Energy
journal homepage: www.elsevier.com/locate/energy
a r t i c l e i n f o
a b s t r a c t
Article history:
Received 12 July 2013
Received in revised form
27 November 2013
Accepted 30 November 2013
Available online 28 December 2013
The waterelithium bromide absorption cooling machine was investigated theoretically in this paper. A
detailed solution procedure was proposed and validated. A parametric study was conducted over the
entire admissible ranges of the desorber, condenser, absorber and evaporator temperatures. The performance of the machine was evaluated based on the circulation ratio which is a measure of the system
size and cost, the rst law coefcient of performance and the second law exergy efciency. The circulation ratio and the coefcient of performance were seen to improve as the temperature of the heat
source increased, while the second law performance deteriorated. The same qualitative responses were
obtained when the temperature of the refrigerated environment was increased. On the other hand,
simultaneously raising the condenser and absorber temperatures was seen to result in a severe deterioration of both the circulation ratio and rst law coefcient of performance, while the second law
performance indicator improved signicantly. The inuence of the difference between the condenser and
absorber exit temperatures, as well as that of the internal recovery heat exchanger on the different
performance indicators was also calculated and discussed.
2013 Elsevier Ltd. All rights reserved.
Keywords:
Absorption cooling
WatereLiBr
Solution procedure
Circulation ratio
1st law
2nd law
1. Introduction
Heating, refrigeration and air conditioning constitutes one of the
most important items of the modern day energy bill. In addition to
being high energy demanding equipment, vapour compression
refrigeration machines operate based on the conversion of high
quality electrical energy into low quality thermal energy. The
search for more energy efcient technologies in general, and the
research on absorption refrigeration systems in particular are
currently gaining momentum, driven by the ever increasing cost of
fossil fuels and the need for adopting environmentally responsible
practices in society. In absorption refrigeration machines, the
refrigerant vapour exiting the evaporator is absorbed into a lean
solution and the pressurization takes place in the liquid phase, thus
requiring very little electrical energy. The mixture is then heated in
a generator to separate the refrigerant from the absorbent, before
the former is sent to the condenser. Absorption refrigeration machines are therefore essentially powered by heat, which not only
minimizes exergy depredations, but it also allows for the use of free
thermal energy resources such as low-grade industrial heat, solar
* Corresponding author. Tel.: 1 613 541 6000; fax: 1 613 542 8612.
E-mail address: Goni.Boulama@rmc.ca (K. Goni Boulama).
0360-5442/$ e see front matter 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.energy.2013.11.087
Nomenclature
COP
ECOP
f
h
_
m
P
Q_
T
_
W
X
273
Subscripts
abs
absorber
cond
condenser
des
desorber or generator
evap
evaporator
in/out
going into/leaving component
pump
pump
rev
reversible
s
isentropic
sat
saturation conditions
SHEX
solution heat exchanger
waste
waste heat, free heat source
Greek letter
h
efciency [e]
source for the second generator) and two absorbers. Other modications to the cycle have been proposed, including one which uses
an ejector to inject the refrigerant out of the generator into the
condenser [15], and the so-called improved single-effect/doublelift absorption machine for which the desorption process is performed in two generators in a series arrangement, each generator
being associated with a pump, a throttle valve, a solution heat
exchanger and an absorber [16]. The latter conguration consistently resulted in a lower COP and a better utilization of the heat
source than the standard single effect absorption machine
conguration.
Solar energy constitutes a popular application of absorption
refrigeration. Among other authors, Onan et al. [17] studied a solar
energy assisted watereLiBr absorption cooling machine, estimating
the hourly variations of the available free energy, outdoor temperature and cooling load of a typical residence during the entire
cooling season in Turkey, and adopting rst and second law approaches to determine the performances of both the solar collector
and refrigeration machine. Xu et al. [18] studied a solar energy
powered absorption cooling machine equipped with a so-called
advanced energy storage system. Palacin et al. [19] validated a
dynamic simulation code using a commercial 4.5 kW solar energy
powered watereLiBr absorption chiller, and used their code to
design and predict the performance of the chiller with an improved
geothermal heat rejection system. Izquierto et al. [20] proposed an
experimental evaluation of a 7 kW natural gas powered air-cooled
watereLiBr absorption machine with hourly varying condenser and
absorber temperatures, obtaining a mean daily COP of 1.05 and a
volume effectiveness of 6 kW/m3, which outperforms the only then
available similar commercial absorption chiller. The cost of the
proposed non-optimized prototype was evaluated to be 15.9%
higher than that of vapour compression refrigeration machines.
