Anda di halaman 1dari 2

Desuperheater Sizing Calculation

Customer: AVANZIA/INITEC ENERGA.


Fisher Controls Intl. Inc
Contact:
Contact:
Customer Reference: 298 CC VALLE DE MXICO II
Sales Office Reference:
Item: 36
Rev: 8
Qty: 1
Quote:
Tags: GX-20LBG70AC001
Date Last Modified: 4/26/2016
Application: Atemperador Tipo Spray
Desuperheater Model: DVI-600-F-BD4
Material of Construction: SA182 GR F91
DSH Pipe Size: NPS 6
DSH Pipe Schedule: XXS
Outlet Pipe Size: NPS 6
Outlet Pipe Schedule: XXS
Min Straight Pipe Length: 3.7 m
Min Temperature Sensor Length: 10.5 m
Unit Weight: 13.6 kg
Throat ID: 2.710 in
Pipeline Orientation: Horizontal
Atmospheric pressure: 0.769 bar
DESIGN CONDITIONS
CONNECTIONS
Mainline Steam Design Pressure
bar(g)
30
Mating
Mainline Steam Design Temperature
deg C
581
Water
Water Design Pressure
bar(g)
30
Water Design Temperature
deg C
53.9
Variable Name
Units
MAXIMA
MINIMA
EXTREMA
ARRANQUE
SIZING INPUTS
Mainline Steam Inlet Pressure
bar(a)
18.2
18.2
Mainline Steam Inlet Temperature
deg C
397.63
397.63
Mainline Steam Inlet Mass Flow
kg/h
7800
7826
Mainline Steam Outlet Temperature
deg C
230
230
Water Pressure
bar(a)
30
30
Water Temperature
deg C
53.9
35.9

ESS Version 2.0.0.0-F

Lead Time:
Rev:

Cv: 1.000
DSH Pipe Wall Thickness: 0.864 in
Outlet Pipe Wall Thickness: 0.864 in
Recommended Mesh Size: 20
PRV not within 3 diameters upstream
NPS 6 CL600 RF Flange
NPS 1 CL600 RF Flange

MINIMA EXTREMA

18.2
580.1
7178
230
30
37.6

SIZING CALCULATION
Water Mass Flow
Water Volumetric Flow
Mainline Steam Outlet Mass Flow
Mainline Steam Inlet Velocity
Mainline Steam Inlet Speed of Sound
Throat Velocity
Mainline Steam Outlet Velocity
Water Pressure Drop - DSH
% Spraywater
Water Pressure Drop - SWV
Water Valve Cv

kg/h
gpm(US)
kg/h
m/s
m/s
m/s
m/s
bar
%
bar

1145.421
5.112
8945.421
29.59
623.51
96.61
23.93
1.8
14.68
10.0
0.421

1117.350
4.949
8943.350
29.69
623.51
96.94
23.93
1.7
14.28
10.1
0.407

2095.366
9.286
9273.366
35.17
703.39
114.85
24.81
5.9
29.19
5.9
1.002

MIN RATED FLOW PERFORMANCE


MR Mainline Steam Inlet Mass Flow
MR Water Mass Flow
MR Water Volumetric Flow
MR Mainline Steam Inlet Velocity
MR Water Pressure Drop - DSH
MR Water Pressure Drop - SWV
MR Water Valve Cv

kg/h
kg/h
gpm(US)
m/s
bar
bar

3433.408
504.192
2.250
13.02
0.3
11.5
0.173

3544.791
506.104
2.242
13.45
0.3
11.5
0.173

1741.648
508.413
2.253
8.53
0.3
11.5
0.174

THERMODYNAMIC PROPERTIES
Mainline Steam Inlet Enthalpy
Btu/lbm
1395.5
1395.5
Mainline Steam Outlet Enthalpy
Btu/lbm
1229.4
1229.4
Water Enthalpy
Btu/lbm
98.1
65.8
Mainline Steam Inlet Density
lb/ft3
0.376
0.376
Mainline Steam Outlet Density
lb/ft3
0.533
0.533
Water Specific Gravity
0.988
0.995
Water Saturation Pressure
bar(a)
0.1
0.1
Mainline Steam Inlet Superheat
deg C
190.0
190.0
Mainline Steam Outlet Superheat
deg C
22.3
22.3
NOTES
PSCD 180 required per ASME B31.1 Table 136.4 (unless Processing Level 8 is specified).

1568.2
1229.4
68.9
0.291
0.533
0.995
0.1
372.4
22.3

NPS 1
CL600
RF

1.5/(38)

NPS 6
CL600
RF

10/(254)

8.5/(216)

3/(76)
3.25/(83)
SA182 GR F91
ESS Version 2.0.0.0-F
DVI-600-F-BD4
Desuperheater Dimensional Drawing
Customer: AVANZIA/INITEC ENERGA.
Contact:
Customer Reference: 298 CC VALLE DE MXICO II
Item: 36
Rev: 8
Tags: GX-20LBG70AC001
Dimensions Certified Correct by Fisher Controls

Fisher Controls Intl. Inc


Contact:
Sales Office Reference:
Quote:
Date Last Modified: 4/26/2016
Scaling: None

Rev:

Anda mungkin juga menyukai