TraceViewTM Network Explorer

Systems Communication Software

Product Specifications

Application . . .
TraceView Network Explorer is a PC based software
package developed specifically for interfacing with
Thermon control and monitoring equipment. TraceView
communicates with these controllers through a local
or remote serial connection. It is able to communicate
through ModBus ASCII/RTU and Ethernet communication protocols.
TraceView can communicate with a client PC as well as
to various DCS systems. Likewise, Traceview communicates to other PC devices or to DCS systems through a
serial port or Ethernet connection.
TraceView Network Explorer can be operated on a PC
at distances of up to 4,000 feet (1219 Meters) 1 from
the heat tracing control hardware. For a ModBus ASCII
or RTU protocol, the system can communicate with
up to 247 controllers (4,446 circuits) per program
instance. For higher circuit count heat tracing systems,
TraceView enables multiple instances of the program to
operate simultaneously on one PC.

Features . . .
Continuous monitoring of the temperature on all
heat traced piping and equipment.
Access to heat tracing operating parameters such
as heater current, ground leakage current, control
and alarm settings for analysis and set point
changes.

System Requirements . . .

Provides system operating status, tracks alarm


events and history.

TraceView Network Explorer is a PC based program


compatible with Microsoft Windows which meets or
exceeds the following:

A user can view isometric drawings to help locate


circuits, report on heat tracing operations/alarms,
and trend circuit data.

Processor............................. Intel Pentium III or faster


(including hyperthreading and dual processor PC systems)
Operating Platform......Windows 2000, XP or Vista
Color Monitor................ 800 x 600 resolution or higher
Available RAM............................................. min 128 MB
Free Hard Disk Space 2...... 100 MB for min. installation
Communication Port......Ethernet, USB, RS485, RS2323

Password protection to assure controller values can


only be changed by authorized users and tracks
user changes in a multiuser database.

Notes . . .
1. Longer distances are possible, contact factory for details.
2. Additional space may be required where trending data storage over long
periods of time.
3. See Data Highway Interface Options on page 2 for details.

THERMON . . . The Heat Tracing Specialists

100 Thermon Dr.


PO Box 609
San Marcos, TX 78667-0609
Phone: 512-396-5801
Facsimile: 512-396-3627
1-800-820-HEAT
www.thermon.com
In Canada call 1-800-563-8461

Provides graphical trends for heater current and


temperature data.
Advanced software based warning system should
a critical event be detected in the heat tracing or
communications network.

TraceView TM Network Explorer


Systems Communication Software

Product Specifications

Communication Configurations . . .
Multiple Workstation/
Monitoring

Single
Workstation

RS485 Data Highway Modbus ASCII or RTU Protocol


Up to 247 Addresses
Maintenance
Computer

Adminstration
Computer

Operators
Computer

Controllers
Ethernet Switch

Dual
Workstation
Ethernet Switch

RS485 Data Highway Modbus ASCII or RTU


Protocol Up to 247 Addresses
RS485 Data Highway Modbus ASCII or RTU Protocol
Up to 247 Addresses

Controllers
Controllers

Data Highway Interface Options . . .

Alarm Relay Options . . .

IM-1... RS232 to RS485 converter for twisted pair data highway


communications.

RC-8... USB relay card added to the server PC for adding eight
dedicated dry contact alarm outputs from TraceView Network Explorer. Two RC-8 cards required for a single PC installation.

IM-2... RS485 converter for fiber optic data highway communications. Two IM-2 modules required for a fiber optic communication
link.
IM-3...RS485 to Ethernet data highway communications converter.
Two IM-3 modules required for an Ethernet communication link.

RC-16... Ethernet relay card added to the server PC for adding sixteen dedicated dry contact alarm outputs from TraceView Network
Explorer.

IM-4...RS485 repeater module for data highway distance greater


than 4,000 ft (1219 meters). One repeater is recommended in the
data highway for every 31 controller addresses.
IM-5...RS485 to USB converter to interconnect the data highway
to a PC. Contact factory for converter that allows USB to multiple
RS485 options.

Form TEP0082-1108

Thermon Manufacturing Co.

Printed in U.S.A.

Information subject to change.