Taurus 60 Generator
Training Manual
Operating Principles
All turbines are basically engines that convert the energy of a moving stream of fluid (liquid / water,
steam or gas) into mechanical energy. The essential element of all turbines is a shaft with blades or
buckets arranged radially around the shaft in such a fashion that the fluid stream imparts a force to
the blades or buckets to cause the shaft to rotate. The rotational torque imparted to the shaft is then
used to provide useable power;
Examples : Waterwheel mechanical drive (corn mill) ,hydro-electric generator.
Windmill mechanical drive (water pump), generator.
Steam Turbine numerous including mechanical drives and generators.
Turbo-charger compressor driver.
Note: The rotating shaft on a Turbo-jet (aircraft engine) drives a compressor and other auxiliary
drives and uses the exhaust gases to provide thrust to push the aircraft forward.
Principle to Practice
As the thermodynamic principle on which Gas Turbines operate has been mentioned, how this is
achieved in practice can now be considered. On Cakerawala, Solar Taurus 60 Generator sets are
installed. While other manufacturers use different arrangements these machines are typical of the
most common internal mechanical arrangements generally used.
The Taurus 60generator sets are referred to as a Single Shaft arrangement. The Single Shaft
configuration is the least complicated arrangement and will be considered first.
T3
P3
T5
P5
T2
P2
T7
P7
SAFETY
Industrial Gas Turbines are high speed rotating heat engines which can present many
potential hazards and caution must be exercised at all times, not only when in the vicinity of
the Turbine package, but also when operating remotely. The following WARNING should be
understood and heeded at all times. Appendix A of these notes contains the Solar Operations
Manual Safety Guides which must be understood and should be used as a guide to the safe
operation and maintenance of the packages.
WARNING
1. Operation of the unit may be performed only when conditions indicate it is safe to
proceed. Dangerously explosive accumulations of natural gas, fuel fumes, oil tank vent
leakage, or solvent fumes must be avoided at all times. This is done by proper
ventilation, elimination of leaks, and by confining the use of solvents to appropriate
maintenance facilities.
2. Appropriate hearing and eye protection must be used by operating and maintenance
personnel in the vicinity of the operating machine.
3. Turn off electrical power. Tag control devices to prevent electrical shock and starting
of unit while unit is shut down.
4. Allow sufficient time for piping and system components to cool. Components can
become extremely hot and cause burns if touched with unprotected hands.
5. Do not allow fluids to come in contact with hot surfaces. Fluids discharged from lines
or fittings may be flammable and could cause a fire hazard.
6. Depressurize system before loosening line fittings or removing components. High
pressure lines or jetstreams can cause serious injury.
NOTE - ORIENTATION
Directional references on the unit (right side, left side, forward, and aft) are
established by viewing the unit facing the engine exhaust (aft) end and looking
forward.
AFT
Orientation Diagram
LEFT
RIGHT
FORWARD
Components
The generator sets accessories include the start, fuel, electrical control, lube oil, pneumatically
controlled air systems, and a governor.
Air Inlet
Assembly
Exhaust
Assembly
Generator
Turbine
Engine
Starter
Motor
Air Inlet
Compressor Assembly
Combustor Assembly
Fuel
Injectors
Compressor
Diffuser
The turbine engine is the package power plant. Air is drawn into the compressor section through the
air inlet and is compressed. Fuel is added to the compressed air in the combustor and is ignited. After
combustion, hot gases expand through turbine nozzles and drive the turbine rotor. The turbine drives
the engine compressor, accessories, and generator. Air and combustion gases are discharged to the
atmosphere through the exhaust system. Major components include air inlet, engine compressor,
compressor diffuser, combustor, turbines, exhaust diffuser and exhaust collector.
Generator
The genator, the driven equipment, transforms Mechanical energy to electrical energy. The
Generator is bolted to the raised mounting pads on The base, in alignment with the gear unit. The
Standard generator set has a two-bearing, revolving field-type, three-phase, ac generator, of
dripproof construction, with damper windings and a direct- connected brushless exciter,controlled by
a Voltage Regulator (AVR).
Electrical Generator
Coupling Guard
Drive End
Non-Drive End
Voltage Regulator
Gear Unit
The two-stage, epicyclic gear unit transmits
power from turbine engine to the electrical
generator and also drives the main lube oil pump.
The unit will sustain momentary overloads of
up to approximately eight times normal operating
torque. The lube oil system lubricates bearings
and the gear train. The engine air system pressurizes
the bearing oil seals
Start System
The start system includes starter and control
devices. The starter rotates the engine to selfsustaining speed, where the starter shuts down,
the starter clutch overruns, and the engine
accelerates under its own power to loading speed.
Starter Motor
Fuel System
The fuel system regulates fuel flow. The dual fuel systemis a combination gas fuel and liquid (diesel)
fuel system.Specially designed components, mechanical linkages, solenoid-operated valves and
other devices combine the gas fuel system and the liquid fuel system into a single intergrated system.
Filler Cap
Electrical System
The 24 Vdc electrical control system
monitors the engine and generator
and controls normal
and emergency (malfunction)
shutdowns. In operation, the
electrical control system protects the
engine and driven equipment from
damage from hazards such as
overspeed, high engine temperature
and vibration levels, low lube oil
pressure, excessive oil temperature
and generator over or undervoltages
and high winding temperature.
Turbotronics Display
Bleed Valve
Injector
Gas Ring
Air Inlet
Exhaust
Power Turbine
Gas Producer
Combustor
Compressor
Accessory Gearbox
SAFETY
WARNING
1. Operation of the unit may be performed only when conditions indicate it is safe to proceed.
2. Dangerously explosive accumulations of natural gas, fuel fumes, oil tank vent leakage, or
solvent fumes must be avoided at all times. This is done by proper ventilation, elimination of
leaks, and by confining the use of solvents to appropriate maintenance facilities.
3. Appropriate hearing and eye protection must be used by operating and maintenance
personnel in the vicinity of the operating machine.
4. Turn off electrical power. Tag control devices to prevent electrical shock and starting of unit
while unit is shut down.
5. Allow sufficient time for piping and system components to cool. Components can become
extremely hot and cause burns if touched with unprotected hands.
6. Do not allow fluids to come in contact with hot surfaces. Fluids discharged from lines or
fittings may be flammable and could cause a fire hazard.
7. Depressurize system before loosening line fittings or removing components. High pressure
lines or jetstreams can cause serious injury.
Take care. They are hard to close against the inside pressure and may require help to close.
Rearm fire system
Relock door
Contact control room operator and tell you have finished inspection, fire system is rearmed
and doors are locked.
on
of
Starter Motor
FUNCTIONAL DESCRIPTION
Starting Sequence
The starting sequence is initiated by pressing the start button. Upon
pressing the start button, the fuel gas valve and pre lube pressure checks
are conducted. Along with this the enclosure pressurization and fan
operation is also checked.
STARTING Light (DS114) begins flashing. Fuel system valve check
sequence begins. Post lubricating backup pump is tested for operation,
post lubricating oil pump is started, and prelubrication begins. Enclosure
ventilation fan is energized.
PRELUBE CYCLE
After the lube oil pump checks are completed, the prelube time out timer (60 seconds)
is started. The prelube time out timer is the allowable time for pump P902 to complete the prelube
cycle. When the lube oil pressure is greater than the prelube low pressure limit of 6 psi (41.3 kPa),
the prelube timer (30 seconds) is started. The engine must be prelubed at a pressure above 6 psi
(41.3 kPa) continuously for the duration of the prelube timer (30 seconds). This prelube must occur
within the time of the prelube time out timer (60 seconds). If the prelube timer times out before the
prelube is done, the start is aborted and a prelube failed fast stop non-lockout alarm is annunciated
on the control console.
CURVE LEGEND :
= Ngp
NOTE : Annunciations are shown in RED font.
Generators at idle and ready to load,
bleed valve open
100
90
80
Generator Excitation
Starter Motor Drop Out Speed
65
START RAMP
Engine
purge
Timer
300
30 Sec
10
20 - 25
T5 Set Point
change
(50% Ngp)
MIN. FUEL
0
T5 < 400F+ > 10 seconds
= IGNITION FAILURE
Pre-start permissives
1 Fuel Valve Checks
2 Lube Oil Pump Checks
3 Prelube
4 Waste Heat Recovery
Pre-start package checks
- Safe to start and no
alarms or inhibits
= READY
Combustion starts
T5> 400F <10 seconds = LIGHTOFF
IGNITION
READY TO LOAD
command ON =
Fuel valves +
torch + ignition
STARTING
RUNNING
Press
Time
FUNCTIONAL DESCRIPTION
General Lube Oil Flow
The lube oil system provides oil delivered by Main Lube Oil Pump (P901) to the lube oil manifold. The
oil is maintained at a nominal engine inlet pressure by Main Lube Oil Pressure Control Valve
(PCV901). Oil pressure is also supplied to Guide Vane Control Actuator (L339) and bleeds valve
actuator, causing the actuator piston to move in response to electrical signals from the control
system.
