW.

HANDLES-D

MILANO S.r.l.

10.12.14

FOR INFORMATION

MB

SM

REV.

DEL/OF

DESCRIZIONE/DESCRIPTION

DIS
DRAWN

VER/APPR.
CHKD/APPR.

DIS.N.
DWG.N.

Forniture Elettriche
Apparecchiature Materiali
FG.
SH.

2040.00578

DI
OF

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEU
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIH

ZIRCSED

.EGGEL ID ENIMRET A OTAVRESIR 'E OTTIRID INGO - .l.r.S MAEF ID 'ATEIRPORP ID 'E OTNEMUCOD OTSEUQ
.WAL OT GNIDROCCA DEVRESER ERA STHGIR LLA - .l.r.S MAEF FO YTREPORP EHT SI TNEMUCOD SIHT

7R

70

EFI EXPL. PROOF TRANSMISSION WITH PADLOCKABLE HANDLE FOR MCB


0

.RPPA/REV
ATAD Vof
ER the national and international specifications and of the technology, the above technical characteristics showed on
SID DueEN
OIZIthe
RCSEDdevelopment
REMARK:
to
5.0
this bulletin
as
on our confirmation
only.
06CI OPITcan
BCMbe
USconsidered
AVITATOR ARV
ONbinding
AM
.NEG .LLOT

ENOIZIRCSED

REDIENHCS

126 I Bartec Feam Catalogue 04


ehcirttelE erutinroF
ilairetaM erutaihccerappA

OTIUGESE

RC M

ATAD

.RPPA/REV

06200.0102

ECIDOC

ALACS

1:1
ELAIRETAM

Explosion Proof Electrical Equipment

EMH9 Instrument housing

Ex Enclosures

www.feam-ex.com

EMH9

Installation:hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II - Category 2G 2D

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex d IIC T6 Gb
II 2 D Ex tb IIIC T85C Db

EXECUTION
RULES OF COMPLIANCE

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-31

EC Type-Examination Certificate
PROTECTION DEGREE

INERIS 02 ATEX 0069X


IP66

AMBIENT TEMPERATURE

-40C +60C

OTHER AVAILABLE CERTIFICATES

IECEx: IECEx INE 14.0014X


EAC: TC RU C-IT.08..01499 (-60C +60C)
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315

Mechanical characteristics
Body

marine grade copper free aluminum

Cover

marine grade copper free aluminum

Round window

thransparent tempered glass

Gasket

NBR O-Ring sealing

On Request Accessories:
External epoxy painting with colour on request
Internal anticondensate painting
AISI 316L stainless steel drain breather valve

Bartec Feam Catalogue 04 I 127

Explosion Proof Electrical Equipment

Ex Enclosures

CODE

A [mm]

B [mm]

C [mm]

D [mm]

E [mm]

F [mm]

G [mm]

H
[mm]]

WEIGHT
[Kg]

EMH9S

160

159

141

120

95

89

110

1,50

EMH2S

160

159

141

120

95

89

110

EMH9SV

160

159

141

120

95

89

110

EMH2SV

160

159

141

120

95

89

110

THREADED
ENTRY

DRAIN VALVE

DETAIL

1 x 3/4"

NO

1,50

2 x 3/4"

NO

1,50

1 x 3/4"

YES

1,50

2 x 3/4"

YES

Reference details

109,97

3/4 NPT

E
3/4 NPT

www.feam-ex.com

EMH9

EMH9 Technical features

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this
bulletin can be considered as binding on our confirmation only.

128 I Bartec Feam Catalogue 04

ESA
Junction boxes

Explosion Proof Electrical Equipment

Ex Enclosures

www.feam-ex.com

ESA

Installation:hazardous areas - Zone 1 / 2 (Gases) - Zone 21 /22 (Dusts)


Classification: Group II Category 2G 2D

Certificate
NEMA Type 4X

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex e IIB or IIC T6 T3 Gb
II 2 D Ex tb IIIC T85C T200C Db

EXECUTION

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-7; EN/IEC 60079-11;


EN/IEC 60079-18; EN/IEC 60079-31

RULES OF COMPLIANCE
EC Type-Examination Certificate

INERIS 02 ATEX 0067X

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +60C

OTHER AVAILABLE CERTIFICATES

Component: INERIS 13 ATEX 9028U


IECEx: IECEx INE11.0016
INMETRO: CEPEL 12.2159
EAC: TC RU C-IT.08..01499
RINA: ELE18111CS_011
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
NEC 505: UL 20141112-E465037 - Type rating NEMA 1, 12, 4 and 4X
Kc (Korean certification): 2014-024207-02

Mechanical characteristics
Body

marine grade copper free aluminium light alloy

Cover

marine grade copper free aluminium light alloy

Screws

stainless steel

Internal plate

aluminium

Gasket

silicon rubber

On Request Accessories:
External epoxy painting with colour on request
Internal anticondensate painting orange RAL-2004
Drain and breather valves

Bartec Feam Catalogue 04 I 129

Explosion Proof Electrical Equipment

Ex Enclosures

CODE

A [mm]

B [mm]

C [mm]

D [mm]

E [mm]

F [mm]

G [mm]

H [mm]

I [mm]

INT.PLATE
X - Y [mm]

WEIGHT [Kg]

DETAIL

ESA1313

130

130

87

115

115

70

112

112

110 - 70

1,20

ESA1717

170

170

97

155

155

81

151

151

150 - 150

1,50

ESA2216

220

160

96

205

145

80

141

201

200 - 100

3,80

ESA2222

220

220

112

205

205

95

201

201

200 - 200

4,40

ESA3322

330

220

123

310

200

103

201

311

294 - 154

6,40

ESA3333

330

330

131

310

310

111

311

311

290 - 290

8,80

ESA4433

440

330

154

420

310

131

311

421

400 - 290

11,40

ESA5242

520

420

183

496

394

159

398

499

460 - 370

20,20

ESA6348

630

480

181

615

465

156

459

609

550 - 400

21,30

Reference Details

Reference Details

A
C

WALL DRILLING AREA

F
B

GxH

www.feam-ex.com

ESA

ESA Technical features

ESA Body Enclosures Drilling Layout


QUANTITY ALLOWED ENTRIES FOR SIZE
(from 1 to size 8)

QUANTITY ALLOWED ENTRIES FOR


SIZE (from 1 to size 8)

DRILLING
AREA C-D
[mm]

88 x55

ENCLOSURE
CODE

DRILLING
AREA A-B
[mm]

ESA1313

88 x55

ESA1717

150 x 70

150 x 70

ESA2216

200 x 70

120 x 70

ESA2222

200 x 85

200 x 85

ESA3322

285 x 90

12

200 x 90

ESA3333

275 x 90

12

275 x 90

12

ESA4433

370 x 110

20

14

12

12

265 x 110

14

10

ESA5242

420 x 145

30

18

16

12

12

360 x 145

28

18

14

11

10

ESA6348

500 x 140

36

24

18

16

12

10

400 x 140

30

21

15

12

10

ESA Indicative quantity of terminals and relevant section


CODE
ENCLOSURE

SECT. 2,5
[sq/mm]

SECT. 6,0
[sq/mm]

SECT. 10,0
[sq/mm]

SEZ. 16,0
[sq/mm]

