OLTC Position Indicators
Drive Position Sensors

MNPP ANTRAX

CATALOGUE
OF PRODUCTION

OLTC Position Indicators ..................................................................................................... 3


Multifunctional Indicator UP 25........................................................................................ 4
Pointer Logometer UP 30 .................................................................................................. 7
OLTC Position Indicator-Regulators .................................................................................... 9
Indicator-Regulator UP 100 ............................................................................................. 10
Indicator-regulator UP 200 .............................................................................................. 11
Drive Position Sensors ........................................................................................................ 12
Tap Sensor DP-1 .............................................................................................................. 13
Tap sensor DP-2............................................................................................................... 13
Tap sensor DP-3............................................................................................................... 14
Tap sensor DP-4............................................................................................................... 15
Tap Sensor DP-5 .............................................................................................................. 15

MNPP ANTRAX

OLTC Position Indicators

OLTC Position Indicators


Small Enterprise Research and Production Company ANTRAX" (MNPP ANTRAX) develops and manufactures one- and two-figure digital position indicators for On-Load Tap Changer (OLTC) drives (logometers).
Available types of digital position indicators are: UP1, UP2, UP21, UP22, UP23, UP25, UP30, UP31 and UP32.
These indicators are intended for OLTC position indication in both domestic and foreign drive units, as well as for
transfer of digital drive position data to Automatic Control Systems (S).
Available logometers perfectly fit a wide range of drive units operated in Russia and CIS.
Drive/Change Type

Position Indicator Type

3RNOA-110/1000

UP31

UP 25

ED100-S

UP 2, UP 4, UP 23, UP 41

UP 25

ED-S

UP 2, UP 4, UP 23, UP 41

UP 25

EM-1

UP 2, 4, UP 23, UP 41

UP 25

PC-3, PC-4

UP 2, UP 22, UP 23, UP 41

UP 25

SAV1-1600-245/245-013

UP 2, UP 4, UP 23, UP 41

UP 25

MA-1

UP 31

UP 25

MAK-1

UP 31

UP 25

MZ-3, MZ-4

UP 2, UP 22, UP 23

UP 25

PDP-4

UP 31

UP 25

PDP-4U

UP 31

UP 25

RNOA

UP 31

UP 25

RNOA -110/1000

UP 31

UP 25

RNOA-220

UP 31

UP 25

RNT -13

UP 31

UP 25

RNT -20

UP 31

UP 25

RNT -20A

UP 31

UP 25

RNT-20A-625/35

UP 31

UP 25

MAK-1/49

UP 32

Indicator UP 1 provides one-digit indication and operates with drive position resistive sensors. Indicators
UP 2x, UP 3x provide two-digit indication and operate with OLTC drive units c/w contact, resistive, current, encoding or contactless rate-of-turn sensors (subject to an indicator variant).
Indicators UP 22, UP 25-Bl, UP 31-Bl and UP 32-Bl allow presetting steps for OLTC position blocking.
Once a drive reaches a blocked step the red LED turns on at the control panel, and the RP25 relay actuating signal is
fed to UP 22 output terminals to block a drive units operation.
All indicators (except for UP 1) can be factory set to any number of drive positions (up to 99). UP 1 indicator is always set to 9 positions. Indicators UP 23, and UP 25 can be connected to any drive units equipped with resistive sensors (for example, MZ-2, MZ-4, ED-S, MR). Number of steps and resistance between the steps can be
changed to comply with specific Customer requirements.
Indicators UP 31 and UP 32 are designed for operation with the drives complete with synchro transmitter.
These indicators are directly connected to standard synchro transmitter of BD404/BD1404 drives.

MNPP ANTRAX

OLTC Position Indicators

All position indicators have a digital output for OLTC position transfer via RS-232 and/or RS-485 interface,
using the MODBUS-ASCII or MODBUS-RU protocol, with the speed up to 115200 Bod. Indicators UP 23, UP 25,
UP 31, UP 32, UP 41 can also be equipped with additional analog output 0-5 mA, 0-20 mA or 4-20 mA (current
loop).
OLTC
current
tapping
step
measured
value
will
be
displayed
on
10 000 mCd LED indicator which allows Operator to easily read the data at his/her workstation at any light conditions. Indicators UP 23, UP 25, UP 31, UP 32 main features:
- lead-wire compensation option
- step-by-step calibration of live fixed-position transformer.