Temperature Control Valve (TCV9011) will divert all of the oil from Air/Oil Cooler (HX901-1) until the
oil temperature reaches a predetermined setting. Temperature control valve TCV9011 then
gradually transitions to supply oil to air/oil cooler HX901-1 in proportion to the oil temperature. From
air/oil cooler HX901-1, the oil flows through Main Lube Oil Filters (FS901-1, FS901-2) to the oil supply
manifold, then through various branch lines to points of lubrication.
Oil to the reduction gear unit enters a port on the right-hand side of the housing. It flows through
internal passages to a tubular oil transfer assembly, which directs the oil to the compressor rotor
forward bearing. An oil jet, from a small tube in the oil transfer cap, lubricates the splined sleeve
coupling on the compressor nose cone hub. Lubricating oil for remaining gears and bearings in the
power train and accessory drive sections of the reduction gear unit is directed to their respective
points through drilled passages in the gear unit housing and individual subassemblies. Oil is drained
from the reduction gear unit housing by gravity to the oil reservoir.
Oil supplied to a port on the compressor bearing support housing is delivered to compressor rotor aft
journal and thrust bearings and, through internal passages, to the turbine rotor bearing. Oil from
turbine rotor and compressor aft bearings drains by gravity to the lube oil reservoir through two drain
outlets in the compressor bearing support housing.
PRELUBE CYCLE
After the lube oil pump checks are completed, the prelube time out timer (60 seconds)
is started. The prelube time out timer is the allowable time for pump P902 to complete the prelube
cycle. When the lube oil pressure is greater than the prelube low pressure limit of 6 psi (41.3 kPa),
the prelube timer (30 seconds) is started. The engine must be prelubed at a pressure above 6 psi
(41.3 kPa) continuously for the duration of the prelube timer (30 seconds). This prelube must occur
within the time of the prelube time out timer (60 seconds). If the prelube timer times out before the
prelube is done, the start is aborted and a prelube failed fast stop non-lockout alarm is annunciated
on the control console.
Engine Running
After the prelube cycle is completed, pump P902 is de-energized when the engine is above starter
dropout speed and the lube oil pressure is at or above 35 psi (241 kPa). At this point, engine-driven
pump P901 begins providing lube oil pressure and continues to the steady state condition. After
engine-driven pump P901 reaches the steady state condition, the lube oil schedule becomes active.
During the steady state engine running condition, pump P902 is energized when:
The engine is below starter dropout speed and the lube oil pressure is at or below 25 psi
(172.25 kPa)
Engine speed of greater than 5% Ngp is detected.
Pump P902 will not be annunciated as failed during the steady state engine running condition when
the lube oil pressure is less than the postlube low pressure shutdown limit, because pump P901 may
be at fault.
Run Protection
During steady state engine running, the control system provides run protection to the engine by
energizing pump P903 anytime the lube oil pressure is below the lube oil pressure low alarm limit
(41psi). When the lube oil pressure is no longer below the lube oil pressure low alarm limit pump
P903 continues to run for 30 seconds and is then de-energized.
The following 3 situations may arise:
If the lube oil pressure continues to decrease below the lube oil pressure low alarm limit to
the low lube oil pressure shutdown limit, a fast stop, lockout engine shutdown is initiated, and
pump P903 contributes to protecting the engine bearings during the engine shutdown.
If the lube oil pressure continues to decrease below the lube oil pressure low alarm limit but
stabilizes between the low lube oil pressure low alarm limit and the low lube oil pressure
shutdown limit continuously for 5 seconds, a fast stop, non-lockout engine shutdown is
initiated, and pump P903 contributes to protecting the engine bearings during the engine
shutdown.
If the lube oil pressure increases above the lube oil pressure low alarm limit, and after 30
seconds or when pump P903 is de-energized, lube oil pressure once again decreases, an
alarm is initiated and pump P903 is once again energized.
Postlube Cycle
The postlube cycle begins when the rundown timer (6 minutes) has expired. Initially, pump P902 is
de-energized to allow a check of pump P903 to take place. A 30 second pressure decay timer is
started to allow the lube oil pressure to drop to 5 psi (34.4 kPa). If the pressure decay timer expires
before the pressure drop occurs, the start is aborted and a backup lube oil pump fail alarm is
annunciated on the control console.
While the engine is in the postlube cycle, if pump P902 fails to keep the lube oil pressure above the
postlube low lube oil pressure shutdown limit, a pump failure is annunciated on the control console.
Pump P903 takes over the postlube and pump P902 is de-energized. However, pump P902 can be
re-initiated to take over the postlube by acknowledging and resetting the alarm. During the time the
lube oil pressure is less than the postlube low lube oil pressure shutdown limit, the postlube timer is
frozen.
Postlube Scenarios
The following are five distinct postlube scenarios which may be initiated:
1. POSTLUBE AFTER SHUTDOWNS BEFORE ENGINE TURNS
If the prelube has been completed, but the starter motor has not yet been engaged, and the engine is
stopped, the rundown timer is not triggered and postlube will not be initiated unless the engine was in
postlube prior to the initiation of the failed start. In this case, the postlube will continue from the
accumulated time from before the start was initiated.
Taurus 60 Generator Set: Pre-Lube, Start & Steady State Lube Oil Diagram
NOT TO SCALE
TP380 (LOP)
PUMP CHECKING ACTIVE remains until Rundown Timer is DONE
Pre-Post High
Pressure Alarm
Enabled
AL = 6 PSI
SD = 4 PSI
60 sec.
AL = 41 PSI
SD = 25 PSI
10 s
STEADY STATE
41 PSI
AL
35 PSI
30 sec.
25 PSI
SD
6 PSI
4 PSI
3 PSI
Time
START REQ.
P202 START
P202 STOP
P203 START
Main Pump Press. Pass
PRELUBE TIMER
ENGAGE STARTER
PRELUBE TIMEOUT TIMER
P203 STOP
LEGEND
Lube Oil Header Pressure (TP380)
High Pre - Post Alarm
Low Alarm
Low Shutdown
FUNCTIONAL DESCRIPTION
Gas Fuel Operation
Sequence of Operation
Sequence of operation includes the following steps:
Valve check sequence
purge crank cycle
Ignition sequence
Acceleration sequence
IGNITION SEQUENCE
After the purge crank is completed, Torch Gas Fuel Shutoff Valve (V2P940), Ignition Exciter (G340),
and the fuel control ramp are energized. Shutoff valves V2P931, V2P931-1, V2P932, and V2P932-1
are opened and gas flows into the system. Fuel flows to the torch and is ignited by Igniter Plug (E340)
in the presence of combustor air. The torch flame flares into the airflow inside the engine combustor
liner.
Gas fuel flows from the shutoff valves and is regulated by Gas Fuel Control Valves (EGF344,
EGF344-1). Fuel passes through fuel injectors, spaced equally around the combustor, to mix with
combustor air stream. Initially, fuel/air mixture is too lean for ignition. The fuel control ramp directs
valves EGF344 and EGF344-1, to move toward a maximum open position. The control ramp enriches
the fuel/air mixture and lightoff occurs smoothly.
ACCELERATION SEQUENCE
Following lightoff, turbine temperature increases rapidly beyond 400_F (204_C). The lightoff ramp is
completed, and the acceleration ramp is initiated. Ignition Exciter (G340) and shutoff valve V2P940
are de-energized and the torch extinguishes. Fuel control valves EGF344 and EGF344-1 are ramped
open to gradually bring T5 temperature up to 800_F (427_C). At 35 percent gas producer speed
(Ngp), fuel control valves EGF344 and EGF344-1 continue to ramp until T5 reaches 1200_F (654_C).
From this point, the control system is switched over to engine speed (Ngp) control.
At 65 percent engine speed (Ngp), the starter clutch overruns and the start system is de-energized.
The engine continues to accelerate. At 70 percent engine speed (Ngp), Compressor Bleed Valve
(PCV942) begins to close. Continuing to 80 percent engine speed (Ngp), the inlet guide vanes begin
to move toward the maximum open position. As engine speed (Ngp) increases to 90 percent, the fuel
supply rate from control valves EGF344 and EGF344-1 level off for 10 seconds to prevent T5
temperature from exceeding the shutdown limit. After the time delay, control valves EGF344 and
EGF344-1 increase fuel supply until engine speed (Ngp) is 100 percent (synchronous idle). At
synchronous idle, the guide vanes are fully open and bleed valve PCV942 is closed. The engine is
now ready for load and the control system switches to generator load control.