SEZ. 35,0
[sq/mm]

SECT. 50,0
[sq/mm

SECT. 70,0
[sq/mm]

ESA1313
ESA1717
ESA2216
ESA2222
ESA3322
ESA3333
ESA4433
ESA5242
ESA6348

SECT. 240,0
[sq/mm]

10 x 1

5x1

4x1

4x1

3x1

2x1

1x1

112 - 70

20 x 1
30 x 1
30 x 1
46 x 1
46 x 2
70 x 2
70 x 3
90 x 3

10 x 1
18 x 1
18 x 1
26 x 1
24 x 2
40 x 2
44 x 3
56 x 3

8x1
14 x 1
14 x 1
22 x 1
22 x 2
32 x 2
34 x 3
44 x 3

8x1
10 x 1
10 x 1
18 x 1
16 x 2
26 x 2
30 x 3
40 x 3

6x1
8x1
8x1
14 x 1
14 x 2
20 x 2
22 x 3
28 x 3

3x1
3x1
4x1
10 x 1
10 x 1
14 x 2
18 x 2
24 x 2

2x1
2x1
2x1
6x1
8x1
10 x 1
14 x 1
20 x 1

1x1
1x1
2x1
2x1
3x1
4x1
6x1
10 x 1

150 - 150
200 - 100
200 - 200
294 - 154
290 - 290
400 - 290
460 - 370
550 - 400

INT.PLATE X - Y [mm]

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on
this bulletin can be considered as binding on our confirmation only.

130 I Bartec Feam Catalogue 04

ESX
Junction boxes

Explosion Proof Electrical Equipment

Ex Enclosures

www.feam-ex.com

ESX

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II Category 2G 2D

Certificate
NEMA Type 4X

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex e IIB or IIC T6 T3 Gb
II 2 D Ex tb IIIC T85C T200C Db

EXECUTION

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-7; EN/IEC 60079-11;


EN/IEC 60079-18; EN/IEC 60079-31

RULES OF COMPLIANCE
EC Type-Examination Certificate

INERIS 02 ATEX 0067X

PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +60C

OTHER AVAILABLE CERTIFICATES

Component: INERIS 13 ATEX 9028U


IECEx: IECEx INE11.0016
INMETRO: CEPEL 12.2159
EAC: TC RU C-IT.08..01499
RINA: ELE18111CS_011
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
NEC 505: UL 20141112-E465037 - Type rating NEMA 1, 12, 4 and 4X
Kc (Korean certification): 2014-024207-02

Mechanical characteristics
Body

stainless steel AISI-316L - th. 1,5mm

Cover

stainless steel AISI-316L - th. 1,5mm

Screws

stainless steel AISI-316L

Internal plate

stainless steel AISI-316L - th. 1,5mm

Gasket

silicon rubber

Fixing

stainless steel AISI-316L fixing lugs, adjustable on horizontal / vertical position

Closing

whit key (on demand) / whit screws (on standard)

On Request Accessories: :
External epoxy painting with colour on request
Internal anticondensate painting orange RAL-2004
Drain and breather valves

Removable flanges on side walls (see identification table)


Locking with screws

Bartec Feam Catalogue 04 I 131

Explosion Proof Electrical Equipment

ESX Technical Features


LONG SIDE

LONG SIDE
FLANGE

SHORT SIDE
FLANGE

HINGES

TYPE OF
CLOSING

INTERNAL
HEIGHT

PLATE
X-Y

WEIGHT

TYPE C [mm]

No.

No.

No.

No.

D [mm]

[mm]

[Kg]

DETAIL

13

130

13

130

087

87

53

80-80

1,00

17

170

17

170

087

87

53

120-120

2,00

12

120

087

87

53

170-70

2,50

16

165

2
2
2
2
2
2

0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
1

2
2
2
2
2
2

0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
1

2
2
2
2
2
2

53
113
53
113
53
113
53
113
113
113

5,00

330

1
1
1
1
1
1

280-170

33

0
0
0
0
0
0
0
0
0
0

4,00

220

2
2
2
2
2
2

170-170

22

1
1
1
1
1
1

3,00

220

0
0
0
0
0
0
0
0
0
0

170-115

22

87
148
87
148
115
148
115
148
148
148

280-280

6,80

390-170
390-280

7,00
8,50

A
A

113

440-310

9,50

470-370

12,00

580-430

16,00

695-350

18,00

87
148

0
1

0
2

44

440

22
33

220
330

087
148
087
148
115
148
115
148
148
148

49

490

36

360

148

148

52

520

42

420

148

148

242

242

63

630

48

480

148

148

74

745

40

400

148

148

227

227

220

ESX

22

33

330

EXAMPLES
OF CREATING
CODE
N
0
1
2

ESX#
ESX#

Long Side Flange


without flange
one flange
two flanges

13
44

13
33
N
0
1
2

Short Side Flange


without flange
one flange
two flanges

0
1

0
1
N
0
1
2

113
206
113
113
190

ESX#1313870000= dimension 130x130x87, without flange, closing lid with screws


ESX#44331481211= dimension 440x330x148, 1 flange on long side, 2 flange on
short side, hinges on long side, closing with key, on long side
Hinges
on long side
on long side
on short side

N
0
1
2

Type of closing
closing lid with screws
closing lid with key, on long side
closing lid with key, on short side

*NOTE: the choice of positioning of the hinge, is linked to the tightening. If you choose option 0 for the hinges, you are forced to use option 0 for tightening.
The same also applies to other options (1, 2). If you want to create some special code, please contact our sales office.

Reference Details

Fixing details

A
B

C
9
D

12

PLATE X-Y

www.feam-ex.com

HEIGHT

SHORT SIDE

TYPE A [mm] TYPE B [mm]

Ex Enclosures

132 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

ESX Distance between fixing centers

Ex Enclosures

DETAIL

ENCLOSURE

DETAIL

ESX#1313
ESX#1717
ESX#2212
ESX#2216
ESX#2222
ESX#3322
ESX#3333
ESX#4422
ESX#4433
ESX#4936
ESX#5242
ESX#6348
ESX#7440

180
220
270
270
270
380
380
490
490
535
570
675
790

50
90
40
80
140
140
250
140
250
280
340
400
360

205
245
295
295
295
405
405
510
510
560
590
700
815

B
B
B
B
B
B
B
B
B
B
B
B
B

ESX#1313
ESX#1717
ESX#2212
ESX#2216
ESX#2222
ESX#3322
ESX#3333
ESX#4422
ESX#4433
ESX#4936
ESX#5242
ESX#6348
ESX#7440

180
220
170
210
270
270
380
270
380
410
470
530
490

50
90
140
140
140
250
250
360
360
410
440
550
660

205
245
245
235
295
295
405
295
405
435
495
555
515

C
C
C
C
C
C
C
C
C
C
C
C
C

ESX Removable flanges drilling layout


ENCLOSURE
CODE

DRILLING AREA
A-B [mm

ESX#2216...

180 - 85

ESX#2222...

180 - 85

QUANTITY ALLOWED ENTRIES FOR


SIZE (from 1 to size 8)

QUANTITY ALLOWED ENTRIES FOR


SIZE (from 1 to size 8)

DRILLING
AREA
C-D [mm]

125 - 85

180 - 85

180 - 85

ESX#3322...

