org
Published in IET Generation, Transmission & Distribution
Received on 11th March 2009
Revised on 23rd July 2009
doi: 10.1049/iet-gtd.2009.0129
ISSN 1751-8687
Frequency-domain modelling of
sub-synchronous torsional interaction of
synchronous machines and a high voltage
direct current transmission link with
line-commutated converters
P. Fischer de Toledo* L. Angquist H.-P. Nee
Division of Electrical Machines and Power Electronics, Royal Institute of Technology, Stockholm S-100 44, Sweden
*ABB AB HVDC
E-mail: paulo.scher@se.abb.com
Abstract: The authors describe a model of a system that includes a high voltage direct current (HVDC)
transmission link with line-commutated current source converters (LCC) closely connected to a synchronous
generator used to perform analysis of sub-synchronous torsional interaction (SSTI) in the frequency domain.
The model of the HVDC transmission link adequately represents the converters in the frequency domain and
includes all essential controls for the operation of the converters, including a new sub-synchronous damping
control used to mitigate interaction between the rectier LCC and the shaft of the synchronous machine. The
frequency domain model has been validated against time domain simulations showing good agreement.
Introduction
and machine impedance has a resonance at a subsynchronous frequency close to one of the natural modes of
torsional oscillation of the machine.
In addition to the phenomenon related to series
compensation, it is possible to excite and destabilise
mechanical torsional modes through the action of
conventional control in the power plant such as the turbinegovernor [5], generator excitation system [6] and the power
system stabiliser [7]. These sub-synchronous torsional
oscillations (SSO) are a result of control interaction rather
than electrical resonance from SSR. The problem in this
case is primarily due to the use of mechanically derived
speed signals in the feedback control system.
A third cause of concern with regard to torsional modes is
that of sub-synchronous torsional interactions (SSTI)
because of other transmission equipment such as static var
compensator [8, 9] or HVDC [10, 11]. In the case of
series capacitors, the device causing the potential SSR
IET Gener. Transm. Distrib., 2010, Vol. 4, Iss. 3, pp. 418 431
doi: 10.1049/iet-gtd.2009.0129
www.ietdl.org
problem is a passive device, and thus modied operating
practices and/or an active damping controller on the
generating unit in question is needed to mitigate the
problem. In the case of SSTI, however, the most effective
solution is to design carefully the controls of the connected
system to eliminate the SSTI problem. The Square Butte
project was the rst to encounter SSTI involving an
HVDC converter (1977). The trip of a nearby AC
transmission line initiated an exponentially growing
oscillation, where the HVDC converter amplied the
11.5 Hz torsional mode of the turbine generator from a
nearby generation station. The HVDC controls were
subsequently tuned to avoid the problem [10].
To illustrate the phenomenon of SSTI, consider the
diagram in Fig. 1.
The natural torsional vibrations of a turbine generator
system produce a slight modulation of the speed of the
generator. This results in a variation in the terminal voltage
of the machine. The voltage variation in phase and
amplitude at the machine produces a current variation at
the HVDC converter terminal, which consequently causes
variation in the DC-side voltage and current. The
regulators within the HVDC converter respond, and this
will produce a change in the electrical torque of the
machine causing a closed-loop control interaction.
As the phenomena of SSR, SSO and SSTI are concerned
with the stability of torsional mechanical modes on the shaft
of a turbine generator system, they are mostly associated
with the small-signal response of the system. This is the
main scope of this paper. Large-signal conditions such as
electrical faults, clearing of transmission lines, high-speed
re-closing of transmission lines, by-pass and re-insertion of
series capacitors on a transmission line during disturbances
etc. can result in damaging transient torques on turbine
generator shafts. These large-signal response cases are not
considered in this paper.
Small-signal phenomena are most effectively analysed by
using either modal analysis or by calculation of damping
and synchronising torques. The disadvantage of modal
analysis (or eigen-analysis) is that it is necessary to model
both the mechanical and electrical systems in detail.