Multifunctional Indicator UP 25
Multifunctional indicator UP 25 has been jointly developed with Federal Grid Company of United Power
System of Russia (FSK EES). The indicator comprises the functions of all the indicators mentioned above.
Our devices can be connected to the following OLTC drive step sensors:
- resistive sensor..(MZ-2, MZ-4, MR type drives and others)
- synchro transmitter BD404, BD1404..(RNT, PDP type drives and others)
- several synchro transmitters..(MAK-1/49 type drives)
- current sensor..(EM, MR type drives and others)
- digital BCD sensor..(MR, Huamin type drives and others)
- digital Gray code sensor..(MR type drives)
- digital sensor with RS-485 interface.. MZ-4, RNT, PDP type drives and others c/w DP-3/DP-4).
Versatility of UP 25 indicator means that all inputs and outputs are integrated in one device, so that our
Customers do not need to order different modifications and types of indicators. Such a "single-device approach
ensures both indication of transformer step data on the control switchboard and transfer of such data to Process
Control Systems (PCS) and other automated systems. The device can be easily set up for some other sensor type;
even if you change your drive unit it is not necessary to change the indicator. Versatility and availability of different
kinds of outputs allow integrating the device with any PCS.

MNPP ANTRAX

OLTC Position Indicators

UP indicator can be connected to any type sensors

MZ-2
MZ-4
MR
ED-S

TM, PCS

4...20

RS

-48

ED-S
...

RS-485

PDP-1
PDP-4
RNT-13
...

mA

The functions of actuator


control

Connection of position indicators to the TM system

MNPP ANTRAX

OLTC Position Indicators

Brief Functional Characteristics


Types of Sensors Connected
Indicator

Available outputs (on request)

Synchro Current sen- Resistive sen- BCDRS-485RS-232 BL RS-485 TP


sor
sor
encoder
transmitter

RV

UP-1

UP -2

UP -4

UP -22

UP -23

UP -25

UP -30

UP -31

UP -32

UP -41

Enclosures
The logometers are available in panel-mounted enclosures 138x138 mm, 91x91 mm, 110x110 mm,
138x67 mm, 44x91 mm for die-cut holes (this facilitates installation of indicators into control switchboard panel),
as well as in wall-mounted enclosure 120x120 mm for direct in-drive installation. Enclosures of other sizes are
available on Customer request.

Enclosure G, 91 91
Enclosure V, 110 110
Enclosure B, 138 138

Enclosure D, 67 138

Enclosure E, 48 96
Enclosure A, wall-mounted

MNPP ANTRAX

OLTC Position Indicators

Overall Dimensions of Indicators

A, wall-mounted
B, panel-mounted
V, panel-mounted
G, panel-mounted
intermediate frame
G, panel-mounted
D, panel-mounted
E, panel-mounted

Height

Width

Depth

Die-cut hole dimension, mm

120
144
120

120
144
120

64
84
96

138x138
110x110

96

96

111

110x110

96
72
48

96
144
96

111
114
96

91x91
67x138
44x91

Overall dimensions, mm

Enclosure type

with

OLTC Position Indicators (UP Type (Logometers)) - Technical Specifications:


Supply voltage
Power consumption, not more than
Indicator light intensity
Maximum current at control relay terminals
Maximum allowable voltage at control relay terminals
Temperature range
Warranty period
Service life period

~220 V 20%
15 W
10000 mCd
120 mA
400 V
-40 .. +50C
5 years
12 years

Pointer Logometer UP 30
Position indicator UP-30 is designed to point out positions of transformer c/w on-load tap changers. It operates in indication mode and is connected to synchro transmitter BD 1404.
Technical Specifications:
Nominal voltage
Nominal frequency
Operation conditions:
- temperature range
- relative humidity at 25C
Overall dimensions
Weight, not more than
* to be specified when ordering

110 V
50/60* Hz
+10 ... +25C
80%
120x120x135 mm
2 kg

MNPP ANTRAX

OLTC Position Indicators

Designation of Position Indicators


UP 1 2 3 4 5 - 6
1 modification (UP1, UP2, UP 21, UP 22 ,UP 23, UP 25, UP 30, UP 31, UP 32? UP 41)
2 enclosure type (A, B, V, G, D, E)
3 digital output (RS232, RS485)
RS-232 digital output of RS-232 type
RS-485 digital output of RS-485 type
4 current loop (TP)
TP analog output current loop
No specific designation no analog output current loop
5 Block (Bl)
BL availability of blocking output and relay output
No specific designation blocking module wasnt installed.
6 relay output (RV)
RV denotes the presence of relay output
No value no relay output module
Example of ordering the UP 25 indicator for OLTC drive unit, made in standard panel mounted enclosure
144x144x85 mm, with digital RS485 output, analog current loop output and blocking module:
OLTC drive position indicator UP 25-B-RS485-TP-Bl