Several studies are also available in the literature where absorption
cooling is part of complex industrial processes. For example, Sun
[21] proposed an experimental study where the waste heat at the
exhaust of a gas turbine was used to power a watereLiBr absorption
chiller, which in turn was used to reduce to load of a mechanical
compression cooling machine. In another study, eight different
arrangements were evaluated for the integration of absorption
cooling in a LNG plant [22]. Absorption cooling has also been used
in combined cooling, heating and power generation applications
(CCHP) [23e25]. Cost and pollutant emissions considerations were
included in Ref. [24], while absorption cooling was coupled to an
organic Rankine cycle (ORC) in Ref. [25]. In both cases, little details
are provided on the absorption cooling process itself.
274
Qdes
Qcond
3
Condenser
Desorber
2p
SHEX
7p
Throttle
valve
Pump
High pressure
Low pressure
Evaporator
Qevap
Wpump
Absorber
Qabs
_
m
in
_
m
(1)
out
X
X
_
_
X m
X m
in
(2)
out
X
X
_
_
_
mh
mh
Q_ W
out
(3)
in
h hT; P; X
(4)
X3 1
(5)
It is also assumed that line pressure losses and pressure variations in all components except for those especially designed for
pressurization (pump) and depressurization (throttle valves) are
negligible, noting that the pressure losses at select portions of the
pipe network were roughly estimated in Refs. [1,12], while the
pressure losses at the absorber were accounted for in Ref. [23]. For
the present study, the following 8 equations apply:
P2 P2p P3 P4 P7 P7p
(6)
P1 P5 P6 P8
(7)
The weak solution at the exit of the absorber, the strong solution at the exit of the desorber and the refrigerant leaving the
condenser and evaporator are assumed to be in saturation conditions. While these are rather common assumptions, they are
not always clearly stated [2,4,11,23,31], and saturated liquid
conditions at the inlet of the evaporator have for example been
assumed in Ref. [9].
State 1:
(8)
State 4:
(9)
State 6:
(10)
State 7:
(11)
275
A large variety of assumptions have been made by different authors for the refrigerant vapour leaving the desorber. This may be due
to the wide range of design possibilities, from a simple boiler to
actively controlled arrangements of vapour generators, distillation
columns, condensers, superheaters, subcoolers, etc. For example, the
temperature of the refrigerant vapour at the exit of the desorber was
arbitrarily prescribed in Ref. [8], T3T4 was used in Ref. [10],
T3T75 C was used in Ref. [15], T3T7 was used in Refs. [11,30], while
this information was not explicit in some other studies [4,13]. In the
present study, a simple design is considered with the weak solution
ashed from the top of desorber where the refrigerant in the vapour
phase leaves the component [2,9,23,32]. In this conguration, the
temperature at State 3 corresponds to the equilibrium temperature of
the weak solution at the desorber pressure [7]:
T3 Tsat P2p ; X2p
(12)
Q_ des
prescribed
(13)
T7
prescribed
(14)
T4
prescribed
(15)
T1
prescribed
(16)
T6
(17)
prescribed
Eqs. (6), (9) and (15) determine the higher pressure of the cycle,
while the lower pressure is determined by Eqs. (7), (10) and (17).
The isentropic efciency of the pump is set to one in this study
[8,23]. Other values were used in Refs. [3,5,13], the compression
was assumed to be isothermal in Ref. [29], but the most popular
assumption is that of negligible pump work [10,11,14e16,30,31]. As
will be discussed later in this paper, the pump efciency has little
effect on the performance of the machine.
hpump
h1 h2s
h1 h2
prescribed
(18)
hSHEX
h7 h7p
h7 h2
prescribed
(19)
276
pressure at the exit of the absorber are known (Eqs. (7) and (16)).