System model
www.ietdl.org
(1)
ui v0 t di
(2)
420
& The Institution of Engineering and Technology 2010
um Q0 (2H )1=2 u
(3)
IET Gener. Transm. Distrib., 2010, Vol. 4, Iss. 3, pp. 418 431
doi: 10.1049/iet-gtd.2009.0129
www.ietdl.org
to Q, (1) becomes
u m Dm u_ m K m um Q0 (2H )1=2 T
(4)
Pe
vg
@T e
@v g
damping
(5)
De
(6)
in
per-unit
" #
@T e [@Pe =@vg ]
Pe0
De
@vg
vg0
v2g0
(with
(7)
@P
e Pe0
@v g
For constant power, which is the inherent characteristic of an
HVDC rectier, the rst term in (7) is zero, so the change of
www.ietdl.org
(8)
following
windings;
u for the
in the ab
(12)
vs Ris
cs [cf , cD , ca , cb , cG , cQ ]
422
& The Institution of Engineering and Technology 2010
(9)
(10)
(11)
dcs
dt
(13)
vs Ris
d s
[L (u)is ]
dt
(14)
www.ietdl.org
This may be simplied to
dDi
L1 [R vN N ]Di L1 B1 Dvs
dt
L1 N i0 Dvr
(15)
di
dt
(16)
(17)
i i0 Di
vs vs0 Dvs
(19)
(21)
Dv dq
s
Dvds
Dvqs
d
q
, Dvs ; Dvdq
s Dvs jDvs :
(22)
(23)
DT e iT0 T M Di
(24)
or
(20)
IET Gener. Transm. Distrib., 2010, Vol. 4, Iss. 3, pp. 418 431
doi: 10.1049/iet-gtd.2009.0129
www.ietdl.org
and DC sides can be related by simple expressions of the type
2
iV (t) K I (t)iD (t)
3
(25)
(28)
(26)
8
2
2 I
I
>
>
< DiV (t) 3 DK (t)ID0 (t) 3 K 0 (t)DiD (t)
Du (t) Re{DK U (t)uV 0 (t) K U
>
0 (t)DuV (t)}
>
: D
C
Ducomm (t) Re{DK (t)uC0 (t) K C
0 (t)DuC (t)}
and
uD (t) Re{K U (t) uV (t)}
(27)
Based on (28) a generic small-signal model of the linecommutated converter can be made. The whole system can
be represented by the simplied block diagram shown in
Fig. 9. Fig. 9 also shows the action from the direct current
control (represented by the G1 transfer function), direct
voltage controller (transfer function G5) and the new
rotating coordinates obtained from the phase-locked loop
(PLL) the dynamics of the controller is represented by a
proportional/integral (PI) regulator, which is indicated by
the G PLL transfer function. The sub-synchronous damping
control (SSDC) is also represented, which has a
characteristic of a band-pass lter and which is indicated by
the G SSDC transfer function.
IET Gener. Transm. Distrib., 2010, Vol. 4, Iss. 3, pp. 418 431
doi: 10.1049/iet-gtd.2009.0129
www.ietdl.org
4.2.3 Description of the main controls included in
the LCC model
Direct current control: The block G1 in Fig. 9 represents the
dynamics of the current control path, which typically is an
ordinary PI regulator.
PLL: The control system operates in the coordinate system
dened by the PLL. The PLL is arranged to follow the
lter bus voltage, which normally is selected to be the
system reference. The PLL detects the argument of
the voltage. During dynamic conditions the dynamics of
the PLL have to be included as they affect the converter
in the same way as the current controller by changing the
control angle a.
As the PLL operates on the lter-bus side of the converter
transformer, the argument of the lter-bus voltage is
calculated from uC0 (t) u^ C0 ej(vN tfC ) . For small-signal
variations the corresponding argument of the voltage to be
used as input to the PLL can be approximated by
Duin
PLL
(uC0 DuC )
DuC
arg
Re j
u^ C0 ej(vN tfC )
u^ C0 ej(vN tfC )
(29)
j
u^ C0 ej(vN
tfC )
(30)
(31)
with
PLL
u^ C0
j
ejfC
(32)
kPLL (1 stPLL )
G(s=vc )
stPLL
1 2z (s=vc ) (s=vc )2
(35)
GPLL
Duin
1 GPLL PLL
(33)
kPLL (1 s tPLL ) 1
s tPLL
s
(34)
In the equation kPLL is the PLL gain and tPLL is the PLL
integral time constant.