If the temperature shutdown timer fails to shut down the engine during an overtemperature condition
and the turbine engine temperature reaches a higher maximum limit, the engine temperature T5
backup shutdown circuit will activate and initiate an immediate engine temperature T5 high
malfunction indication and an engine shutdown.
PURGING SEQUENCE
At initiation of the start sequence, shutoff valve V2P945 is opened and the purge valve timer is
started. Shutoff valve V2P945 remains open until the purge valve timer times out.
At initiation of a liquid fuel start, the liquid fuel select switch is pressed. When the start switch is
pressed, the air assist shutoff valve (L350-1) opens and Liquid Fuel Purge Shutoff Solenoid Valve
(L345-1) opens to purge the fuel metering block and associated lines.
IGNITION SEQUENCE
After the purge cycle is completed, solenoid valve L348-1 opens and Ignition Exciter (G340) is
energized. Liquid fuel flows through solenoid valve L348-1 to the igniter torch, is atomized by torch air
assist pressure, and is ignited by Igniter Plug (E340) in the presence of combustor air.
Simultaneously, fuel from pump P931 flows through open Liquid Fuel Shutoff Valve (V2P939 and a
torch fuel bias pressure valve VCS932 to the fuel injectors. Air from the air assist manifold enters the
injectors and atomizes the fuel. The torch flame flares into the airflow inside the combustor liner and
ignites the mixture from the fuel injectors when the mixture has enriched sufficiently to support
combustion.
ACCELERATION SEQUENCE
Following ignition, turbine temperature increases beyond a predetermined setpoint, ignition exciter
G340 and solenoid valve L348-1 are de-energized, and the torch extinguishes.
The control voltage to control valve ELF344 is slowly ramped open to increase the turbine engine
temperature. When the engine temperature reaches the 1125 F (633C) threshold, the ramp is
halted. Increasing engine airflow reduces engine temperature. At 1110F (599C), the ramp resumes.
At 66 percent engine speed, the start system is de-energized. Engine cranking ceases and fuel
atomizing air is supplied by Pcd through the air blast and injector fittings. Pcd air continues to
circulate through the air assist passages and manifold to keep them purged of liquid fuel. As engine
speed increases, the liquid fuel control valve balances fuel with Pcd to maintain the acceleration
schedule.
As the engine attains 100 percent speed, control of control valve ELF344 is switched from the
acceleration control system to the generator load system. Line synchronization module assumes fuel
control by means of analog signals to control valve ELF344 to control engine speed. Engine
temperature T5 setpoints, which are offset to other-than-normal values during the start sequence, are
switched to the normal operation temperature setpoints at 66 percent speed.
Should the turbine engine temperature exceed the temperature control setpoint at engine speeds
above 65 percent, the engine temperature, T5 delayed shutdown alarm is indicated and, following the
five-second time delay, an engine shutdown is initiated. The time delay is to allow for momentary
overtemperature during load transients.
If the temperature shutdown timer fails to shut down the engine during an overtemperature condition
and the turbine engine temperature reaches a higher maximum limit, the engine temperature T5
backup shutdown circuit will activate and initiate an immediate engine temperature T5 high
malfunction indication and an engine shutdown.
If during normal operation the differential pressure across the duplex low pressure fuel filters should
exceed a predetermined setting, pressure switch S343 will transfer and initiate a high fuel filter
differential pressure alarm without causing an engine shutdown.
If the high pressure fuel pump inlet pressure should drop below a preset value, pressure switch S3872 will transfer. If the engine speed is above 15 percent, pressure switch S387-2 will initiate a sixsecond time delay followed by a low liquid fuel pressure malfunction and an engine shutdown. Upon
engine shutdown (normal or malfunction), shutoff valve V2P945 opens. During run-down, the Pcd
purges the fuel injector, torch nozzle, and the lines back through the purge valve to an external drain,
until the purge valve timer times out, at which time spring pressure closes shutoff valve V2P945.
PURGING SEQUENCE
At start, air assist is first directed to both Air Assist Shutoff Solenoid Valve (L350-1) and pilot solenoid
valve L345-1. Shutoff valve V2P945 is opened and Pcd purges the fuel injectors and the lines back
through shutoff valve V2P945. When purging is completed, internal springs close shutoff valve
V2P945.
IGNITION SEQUENCE
Air Assist Pressure Control Valve (PCV933) senses Pcd to control the air assist pressure at a fixed
bias above Pcd. After passing through a check valve, the pressure-controlled air separates and flows
in two different directions. One path flows to the igniter torch where the air flow is used to provide
positive atomization of the liquid fuel at the torch during the start sequence only. The other path
passes directly to the air assist manifold and out to the injectors.
ACCELERATION SEQUENCE
At 66 percent engine speed, Pcd air is at a sufficient level for proper fuel atomization, and valve L3501 is de-energized. This cuts off air assist to pressure control valve PCV933. Fuel atomizing air is
supplied solely by Pcd air through the air blast and injector fittings.
SHUTDOWN SEQUENCE
During engine shutdown (normal or malfunction), shutoff valve V2P945 is opened. During run-down,
the Pcd purges the fuel injector, torch nozzle, and the lines back through shutoff valve V2P945 to the
purge tank, until engine speed decreases below 15 percent when internal springs close shutoff valve
V2P945.
Fuel Transfer
Fuel transfer is possible only during normal operation when engine speed is above 90 percent.
Automatic transfer is accomplished from gas fuel to liquid fuel only. The transfer takes place
when gas pressure drops below a preset value, or it may be initiated manually. When manual transfer
is initiated, the pressure of the selected fuel system must be within prescribed limits. If the selected
fuel system pressure is not within the prescribed limits, engine operation will continue on the
operating fuel system until the selected system pressure becomes normal. Fuel transfer will then take
place in the usual manner.
An automatic fuel transfer to liquid fuel may occur due to a decrease in gas fuel pressure. However,
since an extremely rapid loss of fuel pressure may cause an engine flameout, the pressure drop must
not be too large or sudden.
COMPONENT DESCRIPTIONS
DUAL FUEL
Main Liquid Fuel Pump Motor
Main Liquid Fuel Pump Motor (B343), connected to Liquid Fuel High Pressure Pump (P931) by a
coupling, is a continuous-duty, squirrel-cage, polyphase electric motor. The motor is used to drive
pump P931. The motor incorporates a space heater.
Gas Fuel Control Valves
Gas Fuel Control Valves (EGF344,
EGF344-1), downstream of Gas Fuel
Secondary Shutoff Valves (V2P932,
V2P932-1), are electrical, closed-loop
servo valve that controls the steady
state flow of gas fuel to the engine.
The electrical control signal is
provided by an analog signal from the
control system.
As the valve piston moves to its
commanded position, the feedback
mechanism spring begins to develop
an equal and opposite force.
This feedback force will balance the
electrically-generated force created by
the input signal. As a result,
movement of the valve piston will stop
at a position proportional to the input
signal current. For each input signal
from the control unit, there is only one
position of the valve piston at which
the feedback spring force exactly
balances the deflection force imposed
on the armature by the torque motor
coil.
During the ignition sequence,
beginning at the moment the torch is
ignited, the valve is energized by an
increasing signal from the control
system. The valve gradually opens,
enriching the fuel/air mixture until
combustion is able to propagate
smoothly from the torch. This action
avoids a lightoff into surge.
When the turbine temperature
reaches 400F (204C), the valve is
commanded to be ramped open at a
predetermined rate.
24 Volts
0 Volts
De-Energized (OFF)
Energized (ON)
During start pr operation above 65 percent speed, if the main fuel actuator exceeds 95 percent of its
acceleration limit and engine Pcd drops by more than the stepping of the pressure switch in 0.25
seconds, the pressure switch is actuated, a flameout malfunction is annunciated, and the engine is
shut down. This time/pressure relationship is a physical characteristic of a flameout.
Liquid Fuel Low Pressure Shutdown Pressure Switch
Liquid Fuel Low Pressure Shutdown Pressure Switch (5387-2), located downstream from Liquid Fuel
Low Pressure Filters (FS935-1, FS935-2), is a double-pole, double-throw, snap-acting-type pressure
switch. The pressure switch senses inlet fuel pressure to the high pressure fuel pump. The switch
transfers to initiate engine shutdown if the liquid fuel pressure decreases below a predetermined
setting.
Sump Level Switches
Sump Level Switches (S542-1, S542-2), are part of Gas Fuel Cpalescing/Filgragipn Module
(FSM932). The switches provide electrical indication to the control system that the sumps require
draining.