The refrigerant concentration and enthalpy at State 1 are calculated
using Eqs. (4) and (8). Mass and energy conservation, pump isentropic efciency and property correlation (Eqs. (1)e(4), (18)) allow
for the calculation of the enthalpy and temperature of the weak
solution downstream the pump. The pressure and concentration do
not change across the solution heat exchanger (Eqs. (1), (2) and (6)),
and determine the temperature and enthalpy of the refrigerant
vapour leaving the desorber (Eqs. (4) and (12)). The temperature
and pressure of the strong solution leaving the desorber are known
(Eqs. (6) and (14)), and the saturation hypothesis allows for the
determination of the composition and enthalpy (Eqs. (4) and (11)).
The mass ow rate and composition of the strong solution are
unchanged across the solution heat exchanger and throttle valve
(Eqs. (1) and (2)). Knowing the efciency of the solution heat
exchanger (Eq. (19)), heat exchanger exit properties h7p and T7p, as
well as the properties h8 and T8 downstream the throttle valve are
determined (Eqs. (1)e(4)). At this point, the three specic enthalpies (h2, h3 and h7p) and the composition of the working uid
(X2, X3 and X7p) at the boundaries of the desorber and solution heat
exchanger are known, as well as the total thermal energy transfer to
the desorber (Eq. (13)). Eqs. (1)e(3) are then written for the
desorber and solution heat exchanger, resulting in a linear matrix of
Step 1
Eqs. 5,13-15,17
Step 2
Eqs. 1,2
X4, X5, X6
Step 3
Eqs. 4,9,10
Step 4
Eqs. 6,7
Step 5
Eqs. 1-4
h5, T5
Step 6
Eqs. 4,8,16
T1, X1, h1
Step 7
Eqs. 1-4,12,18
Step 8
Eqs. 1,2,4,11
Step 9
Eqs. 1-4,19
Step 10
Eqs. 1-3
Step 11
Eqs. 1-4
h2p, T2p
Step 12
Eq. 3
three equations, from which m2, m3 and m7p are calculated. The
total mass ow rates at all remaining states could then be derived
(Eq. (1)). The conditions of the weak solution at the exit of the
solution heat exchanger are then determined using mass and energy conservation equations and property correlation (Eqs. (1)e
(4)). Finally, the energy conservation is used again to calculate the
heat transfer rates at the condenser, evaporator and absorber, and
the power required to drive the pump. The analysis is completed
with the calculation of the COP of the machine, dened as the ratio
between the desired output, i.e. the cooling effect generated, and
the necessary input for the operation of the machine:
COP
Q_ des
Q_ evap
_ pump
W
(20)
It is noted that when waste heat (i.e. free energy) is used for the
desorption process, the COP can be dened by eliminating Q_ des
from the denominator [35]:
COPwaste
Q_ evap
_ pump
W
(21)
_
W
elec
COPrev
Q_
des
!
Carnot
Q_ evap
_
W
elec
rev
T7 T4
T7
T6
T4 T6
(22)
The ratio between the rst law (Eq. (20)) and ideal (Eq. (22))
coefcients of performance denes the exergy or second law efciency of the cycle [2,4,13]:
ECOP
COP
COPrev
(23)
_
_ pump Q_
Q_ des Q_ evap W
cond Q abs 0
(24)
4.1. Validation
The programming of the property correlations for the watere
LiBr solution and pure water vapour has been veried using the
validation cases provided in Refs. [33,34]. The maximum deviation
in the enthalpy values is less than 1% in all cases. The validation of
the cycle solution procedure has been performed using data taken
from the theoretical and experimental study by Florides et al. [8],
and is summarized in Table 1.
5. Performance evaluation
The solution procedure described in Section 4 is applied to
calculate the cooling generation capability of the watereLiBr absorption refrigeration cycle of Fig. 1. The default values of the independent input variables are listed in Table 2; the number of
degrees of freedom of the cycle is consistent with what was found
in previous work [1].