SSDC controller: Together with the direct current control
path an additional path via the block GSSDC used to
mitigate possible SSTI interaction is added. As the current
IET Gener. Transm. Distrib., 2010, Vol. 4, Iss. 3, pp. 418 431
doi: 10.1049/iet-gtd.2009.0129
YHVDC (s)
DiH (s)
DuC (s)
(36)
www.ietdl.org
4.3 Solving the AC network
4.3.1 General: The angular variation of the synchronous
machine causes a modulation of the machine current iM
(see Fig. 3). This current can be subdivided into several
components: the contribution to the innite source iS , the
lter current iF , and the current to the HVDC system iH .
In this section, it is described how these current
components are related to the terminal voltage of the
machine uM .
From the network the following equations can be derived,
assuming that all variables are given in the uC reference
frame, or grid system as indicated by a superscript g.
8
dqg
dq
dqg
>
>
< DuC ZS DiS
dqg
dq
dqg
DuC ZF DiF
>
>
: Dudqg (1=Y dq )Didqg
H
C
HVDC
C 4 L1 N i0
Equation (42) can be written as
dDi
(C 1 C 2 )Di C 3 Du C 4 Dvr
dt
C 10 iT0 T M
(38)
dq
DiM
dq
DiS
dq
DiF
dq
DiH
(45)
DT e C 10 Di
(44)
(43)
C 3 L1 B1 B14
(37)
(42)
Di
z
Du
(47)
(39)
is introduced. Using this new state variable, (44) and (46)
take the following form
yields
dq
dq
(40)
dq
dq
dq
dq
DiM bDu
dq
dq
ZM DiM
a
(41)
8
< z_ C1 C2 C3 z C4 Dv
r
0
0
1
:
DT e C10 0 z
(48)
C1 C2
C3
0
C5
C6
C4
1
C 7 C10
(49)
0
z_ C5 z C 6 Dvr
DT e C7 z
(50)
IET Gener. Transm. Distrib., 2010, Vol. 4, Iss. 3, pp. 418 431
doi: 10.1049/iet-gtd.2009.0129
www.ietdl.org
Using Laplace theory z can be solved for explicitly. The
result is
z (sI C5 )1 C6 Dvr
(51)
(52)
DT e (s)
C7 (sI C5 )1 C6
Dvr (s)
(53)
Application
0:69
1000
4660
UIF
(54)
427
www.ietdl.org
interaction factor is greater than 0.1. This is in accordance to
the recommendations made in the EPRI research report [7].
Fig. 10 shows plots of the electrical damping De Re(Ge )
as a function of frequency for the synchronous machine
inuenced by the converters of the HVDC transmission link.
In order to validate the results this specic case has been
modelled in the time-domain digital simulator (PSCAD/
EMTDC). The evaluation of the electrical damping is
made by frequency scanning, where the angular frequency
is swept from a value close to zero to the synchronous
frequency. The modulating signal is applied to the shaft of
the turbine-generator and by measuring (both amplitude
and the phase) the corresponding electrical torque the
transfer function Ge can be calculated.
In Fig. 10a a plot for the base case conguration is
compared to time-domain simulations performed in
PSCAD/EMTDC. In this case the synchronous machine
delivers 840 MW and 202 MVAr of power, while the
HVDC transmission link operates at nominal conditions,
having the rectier ring angle set to 158. The results show
very good agreement between the frequency-domain and
time-domain simulations.
The small differences observed between the frequency
domain model and results obtained from time-domain
simulations are due to approximations made in the
converter model (see [1] and [2]), estimation of the phasor
in the measurement made in the time-domain simulation,
and, to some extent, the slope in the frequency when
sweeping the angular frequency while scanning the
frequency.
Fig. 10b illustrates the inuence of the SSDC damping
controller, comparing the conditions having the controller
activated and de-activated. The circle in red highlights the
action of the SSDC regulator.
Finally, in Fig. 10c the impact of the strength of the
connected AC network on De is shown. Here, a weak
network with a short-circuit power of 1500 MVA
(TIF 0.69) and a strong network having a short-circuit
power of 9000 MVA (TIF 0.1) are compared. The case
with a strong connected AC network shows marginal
interaction between generator and HVDC converters,
conrming the recommendations of EPRI in [7].