Purge Tank Level Switch
Purge Tank Level Switch (S389), located in Liquid Fuel Purge Tank (R931), is a single-pole, singlethrow one-float-type level switch. The level switch transfers when purge tank R931 level reaches a
preset limit and an alarm is annunciated on the control console.
Liquid Fuel Flow Transmitter
Liquid Fuel Flow Transmitter (TF332), located downstream from Torch Bias Check Valve (VCS932),
is a turbine-type flow transmitter. The flow transmitter senses fuel flow through the liquid fuel system
and sends a signal, corresponding to a flow rate, to the control system for condition monitoring.
Engine Compressor Discharge Pressure Transmitter
Engine Compressor Discharge Pressure Transmitter (TP349), downstream from the engine on the
Pcd line, is a microprocessor based electronic-type pressure transmitter. The pressure transmitter
senses engine compressor discharge pressure and sends a corresponding signal to the control
system for condition monitoring. Instrument Isolation Hand Valve (V1931-3) is used to isolate the
transmitter from the system for calibration, testing, pr replacement.
Gas Fuel Pressure Transmitter
Gas Fuel Pressure Transmitter (TP386), downstream from the package gas fuel connection, is a
small size, microprocessor based electronic-type pressure transmitter. The pressure transmitter
senses gas fuel supply pressure as applied to Gas Fuel Primary Shutoff Valves (V2P931, V2P931-1)
and sends a corresponding signal to the control system for monitoring.
3.3.62 Gas Fuel Flow Scheduling Differential Pressure Transmitter
Gas Fuel Flow Scheduling Differential Pressure Transmitter (TPD344) senses the difference between
gas fuel pressure to the engine and engine combustor pressure and sends a corresponding signal to
the control system for controlling Gas Fuel Control Valves (EGF344, EGF344-1).
Air Inlet Differential Pressure Transmitter
Air Inlet Differential Pressure Transmitter (TPD358), downstream from the air inlet duct, is a solid
state, electronic sensing-type differential pressure transmitter. The differential pressure transmitter
senses the difference between ambient air pressure and the inlet duct air pressure and sends a
corresponding signal to the control system for condition monitoring.
Gas Fuel Coalescing Filter Differential Pressure Transmitter
Gas Fuel Coalescing Filter Differential Pressure Transmitter (TPD542), offskid on Gas Fuel
Coalescing/Filtration Module (FSM932), is a solid state, electronic sensing-type differential pressure
transmitter. Connected across the inlet and outlet of the fuel module, the differential pressure
transmitter senses the differential pressure between the inlet and outlet of Gas Fuel
Coalescing/Filtration Module (FSM932) and sends a corresponding signal to the control system for
monitoring.
from
open
are
and
to
Principles
Ambient air is drawn into the Compressor data point T1, P1. Work is done by the Compressor to
increase the pressure (and temperature) of the air and to decrease its actual volume data point T2,
P2, at the exit of the Compressor. As will be seen a further pressure increase then occurs in the
Compressor Diffuser and the pressure here is monitored and is also used for control purposes. This
pressure is known as Pcd
From the Compressor Diffuser the air path is divided to supply Primary Air for combustion and
Secondary Air for cooling and sealing (although some applications divert air from some of the
compressor stages for sealing rather than use the higher Pcd pressure). Spent Primary Air and air
used for cooling then exits through the Turbine Section and through the Exhaust Assemblies to
atmosphere. Air used for sealing should exit to atmosphere along with the oil in the bearing lube oil
drains to the Lube Oil Reservoir and its vent.
The following 3 diagrams show simplified points for temperature, pressure and basic principle of
turbine operation.
in a
the
row
stator
a
Velocity Up
Nozzle Effect
Principle of Operation
The diagrams above illustrate the principle of operation of an Axial Flow Compressor. The Rotor
Assembly is driven by the turbine shaft and the Rotor Blades impart energy to the air by increasing its
velocity. The Rotor Blades are arranged to force the air into the Stator stage that follows, where the
blades are arranged to offer an increasing path for the air that enters. This causes the air velocity to
decrease with a corresponding increase in pressure (and temperature). This process is repeated
throughout each compressor stage.
Compressor Diffuser
The Compressor Diffuser is located at the exit of the Compressor. The process of energy conversion
continues in the Compressor Diffuser. The picture below shows the Diffuser attached to the
Compressor exit and the air path is again expanding. This results in the air velocity again decreasing
with a corresponding increase in the air pressure (and temperature). The greater air pressure in the
Diffuser is known as Pcd (Pressure, Compressor Discharge.)
Primary Air
The air used for combustion is known as Primary Air and usually accounts for about 25% of the total
air required. It is mixed with the fuel used and the resultant fuel air mixture will burn if the proportions
are suitable .It should be noted here that the routing of Primary Air varies between engine designs.
System Function
The engine air system, in addition to its main function of supporting combustion, also pressurises oil
seals, cools turbine rotor blades and nozzles, assist in obtaining smooth engine operation by
preventing surge conditions at critical speeds, and supplies control air for operation of the fuel control
system. Air system supply is compressor discharge air pressure (Pcd).
The air system starts to function with the rotation of the engine compressor rotor which draws in
ambient air. The air is compressed and directed through the diffuser to the combustion chamber
where fuel is injected and the combustible mixture is burned. This action transforms the air into a hot
gas, which expands through the turbine, creating mechanical energy. The gas is expelled to
atmosphere through the exhaust collector.
The entire turbine cooling air is returned to the main gas stream in the turbine section. The seal air
that leaks past the labyrinth seals travels through the engine oil drain lines and is vented from the
main lube oil tank.
Sealing Air
The engine incorporates three airpressurized labyrinth seals to
prevent leakage of lube oil from
the bearings. Compressor
discharge pressure is routed by
external air lines through orifices
to the compressor rotor forward oil
seal. Compressor diffuser air is
metered through internal
passages to the compressor rotor
aft oil seal and gas producer
turbine oil seal.
Bleed Valve
Actuator
Assembly
The
trunnion valve body is mounted between flanges on the combustor case assembly and the bleed
valve exhaust duct. The duct directs compressor discharge pressure to the turbine exhaust diffuser. A
flange at the stem packing gland supports the valve on the actuator bracket. The end of the stem is
machined with a keyway and fits into the bleed valve.
T5 THERMOCOUPLES
The T5 Thermocouples (TC1 through TC6) are mounted around the combustor aft housing. The
thermocouples protrude into the turbine nozzle area, where they sense the temperature of the thirdstage turbine inlet (T5).
Engine Support
The turbine engine is cantilevered aft from the forward
flange of the air inlet housing, which is bolted to the
reduction drive assembly. Additional rear support is provided
by a steel pedestal attached to the combustor housing aft
flange. The pedestal base rests on a vibration isolating pad
located on the steel base crossmember below the
combustor housing.
The vibration pad is provided with load springs, adjustment
bolts, and spacers, that in addition to serving as a resilient
rear mount, also permit vertical and horizontal adjustments
of the engine for purposes of alignment.
Mounted on the reduction drive assembly is a magnetic pickup which counts the speed of the gear
teeth and transmits a signal to the speed monitor control box in the control panel. Another magnetic
pickup device directs a signal to the governor to control turbine speed.
The reduction drive assembly gear train is a compound star arrangement with three equally spaced
star clusters. The power flows through the input pinion (sun gear) (5) into three first-stage star gears
(6), through three second-stage pinion gears (7), and to the second-stage ring gear (4) on the output
shaft (9).
The input pinion assembly (5) is supported at one end by a ramp bearing mounted on an adapter on
the gear carrier. The other end is supported by the three first-stage star gears (6). Pinion thrust loads
are taken by a tapered land thrust bearing. The gear clusters have two sleeve bearings mounted
inside their bores. The journal bearing is stationary and is mounted in the carrier to support the gear
clusters.
The second-stage ring gear (4) is mounted on a hub with a loose fitting spline, which allows the ring
to center itself on the output shaft (9) through a fixed spline.
A sprag-type one-way clutch is mounted on the starter gear shaft. The starter drives through the
clutch. When the starter disengages, the sprags lift off the shaft and the clutch overruns continuously.
Each of the first-stage meshes in the power train is cooled and lubricated by three sets of two oil jets
directed toward the sun gear between each pair of meshes. Each pinion in the second-stage is
cooled and lubricated by two jets on the inboard side. Centrifugal force drives this oil into the ring
gear teeth. It is then flung out at the open end of the ring and through holes at the inner end.
Additional oil jets cool and lubricate the accessory pinion gear mesh, the output ball bearing, and the
one-way clutch on the starter shaft. All other accessory gear meshes and bearings are lubricated by
air-oil mist generated in the housing by the high speed meshes.