To make sure the ordered indicator perfectly fits your application, please fill in a Datasheet and send it to
MNPP ANTRAX.
All the devices comply with the requirements of GOST R normative documents. Manufacturer warranty for all the devices is five years. The MNPP
ANTRAX logometers have been successfully operated for more than 10 years in
the branches of RAO UES of Russia and other power systems, including the power
systems in Kazakhstan, Belarus and Ukraine.

MNPP ANTRAX

OLTC Position Indicators-Regulator

OLTC Position Indicator-Regulators


Position indicators-regulators UP 100 and UP 200 are designed to control OLTC electrical drives under
automatic regulation of power transformers transformation ratio. The position indicator-regulator combines functions of voltage regulator and OLTC position indicator. The device can be used at the 35 750 kV substations with
gradually or abruptly varying load.
The device is designed for the panel mounting (overall dimensions are 144x144 mm or 120x120 mm),
which allows to install the device on the switchboard control panels instead of the OLTC drive position indicators
of LKM (Bulgaria), MR, MZ, ED (Germany) types.
Position indicator-regulator is connected to the measurement voltage transformers with nominal secondary
voltage of 100 V and current transformers with nominal secondary current of 5 A or 1 A (depends on make).
This device is designed to control the drives with up to 99 tapping steps.
Indicators UP 100 and UP 200 combine functions of voltage regulator and OLTC position indicator and
consist of two blocks: Indicator and Regulator.
Indicators UP 100 and UP 200 provide:
control of the voltage ratio of power transformer by changing its primary winding taps with the use of
OLTC;
necessary interlocks to disable regulation;
control of command execution by OLTC device;
measurement of OLTC current switching step.
Advantages:
Combination of regulator and indicator functions results into:
o multiple enhancement of reliability of OLTC electrical drive operation control;
o additional adjustment settings, emergency diagnosis settings;
o space saving on the control switchboard.
Indicator-regulator may be connected directly to synchro transmitter; to resistive sensors installed on German, Bulgarian and other drives; to BCD-sensor or Gray-code sensors installed on German, Korean or
Chinese drives, as well as to Russian/foreign sensors with 4..20 mA (0-5 mA, 0-20 mA) output or digital
Modbus output.
The OLTC current tapping step value is displayed on LED indicator with light intensity of 10 000 mCd,
this allows Operator to easily read the data on his/her workstation at any light conditions;
Position indicator-regulator can work together with any drive type operated in Russia.

Additional Service Functions:


built-in calendar and clock;
measurement and display of compensation voltage and current;
storage, viewing on the built-in LCD-indicator and transfer via telecommunication line of the data on last
256 fixed events;
three independent communication interfaces (USB is on the front panel and two RS485 are on the rear
panel). USB-interface and one of the RS485 interfaces are used to control parameters, transfer emergency
data to PC, view and change the preset values, remote change of the OLTC steps. Second RS485 communication channel is used for connection of OLTC position sensor. Program protocol used is MODBUS;
OLTC actual tapping step transfer in analog form for the input to TM and PCS.

MNPP ANTRAX

OLTC Position Indicators-Regulator

Indicator-Regulator UP 100

UP 100 provides the following functions:


automatic voltage maintenance within the set up limits;
load current adjustment of the regulated voltage;
generation of impulse or continuous control commands for OLTC electrical drives;
OLTC electrical drive supervising control in the impulse work mode;
blocking of operation and alarm initiating when a fault is found in OLTC electrical drive;
blocking of regulation by external binary signals;
blocking of regulation when overload, 3U0 override or low voltage is detected;
online change of one maintained voltage to another.
Operational Functionalities:

possibility to change internal settings and operation mode;


input and storage of preset values;
control and display of input voltage and current values;
regulation of power transformer transformation ratio;
transmission of actual parameters, input and change of preset values via communication line;
self-test;
blocking of outputs when the device is faulty in order to exclude false activation;
reception digital signals,
warning alarm generation;
galvanic isolation of all inputs, outputs and supply circuits.