290 - 85

12

ESX#3333...

290 - 85

12

290 - 85

12

12

ESX#4422...

400 - 85

16

11

290 - 85

ESX#4433...

400 - 85

16

11

290 - 85

12

ESX#4936...

450 - 85

18

13

11

320 - 85

14

380 - 85

16

11

ESX#5242*

480 - 85

20

14

ESX#5242...

480 - 178

40

28

ESX#6348...

590 - 85

24

17

11

22

16

14

12

380 - 178

32

22

18

14

10

14

10

440 - 85

18

13

10

14

10

25

18

16

12

10

ESX#7440*

705 - 85

30

21

17

13

10

360 - 85

ESX#7440...

705 - 163

53

38

34

26

20

14

360 163

* Enclosure height 148 mm

FLANGES DRILLING AREA


C

G [mm]

G1 [mm]

ESX#2216...

214

159

119

ESX#2222...

214

214

119

ESX#3322...

324

214

119

ESX#3333...

324

324

119

ESX#4422...

434

214

119

ESX#4433...

434

324

119

ESX#4936...

484

359

119

ESX#5242...*

514

414

212,5

119

ESX#6348...

624

474

119

ESX#7440...*

739

394

197,5

119

Reference Details

FLANGES

G1

F [mm]

E [mm]

CODE

G1

ESX Removable flanges dimensions

* ENCLOSURES WITH TWO HEIGHTS (see ESX technical features table)

Bartec Feam Catalogue 04 I 133

www.feam-ex.com

ESX

ENCLOSURE

Explosion Proof Electrical Equipment

Ex Enclosures

CODE
ENCLOSUR

SECT. 2,5
[sq/mm]

SECT. 6,0
[sq/mm]

SECT. 10,0
[sq/mm]

SECT. 16,0
[sq/mm]

SECT. 35,0
[sq/mm]

SECT. 50,0
[sq/mm]

SECT. 70,0
[sq/mm]

SECT. 240,0
[sq/mm]

INT.PLATE
X - Y [mm]

ESX-1313

8x1

5x1

4x1

4x1

3x1

2x1

1x1

80 - 80

ESX-1717

22 x 1

12 x 1

10 x 1

8x1

7x1

5x1

4x1

1x1

128 - 128

ESX-2212

30 x 1

18 x 1

14 x 1

12 x 1

9x1

8x1

6x1

178 - 78

ESX-2216

30 x1

18 x 1

14 x 1

12 x 1

9x1

8x1

6x1

1x1

178 - 118

ESX-2222

30 x 1

18 x 1

14 x 1

12 x 1

9x1

8x1

6x1

2x1

170 - 170

ESX-3322

48 x 1

30 x 1

24 x 1

18 x 1

15 x 1

12 x 1

11 x 1

2x1

280 - 170

ESX-3333

48 x 2

30 x 2

24 x 2

18 x 2

15 x 2

12 x 2

11 x 1

2x1

280 - 280

ESX-4422

70 x 1

45 x 1

36 x 1

30 x 1

23 x 1

19 x 1

17 x 1

6x1

398 - 178

ESX-4433

70 x 2

42 x 2

34 x 2

28 x 2

22 x 2

18 x 2

16 x 1

4x1

390 - 290

ESX-4936

78 x 2

50 x 2

40 x 2

34 x 2

26 x 2

20 x 2

18 x 1

8x1

440 - 315

ESX-5242

86 x 2

55 x 2

44 x 2

36 x 2

28 x 2

22 x 2

19 x 2

6x1

470 - 370

ESX-6348

108 x 3

68 x 3

54 x 3

46 x 3

34 x 3

28 x 3

26 x 2

10 x 1

580 - 430

ESX-7440

140 x 2

80 x 2

64 x 2

54 x 2

40 x 2

34 x 2

30 x 2

12 x 1

695 - 350

ESX Body Enclosures Drilling Layout


ENCLOSURE
CODE

DRILLING
AREA A-B
[mm]

QUANTITY ALLOWED ENTRIES FOR


SIZE (from 1 to size 8)
1

DRILLING
AREA C-D
[mm]

QUANTITY ALLOWED ENTRIES FOR


SIZE (from 1 to size 8)
1

ESX#1313...

117 - 44

117 - 44

ESX#1717...

160 - 44

160 - 44

ESX#2212...

210 - 44

110 - 44

ESX#2216...*

210 - 44

155 - 44

ESX#2216...

210 - 100

155 - 100

ESX#2222...*

210 - 44

210 - 44

ESX#2222...

210 - 100

210 - 100

ESX#3322...*

320 - 64

210 - 64

ESX#3322...

320 - 100

12

12

10

210 - 100

12

12

10

ESX#3333...*

320 - 64

320 - 64

ESX#3333...

320 - 100

12

12

10

320 - 100

ESX#4422...

430 - 100

16

16

14

11

210 - 100

ESX#4433...

430 - 100

16

16

14

11

320 - 100

12

12

10

ESX#4936...

480 - 100

20

18

15

12

350 - 100

14

14

10

ESX#5242...*

510 - 100

22

18

16

13

410 - 100

18

14

13

10

ESX#5242...

510 - 195

44

27

24

21

16

14

10

410 - 195

36

21

18

15

12

11

ESX#6348...

620 - 100

29

22

20

16

10

470 - 100

21

16

15

12

ESX#7440...*

735 - 100

33

26

24

18

12

390 - 100

18

14

12

ESX#7440...

735 - 180

55

43

38

33

20

18

14

390 - 180

30

23

20

15

* LOW ENCLOSURE (see ESX technical features table)

Reference Details

BODY DRILLING AREA


A

www.feam-ex.com

ESX

ESX Indicative quantity of terminals and


relevant section

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on
this bulletin can be considered as binding on our confirmation only.

134 I Bartec Feam Catalogue 04

GWR Glass fibre reinforced


polyester resin junction boxes

Explosion Proof Electrical Equipment

Ex Enclosures

www.feam-ex.com

GWR

Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II - Category 2G 2D

Certificate
NEMA Type 4X

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex d e ia/ib mb IIC T6 or T3 Gb
II 2 D Ex tb IIIC T85C or T100C Db

EXECUTION

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-7; EN/IEC 60079-11;


EN/IEC 60079-18; EN/IEC 60079-31

RULES OF COMPLIANCE
EC Type-Examination Certificate
PROTECTION DEGREE

INERIS 13 ATEX 0042


IP66

AMBIENT TEMPERATURE

-50C +55C

OTHER AVAILABLE CERTIFICATES

Component: INERIS 13ATEX 9009U


IECEx: IECEx INE 13.0058
IECEx (component): IECEx INE 13.0021U
INMETRO: CEPEL 13.2287
INMETRO (component): CEPEL 13.2273U
EAC: TC RU C-IT.08..01499
RINA: ELE18111CS_011
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
NEC 505: UL 20141112-E465037 - Type rating NEMA 1, 12, 4 and 4X

Mechanical characteristics
Body
Cover
Screws
Internal plate
Gasket
Strenght

glass fibre reinforced polyester resin


glass fibre reinforced polyester resin
external - stainless steel
aluminium sp. 1,5mm
silicon rubber
4 Joule impact resistance