The heat source conditions in Table 2 can correspond to the heat
rejected to the atmosphere by a variety of industrial processes. In
fact, these values are consistent with measurements performed by
the present authors on a 50 kW CAT3126 diesel generator operated
277
Table 1
Validation.
Input parameters
T1 34.9 C
P4 9.66 kPa
Q_ des 14:2 kW
T3 85 C
T6 6 C
hSHEX 0.522
Results: [8]
Q_ evap 10:0 kW
Q_ cond 10:78 kW
Q_ abs 13:51 kW
_ pump 0:29 W
W
COP 0.704
T4 44.3 C
T7 90 C
at 1000 rpm. The selected default values for the condensation and
absorber exit temperatures are also consistent with typical ambient
temperatures. The selected evaporation temperature could be
correlated to a cooled medium at around 10 C. Using the values in
Table 2, the refrigeration cycle is calculated to generate the thermodynamic properties summarized in Table 3.
Table 3 allows for the verication of one of the main features of
the watereLiBr refrigeration machine operation: the machine
operates entirely under vacuum, which implies inltration prevention measures. It is also observed that the temperature of the
refrigerant as it exits the desorber (State 3) assumes a value that is
lower than that of the strong solution returned to the absorber
(State 7) and greater than that of the weak solution introduced into
the desorber (State 2p). Also note that the temperature at State 2p is
essentially the same as that upstream the pump, which is also
expected because of the isentropic pressurization assumption (Eq.
(18), Table 2). Using the data in Table 3, the energy transfer rates at
each of the components of the machine are calculated and summarized in Table 4.
The amount of thermal energy rejected to the environment
(condenser and absorber) is considerable, and may be of interest if
heating is a desired output [22e25]. In the present case, cooling is
the desired effect, and this analysis shows that up to 14.87 kW
cooling effect could be generated by the machine, corresponding to
a COP of 0.743. This value is signicantly lower than the COP of
conventional vapour compression refrigeration machines, which
was expected. It is also signicantly lower than the ideal COPrev
value of 2.09 (Eq. (22)), which suggests a signicant potential for
cycle design improvement.
The pump power consumption is calculated to be 0.05 W, which
is well within the margin of error in this study, and conrms that
the machine essentially operates out of the external heat source.
For the same reasons, using Eq. (21) to calculate the COP is
valueless.
In the following, the sensitivity of the performance of the absorption machine to variations of the selected input parameters is
discussed.
20 kW
100 C
30 C
30 C
5 C
100%
0%
278
Table 3
Solution of the watereLiBr base case refrigeration cycle.
16
Temperature
[ C]
Pressure
[kPa]
Refrigerant
mass fraction
[e]
Enthalpy
[kJ/kg]
Mass ow
rate [g/s]
1
2
2p
3
4
5
6
7
7p
8
30.0
30.0
30.0
58.4
30.0
5.00
5.00
100.0
100.0
e
0.873
4.247
4.247
4.247
4.247
0.873
0.873
4.247
4.247
0.873
0.47
0.47
0.47
1.00
1.00
1.00
1.00
0.29
0.29
0.29
66.605
66.607
66.607
2610.4
125.85
125.85
2510.3
301.26
301.26
301.26
23.87
23.87
23.87
6.236
6.236
6.236
6.236
17.63
17.63
17.63
12
Qevap [kW]
States
60
80
100
120
o
Fig. 3 shows that the cooling generation capability initially increases very sharply, and then plateaus when the temperature of
the strong saturated solution leaving the desorber increases, with
all other operating parameters remaining constant (Table 2). The
lower end of the admissible T7 variation interval is determined by
the fact that the separation of the refrigerant in the desorber becomes increasingly difcult at low desorber temperatures. On the
other hand, the saturation condition (Eq. (11)) means that as T7
increases, the concentration of lithium bromide in the strong solution exiting the desorber increases, which increases the crystallization risks at the absorber. This phenomenon is well illustrated
on the Duhring chart of the watereLiBr cycle in Refs. [7e9,26,27].
No cooling generation capability is predicted outside the aforementioned admissible temperature variation range. The results in
Fig. 3 are consistent with other published results [10,11,13e16,29].
