Cast Resin Transformers

eco
design

Trihal - up to 3 150 kVA


Standard fittings

Trihal without enclosure (IP00):


HV voltage variation by off circuit tapping links
4 bi-directional flat rollers
4 lifting holes
4 haulage holes on the underbase
2 earthing points
1 rating plate (on HV side)

Description
Cast resin, 50 Hz , three-phased distribution
transformers with the following characteristics:
Indoor use / Outdoor use with properly
designed enclosure
Thermal class F - Temperature rise 100 K
Ambient 40 C, altitude 1000 m
MV windings encapsulated in cast resin
Pre-impregnated LV windings
Natural air cooling system (AN type)
Core and frame covered with protective coating

Trihal with IP31 metal enclosure (except


underframe IP21):
- 2 lifting lugs for transformer and enclosure
assembly
- 1 earthing point on enclosure
- access to HV tapping by removing a bolted
panel
- enclosure final colour RAL9002

Ecodesign regulation EU 548-2014



Standard
These transformers comply with standards:
IEC 60076-11, PS EN 50588
Ecodesign Directive EU 548-2014
Schneider Electric guarantees that its transformers
are:
C3* Climatic class
E3 Environment class according to
IEC 60076-16
F1 Fire behaviour class
Almost partial discharge free - Acceptance level:
- 10 pC Routine Test
- 5 pC Special Test according to IEC 60076
standard
* C2 Thermal shock test carried out at -50C

Maximal Loss levels


Statement on Loss tolerences:
- No tolerance on transformer design
- 5% tolerance for end user checks
Additional data requested on the name plates
- Loss level and measured values
- Type and weight of mail materials used
- CE Marking is MANDATORY

Dry Type Transformers maximum loss


levels according to Ecodesign:

Insulation voltage MV 24 kV & LV 1.1 kV


- A0Bk up to 630 kVA
- A0Ak over 630 kVA
Insulation voltage: MV 36 kV & LV 1.1 kV
- A0 +15% Bk +10% 630 kVA
- A0 +15% Ak +10% > 630 kVA
0

Ak
Bk
Ck

Cast Resin Transformers

02

Trihal - 7.2 kV and 12 kV A0Ak

Electrical characteristics
Rated power (kVA)

250

315

400

500

630

800

1000

1250

1600

2000

2500

Rated frequency (Hz)

50

50

50

50

50

50

50

50

50

50

50

50

10000

10000

10000

10000

10000

10000

10000

10000

10000

10000

10000

10000

Primary voltage (V)

3150

Isolation level (kV)

12

12

12

12

12

12

12

12

12

12

12

12

Secondary voltage at no-load (V)

400

400

400

400

400

400

400

400

400

400

400

400

Tappings (%)

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

Vector groups

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Losses (W) - no-load losses

520

620

750

900

1100

1300

1550

1800

2200

2600

3100

3800

Losses (W) - load losses at 120C

3400

3900

4500

5630

7100

8000

9000

11000

13000

16000

19000

22000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

Rated impedance voltage (%)


Max altitude (m)
Max ambiental temperature (C)
Nature of HV/LV windings

40

40

40

40

40

40

40

40

40

40

40

40

AI/AI

AI/AI

AI/AI

AI/AI

AI/AI

AI/AI

AI/AI

AI/AI

AI/AI

AI/AI

AI/AI

AI/AI
E/2

Dimensions and weights without


enclosure housing (IP00)
Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually.
For other voltages, impedance voltages and
dual-voltages, weights and dimensions are
different (consult us).

13
tapping
links

C
M

H
B

earthing
terminal
40 (50)

125 (160)

D
E

Trihal IP00

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA)

250

315

400

500

630

800

1000

1250

1600

- Lenght A

1290

1350

1370

1420

1500

1530

1620

1700

1830

1880

2050

2330

- Width B

680

800

800

800

800

800

950

950

950

1230

1230

1270

- Height C

1340

1430

1510

1550

1570

1720

1880

1940

2140

2220

2250

2680

- Roller pitch D

520

670

670

670

670

670

820

820

820

1070

1070

1070

Dimensions (mm)