On Request Accessories:
Drain and breather valves

Bartec Feam Catalogue 04 I 135

Explosion Proof Electrical Equipment

GWR

GWR Technical Features


CODE

A [mm]]

B [mm]

GWR11(1)

110

110

GWR14(1)

140

GWR21(1)

175

GWR22(1)
GWR42(1)

C [mm]

Ex Enclosures

D [mm]

E [mm]

F [mm]

G [mm]

H [mm]

65

102

102

INT. PLATE
X - Y [mm]

WEIGHT
[Kg]

DETAIL

0,30

86

96

96

140

84

108

110

62

132

132

0,40

85

121

125

72

102

167

77

0,88

175

175

121

162

125

100

167

167

135 - 135

1,25

360

175

121

310

161

102

352

167

320 - 135

2,50

GWR44(1)

360

360

121

346

307

102

352

352

320 - 320

3,40

GWR84(1)

730

360

168

670

340

147

720

350

670 - 310

8,00

(1) ENCLOSURES COLOUR: N = DARK GREY RAL7021 - B = LIGHT BLUE RAL5015 / EXAMPLE: GWR14N = COLOUR DARK GREY RAL 7021 GWR42B = COLOUR LIGHT BLUE RAL5015

Reference Details

Reference Details

WALL DRILLING AREA

A
B

F
PLATE X-Y

GxH

www.feam-ex.com

I [mm]

BACK SIDE
FIXING DETAIL

GWR Body Enclosures Drilling Layout


ENCLOSURE
CODE

DRILLING AREA
A-B [mm]

GWR11N

QUANTITY ALLOWED ENTRIES FOR SIZE


(from 1 to size 8)
1

64 x 52

GWR14N

90 X 52

GWR21

108 - 85

GWR22

125 - 85

GWR42

310 - 85

12

GWR44

310 - 85

12

GWR84N

640 - 115

35

23

20

DRILLING AREA
C-D [mm]

QUANTITY ALLOWED ENTRIES FOR SIZE


(from 1 to size 8)
1

64 x 52

90 X 52

37 - 85

125 - 85

125 - 85

310 - 85

12

17

13

310 - 115

17

11

GWR Indicative quantity of terminals and relevant section


CODE
ENCLOSURE

SECT. 2,5
[sq/mm]

GWR11N

12 x 1

SECT. 6,0
[sq/mm]
8x1

SECT. 10,0
[sq/mm]
6x1

SECT. 16,0
[sq/mm]
5x1

SECT. 35,0
[sq/mm]
3x1

SECT. 50,0
[sq/mm]
3x1

SECT. 70,0
[sq/mm]
1x1

SECT.240,0
[sq/mm]
1x1

INT.PLATE X - Y
[mm]
-

GWR14N

18 x 1

10 x 1

8x1

7x1

5x1

4x1

2x1

1x1

GWR21

18 x 1

10 x 1

8x1

7x1

5x1

4x1

2x1

1x1

GWR22

20 x 1

10 x 1

10 x 1

6x1

6x1

4x1

2x1

1x1

135 - 135

GWR42

48 x 1

28 x 1

24 x 1

20 x 1

12 x 1

10 x 1

4x1

2x1

320 - 135

GWR44

48 x 2

28 x 2

24 x 2

20 x 2

12 x 2

10 x 2

8x1

4x1

320 - 320

GWR84N

120 x 2

70 x 2

60 x 2

50 x 2

44 x 2

30 x 2

20 x 1

14 x 1

670 - 310

136 I Bartec Feam Catalogue 04

HANDLES DE
Operators for Ex de enclosures

Explosion Proof Electrical Equipment

Ex Enclosures

(pilot light - push button - ammeter - selector switch)


Installation: hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)
Classification: Group II - Category 2G 2D

AM72#

HANDLES DE

SEL-DE#

EFL-DE#

EFP-DE#

REFERENCE STANDARDS
Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
EXECUTION

III 2 G Ex de IIC Gb

RULES OF COMPLIANCE

EN/IEC 60079-1; EN/IEC 60079-7; IEC 60079-0


LCIE 13 ATEX 3021U (pilot lights - type LIE...)
LCIE 13 ATEX 3005U (push buttons - type PBE...)
LCIE 13 ATEX 3070U (ammeters - type AM...)
LCIE 13 ATEX 3004U (selector switches - type IRE...)

EC Type-Examination Certificate
PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-20C +60C
IECEX: IECEx LCIE 13.0018U (pilot lights)
IECEx LCIE 13.0007U (push buttons)
IECEx LCIE 13.0009U (ammeters)
IECEx LCIE 13.0005U (selector switches)

OTHER AVAILABLE CERTIFICATES

EAC: TC RU C-IT.08..01323 (-50C +55C)

Mechanical characteristics
AMMETERS

PILOT LIGHTS
Body
Diffuser / Lens
Voltage

thermo plastic
polycarbonate
12V 380V ac/dc

PUSH BUTTONS / SELECTOR SWITCHES


Body

thermo plastic

Ring

thermo plastic

Operator

thermo plastic

Housing

fire retardant plastic

Insulating voltage

690V ac

Working mode

electromagnetic

Accuracy

1,50%

Start up
over current

5 times - (other of request)

Bartec Feam Catalogue 04 I 137

www.feam-ex.com

EFPF-DE#

Explosion Proof Electrical Equipment

HANDLES DE Technical data

Ex Enclosures

SPRING RETURN PUSH BUTTON - 10AMP CONTACT

www.feam-ex.com

HANDLES DE

HANDLES-DE

CODE

CONTACT BLOCK

OPERATOR COLOR

BODY DIAMETER [mm]

EFP-DE#GI1
EFP-DE#GI2
EFP-DE#GI3
EFP-DE#GI4
EFP-DE#GI5
EFP-DE#RO1
EFP-DE#RO2
EFP-DE#RO3
EFP-DE#RO4
EFP-DE#RO5
EFP-DE#VE1
EFP-DE#VE2
EFP-DE#VE3
EFP-DE#VE4

1 NO
1 NC
1 NO + 1 NC
2 NO
2 NC
1 NO
1 NC
1 NO + 1 NC
2 NO
2 NC
1 NO
1 NC
1 NO + 1 NC
2 NO

YELLOW
YELLOW
YELLOW
YELLOW
YELLOW
RED
RED
RED
RED
RED
GREEN
GREEN
GREEN
GREEN

30
30
30
30
30
30
30
30
30
30
30
30
30
30

2 NC

GREEN

30

EFP-DE#VE5

TURN TO RELEASE MUSHROOM PUSH BUTTON


EFPF-DE#1

1 NO

RED

30

EFPF-DE#2

1 NC

RED

30

EFPF-DE#3

1 NO + 1 NC

RED

30

EFPF-DE#4

2 NO

RED

30

EFPF-DE#5

2 NC

RED

30

PILOT LIGHT FOR BACK COVER INSTALLATION

QUESTO DOCUMENTO E' DI PROPRIETA' DI FEAM S.r.l. - OGNI DIRITTO E' RISERVATO A TERMINE DI LEGGE.
THIS DOCUMENT IS THE PROPERTY OF FEAM S.r.l. - ALL RIGHTS ARE RESERVED ACCORDING TO LAW.