While in the presence of very high temperature heat sources, Hong
et al. [14,15] suggested maintaining the strong solution desorber
exit temperature at 110 C in order to prevent crystallization, Fig. 3
demonstrates that as moderate as 90 C heat source temperatures
are perfectly suitable for an efcient operation of a watereLiBr
absorption cooling machine.
Fig. 4 shows the effect of the desorber exit temperature on the
heat rejection at the condenser and absorber of the watereLiBr
absorption machine. The heat rejection at the absorber slightly
decreases and then remains constant. Over the entire T7 variation
range, Q_ abs varied by less than 3%, which implies that the absorber
cooling demand is essentially determined by the conditions of the
incoming refrigerant vapour and those prescribed of the weak solution leaving the component. The heat rejection at the condenser
Table 4
Energy transfer rates for the watereLiBr base case refrigeration cycle.
Desorber
Q_ des
20.00 kW
Condenser
Evaporator
Absorber
Pump
Cycle COP
Q_ cond
Q_ evap
Q_ abs
_ pump
W
15.50
14.87
19.38
0.000
0.743
kW
kW
kW
kW
36
30
24
18
12
Qcond
Qabs
Qcond + Qabs
60
80
100
120
o
0.0008
279
0.35
0.3
m1 (Weak solution)
0.0006
m7 (Strong solution)
m3 (Pure refrigerant)
Wpump [kW]
0.25
0.0004
0.0002
0.2
0.15
0.1
0.05
0
60
80
100
120
o
0
60
100
120
2.5
140
120
COP
COPrev
80
Fig. 5. Effect of the desorber temperature on the power required to drive the pump.
1.5
100
80
60
40
0.5
20
60
80
100
120
o
60
80
100
120
o
_1
m
_3
m
(25)
10
280
COP
COPrev
6
10
15
20
25
30
0.8
20
X1 and X7 [-]
0.6
0.4
0.2
T7 = 70oC
T7 = 85oC
T7 = 100oC
15
10
60
80
100
120
o
10
20
30
o
281
20
COP
COPrev
T1 = T4 + 10oC
T1 = T4
15
T1 = T4 - 10 C
10
0
15
20
25
30
35
40
45
50
20
25
30
35
40
45
50
Fig. 12. Effect of the condensation temperature on the COP (T1 T4).
Fig. 14. Effect of the condenser and absorber temperature difference on the circulation
ratio.
0.8
0.6
COP [-]
0.4
T1 = T4 + 10oC
T1 = T4
o
T1 = T4 - 10 C
0.2
0
15
0
15
20
25
30
35
40
45
50
terms of Eq. (22) decrease with increasing T4, which explains the
parabolic decline of the reversible COP. Over most of the considered
condenser temperature range, the COPrev variation is much more
pronounced than that of COP, suggesting a rapid improvement in
the second law efciency of the machine with increasing condensation temperature. T4 45 C seems to correspond to a maximum
value for ECOP. Because the heat input to the machine is maintained
constant, the cooling generation capability varies in a similar
fashion as the COP. Not shown in Fig. 12 is that the heat rejection at
the condenser also gradually decreases by approximately the same
percentage as Q_ evap , while the variation of the heat rejection at the
absorber with the condenser and absorber temperatures is slim.
Finally, the pumping power requirement signicantly increases
with T1 and T4, and remains always several orders of magnitude
smaller than the heat transfer rates at the desorber, condenser,
absorber and evaporator.
Fig. 13 shows that the COP of the machine markedly decreases
when the temperature of the weak saturated solution exiting the
absorber is higher than that of the saturated refrigerant leaving the
condenser, and increases when the condensation temperature is
higher than the absorption temperature. This result is consistent
with the experimental observations by Eisa et al. [9] and the numerical predictions by Sun [32], noting that these are the only two
of the reviewed references to have studied the inuence of the
difference T1 T4 on the performance of the absorption cooling
machine. In fact, the majority of the reviewed articles adopted
T1 T4 [3,5,11,13e16,23,30,31], while T1 < T4 was adopted in
Refs. [8,10,12,20,29] and T1 > T4 was adopted in Refs. [1,4,17], often
without any justication.
