C264-R Application
Modular Remote
Terminal Unit
AREVA T&D
FIELD OF APPLICATION
The MiCOM C264-R modular Remote Terminal Unit (RTU) provides a powerful solution for SCADA
communication, Sequence of Event Recorder (SER), and can be integrated to digital substation
control systems. It is designed for a wide range of applications:
Electrical utility
> Transmission and distribution substations
> Power Plant substations
Industry
> Process control, including manufacturing, transit, telecommunications, testing, etc...
> Oil and gas, including pipelines
> Water and wastewater
Tr a n s p o r t a t i o n e l e c t r i c a l s u p e r v i s i o n a n d c o n t ro l
> Railways
> Airport
APPLICATION PROFILE
TECHNICAL DATA
HARDWARE
> Case
MiCOM C264C
WxHxD
Slots
MiCOM C264
GENERAL FUNCTIONS
> Data acquisition and processes for digital, analogue
values inputs and outputs
> Control and monitoring of switching devices
> Configurable indications on local LCD screen,
graphical Mimics and LEDs
> Standardised and proprietary communication
protocols
> Sequence of Events (SOE) print in chronological
order
> Local storage of events, counters and measurement
values
> Download of the configuration thru Ethernet
or from SCADA (IEC101 serial communication)
WxHxD
Slots
> C o n t ro l p a n e l
> Po w e r s u p p ly b o a rd
UN
> P ro c e s s o r b o a rd
80 Mhz
64 Mbytes
Flash
16 Mbytes
Ethernet-Based 10/100Base-FX or
10/100Base-TX
on each rack
Ethernet link to
SCADA (IEC104)
Configuration and
Maintenance Tools
Main
Printer
Extension racks
Legacy serial buses
(IEC103, IEC101,
Modbus, DNP3)
Inputs / Outputs
IEDs, relays, Sub-RTUs
2>3
COMMUNICATIONS
Standard Ethernet SCADA p ro t o c o l s
IEC 60870-5-104 (multi-client), DNP3/IP (option)
Ethernet 10/100Base-FX or 10/100Base-TX
Interfaces
Optical / RS232 / RS422 / RS485
S t a n d a rd I E D s p ro t o c o l s
IEC 60870-5-103, MODBUS,
IEC 60870-5-101, DNP3 (option)
S y n c h ro n i s a t i o n
External synchronisation using IRIG-B
RTU CAPACITY
> Multiple acquisition racks over Ethernet
Continuous current: 5A
short duration current: 250A for 30ms
Breaking capacity:
(double pole contacts wired in serial)
DC: 100W resistive
30W inductive
> A n a l o g u e I n p u t B o a rd (4AI /8AI)
SOE RECORDS
> 1ms time tagging
Chronological order
1 standard serial printer
> 2000 events recorded in non volatile memory
(Flash disk)
> The 200 most recent events readable on optional
LCD screen
STANDARD COMPLIANCE
Superior construction: environment, EMC, isolations in
accordance with IEC Standards.
MiCOM C264:
a compact, powerfull and innovative RTU
for electrical applications
AUTOMATION-L3-C264RTU-BR-05.07-1287b-GB - - AREVA - 2007. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France
www.areva-td.com
www.areva-td.com/substationautomation