Conclusions
Acknowledgments
References
www.ietdl.org
[6] WATSON W., COULTES M.E.: Static exciter stability signal on
large generators mechanical problems, IEEE Trans. Power
Appar. Syst., 1973, pp. 204 211
[7] HVDC system control for damping of sub-synchronous
oscillations. EPRI research project RP1425-1, December 1981
[8]
FOUAD A.A.:
fs
f as
fb
s
f
and f fd
q
Then
f eJuN f s
or
Appendix 1
fd
fq
sin uN
cos uN
cos uN
sin uN
fas
fbs
where
e
JuN
sin uN
cos uN
cos uN
sin uN
and
0 1
J
1 0
fas
fbs
cos uN
sin uN
sin uN
cos uN
"
fd
fq
IET Gener. Transm. Distrib., 2010, Vol. 4, Iss. 3, pp. 418 431
doi: 10.1049/iet-gtd.2009.0129
where
JuN
cos uN
sin uN
sin uN
cos uN
429
www.ietdl.org
10
Appendix 2
12
Perturbation
A small perturbation is added to the rotor speed, denoted by
Dvr , such that the rotor speed is given by
vr vN Dvr
The rotor position u is related to the rotor speed as
u_ vr vN Dvr
It is possible to dene the deviation of the rotor position
because of a small perturbation in the rotor as
Du u uN ,
uN vN t
Appendix 4
11
Appendix 3
3
Lmd Lmd Lmd 0
0
0
6 Lmd Lmd Lmd 0
0
0 7
6
7
6 Lmd Lmd Lmd 0
0
0 7
6
7
Lm 6 0
0
0 Lmq Lmq Lmq 7
6
7
4 0
0
0 Lmq Lmq Lmq 5
0
0
0 Lmq Lmq Lmq
Ll diagb Lf l LDl Lsl Lsl LGl LQl c
2
3
0
0
0
0
0
0
6 0
0
0
0
0
0 7
6
7
6 0
0
0
(Lmq Lsl ) Lmq Lmq 7
7
N 6
6 Lmd Lmd (Lmd Lsl )
0
0
0 7
6
7
4 0
0
0
0
0
0 5
0
0
0
0
0
0
2 3
2
3
1
0 0
607
60 07
6 7
6
7
607
61 07
6
6
7
7
B0 6 7 and B1 6
7
607
60 17
405
40 05
0
0 0
2
3
0
0
0
Lmd
0
0
6 0
0
0 7
0
0
Lmd
6
7
6 0
L
)
0
0 7
0
0
(L
d
q
7
TM 6
6 Lmd Lmd (Ld Lq )
0
Lmq Lmq 7
6
7
4 0
0
Lmq
0
0
0 5
0
0
0
0
0
Lmq
430
& The Institution of Engineering and Technology 2010
8
p
>
< vd0 jvS0 j cos b0
p2
>
: vq0 jvS0 j sin b0
2
and
8
p
>
< i d 0 jiS0 j cos
b0 w0
2
p
>
: i q0 jiS0 j sin
b0 w0
2
www.ietdl.org
The excitation voltage E 0 , that is, the voltage behind the
synchronous impedance, or the steady-state internal
voltage, also lies along the q-axis and can be calculated from
jE 0 j jE q0 j vq0 xd i d 0
Finally, the eld current is obtained from
if 0
jE q0 j
Step-up transformer:
Nominal rating: S 1000 MVA
X 0.1265 pu
Network:
Nominal voltage: 422.5 kV
xmd
13
Appendix 5
Synchronous generator:
Nominal rating: S 1000 MVA
Xd 1.8 pu
Xq 1.7 pu
Xdp 0.245 pu
by
equivalent
14
Appendix 6
Xqp 0.43 pu
Xdb 0.19 pu
Xqb 0.19 pu
Lsl 0.06 pu
Td0p 5.3 s
Tq0p 0.54 s
Td0b 0.038 s
Tq0b 0.095 s
Rs 0.003 pu
IET Gener. Transm. Distrib., 2010, Vol. 4, Iss. 3, pp. 418 431
doi: 10.1049/iet-gtd.2009.0129
431