HANDLES-DE

CODE

SUPPLY

LAMP TYPE

LAMP COLOR

BODY DIAMETER [mm]

EFL-DE#BI1

12V 36V ac/dc

LED

WHITE

30

EFL-DE#BI2

48V 110V ac/dc

LED

WHITE

30

EFL-DE#BI3

220V 380V ac/dc

LED

WHITE

30

EFL-DE#GI1

12V 36V ac/dc

LED

YELLOW

30

EFL-DE#GI2

48V 110V ac/dc

LED

YELLOW

30

EFL-DE#GI3

220V 380V ac/dc

LED

YELLOW

30

EFL-DE#RO1

12V 36V ac/dc

LED

RED

30

EFL-DE#RO2

48V 110V ac/dc

LED

RED

30

EFL-DE#RO3

220V 380V ac/dc

LED

RED

30

EFL-DE#VE1

12V 36V ac/dc

LED

GREEN

30

EFL-DE#VE2

48V 110V ac/dc

LED

GREEN

30

EFL-DE#VE3

220V 380V ac/dc

LED

GREEN

30

AMMETER AND MILLIAMMETER


HANDLES-DE

CODE

AM72#

138 I Bartec Feam Catalogue 04


MILANO S.r.l.

Forniture Elettriche
Apparecchiature Materiali

RATED CURRENT

SCALE

40mA

020mA

40mA

020mA

1A

01A

5A

05A

X/1A

01A; 5A; 10A, 15A; 20A; 25A; 30A; 40A; 60A; 75A;
100A; 150A; 200A; 300A; 500A;

X/5A

01A; 5A; 10A, 15A; 20A; 25A; 30A; 40A; 60A; 75A;
100A; 150A; 200A; 300A; 500A;

Explosion Proof Electrical Equipment

HANDLES DE Technical data

U1

8
2Z NO.
NO.
8
NO.
8
NO.
8

U1

SEL-DE#2Z1

SEL-DE#01C

9
9
9
2ZI 9

10
10
1C 10
10

F
F
10
F
10
F

SEL-DE#1C1

11
1CI 11
11
11

2C 12
12
12
12

F111
11
F1
F1
F1

12
12
F2

F2
F2
F2

HANDLES DE
www.feam-ex.com

ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ONON

ON
ON
ON
ON
ON
ON
ON

ON

STOP
STOP
STOP
STOP

STOP
STOP
STOP
STOP
0 0 00
00 00
START
START
START
START
START
START
START
START

OFF
OFF
OFF
OFF

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON

ON
ON
ON
ON

OFF
OFF
OFF
OFF
OFF OFF

OFF
OFFOFF
ON

OFF
7-8

22

45

7-8

2
P1
C 45 45
P
45

1-2

1-2

3-4 3-4

1
2
P 45 45
1

1-2

3-4
5-6

3-4

SWITCH
SWITCH
(POSITION)
SWITCH
(POSITION)
SWITCH
(POSITION)
SWITCH
(POSITION)
SWITCH

3-4
5-6
7-8

(POSITION)
SWITCH
(POSITION)
(POSITION)

CONTACT CH
AND POSIT

SWITCH
(POSITION)

1-2
3-4

CONTACT
5-6
AND POS

5
7

7-8

1
3

1
P 45

1
3

1
P
C 1 45
0
P 1-2
45

1-2 3-4
3-4 5-6

00

1
P 45

1-2

11
3

7-8

1 1 0
P P 45
C C 45
1-2
1-2
3-4
3-4

1
0
P 45
1
1
P
1-2
45 3
C
3-4
1-2

1
53

5-6
3-4
7-8

3-4 5-6
5-6 7-8
7-8
1-2 3-4
5-6 7-8
5-6
7-8X7-8
3-4 5-6
X
5-6 7-8

P 45

1-2

7-8

3-4 XX
POSITION 1-2
22
3-4
POSITION
1-2 3-4
POSITION
1-2 3-4
POSITION
1-2
3-4
POSITION
1-2
1
X
1X
3-4
POSITION
1
11-2
XX
F1
1 POSITIONX 1-2 3-4 5-6 7-8
F1
0
POSITION
1-2 3-4
1
00X
0
1
X
X
0
2
XX
21
12
F2 0
2
XX
11
F1
2
X
0
0
2
X
2
2
2
XX X X

X
X
5-6
7-8
X
X
XX
X
X
X
X
X
X

1
5

XX

POSITION
1-2
POSITION
1-2 3-4
3-41-2
POSITION POSITION
1-2
1X1
3-4XX
POSITION
1-2
1
1
F2
3-4 X
POSITION 1-2
X0
12F2 1F2
0X
0
1
0
1
X
0
22 2
0
2
X
0
2
X
2
X
2
X

3-4

CONTACT

11

POSITION

SEL-DE#02C

POSITION 1-2 3-4


POSITION
1-21-2 3-4
3-4 5-6 7-8
POSITION
3-4X
POSITION 1-2
1
1 1-2 X 3-4
910
U3
POSITION
F 1
3-4
POSITION
1-2 X3-4
X0
POSITION
1-2
3-4
POSITION
1-2
1
X
X
2
X
1
1X2
X X
0
1
X
1
X
F
0
F
0
0
0
2
X
0
2
X
X
22
2
X
POSITION
1-2
3-4X
POSITION
1-2 3-4
2
X

FF1

1-2 1
P3-445

1-2 5-6

POSITION 1-2 3-4 5-6 7-8


POSITION 1-2 3-4 5-6 7-8
3-4 5-6
7-8
POSITION
1-2
1
X
X
7-8
3-41-2
5-63-4 5-6
POSITION
1-2
1
X
POSITION
1-2 X3-4
5-67-87-8
7-8
POSITION
1-2
1 POSITION
X
X3-4 5-6
X
2
X
1
X
XX
9
X
X X X
X
U3 21U3
11
U3
XX X
2
XX
2
X
NO. SCHEME
CONTACT
X
X
2
XX
22
XX

1011

OFF
P 45

POSITION
1-2 3-4 5-6 7-8
POSITION 1-2 3-4 5-6 7-8
POSITION
POSITION
3-4 3-4
5-6 5-6
7-8 7-8
1-2 1-2
POSITION
5-6
7-8 7-8
1 1-2
X3-4 3-4
X 1-2
X X 5-6
U2 1POSITION
U2 8
SCHEME
CONTACT
3-4
5-6
7-8
1-2
1CONTACT
X
X
1
X
X
8SCHEME
U2 U2 POSITION
2 X
1CONTACT
XX X X
XXX
U2 U2
8SCHEME
21
1
X
X
SCHEME
U2
X
X
2CONTACT
X
X
2
X
X
2
X
X
2
NO. SCHEME
SCHEME
CONTACT
NO.
CONTACT
X
X
2

U3
U3
U3
U39

POSITION 1-2 3-4


POSITION
POSITION
3-4 3-4
1-2 1-2
POSITION
3-4 3-4
1-2
1POSITION
X 1-2
POSITION
3-4
1 1-2
X 3-4 5-6
1 POSITION
X 1-2
POSITION
1-2
1
1 X
XX3-4
U2 2
12
XX
21 1 X X X X
X X X
2
2 2
2
XX
2

