Orifice calculation for Bore size - Flange Taps - Gas

Customer: FE
Tag: 1500
Flow Rate
Differential Pressure
Operating Temperature
Operating Pressure
Compressibility Factor:
Operating Density
Pipe Diameter
Bore Diameter (approximate)
Beta (approximate)

87.812,86
98,43
49,00
60,00

Kilograms/Hour
Inches Water
Deg C
kg/cm2 (gauge)

40,770 kg/cubic meter


10,250 Inches
7,072 Inches
0,68996

Warning: Beta value exceeds standard range (0.15 to 0.67).

Note: Values for the beta ratio are approximate, typically within
2% - 5% for gases and steam
1% for liquids
The ASME MFC-3M 1989 equation is used in this program. However,
several equation factors are assumed and can directly affect the
calculation results
Coefficient of Thermal Expansion:
1.0
Discharge Coefficient:
0.6
Base Temperature:
60 Deg F (15.56 Deg C)
Base Pressure:
14.7 PSIA (101.3 kPa-A)
Pressure Tap Location:
Flange Tap
Also, this program does not take into consideration two calculation
variables - the Reynolds Number correction and the expansion factor.
If it is necessary to have a closely specified beta ratio, differential
pressure, or flow rate, please consult your Daniel representative for
assistance