2000

2500

3150

- Frame width E

645

795

795

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

125

160

160

200

- Roller width G

40

40

40

40

40

40

40

40

40

50

50

70

1180

1400

1600

1780

2080

2400

3020

3600

4180

5160

6240

10060

Weight without enclosure (kg)

Dimensions and weights with IP31 metal


enclosure

Dimensions and weights are for guidance only,


and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13

tapping
links

earthing
terminal

40 (50)
D
B

125 (160)

2015 Schneider Electric. All rights reserved.

Trihal IP31

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA)

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

- Lenght A

1650

1700

1800

1800

1800

1900

2150

2150

2130

2180

2350

2630

- Width B

950

1020

1020

1020

1020

1100

1170

1170

980

1230

1230

1270

- Height C

1750

1900

2050

2050

2050

2480

2480

2480

2440

2620

2650

3080

- Roller pitch D

520

670

670

670

670

670

820

820

820

1070

1070

1070

- Frame width E

645

795

795

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

125

160

160

200

- Roller width G

40

40

40

40

40

40

40

40

40

50

50

70

1340

1580

1790

1870

2270

2620

3320

3900

4470

5470

6565

10470

Dimensions (mm)

Weight without enclosure (kg)

NRJED315631EN

02 2015

Cast Resin Transformers

03

Trihal - 7.2 kV and 12 kV A0Bk

Electrical characteristics
Rated power (kVA)

250

315

400

500

Rated frequency (Hz)

50

50

50

50

50

10000

10000

10000

10000

10000

Primary voltage (V)

630

Isolation level (kV)

12

12

12

12

12

Secondary voltage at no-load (V)

400

400

400

400

400
+/- 5

Tappings (%)

+/- 5

+/- 5

+/- 5

+/- 5

Vector groups

Dyn

Dyn

Dyn

Dyn

Dyn

Losses (W) - no-load losses

520

623

750

900

1100

Losses (W) - load losses at 120C

3800

4550

5500

6425

7600

1000

1000

1000

1000

1000

Rated impedance voltage (%)


Max altitude (m)
Max ambiental temperature (C)
Nature of HV/LV windings

40

40

40

40

40

AI/AI

AI/AI

AI/AI

AI/AI

AI/AI

E/2
J

Dimensions and weights without


enclosure housing (IP00)
Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13
tapping
links

C
M

H
B

earthing
terminal
40 (50)

125 (160)

D
E

Trihal IP00

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA)
Dimensions (mm)

- Lenght A

250

315

400

500

630

1270

1290

1320

1370

1410

- Width B

680

800

800

800

800

- Height C

1340

1410

1510

1530

1660

- Roller pitch D

520

670

670

670

670

- Frame width E

645

795

795

795

795

- Roller diam. F

125

125

125

125

125

- Roller width G

40

40

40

40

40

1140

1260

1460

1640

1880

Weight without enclosure (kg)

Dimensions and weights with IP31 metal


enclosure

Dimensions and weights are for guidance only,


and are provided for a single-voltage
transformer with the following HV insulation levels and low voltages. Only the definitive drawings
following from the order will commit us contractually. For other voltages, impedance voltages
and dual-voltages, weights and dimensions are
different (consult us).

13

tapping
links

earthing
terminal
125 (160)

D
A

40 (50)
D
B

2015 Schneider Electric. All rights reserved.

Trihal IP31

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA)

250

315

400

500

630

- Lenght A

1650

1700

1800

1370

1900

- Width B

950

1020

1020

800

1100

- Height C

1750

1900

2050

1530

2300

- Roller pitch D

520

670

670

670

670

- Frame width E

645

795

795

795

795

- Roller diam. F

125

125

125

125

125

- Roller width G

40

40

40

40

40

1300

1440

1650

1830

2100

Dimensions (mm)

Weight without enclosure (kg)

NRJED315631EN

02 2015

Cast Resin Transformers

04

Trihal - 17.5 kV and 24 kV A0Ak

Electrical characteristics for insulation level


Rated power (kVA)

250

315

400

500

630

800

1000

1250

1600

2000

2500

Rated frequency (Hz)

50

50

50

50

50

50

50

50

50

50

50

50

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

Primary voltage (V)

3150

Isolation level (kV)

24

24

24

24

24

24

24

24

24

24

24

24

Secondary voltage at no-load (V)