The device measures parameters of the analog input signals:

bus section phase-to-phase voltage;


bus section zero phase sequence voltage;
one analog input phase current signal;
one of the phase currents on the bus section breaker.

10

MNPP ANTRAX

OLTC Position Indicators-Regulator

Indicator-regulator UP 200

The following functions are provided by UP 200 additionally to the operational functionalities of UP 100:
simultaneous control of two bus sections;
function of dead steps; these steps achieved, the "Switching" signal at a specific OLTC position will not
be considered as "Drive out of control" situation and no blocking will occur.
operational regulation change from one bus system to another;
General Specifications:
Power consumption, not more than, W
Supply voltage
- AC input voltage, V
- DC input voltage, V
Indicator light intensity
Device weight, not more than, kg
Temperature range
Warranty period
Service life period

15
85...264
120...370
10000 mCd
3
From -40C to +55C
5 years
12 years

11

MNPP ANTRAX

Drive Position Sensors

Drive Position Sensors


Transformer tap sensors DP-1, DP-2, DP-3, DP-4 and DP-5 will be installed in the transformer changer
drive. These sensors are available in two types of enclosures:
with the dimensions similar to those of synchro transmitter BD404/BD1404;
45x88x62 mm - which is the optimum solution for replacement of resistive sensors based on circular selectors (for example, MZ-2, MZ-2);
The sensors represent both purely resistive sensors (DP-1, DP-2) and multifunctional sensors (DP-3, DP-4)
with analog (0-5 mA, 0-20 mA, 4-20 mA, 0-5 V, 0-24 V) and digital outputs (RS-232, RS-485).
Sensor Technical Specifications

Installation
(attachment)

On
the
existing
synchro
DP-1 transmitters
BD404,
BD1404
Instead of
synchro
transmitDP -2
ter
BD404,
BD1404
Instead of
synchro
transmitDP -3
ter
BD404,
BD1404
On
the
DP -4 existing
sensor

AdditioninDP -5 ally
stalled

Overall dimensions,
mm

68x104

67x107

Total turn
angle

275+15

275+15

Resistive
output

Analog
output
0-24 V*

Analog
output
0-20
mA*

Digital
output
RS-485*

BCDoutput

Compatible
indicators

UP-1
UP -2
UP -22
UP -23
UP -25

UP -2
UP -22
UP -23
UP -25

UP 21
UP 25
67x107

360
(with no
stopper)

45x88x62

360
(with no
stopper)

27x88x77

UP -2
UP -21
UP -22
UP -23
UP -25
UP -25

Drives

PDP-1
PDP -4
PDP -4U
RNOA
RNOA110
RNOA 220
RNT-13
RNT -18
RNT -20
RNT -20A
MA-1
MAK-1
MAK1/49
ZRNOA110/1000
PM-2M
PBV
MZ-2
MZ-3
MZ-4

SMA-7
SMA-9
SHM
EM-1
MR
ED

12

MNPP ANTRAX

Drive Position Sensors

Tap Sensor DP-1


Drive position sensor DP-1 is designed to determine actual position of PDP-1 and other drives operating
with synchro transmitter and synchro receiver.
Drive position sensor DP-1 represents a metal cylinder with chamfers for installation needs. Sensor DP-2 is
a drive turn angle resistive transducer which is installed on the existing synchro transmitter. This sensor is designed
for connection to LKM, UP 1/ UP 2/ UP 22/ UP 23/ UP 24/UP 25 logometers with drives that ensure operation with
synchro transmitters (types RNT-13, PDP-4 etc.)

Specifications:
Total resistance of the sensor resistor
Total turn angle
Service life, not less than

100 Ohm 20%


275 15
12 years

Tap sensor DP-2


Drive position sensor DP-2 is designed to determine actual position of PDP-4 and other drives connected
to the synchro transmitter and synchro receiver.
Drive position sensor DP-2 represents a metal cylinder with chamfers for installation needs. Overall dimensions and mounting points of DP-2 type sensor are the same as those of BD404 or BD1404 synchro transmitters.
Sensor DP-2 is a drive turn angle resistive transducer which can be installed instead of synchro transmitter. This
sensor is designed for connection to LKM, UP 1/UP 2/UP 22/UP 23/ UP 25 logometers with drives c/w transmitters
(types RNT-13, PDP-4 etc.)
This sensor allows connecting Siemens and ABB transformer protection and control automatics to Russianmade drives.
Specifications:
Total resistance of the sensor resistor
Total turn angle
Service life, not less than