NO. SCHEME

15

00
22

SEL-DE#02Z

7
7

U1
U1 U1
U1 U1
U1 7

7-8

00
22

SEL-DE#1Z1

7
1ZI 7
7
7

5-6

22

U7

OFF O
P 45 45

1-2

22

U
U

3-4

1
1
31
31
3
5
3
5
5
5

CONTACT
3-4
AND POS

22

U
U
U
U

7-8

XX

00
22

6
6

1-2

11
2222

6
6
6

1Z 6

5-6

1
1
31
31
3
3

CONTACT CH
AND POSITI

SEL-DE#01Z

POSITION

SWITCH
(POSITION)

SWITCH
(POSITION)

11
2222

3-4

1-2

OFF

POSITION
3-4
1-2
ON
X 1X1-2
U POSITION
POSITION
1-2 3-4XX 3-4X
POSITION
3-4 3-4X
1-2
1POSITION
X 2 1-2
POSITION
3-4
1-2
1 X
X
1
1 X
XX
21
12
X
2 X
X
X
2
X
2
1-2 3-4
2 POSITION
POSITIONX 1-2 3-4

1111

D2

SWITCH
SWITCH
SWITCH
(POSITION)
SWITCH
SWITCH
(POSITION)
(POSITION)
SWITCH
(POSITION)
(POSITION)
(POSITION)

POSITION

ON OFF
OFF

CONTACT

POSITION 1-2 3-4 5-6 7-8


POSITION
7-8 7-8
3-4 3-4
5-6 5-6
POSITION
1-2 1-2
7-8 7-8
3-4 3-4
5-6 5-6
POSITION
1-2 1-2
POSITION
OFF
D2
3-4 1-2
5-63-4 7-8
OFF OFF 1-2POSITION
5-6 7-8
D2 D2 POSITION
OFF
OFF X
D2NO.
D2SCHEME
X
ON D2
X
OFFX
5
OFF
CONTACT
D2
X
XX
XX
XX
ON ON X
ON ON X ONXX XXX X XXX XX
ON
X
X
X
X

4I

5-6
5-6
5-6
5-6
X
X
X
X

SEL-DE#04I

5
5

1
1
31
31
3
5
3
5
5
5

NO. SCHEME

5
5
5
5

3-4
3-4
3-4

1-2
1-2
1-2

OFF
POSITION
3-4 3-4
5-6
1-2 1-2
POSITION
OFF
POSITION
1-2 3-4 5-6
ON1-2 3-4
X
X
POSITIONOFF
5-6
OFF
ON
X
X
OFF CONTACT
POSITION
3-4
5-6
1-2
OFF ONCONTACT
X
X
OFF CONTACT
ONCONTACT
X
X
CONTACT
ON
X
X
X
OFF
ON CONTACT
X
X
X
ON
X
X
X
ON
X
X
X

11
2222

NO.NO.
SCHEME
SCHEME
D
4 SCHEME
NO.

1
1
31
31
3
5
3
5
5
5

112
2 2 22

3I NO.
D
4 NO.
SCHEME
SCHEME
D
4

SWITCH
(POSITION)
SWITCH
(POSITION)
(POSITION)

POSITION
POSITION
POSITION

D
D
D
D

4
4
4
NO.
D4
4 SCHEME

3-4
3-4
3-4
3-4
X
X
X
X

1-2
3-4
1-2
3-4
1-2
3-4
1-2
3-4
X
XX
XX
XX

1111

SEL-DE#03I

2I

POSITION
POSITION
1-2
POSITION
POSITION
1-2
POSITION
OFF1-2
POSITION
POSITION
OFF
OFF
POSITION
1-2
OFF OFF
ON
OFF OFF
ON X
ON
OFF
ON ON X
ON X
ON
ON
X

D1
D1
D1
D1

3
D1
D1
3
D1
3
D1

SEL-DE#02I

33
3
3

OFF
OFF
OFF
OFF

ON

5-6
5-6
5-6
5-6
X
X
X
X

5-6
5-6

3-4
5-6
3-4
5-6
3-4
3-4
X
XX
XX
XX
X

Z
Z
Z
Z

3-4
3-4

1-2
3-4
1-2
3-4
1-2
X
1-2
X
X
XX
X
X

POSITION 1-2
POSITION 1-2
POSITION
POSITION
1-2
OFF POSITION
X
POSITION
1-2
OFFPOSITION
OFFX
OFF POSITION
OFFX
ON
OFF
ON OFF
ON X
OFF
ON
ON
ON
ON

X
X
X

OFF
OFF
OFF
OFF

START
START
START

Z
Z
Z22
Z2

X
X
X
XX

5-6
5-6
5-6
5-6
X
X
X
X
X
X

22
2
2

5-6

3-4
3-4
X
3-4X
3-4X

1 11

1
1
1

3-4

1-2
1-2
1-2
X
1-2
X
X
X
X
X
X

11

Y
Y
Y
Y1

1111

STOP
X
POSITION
1-2
STOP
X
STOPPOSITION
X
POSITION
0
STOP
0 POSITION
STOPX
0 POSITION
STOP
Y
0
STOP
Y START
0
START
0
Y START STOP
Y START START
0
0

SWITCH
(POSITION)
(POSITION)

1 1 1 1 11
0
0 0 0 02
2
1
2 12 2 2

11
1
1

CONTACT

SCHEME
CONTACT
SCHEME
CONTACT
3-4 5-6
POSITION 1-2
SCHEME
CONTACT
3-4 5-6
POSITION 1-2
SCHEME
CONTACT
3-4 5-6
POSITION 1-2

SWITCH
SWITCH
SWITCH
(POSITION)
(POSITION)
SWITCH
SWITCH
(POSITION)
(POSITION)
SWITCH

1
0
2

SEL-DE#1Z

NO.
NO.
NO.
NO.

CONTACT
CONTACT
CONTACT

1 1 11
0 0 00
1
2 2 21 2

SEL-DE#01Y

SCHEME

SELECTOR
SWITCHES
CONTACT

SCHEME
SCHEME
SCHEME
SCHEME

11
00
22

CODE

NO.
NO.
NO.
NO.

1 1 11 1
0 0 00 0
2 1
2 2 2 21

HANDLES-DE

Ex Enclosures

1
P 45

3-4
5

Bartec Feam Catalogue 04 I 139

1-2

5-6
7-8

Explosion Proof Electrical Equipment

HANDLES DE Technical data

Ex Enclosures

SELECTOR SWITCHES

14

www.feam-ex.com

14
14

C
C 14
C
C 14

3-4 X

2
CONTACT

SEL-DE#1W1

15
15
1WI 15
15

C1 15
C1
C1 15
C1

0
2

POSITION

X1-2

SEL-DE#02W

3-4

7-8

17

START

10

2
POSITION

1-2

3-4X

SEL-DE#01R

10

18

10

19

3-4
POSITION
1-2
X1-2 3-4
STARTPOSITION
X
3-4
POSITION
1-2
START
X
XX
X
START
0
X
POSITION
1-2 3-4
3-4
POSITION
1-2
X
START
X
0
0
X X XX
STOP
START
X
START X X
20 0
STOP0
X
STOP
0 STOP

STOP

1-2

POSITION

SEL-DE#01X

19
19
1X 19

20
19
20
20
19

20
20

3-4

1-2

3-4
POSITION
1-2
X
X
START
X
START
3-4
POSITION
1-2
X
X1-2
START
0 POSITION
X
0
START
X
XX
START
0
X
STOP
STOP
0
X
0
STOP
STOP

3-4
5-6

3-4
X
3-4
X
X

1
P 45

1-2
3-4

1
P 45

1-2

5-6

X
X

1
3
5

1
P 45

1-2
3-4
5-6
7-8

0
2

7-8

1
3

1
3

STOP

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on
this bulletin can be considered as binding on our confirmation only.