400

400

400

400

400

400

400

400

400

400

400

400

Tappings (%)

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

Vector groups

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Losses (W) - no-load losses

520

620

750

900

1100

1300

1550

1800

2200

2600

3100

3800

Losses (W) - load losses at 120C

3400

3900

4500

5630

7100

8000

9000

11000

13000

16000

19000

22000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

40

40

40

40

40

40

40

40

40

40

40

40

Rated impedance voltage (%)


Max altitude (m)
Max ambiental temperature (C)

E/2
J

Dimensions and weights without


enclosure housing (IP00)
Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13
tapping
links

C
M

H
B

earthing
terminal
40 (50)

125 (160)

D
E

Trihal IP00

Insulation level: 17.5 kV and 24 kV- low voltage 400 V to 433 V


Rated power (kVA)
Dimensions (mm)

- Lenght A

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

1320

1365

1410

1460

1480

1630

1660

1740

1850

1960

2050

2320

- Width B

730

810

820

830

830

850

950

950

970

1230

1230

1270

- Height C

1430

1520

1600

1640

1770

1810

1970

2140

2180

2280

2500

2660

- Roller pitch D

520

670

670

670

670

670

820

820

820

1070

1070

1070

- Frame width E

645

795

795

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

125

160

160

200

- Roller width G
Weight without enclosure (kg)

40

40

40

40

40

40

40

40

40

50

50

70

1180

1400

1600

1780

2000

2840

2840

3460

4180

5120

6160

8520

Dimensions and weights with IP31 metal


enclosure

Dimensions and weights are for guidance only,


and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13

tapping
links

earthing
terminal

40 (50)
D
B

125 (160)

2015 Schneider Electric. All rights reserved.

Trihal IP31

Insulation level: 17.5 kV and 24 kV- low voltage 400 V to 433 V


Rated power (kVA)
Dimensions (mm)

- Lenght A

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

1720

1800

1900

1900

1900

1900

2150

2140

2250

2360

2450

2720

- Width B

990

1020

1100

1100

1100

1100

1170

1130

1170

1230

1230

1270

- Height C

1730

2050

2300

2300

2300

2300

2480

2440

2480

2680

2900

3060

- Roller pitch D

520

670

670

670

670

670

820

820

820

1070

1070

1070

- Frame width E

645

795

795

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

125

160

160

200

- Roller width G

40

40

40

40

40

40

40

40

40

50

50

70

1360

1590

1820

2000

2220

3060

3140

3810

4530

5495

6560

8970

Weight without enclosure (kg)

NRJED315631EN

02 2015

Cast Resin Transformers

05

Trihal - 17.5 kV and 24 kV A0Bk

Electrical characteristics for insulation level


Rated power (kVA)

250

315

400

500

Rated frequency (Hz)

50

50

50

50

50

20000

20000

20000

20000

20000

Primary voltage (V)

630

Isolation level (kV)

24

24

24

24

24

Secondary voltage at no-load (V)

400

400

400

400

400
+/- 5

Tappings (%)

+/- 5

+/- 5

+/- 5

+/- 5

Vector groups

Dyn

Dyn

Dyn

Dyn

Dyn

Losses (W) - no-load losses

520

620

750

900

1100

Losses (W) - load losses at 120C

3800

4550

5500

6425

7600

1000

1000

1000

1000

1000

40

40

40

40

40

Rated impedance voltage (%)


Max altitude (m)
Max ambiental temperature (C)

E/2

Dimensions and weights without


enclosure housing (IP00)

Dimensions and weights are for guidance only,


and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13
tapping
links

C
M

H
B

earthing
terminal
40 (50)

125 (160)

D
E

Trihal IP00

Insulation level: 17.5 kV and 24 kV- low voltage 400 V to 433 V


Rated power (kVA)
Dimensions (mm)

- Lenght A

250

315

400

500

630

1300

1330

1360

1430

1480

- Width B

730

810

810

820

830

- Height C

1430

1520

1600

1640

1790

- Roller pitch D

520

670

670

670

670

- Frame width E

645

795

795

795

795

- Roller diam. F

125

125

125

125

125

- Roller width G

40

40

40

40

40

1140

1360

1520

1720

2040

Weight without enclosure (kg)