The effect of the difference between the condenser and absorber
temperatures on the circulation ratio is illustrated in Fig. 14. As the
condensation temperature increases, both the weak and strong
solution ow rates increase, while the refrigerant mass ow rate
decreases. As a consequence, the circulation ratio drastically increases with the condensation temperature. The calculated results
also indicate that the circulation ratio is reduced by an average of
36% when the absorber exit temperature is 10 C lower than the
condenser exit temperature compared to the case where the two
temperatures are equal. On the other hand, the circulation ratio also
1
0.8
0.8
0.6
COP [-]
282
T6 = 5oC
o
T6 = 10 C
o
T6 = 15 C
0.4
0.2
0.2
0.4
0.6
0.8
increases by approximately 52% when the weak watereLiBr solution leaves the absorber 10 C warmer than the temperature at
which the refrigerant leaves the condenser. The results in Fig. 14 are
consistent with those in Fig. 13, and further justify the operation of
the absorption machine at the smallest possible T1 T4 temperature difference.
The variation of the working uid composition throughout the
different components of the cycle with increasing condensation
temperatures is illustrated in Fig. 15. The driving temperature is
maintained at T7 100 C for all simulations, thus the refrigerant
mass fraction in the saturated strong solution at the exit of the
desorber is solely determined by the condensation temperature (or
pressure). This explains why only one X7 curve is given in Fig. 15,
and X7 is observed to gradually increase as T4 increases. On the
other hand, the concentration of the refrigerant in the weak solution at the exit of the absorber is observed to decrease as T4 increases. However, contrarily to X7, X1 is affected by the absorber
temperature, and the refrigerant content in the solution passing
through the pump becomes larger as the difference T1 T4 decreases. When X1 and X7 curves intersect, no refrigerant is separated in the desorber, and no cooling is generated at the evaporator.
Fig. 15 indicates that this intersection occurs at lower condenser
temperatures when T1 > T4, and it is delayed when T1 < T4.
0.6
0.4
0.2
0
15
20
25
30
35
40
45
50
Canadas Academic
acknowledged.
283
Research
Program
(ARP)
is
gratefully
References
[1] Bulgan AT. Optimization of the thermodynamic model of aqua-ammonia absorption refrigeration systems. Energy Convers Manag 1995;36(2):135e43.
[2] Ben Ezzine N, Barhoumi M, Mejbri Kh, Chemkhi S, Bellagi A. Solar cooling with
the absorption principle: rst and second law analysis of an ammonia-water
double-generator absorption chiller. Desalination 2004;168:137e44.
[3] Adewusi SA, Zubair SM. Second law based thermodynamic analysis of
ammonia-water absorption systems. Energy Convers Manag 2004;45(15e16):
2355e69.
[4] Sozen A, Ozalp M. Performance improvement of absorption refrigeration
system using triple-pressure-level. Appl Therm Eng 2003;23(13):1577e
93.
[5] Hong D, Tang L, He Y, Chen G. A novel absorption refrigeration cycle. Appl
Therm Eng 2010;30(14e15):2045e50.
[6] Srikhirin P, Aphornratana S, Chungpaibulpatana S. A review of absorption
refrigeration technologies. Renew Sustain Energy Rev 2001;5(4):343e72.
[7] ASHRAE. Handbook of fundamentals. Atlanta: ASHRAE; 2009.
[8] Florides GA, Kalogirou SA, Tassou SA, Wrobel LC. Design and construction of a
LiBr-water absorption machine. Energy Convers Manag 2003;44(15):2483e
508.
[9] Eisa MAR, Diggory PJ, Holland FA. Experimental studies to determine the effect of difference in absorber and condenser temperatures on the performance
of a water-lithium bromide absorption cooler. Energy Convers Manag
1987;27(2):253e9.
[10] Joudi KA, Lafta AH. Simulation of a simple absorption refrigeration system.
Energy Convers Manag 2001;42(13):1575e605.
[11] Sencan A, Yakut KA, Kalogirou SA. Exergy analysis of lithium bromide/water
absorption systems. Renew Energy 2005;30(5):645e57.