140 I Bartec Feam Catalogue 04

1-2
3-4

CONTACT
AND PO

STOP

POSITION

7-8

SWITCH
(POSITION)

STOP

10
10
18
10

7-8

1 1 11
0 000
2
2

7-8

17
C3POSITION
POSITION
1-2
5-6
1
X 03-41-2 5-6
X3-4 7-8
0
1
1
X 2 X X X X
C3 02 POSITION X1-2 3-4 X
5-6
0
0
2
XX
XX
1
2
POSITION X
1-2 3-4
C3 2
X
X
18

18
1R 18
18

0
2

1
0
2

SWITCH
(POSITION)
SWITCH
SWITCH
SWITCH
(POSITION)
(POSITION)SWITCH
(POSITION)
(POSITION)
1
2 2
0
2

C3
C3
17
C3

P 45
1
P
C1-2 45
C

3-4

STARTSTART
START
START
START
0
0
0 0 0
STOP 1

5-6

3-4

5-6
3-4
7-8

7-8

STOP START
START
STOP
STOP
STOP
0
0
STOP STOP

1-2

POSITION 1-2 3-4 5-6


NO. SCHEME
CONTACT
5-6 7-8
POSITION
1-2
1
X 13-4
XX
X

START
START
START
0 0 0

17
17

STARTSTART
STOP
STOP
STOP
0
0
STOP STOP

2WI 17

CONTACT
CONTACT
NO. SCHEME
CONTACT
CONTACT
NO. SCHEME
CONTACT

SEL-DE#2W1

1
5

NO. SCHEME
NO. SCHEME
NO. SCHEME

POSITION

1
P 45
1
P
1-2 45
C
3-4
1-2

7-8

3-4
5-6 7-8
POSITION
1-2
C21
2
X
X
POSITION
1-2X 3-4 5-6 7-8
0
7-8
POSITION
1-2
1
X 1 3-4 X5-6
X
0
X
2
X
X
C21
7-8
POSITION
1-2
X 0 3-4 5-6
X
0
POSITION
2
X 1-2 3-4 5-6
X 7-8
1
X 21
X X X
0
X
2 C2
X X
X
16
0
0
2
X
X
2

1-2

1 1 1
0 0 0
2 12 2 1

C2
C2 16
C2
C2

1
P 45

1
1

11
0
0
2

16
16
16
2W 16

3-4

7-8

3-4
CONTAC
AND PO

31

2POSITION1 1-2XX3-4 5-6


15
C1
5-6 7-8
POSITION
1-2 3-4
0

16

SWITCH
(POSITION)

53

POSITION
1-2
3-4 3-4
5-6 7-8
POSITION
1-2
1 POSITION
X1 1-23-4
X
1 X
X
1 1-2
X
C1 POSITION
14
C 0
1
X00 3-4 1-2 3-4
16
C2
POSITION
0
3-4 X X
POSITION
1-2
1
X
1
2
0
2
2
XX
2
XX
C1
1
X0
0
2
X

3-4
5-6

2
X
POSITION POSITION
1-2 3-4 1-2

1-2

3-4 1-2 3-4


1-2
1
X
POSITION
POSITION
1-2
1
X1 3-4 X
0
C POSITION
1-2
3-4
7-8
POSITION
1 POSITION
X0 1-2 3-4
3-4 3-4
POSITION
1-21-25-6
0
2
X
1
X
X X X
1
X211
X
13
F3
15
C1 0
2
X
0
C
0
0
0
2
2
XX X X
2

1
P 45

0
2

2 C
X
POSITION2 1-20

NO. SCHEME
POSITION

1W 14

0
2

14

SEL-DE#01W

1-2
POSITION
1
X 0 3-4 1-25-6
X 3-47-85-6 7-8
0
POSITION
1-2
1
X 12 3-4 X5-6
X X 7-8 XX
0
X
X
F32
POSITION
1-2X 3-4 5-6 7-8
1
X0
0
2
X
X
1
X
X
2
X
X
POSITION
1-2 3-4
X
X
F302

0
2

13

13
F3
POSITION

0
2

F3
F3
F3 13
F3

SWITCH
(POSITION)

0
2

13
13
13

7-8

0
2

2CI 13

5-6

3-4CONTACT
5-6
7-8
X

CONTAC
AND PO

(POSITION)
SWITCH
(POSITION)
(POSITION)

SEL-DE#2C1

3-4

1-2

1 1 1 11
0 0 0 00
2
2 12 2 2

HANDLES DE

POSITION

POSITION
1-2
1
X
NO. SCHEME

SWITCH
(POSITION)
SWITCH
(POSITION) SWITCH

1
0
2

NO. SCHEME
NO. SCHEME
NO.
NO. SCHEME

SWITCH
SWITCH
(POSITION)
(POSITION)
SWITCH

CONTACT
CONTACT
CONTACT
NO. SCHEME
CONTACT
CONTACT
SCHEME
CONTACT
CONTACT
POSITION 1-2 3-4 5-6 7-8

111 1 1 1
0
00
0 0 0
22
12 2 12 2

SCHEME
NO. SCHEME

1 1 111 1
0 0 000 0
22
2 12 2 12

CODE

1
0
2

HANDLES-DE

START
P 45

1-2
3-4

START
P 45

1-2
3-4

GWRCS - ESX grp and stainless steel


ex-de push button stations

Explosion Proof Electrical Equipment

Ex Enclosures

www.feam-ex.com

GWRCS - ESX

Installation:hazardous areas - Zone 1 / 2 (Gases) - Zone 21 / 22 (Dusts)


Classification: Group II Category 2G 2D

Certificate
NEMA Type 4X

REFERENCE STANDARDS

CONTROL STATIONS - GWRCS


Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex d e ia/ib mb IIC T6 or T3 Gb
II 2 D Ex tb IIIC T85C or T100C Db

EXECUTION
RULES OF COMPLIANCE
EC Type-Examination Certificate
PROTECTION DEGREE
AMBIENT TEMPERATURE
OTHER AVAILABLE CERTIFICATES

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-7; EN/IEC 60079-11;


EN/IEC 60079-18; EN/IEC 60079-31
INERIS 13 ATEX 0042
IP66
-50C +55C
Component: INERIS 13ATEX 9009U
IECEx: IECEx INE 13.0058
IECEx (component): IECEx INE 13.0021U
INMETRO: CEPEL 13.2287
INMETRO (component): CEPEL 13.2273U
EAC: TC RU C-IT.08..01499
RINA: ELE18111CS_011
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
NEC 505: UL 20141112-E465037 - Type rating NEMA 1, 12, 4 and 4X

CONTROL STATIONS - ESX


Directive 94/9/EC (until April 19th, 2016) and Directive 2014/34/EU (from April 20th, 2016)
II 2 G Ex e IIB or IIC T6 T3 Gb
II 2 D Ex tb IIIC T85C T200C Db