Dimensions and weights with IP31 metal


enclosure

Dimensions and weights are for guidance only,


and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13

tapping
links

earthing
terminal
125 (160)

D
A

40 (50)
D
B

2015 Schneider Electric. All rights reserved.

Trihal IP31

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA)
Dimensions (mm)

250

315

400

500

630

1650

1700

1800

1370

1900

- Width B

950

1020

1020

800

1100

- Height C

1750

1900

2050

1530

2300

- Lenght A

- Roller pitch D

520

670

670

670

670

- Frame width E

645

795

795

795

795

- Roller diam. F

125

125

125

125

125

- Roller width G

40

40

40

40

40

1300

1440

1650

1830

2100

Weight without enclosure (kg)

NRJED315631EN

02 2015

Cast Resin Transformers

06

Trihal - 36 kV A0Ak

Electrical characteristics for insulation level: up to 36 kVA


Rated power (kVA)

250

315

400

500

630

800

1000

1250

1600

2000

2500

Rated frequency (Hz)

50

50

50

50

50

50

50

50

50

50

50

50

30000

30000

30000

30000

30000

30000

30000

30000

30000

30000

30000

30000

Primary voltage (V)

3150

Isolation level (kV)

36

36

36

36

36

36

36

36

36

36

36

36

Secondary voltage at no-load (V)

400

400

400

400

400

400

400

400

400

400

400

400

Tappings (%)

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

Vector groups

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Dyn

Losses (W) - no-load losses

598

712

862

1037

1265

1495

1782

2070

2530

2990

3565

4370

Losses (W) - load losses at 120C

3740

4264

4950

6193

7810

8800

9900

12100

14300

17600

20900

24200

Rated impedance voltage (%)

6.5

6.5

6.5

6.5

6.5

6.5

6.5

6.5

6.5

6.5

6.5

6.5

Max ambiental temperature (C)

40

40

40

40

40

40

40

40

40

40

40

40
E/2

Dimensions and weights without


enclosure housing (IP00)
Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13
tapping
links

C
M

H
B

earthing
terminal
40 (50)

125 (160)

D
E

Trihal IP00

Insulation level: up to 36 kV - low voltage 400 V to 433 V


Rated power (kVA)
Dimensions (mm)

250

315

400

500

630

800

1000

1250

1600

2000

2500

- Lenght A

1490

1490

1530

1530

1580

1740

1810

1870

1950

2280

2500

3150
2840

- Width B

800

870

880

880

890

920

1000

1010

1030

1230

1260

1340

- Height C

1790

1790

1950

1950

1990

2160

2230

2420

2460

2630

2710

2750

- Roller pitch D

520

670

670

670

670

670

820

820

820

1070

1070

1070

- Frame width E

645

795

795

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

125

160

160

200

- Roller width G

40

40

40

40

40

40

40

40

40

50

50

70

1660

1660

1960

2000

2240

2960

3420

3980

4700

7220

9260

13180

Weight without enclosure (kg)

Dimensions and weights with IP31


metal enclosure

Dimensions and weights are for guidance only,


and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13

tapping
links

earthing
terminal

40 (50)
D
B

125 (160)

2015 Schneider Electric. All rights reserved.

Trihal IP31

Insulation level: up to 36 kV - low voltage 400 V to 433 V


Rated power (kVA)

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

- Lenght A

1990

1990

2030

2030

2080

2240

2310

2370

2450

2780

3000

3340

- Width B

1220

1220

1230

1240

1250

1310

1330

1350

1380

1490

1560

1670

- Height C

2090

2090

2250

2250

2290

2460

2530

2720

2760

3030

3110

3150

- Roller pitch D

520

670

670

670

670

670

820

820

820

1070

1070

1070

- Frame width E

645

795

795

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

125

160

160

200

- Roller width G

40

40

40

40

40

40

40

40

40

50

50

70

1890

1895

2200

2245

2500

3260

3740

4320

5060

7650

9760

13760

Dimensions (mm)

Weight without enclosure (kg)

NRJED315631EN

02 2015

Cast Resin Transformers

07

Trihal - 36 kV A0Bk

Electrical characteristics for insulation level


Rated power (kVA)

250

315

400

500

630

Rated frequency (Hz)

50

50

50

50

50

Primary voltage (V)