[12] Morosuk T, Tsatsaronis G. A new approach to the exergy analysis of absorption refrigeration machines. Energy 2008;33(6):890e907.
[13] Gomri R. Second law comparison of single effect and double effect vapour
absorption refrigeration systems. Energy Convers Manag 2009;50(5):1279e
87.
[14] Hong DL, Chen GM, Tang LM, He YJ. Simulation research on an EAX (evaporator-absorber-exchange) absorption refrigeration cycle. Energy 2011;36(1):
94e8.
[15] Hong D, Chen G, Tang L, He Y. A novel ejector-absorption combined refrigeration cycle. Int J Refrig 2011;34(7):1596e603.
[16] Yan X, Chen G, Hong D, Lin S, Tang L. A novel absorption refrigeration cycle for
heat sources with large temperature change. Appl Therm Eng 2013;52(1):
179e86.
[17] Onan C, Ozkan DB, Erdem S. Exergy analysis of a solar assisted absorption
cooling system on an hourly basis in villa applications. Energy 2010;35(12):
5277e85.
[18] Xu SM, Huang XD, Du R. An investigation of the solar powered absorption
refrigeration system with advanced energy storage technology. Solar Energy
2011;85(9):1794e804.
[19] Palacin F, Monne C, Alonso S. Improvement of an existing solar powered
absorption cooling system by means of dynamic simulation and experimental
diagnosis. Energy 2011;36(7):4109e18.
[20] Izquierto M, Marcos JD, Palacios ME, Gonzalez-Gil A. Experimental evaluation
of a low-power direct air-cooled double effect water/LiBr absorption prototype. Energy 2012;37(1):737e48.
[21] Sun ZG. Experimental investigation of integrated refrigeration system (IRS)
with gas turbine, compression chiller and absorption chiller. Energy
2008;33(3):431e6.
[22] Mortazavi A, Somers C, Alabdulkarem A, Hwang Y, Radermacher R.
Enhancement of APCI cycle efciency with absorption chillers. Energy
2010;35(9):3877e82.
[23] Colonna P, Gabrielli S. Industrial trigeneration using ammonia-water absorption refrigeration systems (AAR). Appl Therm Eng 2003;23(4):381e96.
[24] Ebrahimi M, Keshavarz A. Sizing the prime mover of a residential microcombined cooling heating and power (CHP) system by multi-criteria sizing
method for different climates. Energy 2013;54(1):291e301.
[25] Fang F, Wei L, Liu J, Zhang J, Hou G. Complementary conguration and
operation of a CCHP-ORC system. Energy 2012;46(1):211e20.
[26] Wang X, Chua H. Absorption cooling: a review of lithium bromide-water
chiller technologies. Recent Patents Mech Eng 2009;2(3):193e213.
[27] Wang K, Abdelaziz O, Kisari P, Vineyard EA. State-of-the-art review on crystallization control technologies for water/LiBr absorption heat pumps. Int J
Refrig 2011;34(6):1325e37.
[28] Macriss RA, Gutraj JM, Zawacki TS. Absorption uid data survey: nal report
on worldwide data. ORLN/sb/8447989/3. Institute of Vapour Technology;
1988.
[29] Dincer I, Edin M, Ture IE. Investigation of thermal performance of a solar
powered absorption refrigeration system. Energy Convers Manag 1996;37(1):
51e8.
284
[30] He LJ, Tang LM, Chen GM. Performance prediction of refrigerant-DMF solutions in a single-stage solar-powered absorption refrigeration system at low
generating temperatures. Solar Energy 2009;83(11):2029e38.
[31] Chekir N, Bellagi A. Performance improvement of a butane/octane absorption
chiller. Energy 2011;36(10):6278e84.
[32] Sun DW. Thermodynamic design data and optimum design maps for absorption refrigeration systems. Appl Therm Eng 1997;17(3):211e21.
[33] Patek J, Klomfar J. A computationally effective formulation of the thermodynamic properties of LiBr-H2O solutions from 273 to 500 K over a full
composition range. Int J Refrig 2006;29(4):566e78.