The hydrodynamic ramp bearing and thrust bearing on the input pinion assembly and the sleeve
bearings on the countershafts are pressure-fed with oil. Pressurized oil is provided by the externally
mounted main lube oil pump.
Reduction/Accessory
Drive Assembly
Generator
Starter Motor
Generator
Introduction
Electricity generation was first developed in the 1800's using Faradays dynamo generator. Almost
200 years later we are still using the same basic principles to generate electricity, only on a much
larger scale.
Electricity can be made or generated by moving a wire (conductor) through a magnetic field.
Magnetism
A bar magnet has a north and south pole. If it is placed
under a sheet of paper and iron filings are sprinkled over
the top of the paper, these iron filings will arrange
themselves into a pattern of lines that link the north pole
with the south pole of the magnet (diagram 1). These lines
show the magnetic field around the magnet.
Diagram 1
Making electricity
If a coil of wire is moved within a magnetic field so that it passes through the magnetic field, electrons
in the wire are made to move (as in diagram 2). When the
coil of wire is connected into an electric circuit (at the
terminals A and a) the electrons are under pressure to
move in a certain direction and a current will flow. This
electrical pressure is called voltage.
The amount of pressure or voltage depends on the strength
and position of the magnetic field relative to the coil, as well
as the speed at which the coil is turning. As the amount of
electricity changes so does its voltage.
Diagram 2
Diagram 3.1
Diagram 3.2
Diagram 3.3
Diagram 4
In the diagrams above, the coil of wire is rotating in a clockwise direction. When the coil of wire is in
the horizontal position (3.3), the voltage is greatest (diagram 4) because the coil is passing through
the strongest part of the magnetic field. At this stage the current flows from 1 to 2 to 3 to 4, out
through terminal A, through the globe and back into terminal a. When the coil of wire is in the vertical
position (3.2), no electricity is produced because the coil does not cut the magnetic field, and no
current flows. When the coil of wire is in the horizontal position again (3.3), the voltage is at its
maximum (diagram 3.3), however the current flows in the opposite direction 4 to 3 to 2 to 1, out
through terminal a, through the globe, and back into terminal A.The current produced changes
direction every half turn (180 degrees). This is called alternating current or AC. The generators at
large power stations produce nearly all the electricity we use in this way.
Diagram 5.1
Diagram 5.2
Diagram 5.3
Diagram 5.4
Diagram 5.5
It is more cost efficient and technically better to connect three sets of coils in the stator.
Diagram 5.4 shows how these coils are mounted. Each of these coils will be connected as separate
electrical circuits. When the magnet rotates an identical voltage is produced in each coil and circuit,
but each is staggered or delayed from one another (diagram 5.5). The electricity circuit is said to be
three phase.
Relative Motion between conductor and magnetic field (Condition 3 above), will result in a similar
effect if the conductor is stationary and the magnetic field moves.
In practice the generator output voltage and current will be high and require good connections
between the conductors and the load circuit cables to minimise resistance and losses and therefore
the generation of heat. These results in the conductors being stationary and the magnetic field being
rotated in practical generators. The following diagrams will examine the construction and operating
principles of a typical generator.
The turbine is called the prime mover and the shaft, magnet and copper windings make up the
alternator.
An alternator consists of a rotor and a stator. The rotor is directly connected to the prime mover and
rotates as the prime mover turns.
The rotor contains a magnet that, when turned, produces a moving or rotating magnetic field. The
rotor is surrounded by a stationary casing called the stator, which contains the wound copper coils or
windings. When the moving magnetic field passes by these windings, electricity is produced in them.
By controlling the speed at which the rotor is turned, a steady flow of electricity is produced in the
windings. These windings are connected to the electricity network.
The structure of the alternator usually stays the same regardless of the type of energy being used to
produce electricity.
The prime mover can be a turbine driven by steam, water, wind or burning gases. The prime mover
can also be an engine (like a car engine) that uses fuel to turn the generator.
Rotor Shaft
Gear Unit
Gear Unit Bearing
Gear Unit Output Shaft
Rotor
Stator (Windings)
Stator Casing
End Plate
Exciter
Exciter Field
PMG
PMG Field
Generator
Base
Fan (Fixed to Rotor)
Drive End Bearing
Rectifier
End Plate (includes Bearing Housing)
ND End Bearing
Coupling
Cabling
The diagram above shows that the generator rotor shaft is supported by bearings at the Drive and
Non-Drive ends and is rotated by the torque transmitted from the engine through the gear unit and
coupling. Attached to the rotor shaft is a fan and the rotor which is located within the stator casing so
that it aligns with the stator windings. Also attached to the rotor shaft are the rectifier, exciter armature
and the PMG (Permanent Magnet Generator). There will be interconnecting conductors between the
rotor, rectifier and the exciter armature, shown above as .
The following descriptions have been taken from the Installation and Maintenance Manual.
Functional Discription
During generator set operation, the three-phase ac power generated in the exciter armature is applied
to the rectifier where it is converted to direct current power. The dc output from the rotating rectifier is
then applied as field excitation current to the generator rotating field coils. It should be noted that, with
this arrangement, the main generator field coils rotate and its armature is stationary, while the exciter
field is stationary but its armature rotates with the main generator rotor shaft. As a result, a single
rotating assembly, consisting of exciter armature, exciter rectifier, and main generator field coils is
formed, greatly simplifying all electrical connections within the generator assembly.
A sensing transformer supplies the bus potential signal to the regulator. The main generator output is
controlled by the generator field current. The generator field current is in turn controlled by the
brushless exciter circuit. The power transformer through the regulator, furnishes the excitation to the
exciter field. Variations in bus potential, then, will be sensed and subsequently corrected by this
circuit.
All ac generators require that direct current (excitation) be applied to the rotor windings (field coils) in
order to set up the magnetic flux necessary for generator operation. Because the amount of dc
current going into the field of the exciter will determine the output voltage of the exciter, the exciter
output, being applied to the generator field, will therefore control the output voltage of the main
generator.
Upon proper voltage buildup, the generator accelerates to 100 percent speed and excitation and
voltage control are assumed by the voltage regulator.
A crosscurrent-compensating transformer provides the proper signals to the regulator to
accommodate reactive loadsharing between multiple units in parallel.
COMPONENT DESCRIPTIONS
Rotor
The rotor is dynamically
balanced so that the
degree of dynamic
imbalance provides
minimum vibration.
Efficient rotor fans move
air through the generator
and around the rotor for
cooling. The rotors have
layer-wound field
windings, which are then
cemented with a highstrength resin and baked.
The rotor is in electrical
and mechanical balance
at all speeds, up to 125
percent of rated speed.
Stator
The stator is built with high-grade silicon steel
laminations, which are precision punched and
individually insulated. Windings, form-wound in
lined slots, are repeatedly treated with
thermosetting synthetic varnish and baked for
maximum moisture resistance, high dielectric
strength, and high bonding qualities. The windings
are also braced to withstand shock loads such as
motor starting and short circuits. Space heaters can
be supplied to minimize condensation during
shutdowns.
Shaft
The shaft diameter is sufficient to provide the stiffness necessary to preclude torsional problems.
Frame
The frame is heavy-duty steel, fabricated with deep welds and internal reinforcing for extra rigidity and
strength. Lifting lugs are provided.
Exciter
Excitation current for the generator field coils is provided by a brushless rotating exciter unit with
permanent magnet generator (PMG) pilot exciter. The generator is a synchronous, three-phase,
alternating current generator with rotating field coils, and the exciter unit is mounted directly on the
generator rotor shaft.
The exciter unit consists of two basic parts, a small three-phase, ac generator with rotating armature,
and a three-phase, full-wave, diode-type bridge rectifier portion that rotates together with the
armature. The pilot exciter is a permanent magnet generator that rotates with the main generator
rotor shaft. It feeds the exciter field windings with excitation current through the voltage regulator.
Since the exciter unit itself also requires dc current for excitation of its own stationary field coils, this is
furnished by a pilot exciter which is simply a PMG that is mounted on and rotates together with the
main rotor shaft.
It will be apparent that when starting the generator set, little or no direct current will be available for
excitation of either the main generator or the exciter fields, were it not for the action of the PMG pilot
exciter.
Permanent Magnet
Generator Field
Rotating
Rectifier
Assembly
Exciter Armature
Voltage regulator
The control of the arrangement is undertaken by the Voltage Regulator. As most are able to control
the generator automatically, they are known as Automatic Voltage Regulators, or AVR s.
The schematic on the previous page shows that the AVR is powered by voltage from the PMG. On
GT7300 & GT7400 power to the AVR will be available once K261 is energised (represented by
Contacts close at 65%NGP). Power is basically available if no over-voltage condition exists and Ngp
is > 80%.