100 Ohm 20%


275 15
12 years

13

MNPP ANTRAX

Drive Position Sensors

Tap sensor DP-3


Drive position sensor DP-3 is designed to determine actual transformer tap on load. This sensor can be
used with PDP-1, PDP-4, MA-1, RNT -13 drives, as well as the other drives that can be completed with synchro
transmitters (BD404 or BD1404) or other sensors with the dimensions of BD404/ BD1404 type sensors.
Drive position sensor DP-3 is a metal cylinder with chamfers for installation needs. Overall dimensions
and mounting points of DP-3 type sensor are the same as those of BD404 or BD1404 synchro transmitters. Sensor DP-3 is a drive turn angle encoder with signal conversion circuit, it can be installed instead of synchro transmitter.
Sensor DP-3 has different interfaces in order to transmit the drive turn angle. These are: interface RS-485
for the transformer tap data transfer to PCS or to UP 25 position indicators in digital form via MODBUS protocol.
Current analog interface "current loop" 4-20 A, 0-5 mA or 0-20 mA is designed for the transformer tap data transfer to UP 21/UP 25 position indicators or PCS by additional transmitters. Analog interface 0-5 V or 0-24 V for
the transformer tap data transfer to UP 2/UP 23/UP 25 or to PCS via additional transmitters. When using this interface sensor DP-3 can function as a resistive sensor of MZ-2, MZ-4, EM1, MR, ED-S drives. In this case the
sensor can be used for connecting the Siemens and ABB transformer protection and control automatics together
with Russian-made drives PDP-1, PDP-4, MA-1, RNT-13 and other types.
Specifications:
Supply voltage
Total turn angle
Turn angle accuracy
Analog output, "current loop"

Analog output
Digital output

5 V 5%
24 V 5%
360 with no stopper
2
0-20 mA
0-5 mA
4-20 mA
0-5 V
0-24 V
RS-485 MODBUS format

14

MNPP ANTRAX

Drive Position Sensors

Tap sensor DP-4


Drive position sensor DP-4 is designed to determine actual transformer tap on load. This sensor may be
connected to the MZ-2, MZ-3, MZ-4 type drives.
Sensor DP-4 is an electronic sensor of drive turn angle with the signal conversion circuit; it can be used
instead of resistive sensor.
Sensor DP-4 has different interfaces in order to transmit the drive turn angle. These are: interface RS-485
for the transformer tap data transfer to PCS or UP 25 position indicators in digital form via MODBUS protocol.
"Current loop" analog current interface 4-20 A, 0-5 mA or 0-20 mA is designed for the transformer tap data transfer to UP 25 position indicators or PCS by additional transmitters. Analog interface 0-5 V or 0-24 V is used for
the transformer tap data transfer to UP 2/UP 22/UP 23/UP 25 or PCS by additional transmitters. When using this
interface sensor DP-4 can function as a resistive sensor of MZ-2, MZ-4, EM1, MR, ED-S drives, the sensor can
be used for connecting Siemens and ABB transformer protection and control automatics to Russian-made drives.
Specifications:
Supply voltage
Total turn angle
Turn angle accuracy
Analog output, "current loop"

Analog output
Digital output
Service life, not less than

5 V 5%
24 V 5%
360 with no stopper
1
0-20 mA
0-5 mA
4-20 mA
0-5 V
0-24 V
RS-485 MODBUS format
12 years

Tap Sensor DP-5


Drive position sensor DP-5 is designed to determine actual transformer tap on load. This sensor can be
connected to SMA-7, SMA-9, SHM, EM-1, MR, ED drives with the number of contacts corresponding to the
number of drive positions. The sensor converts OLTC step number into BCD-code.
Sensor DP-5 has a BCD-output to deliver transformer tap data to UP 25 position indicators (to display the
OLTC step number on the control switchboard) or to TM and PCS.
Specifications:
Supply voltage
Service life, not less than

5 V 5%
24 V 5%
12 years

15

____________________________________________________________________
124460 Russia, Moscow, Zelenograd, 1135 - 46,
Tel. +7 (495) 991 12 30, Tel./fax +7 (499) 681 01 09,
E-mail: mail@antrax-energo.ru
Web: http://antrax-energo.ru