30000

30000

30000

30000

30000

Isolation level (kV)

36

36

36

36

36

Secondary voltage at no-load (V)

400

400

400

400

400

Tappings (%)

+/- 5

+/- 5

+/- 5

+/- 5

+/- 5

Vector groups

Dyn

Dyn

Dyn

Dyn

Dyn

Losses (W) - no-load losses

598

712

862

1037

1265

Losses (W) - load losses at 120C

4180

4990

6050

7054

8360

Rated impedance voltage (%)

6.5

6.5

6.5

6.5

6.5

Max ambiental temperature (C)

40

40

40

40

40
E/2
J

Dimensions and weights without


enclosure housing (IP00)
Dimensions and weights are for guidance only,
and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13
tapping
links

C
M

H
B

earthing
terminal
40 (50)

125 (160)

D
E

Trihal IP00

Insulation level: up to 36 kV low voltage 400 V to 433 V


Rated power (kVA)
Dimensions (mm)

- Lenght A

250

315

400

500

630

1490

1470

1470

1500

1570

- Width B

800

870

870

880

890

- Height C

1790

1790

1810

1950

1990

- Roller pitch D

520

670

670

670

670

- Frame width E

645

795

795

795

795

- Roller diam. F

125

125

125

125

125

- Roller width G
Weight without enclosure (kg)

40

40

40

40

40

1660

1640

1800

1920

2220

Dimensions and weights with IP31 metal


enclosure

Dimensions and weights are for guidance only,


and are provided for a single-voltage transformer
with the following HV insulation levels and low
voltages. Only the definitive drawings following
from the order will commit us contractually. For
other voltages, impedance voltages and dualvoltages, weights and dimensions are different
(consult us).

13

tapping
links

earthing
terminal
125 (160)

D
A

40 (50)
D
B

2015 Schneider Electric. All rights reserved.

Trihal IP31

Insulation level: up to 36 kV- low voltage 400 V to 433 V


Rated power (kVA)
Dimensions (mm)

- Lenght A

250

315

400

500

630

1990

1970

1970

2000

2070

- Width B

1220

1220

1220

1230

1250

- Height C

2090

2090

2110

2250

2290

- Roller pitch D

520

670

670

670

670

- Frame width E

645

795

795

795

795

- Roller diam. F

125

125

125

125

125

- Roller width G

40

40

40

40

40

1885

1870

2040

2165

2480

Weight without enclosure (kg)

NRJED315631EN

02 2015

Cast Resin Transformers

08

Trihal - up to 3 150 kVA

Connections - Trihal transformers without


enclosure housing (IP 00)
The winding resin coating and the plug-in
connectors dont ensure any protection against
touch when the transformer is energized. The
contrator must ensure that cables and busbars
are adequately supported to prevent
mechanical stresses from being imposed on the
transformer terminals, busbars or bushings.

HV and LV standard connection

Insulation
(kV)

LV

Full wall

Grid wall

7.5

90

300

12

120

300

17.5-24

220

300

Dimension X (mm)

SM100019

SM100018

Minimum clearances required

cable support

LV

HV

120

120
mini

mini

HV

Connections -Trihal transformers with


IP 31 metal enclosure
HV and LV standard connection

200 mm

LV

HV

HV

cable support

200 mm

200 mm

LV

cable support

SM100021

SM100020

Minimum clearances required

500 mm*

160 to 400 kVA*

500 to 800 kVA*

thickness 5

thickness 6

4 x 14

1600 kVA*
thickness 12

SM100023

thickness 10
40

35

25
50

4 x 14

50

1000 to 1250 kVA*


160
80

100
50

23.5
33

33

4 x 14

4 x 16

50

14

80
33

23.5

70
33

15

40

HV terminations

33

SM100022

LV terminations

13

2000 kVA* thickness 10


2500 kVA* thickness 2u10

The contrator must ensure that cables and


busbars are adequately supported to prevent
mechanical stresses from being imposed on the
transformer terminals, busbars or bushings.
Schneider Electric Industries SAS
Head Office
35, rue Joseph Monier - CS 30323
F92506 Rueil-Malmaison Cedex
FRANCE
www.schneider-electric.com

For more information about Ecodesign, visit:


www.schneider-electric.com/transformers