The AVR is set to allow the generator to generate voltage of an amplitude which is determined by the
controls at the setup stage (Voltage Adjust Potentiometer in the schematic).This is achieved by the
AVR controlling the amount of DC current sent to the exciter field windings. The actual generator
output voltage is sensed by the AVR and this forms the feedback for the AVR control algorithm to
compare with the desired set voltage. If it is too high the field current output to the exciter field will be
reduced. If it is too low the exciter field current will be increased. The output current is also sensed to
allow load sharing with other generators to be achieved.
Although the frequency of the generator output voltage is largely determined by the rotational speed
of the rotor, which will be set and controlled by the prime mover, the frequency is also monitored by
the AVR to alter the control voltage characteristics as the frequency changes. Additional protection is
afforded by monitoring the current output to the exciter field for over current and also over voltage at
the generator output as well as loss of sense voltage. Over temperature operation of the AVR will
result in the AVR automatically turning itself off.
The AVR will need to be set to control the generator output voltage by a control scheme which will
differ if it is required to operate in parallel (load share) with other machines. If a generator is operating
alone ISOCH should be set for Voltage Control mode on S260. If either generator is to be paralleled
with other generators, DROOP mode should be selected for Voltage Control mode on S260-1. The
speed (frequency) should in both cases be set to ISOCH on SPD ISOCH/SPD DROOP Switch
(S/DS191).
Coupling
The rotational torque to drive the generator is transmitted from the engine through the gear unit and
then to the generator by connecting the gear unit output shaft to the generator rotor shaft with a
coupling. The coupling is designed to allow transmission of power only within certain limits.
Firstly, it is important to ensure that the alignment of the two shafts is within allowable limits of runout. This will ensure that not only is the coupling not exposed to excessive stress, but will ensure that
the shaft bearings are not adversely loaded and that vibration will be minimised.
Although the design will allow some mis-alignment to be accommodated and this is achieved by the
use of disc packs, whatever method is used, must be in a suitable condition for use. Disc packs are
normally made from thin steel sheets with the appropriate profile and holes formed on each sheet.
The sheets are then riveted together to form a laminated spacer, which is then installed in the
coupling assembly, by bolts which pass through the rivets. Misalignment is accommodated by the
sheets flexing slightly. Care should therefore be taken to ensure that the disc packs sheets are not
excessively cracked and that they are clean. Ingress of dirt, etc between the sheets can cause
abrasive wear and also possibly imbalance.
Secondly, to protect the engine and gear unit as well as the generator from potentially damaging
operating conditions, the coupling is also designed to shear if subjected to excessive torsional
forces. These could arise if the generator was subjected to a massive overload or more commonly, if
the generator was attempted to be synchronised Out of phase with the output bus. The shear
elements (basically mechanical fuses) are usually specially machined bolts or pins which connect
the coupling halves together, but are designed to shear (break) if the load they are transmitting
becomes too great. This then allows the engine to continue to drive the gear unit and the part of the
coupling connected to the gear unit output shaft, but the generator will no longer be driven by the
engine.
Flexible Coupling
These couplings eliminate the need for lubrication. However, lube oil may be present in the shaft
cover. Hubs are attached to the rotating equipment with splines and / or interference fit pilots. The
flexing of the coupling is accommodated through the use of flexible disks in a plane perpendicular to
the shaft centre line.
Sequence
Control
Protect
Display
Functional Discription
The control system is microprocessor-based and
customized for each application using a combination of input and output (I/O) modules. The system
controls scanning, monitoring, and reception of data. Data is processed in the Programmable Logic
Controller (PLC) and sent to output modules for transmittal to package control elements.
The control panel is electrical switch-based, allows command input, and indicates status.
The turbine package includes instrumentation to report operating conditions to the control system and
control devices to receive control output from primary or backup control systems. Control elements
are primarily electrical, electromechanical, and electrohydromechanical devices controlled by the
PLC.
Sequence
Sequencing functions control logic elements in the control system. Logic elements are (on/off,
open/close, start/stop, yes/no) events associated with switches, solenoids, relays, and comparator
devices. Sequencing monitors and senses events, and carries out computations to operate
components in the system.
Examples of sequencing elements include:
Start
Load
Stop
Postlube
Start
Manual actions to start the turbomachinery are:
Arm the system
Reset malfunctions
Select operating mode
Initiate start
After start is manually initiated, the system accomplishes the following:
Purge crank
Lightoff
Starter dropout
Lubrication check
Load
The load function maintains operating speed, loads the generator and transfers to steady state
control.[RUNNING] is highlighted on the operation summary screen.
When the engine reaches 90 percent speed, the ready to load timer starts to time.
When the ready to load timer times out, the READY-TO-LOAD light illuminates.
When [READY TO LOAD] is displayed on the operation summary screen, the generator can be
connected to the load bus by closing the generator circuit breaker. The circuit breaker can be closed
to a dead bus or a hot bus. When a dead bus is sensed, the circuit may be manually closed. When a
hot bus is sensed, the generator is synchronized to the load bus before closing the circuit breaker.
The voltage is matched to minimize flow of circulating current between the generators. The frequency
is matched to minimize initial loading and allow phase matching (synchronization). Phase is
synchronized to allow safe closing of the circuit breaker. Closing the circuit breaker when the
generator and load bus are out-of-phase
can cause equipment damage, and is not permitted by the control system.
Synchronization
Before the generator circuit breaker can be closed to the load or tie bus, the generator frequency,
voltage, and phase must be synchronized to the bus. The operator can manually synchronize the
generator to the load or tie bus, or the control system can automatically perform the synchronization
process. This process includes matching of the generator and load or tie bus voltage, frequency, and
phase.
To synchronize automatically, AUTOMATIC SYNCHRONIZE INITIATE is selected. The auto
synchronization fail timer starts timing and an AUTO SYNCH indication is displayed. The automatic
synchronizer matches the generator frequency, voltage, and phase to the load or ties bus and closes
the generator circuit breaker. When automatic synchronization is complete and the synchronization
check relay monitor permissive is closed, the circuit breaker closes and connects the generator to the
load bus. Indicators operate as described under dead bus.
If the generator circuit breaker does not close before the auto synchronization fail timer times out, the
generator circuit breaker lockout relay is activated. The automatic synchronization function is deenergized. The auto synch selection highlight is extinguished and the Auto Sync Fail alarm is
annunciated on the display screen.
Stop
Turbine shutdown can be manual or automatic with either a cooldown or fast stop.
Cooldown stop
Unloads the generator by reducing engine operating speed to idle, and starts the cooldown timer (5
minitues). If a start is re-initiated during the cooldown stop, the shutdown is aborted.
A start can be re-initiated during the cooldown period by pressing :- acknowledge, reset and start.
Fast stop
Unloads the gas compressor, (or generator) closes the fuel shutoff valves and stops the turbine
without a cooldown period
Manual shutdown
Is initiated by either activating the stop switch or the emergency stop switch. The stop switch provides
a cooldown stop and the emergency stop switch provides a fast stop. The gas compressor is
unloaded once a stop is initiated.
For a normal and/or station shutdown, compressor (or generator) load should be reduced before
initiating a stop.
When the gas compressor(or generator) is under a load and a malfunction occurs, the control system
unloads the compressor(or generator) and shuts off fuel to the turbine. The control system provides
both a cooldown stop (lockout or nonlockout) and a fast stop (lockout or nonlockout).
Emergency Stop
The Emergency Shutdown (ESD) is initiated by detection of a fire, backup overspeed system failure,
PLC failure, or the operator pressing the ESD switch.
The ESD stop unloads the gas compressor (or generator), closes the fuel shutoff valves and stops
the turbine without a cooldown period. Lube oil control for turbine rundown and postlube is controlled
by the backup relay system.
If an ESD stop has been initiated, the backup system must be reset with the BACKUP RESET
keyswitch and by pressing the ACKNOWLEDGE and RESET switches prior to restart.
Postlube
As the engine slows, the engine driven lube oil pump pressure decreases and the ac lube pump
starts. If the ac lube oil pump fails to
provide minimum pressure, the backup
pump is started.
Control
The control function monitors and
regulates process variables such as
speed, pressure, and temperature. The
function controls transient response to
load changes and controls actuators
during start, stop, and load.
Fuel Control
Turbine fuel flow control regulates
pressure and fuel flow. Fuel flow is controlled by regulating the electronic fuel control valve.
The fuel system establishes the fuel flow range by regulating fuel supply pressure and flow. Fuel
pressure is regulated to a value greater than Pcd between maximum and minimum valve positions.
The control system positions the electronic fuel control valve and regulates fuel flow to regulate
engine speed, power, and T5 temperature during lightoff, acceleration, steady state, and transient
load conditions.