EXECUTION
RULES OF COMPLIANCE
EC Type-Examination Certificate
PROTECTION DEGREE
AMBIENT TEMPERATURE
OTHER AVAILABLE CERTIFICATES

EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-7; EN/IEC 60079-11;


EN/IEC 60079-18; EN/IEC 60079-31
INERIS 02 ATEX 0067X
IP66
-60C +60C
Component: INERIS 13 ATEX 9028U
IECEx: IECEx INE11.0016
INMETRO: CEPEL 12.2159
EAC: TC RU C-IT.08..01499
RINA: ELE18111CS_011
RUSSIAN MARINE CERTIFICATE (RMRS): 13.03518.315
NEC 505: UL 20141112-E465037 - Type rating NEMA 1, 12, 4 and 4X
Kc (Korean certification): 2014-024207-02

Mechanical characteristics - GWRCS

Mechanical characteristics - ESX

Body
Cover
Screws
Internal plate
Gasket
Strenght

Body
Cover
Screws
Internal plate
Gasket
Strenght

glass fibre reinforced polyester resin color dark grey RAL 7021
glass fibre reinforced polyester resin color dark grey RAL 7021
stainless steel
stainless steel - aluminium
silicon
4 Joule impact resistance

stainless steel AISI 316l sp. 1,5mm


stainless steel AISI 316l sp. 1,5mm
stainless steel AISI 316L
stainless steel AISI 316L
silicon
4 Joule impact resistance

On Request Accessories:
External epoxy painting with colour on request
Internal anticondensate painting orange RAL 2004 (ESX) Valvola di

Drain and breather valves


Removable flanges (only stainless steel enclosures)

Bartec Feam Catalogue 04 I 141

Explosion Proof Electrical Equipment

GWRCS - ESX Typical installation


GWRCS 44

GWRCS 42

120

359.5

120

GWRCS 22

175

0 1

360

175

359.5

175

AU

EME

TOP NO

GWRCS - ESX

120
A

NO
P
TO

NO

AU

E NC Y S

P
TO

E ME

E ME

RG

E ME

E NC Y S

P
TO

AU

RG

NO

RGENCY S

AU

S
RG

E NC Y S

GWRCS 44

GWRCS 22

GWRCS 42

ESX 5242

ESX 2216

242

ESX 3333

520

148.5
148.5

330

165
A

330

220

P
TO

NO

AU

E NC Y S

E ME

420

RG

www.feam-ex.com

Ex Enclosures

GWRCS - ESX examples of application

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this
bulletin can be considered as binding on our confirmation only.

142 I Bartec Feam Catalogue 04

Explosion Proof Electrical Equipment

ES Junction boxes

Waterproof Enclosures

www.feam-ex.com

ES

Installation: Safe Areas


Classification:IP66

REFERENCE STANDARDS
ENCLOSURES
EXECUTION

INDUSTRIAL WEATHERPROOF

RULES OF COMPLIANCE

EN 60529

EC Type-Examination Certificate
PROTECTION DEGREE

IP66

AMBIENT TEMPERATURE

-60C +60C

Mechanical characteristics
Body

marine grade copper free aluminium light alloy

Cover

marine grade copper free aluminium light alloy

Screws

stainless steel

Internal plate

aluminium

Gasket

silicon rubber

On Request Accessories:
External epoxy painting with colour on request
Internal anticondensate painting orange RAL-2004
Drain and breather valves

Bartec Feam Catalogue 04 I 143

Explosion Proof Electrical Equipment

Waterproof Enclosures

CODE

A
[mm]

B
[mm]

C
[mm]

D
[mm]

E
[mm]

F
[mm]

G
[mm]

H
[mm]

I
[mm]

INT.PLATE
X - Y [mm]

WEIGHT
[Kg]

DETAIL

ES1313

130

130

87

115

115

70

112

112

110 - 70

1,20

ES1717

170

170

97

155

155

81

151

151

150 - 150

1,50

ES2216

220

160

96

205

145

80

141

201

200 - 100

3,80

ES2222

220

220

112

205

205

95

201

201

200 - 200

4,40

ES3322

330

220

123

310

200

103

201

311

294 - 154

6,40

ES3333

330

330

131

310

310

111

311

311

290 - 290

8,80

ES4433

440

330

154

420

310

131

311

421

400 - 290

11,40

ES5242

520

420

183

496

394

159

398

499

460 - 370

20,20

ES6348

630

480

181

615

465

156

459

609

550 - 400

21,30

Reference Details

Reference Details

A
C

WALL DRILLING AREA

F
B

GxH

www.feam-ex.com

ES

ES Technical Features

ES Body Enclosures Drilling Layout


QUANTITY ALLOWED ENTRIES FOR
SIZE (from 1 to size 8)

DRILLING AREA
C-D [mm]

QUANTITY ALLOWED ENTRIES FOR


SIZE (from 1 to size 8)

ENCLOSURE CODE

DRILLING AREA
A-B [mm]

ES1313

88 x55

88 x55

ES1717

150 x 70

150 x 70

ES2216

200 x 70

120 x 70

ES2222

200 x 85

200 x 85

ES3322

285 x 90

12

200 x 90

ES3333

275 x 90

12

275 x 90

12

ES4433

370 x 110

20

14

12

12

265 x 110

14

10

ES5242

420 x 145

30

18

16

12

12

360 x 145

28

18

14

11

10

ES6348

500 x 140

36

24

18

16

12

10

400 x 140

30

21

15

12

10

ES Indicative quantity of terminals and relevant section


CODE
ENCLOSURE

SECT. 2,5
[sq/mm]

SECT. 6,0
[sq/mm]

SECT. 10,0
[sq/mm]

SECT. 16,0
[sq/mm]

SECT. 35,0
[sq/mm]

SECT. 50,0
[sq/mm]

SECT. 70,0
[sq/mm]

SECT.240,0
[sq/mm]

NT.PLATE X - Y
[mm]

ES1313

10 x 1

5x1

4x1

4x1

3x1

2x1

1x1

112 - 70

ES1717

20 x 1

10 x 1

8x1

8x1

6x1

3x1

2x1

1x1

150 - 150

ES2216

30 x 1

18 x 1

14 x 1

10 x 1

8x1

3x1

2x1

1x1

200 - 100

ES2222

26 x 1

16 x 1

12 x 1

10 x 1

8x1

4x1

2x1

2x1

200 - 200

ES3322

46 x 1

26 x 1

22 x 1

18 x 1

14 x 1

10 x 1

6x1

2x1

294 - 154

ES3333

46 x 2

24 x 2

22 x 2

16 x 2

14 x 2

10 x 1

8x1

3x1

290 - 290

ES4433

70 x 2

40 x 2

32 x 2

26 x 2

20 x 2

14 x 2

10 x 1

4x1

400 - 290

ES5242

70 x 3

44 x 3

34 x 3

30 x 3

22 x 3

18 x 2

14 x 1

6x1

460 - 370

ES6348

120 x 3

76 x 3

60 x 3

50 x 3

34 x 3

30 x 2

24 x 1

12 x 1

550- 400

REMARK: Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on
this bulletin can be considered as binding on our confirmation only.

144 I Bartec Feam Catalogue 04