Bleed Valve
Bleed valve position control regulates Pcd by routing airflow to the exhaust, bypassing combustor and
turbine.
During start and acceleration, the bleed valve avoids engine surge. During start and acceleration, the
bleed valve is opened to allow airflow to bypass combustor and turbine
.
An open bleed valve reduces turbine compressor back pressure and avoids engine surge, the bleed
valve position is determined as a function of kilowatt load.
Protect
The protect function monitors operating conditions, compares to limits, identifies when a limit is
exceeded, annunciates the fault, and initiates a stop if the fault is a shutdown-type malfunction.
A backup relay system protects in the event of PLC failure, fire, power turbine overspeed, or a
manual emergency stop.
Malfunction Alarm
The alarm task detects when a condition changes from normal to a level of concern. It annunciates
the problem to communicate that corrective action is required.
Malfunction Shutdown
The shutdown task detects when a danger level is reached, or a major malfunction occurs.
Shutdowns are one of four types:1. Cooldown Stop Nonlockout
2. Cooldown Stop Lockout
3. Fast Stop Nonlockout
4. Fast Stop Lockout
CN
CL
FN
FL
Microprocessor Fail
When microprocessor failure is detected, a fast stop is initiated and backup control is activated.
Fire Detected
When fire is detected, the backup system immediately sets the fast stop latch in backup control and
the shutdown sequence proceeds as with the manual emergency stop except enclosure fans, if
present, are stopped, and lube continues for engine rolldown, is stopped for 20 minutes, and, if the
PLC is functioning after the 20 minute hold, a postlube cycle is completed.
Turbotronics Display
The display function formats systems operating information, collects data, and provides the
information to the operator through the display device. The display device allows the operator to
monitor the operating conditions of the turbomachinery and perform limited turbine control functions.
This display device may provide historical as well as current information.
The display computer is an industrial personal computer (PC) with video display monitor and
software. The computer has a rear power switch and a floppy disk drive. The monitor has a color
display screen and two sealed-membrane keypads. The function keypad accesses display features
listed on the MENU SELECTION screen. Display software is on floppy disks.
Control Key
The CTRL (Control) key, with the ENTER key, activates or deactivates display functions indicated
with a blinking asterisk (*). With the PAGE DOWN key, the CTRL key prints the screen.
Cursor Controls
Up, down, left, and right arrow keys move the cursor on the screen.
On the MENU SELECTION screen, the green rectangle cursor highlights display feature blocks. In
stripchart screens, the blue bar cursor moves up or down to highlight a listed variables.
On the OPERATION SUMMARY screen, the cursor is a blinking asterisk.
Enter
The ENTER key activates the current selection.
On the MENU SELECTION screen, for example, after a display feature is selected (the block is
highlighted), pressing ENTER causes the selected screen to appear.
CTRL and ENTER keys activate the blinking asterisk function.
Escape
The ESC (Escape) key recalls the MENU SELECTION screen. The key cancels any operation in
progress.
Function Keys
Function keys, F1 through F10, SHIFT F1 through SHIFT F10, CTRL F1 through CTRL F10, and ALT
F1 through ALT F10, access MENU SELECTION display features.
To change from one screen to another, the function key is pressed, without returning to MENU
SELECTION. In lower level menu screens, function keys are used as prompted.
Number Keys
Number keys select options for loading software, resetting passwords, initializing the history file,
changing package constants (Kvals), initiating printing functions, and multi-package monitoring.
System Reboot
To reboot the system, turn power OFF and ON using the power ON/OFF push-button on the rear of
the computer. Reboot diagnoses and resets the system.
Display Screens
Display screens can be viewed in the on-line or the optional playback mode. Refer to SYSTEM
MANAGER display screen to access playback mode.
The MENU SELECTION
display screen contains the
display screen selection
blocks and will be the first
screen displayed after
power is supplied to the
operator interface display
computer.
Follow the instructions
provided on the message
at the bottom of each
screen for additional display
feature selections or
operating procedures.
line
On-line mode, some of the screens display real-time data being collected from the controller, and
others display data stored in the computer. When powered-up, the system is placed in the on-line
mode.
Playback mode, the screens only display data stored in the computer. The background display tasks,
such as alarm checking and data logging, continue to operate and real-time alarms are displayed at
the top of the screens. The FIRST OUT ALARMS, STRIPCHART, and PROGRAM CONSTANTS
display screens are not active in the playback mode. In the playback mode, the operator can
interrogate and view data in the EVENTLOG, TRIGGER, ELAPSED TIME, and HISTORY databases.
The screens that normally display stored data, in the on-line mode, are also used to select the
database to be viewed.
TEMPERATURE SUMMARY
The GENERATOR SUMMARY display screen displays generator operating values. The
displayed values include setpoint, alternator, bus, balance line, and power status.
ACKNOWLEDGE switch on the turbine control panel is pressed. As malfunctions are acknowledged,
they will stop flashing and remain highlighted on the screen until cleared from the system and the
RESET switch is pressed. In a single unit configuration, the first four malfunctions detected are
displayed at the top of all screens until cleared. In a multi-unit configuration, one alarm is displayed
per unit. The display screen is divided into four columns. At the left is the date, in the center is the
time, and on the right is the alarm designation and description. If more alarms have occurred than will
fit on one page, the additional alarms can be viewed by pressing the PAGE UP/PAGE DOWN keys
on the number/control keypad.
Noncritical alarms are shown in yellow. Critical alarms (shutdowns) are shown in red.
Unacknowledged alarms blink in yellow highlights with black letters. Acknowledged alarms appear
unblinking in reverse video (yellow letters on black background).
The FIRST OUT ALARMS display screen shows only unacknowledged alarms in the order in which
they occurred.
The METERS display screen shows, in real time, all the monitored functions in a bar-graph format.
Up to 33 meters are displayed on each page. When a transmitted value is under or over range, the
color will change to blinking blue color to indicate this condition.
Press the PAGE UP or PAGE DOWN to display more Meters.
Use the following procedures to select and display variables in stripchart format.
1. Use PAGE UP/PAGE DOWN keys to view all available titles of analog variables.
2. Select any four variables to be displayed in stripchart format.
3. Use the arrow keys to move the highlighting bar up or down to each of the selected variables.
4. Press ENTER after each selection.
5. When all four variables are selected, press ENTER once again to view the stripcharts of the
four selected variables, or press ESC to clear.
The second screen emulates a four-pen stripchart recorder to monitor the selected analog variables.
The stripcharts displays raw, real time data.
After viewing original stripcharts, to choose four different variables for display, return to the selection
screen by pressing the ESC key at the stripchart screen.
The system will return to the MENU SELECTION display screen.
Choose the STRIPCHART display screen.
When at the STRIPCHART display screen, displaying the titles of the analog variables, press the
ESC key to clear the entries.
Select four different variables as described in Steps 1 through 5.
When done, press the ESC key to return to the MENU SELECTION display screen.
The stripchart display screens are not available in playback mode.
Use the following procedures to select and display variables in stripchart format.
1. Use PAGE UP/PAGE DOWN keys to view all available titles of analog variables.
2. Select any four variables to be displayed in stripchart format.
3. Use the arrow keys to move the highlighting bar up or down to each of the selected
variables.
4. Press ENTER after each selection.
5. When all four variables are selected, press ENTER once again to view the stripcharts
of the four selected variables, or press ESC to clear.
6. When the stripchart screen appears, the stripcharts will be blank.
7. Select the desired time interval for display.
8. Press the function key for desired time interval. Function keys F1 and F2 offer the
fastest changing historical data available.
9. Function key F7 offers the slowest changing historical data available.
10. When the stripcharts reflect data, move the vertical line with the left and right arrow
keys over the data to display the value and time for specific data points.
The second screen shows the data in stripchart form. The data is conditioned and historical rather
than raw and real-time. The stripchart display also includes a bar graph and digital indicator that show
the current value of the data point.
In the playback mode, when viewing Analog History data, the time interval in effect will remain the
same as the time interval chosen in the Analog History option. If the operator is looking at the data in
the minutes time-base, after exiting the option, the data shown is the minutes data from the History
file, until another database or time interval is chosen.
Moving the vertical line with the left and right arrow keys over the data, in playback mode, selects the
ANALOG HISTORY database and record group that will also be viewed in other applicable screens.
Press the END key to move the view to the oldest data point displayed (last point displayed
on left-most side).
Press the HOME key to move the data to the most recent data point displayed (last data point
on the right-most side).
To display the same variables but at a different time interval. Press the function key for the
desired new time interval.
To choose four different variables, return to the selection screen by pressing the ESC key at the
stripchart screen. The system will return to the MENU SELECTION display screen.
Choose the ANALOG HISTORY display screen.
When at the ANALOG HISTORY display screen, displaying the titles of the analog
variables, press the ESC key to clear the entries.
Select four variables as described in Steps 1 through 6.
When done, press the ESC key to return to the MENU SELECTION display screen.
Use the following procedures to select and display variables in stripchart format.
1. Use PAGE UP/PAGE DOWN keys to view all available titles of analog variables
2. Select any four variables to be displayed in stripchart format.
3. Use the arrow keys to move the highlighting bar up or down to each of the selected variables.
4. Press ENTER after each selection.
When all four variables are selected, press ENTER once again to view the stripcharts of the four
selected variables, or press ESC to clear selections.
The second screen shows the data in stripchart form. The predictive trend feature can be used to
identify and schedule requirements for corrective or preventive maintenance.
When the stripchart screen appears, the stripcharts will be blank. Select the desired time interval for
display. Press the function key for desired time interval. Function keys F1 and F2 offer the fastest
changing historical data available. Function key F7 offers the slowest changing historical data
available.
When the stripcharts reflect data, move the vertical line with the left and right arrow keys over the
data to display the value and time for specific data points.
Moving the vertical line with the left and right arrow keys over the data, in playback mode, selects the
ANALOG HISTORY database and record group that will also be viewed in other applicable screens.
Press the END key to move the view to the oldest data point displayed (last point displayed on leftmost side).
Press the HOME key to move the data to the most recent data point displayed (last data point on the
right-most side).
To display the same variables but at a different time interval, press the function key for the desired
new time interval.
To choose four different variables, return to the selection screen by pressing the ESC key at the
stripchart screen. The system will return to the MENU SELECTION display screen.
Choose the PREDICTIVE TREND display screen.
When at the PREDICTIVE TREND display screen, displaying the titles of the analog variables, press
the ESC key to clear the entries.
Select four variables as described in Steps 1 through 6.
When done, press the ESC key to return to the MENU SELECTION display screen.
The predictive trend stripchart display screen is divided into two sections. The left side shows a plot
using real-time package operation, the right side displays the predicted values of operation. A graphic
plot is developed using data points collected during package operation. Data points are compressed
by using an averaging period. The averaging period is based on designated time intervals from 1
second to 10 000 hours. The time interval for predictive trend is the same as analog history. The plot
is developed by using intervals of time as data points.
When the predicted curve, on the right side of the plot, is not on the screen, assume that the
prediction is off scale, and reexamine the variable values. Alarm or shutdown values associated with
the selected variables may be read by moving the cursor, with the arrow keys, from the left side of the
graph to the right side. Alarm levels are shown in yellow and shutdown levels are shown in red.
In playback mode, when viewing the predictive trend data, the time interval will remain the same as
the time interval chosen in the predictive trend option. If the operator is exiting this option while
looking at future data, the point of entry will be the latest, or center point displayed.
The second screen, ELAPSED TIME DATA, shows the data in stripchart form.
This elapsed time data feature provides a file of analog data showing the actual conditions at specific
intervals of time. This allows for plotting of the actual operating duty cycle of the equipment over long
periods of time by showing start and stop events and operating power levels.
Use the following procedures to select and display variables in stripchart format.
1. Use PAGE UP/PAGE DOWN keys to view all available titles of analog variables.
2. Select any four variables to be displayed in stripchart format.
3. Use the arrow keys to move the highlighting bar up or down to each of the selected variables.
4. Press ENTER after each selection.
5. When all four variables are selected, press ENTER once again to view the stripcharts of the
four selected variables, or press ESC to clear.
6. When the stripchart screen appears, the stripcharts will be blank.
Select the desired elapsed time interval for display. Function keys F2 and F3 offer the fastest
changing elapsed time data. Function key F6 offers the slowest changing elapsed time data.
When the stripcharts reflect data, move the vertical line with the left and right arrow keys over the
data to display the value and time for specific data points. When the plot is larger than the screen
display, function keys F2 (left) and F6 (right) may be used to shift the screen viewing area.
Moving the vertical line with the left and right arrow keys over the data, in playback mode, selects the
ELAPSED TIME database and record group that will also be viewed in other applicable screens.
Press the END key to move the view to the oldest data point displayed (last point displayed on leftmost side).
Press the HOME key to move the data to the most recent data point displayed (last data point on the
right-most side).
Press function key F4, NEWSTEP, to select a new time interval. The data shown on the stripchart is
historical. When a new time interval is selected, the latest data available is
displayed.
To choose four different variables, return to the selection screen by pressing the ESC key at the
stripchart screen. The system will return to the MENU SELECTION display screen.
Choose the ELAPSED TIME SELECT display screen.
When at the ELAPSED TIME SELECT display screen, displaying the titles of the analog variables,
press the ESC key to clear the entries.
Select four variables as described in Steps 1 through 6.
When done, press the ESC key to return to the MENU SELECTION display screen.
In playback mode, when viewing the elapsed time data, the time interval will remain the same as the
time interval chosen in the elapsed time option.
Use the following procedure to select and display analog variables and trigger files in stripchart
format.
1. Use PAGE UP/PAGE DOWN keys to view available titles of analog variables.
2. Select four analog variables to be displayed or select the same analog variable four times to
view the variable over more than one time frame.
3. Use arrow keys to move highlighting bar up or down to select analog variables.
4. Press ENTER after each selection.
5. When four analog variables are selected, press ENTER to view the trigger file, or press ESC
to clear.
6. Use arrow keys to move the highlighting bar up or down to each of the trigger files.
7. Press ENTER after each selection. As each file is selected, the file name is displayed next to
the analog variable on the lower portion of the screen.
8. When four files are selected, press ENTER, or press ESC to clear. When ENTER is pressed,
the screen clears, the files are read, and data are displayed in stripchart format.
9. When the stripcharts show data, move the vertical line with the arrow keys over the data to
display value and time for specific points.
The second, shows optional trigger files for selected analog variables.
Moving the vertical line with arrow keys over the data, in playback mode, selects the TRIGGER
database and record group that will also be viewed in other applicable screens.
Press the ESC key to return to the MENU SELECTION display screen.
While being viewed, the DISCRETE EVENT LOG display screen is not updated to display new
events. To view the latest list of discrete events, press ESC key to return to MENU SELECTION
screen and select the DISCRETE EVENT LOG screen as described above.
Selecting DISCRETE EVENT LOG display screen, in playback mode, selects the EVENTLOG
database that will be viewed in other applicable screens.
Use the number/control keypad to enter the password and press ENTER. When the correct password
has been entered, functions from the menu may be selected.
Enter the function's corresponding number using the number/control keypad and pressing ENTER.
The available display system functions are shown on the screen. The screen includes: Exit to DOS ,
Set New Password,Disable Printer, Purge Print Buffer, Playback Remote, and select Controller
Maintance.
0.
EXIT TO DOS
CAUTION
The EXIT TO DOS command should be entered only by operators familiar with operating systems.
Menu item 0 (EXIT TO DOS) should be accessed by qualified maintenance personnel only.
EXIT TO DOS function allows the operator to exit the display program and access DOS (disk
operating system).
2. DISABLE PRINTER
Selecting this option will either disable or enable the printer.
4. .PLAYBACK REMOTE
The off-line playback mode allows the interrogation of previously saved data files on the
operator interface display or other desktop PC as described below.
Playback mode, the screens only display data stored in the computer. The background display tasks,
such as alarm checking and data logging, continue to operate and real-time alarms are displayed at
the top of the screens. The FIRST OUT ALARMS, STRIPCHART, and PROGRAM CONSTANTS
display screens are not active in the playback mode.
In the playback mode, the operator can interrogate and view data in the EVENTLOG,
TRIGGER, ELAPSED TIME, and HISTORY databases.
The screens that normally display stored data, in the on-line mode, are also used to select the
database to be viewed.
DAILY LOG
The DAILY LOG is selected from the MENU SELECTION display screen by pressing appropriate
function key or by positioning the cursor to the DAILY LOG block with the up, down, left, or right arrow
keys and pressing ENTER. This issues a command to print out the DAILY LOG. The DAILY LOG IS
NOT A DISPLAY SCREEN. The DAILY LOG gives a print out of selected data for the last 24 hours
and includes minimun,maximum and average readings for the selected data.
STATUS PRINT
The STATUS PRINT is selected from the MENU SELECTION display screen by pressing
appropriate function key or by positioning the cursor to the STATUS PRINT block with the up, down,
left, or right arrow keys and pressing ENTER. This issues a command to print out the STATUS
PRINT. The STATUS PRINT IS NOT A DISPLAY SCREEN. The STATUS PRINT gives a print out of
selected data at the time of selection.