Models:

ACC 75D/DR
ACC 100D/DR

ACC - D- 2005

Ceiling Concealed
Split Systems

CONTENTS
1. NOMENECLATURE ................................................................................................... 2
2. FEATURES ................................................................................................................ 4
3. PRODUCT LINE UP ..................................................................................................... 5
4. SPECIFICATIONS ............................................................................................... 8
5. OPERATING RANGE ......................................................................................... 22
6. SOUND DATA ................................................................................ 23
7. PERFORMANCE TABLE .................................................................... 25
8. OUTLINES AND DIMENSIONS................................................................................................ 35
9. REFRIGERANT CIRCUIT ......................................................................................................... 37
10. WIRING DIAGRAMS ....................................................................................................... 38
11. INSTALLATION ......................................................................... 40
12. SERVICING AND MAINTENANCE ............................................................................................ 43
13. TROUBLESHOOTING ......................................................................... 45
14. EXPLODED VIEW AND PARTS LIST ......................................................................... 51

1. NOMENCLATURE
INDOOR
Product Specification Variation
A : First Issue
Type of Connection
B : For Brazed

Electrical Characteristic
A : 50Hz / 1Ph / 220-240V

CC

75

Model Type
R : Heatpump
Omitted if Cooling Only
Series
D : D Series
Capacity
75 : 75,000 Btu/h
Model Name
CC : Ceiling Concealed
Refrigerant
Blank : R22
4 : R407C
Brand
A : Acson

OUTDOOR
Product Specification Variation
A : First issue
Type of Connection
B : For Brazed
Electrical Characteristic
F : 50Hz / 3Ph / 220-240V
P : 60Hz / 3Ph / 208-230V
Q : 60Hz / 3Ph / 460V

MC

75

Model Type
R : Heatpump
Omitted if Cooling Only
Series
E : E Series
D : D Series
Capacity
75 : 75,000 Btu/h
Model Name
MC : Single Split Condensin g Unit
Refrigerant
Blank : R22
4 : R407C
Brand
A : Acson

2. FEATURES
Invisible Operation

The unit is installed concealed above the ceiling. ACC-D is designed to intelligently create a
comfortable and healthy indoor air climate, while remaining invisible. This allows user to enjoy
conditioned air without sacrificing room space or interior design creativity.

Flexibility in System Design

The unit offers fan motor that can operate up to 4 speeds, thus provide choices of external static
pressure for designing ducting system.

Easy Serviceability

With the concept of easy serviceability in mind, ACC-D series is designed for easy access to
internal components. The internal components, such as fan motor or blower, can be easily
accessed for servicing through both sides or bottom of the unit.

High Level of Protection

The unit is incorporated with a unique safety feature, i.e. a float switch, to provide an additional
protection from possible problems of condensate water over flow inside the unit. Once the
condensate water reaches critical level, the level switch will be activated and signal will be sent to
the microprocessor controller to stop the compressor as well as sending an error message to the
wired controller, alerting the user, for further action.

Wired Remote Controller

The standard unit comes with the Netware III controller, which offers wide range of control
features that, includes 7 days and 24 hours timer setting and more. The ACC-D series is able to
communicate with the versatile NIM network control module and offers the opportunity of one
centralized control for a system of multiple indoor units in a building.

Auto Random Restart

Auto random restart function allows the unit to automatic restart as the last setting condition when
the power supply is resumed after power failure. However, the compressor will restart randomly if
more than one unit is installed and sharing the same phase of power.

Self Diagnosis

The microprocessor provides the possibility to detect and diagnose any fault or malfunction that
occurs in the system. The error will be reflected by the wired remote controller with a series of
error code.

Handset
Control Module
Filtration
Marking
Refrigerant
Control

NETWARE III

Air Filter
CE Mark
Cap. Tube

Level Switch

L2

Built-in Filter Rail


Auto Random Restart

ABAA
X
X
X
X
X
X
X
X

ABAA
X
X
X
X
X
X
X
X

TXV

NONMENCLATURE

75DR

ACC

100DR

Heat Pump Model

3. PRODUCT LINE UP

INDOOR UNIT
ACC-D SERIES PRODUCT LINE UP
Classification

Cooling Only Model

A4MC

75D

100D

FBAA
FBAA
FCAA
FCAB
FBAA
FBAA
FCAA
FCAB
X

X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

6
X

X
X

X
X

X
X

X
X

X
X

Gas pipe size (in)

X
X

Liquid Pipe Size (in)

X
X
X
X
X
X
X
X

Gold Fin (NA549)

X
X
X

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

With Type Brazed Ball Valve

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

With Accumulator

For Sequential Controller

X
X
X
X
X

Refrigerant
Control

ETL

X
X
X

X
X

Refrigerant
Control

Compressor

Gas Pipe Size (in)

Liquid Pipe Size (in)

Gold Fin (NA549)

Phase Protector

With Type Brazed Ball Valve

With Accumulator

Rivet "Made In Malaysia"

Without Expansion Device

TXV

Scroll-Copeland

Without Marking

Marking

Without Expansion Device

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

CE Mark

With Manual HP/LP

With Auto HP/LP

With 24Vac Control Circuit

Without Contactor

Controller

TXV

Compressor

X
X

Scroll-Copeland

Marking

X
X

CE Mark

Auto HP/LP

Controller

100D
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

With Contactor

75D

FBAF
FBAG
FBAH
FCAA
FCAB
PBAB
PBAC
PCAA
QBAB
QBAC
QCAB
FBAF
FBAG
FBAH
FCAA
FCAB
PBAB
PBAC
PCAA
QBAB
QBAC
QCAB
With Contactor

Nomenclature

AMC

Nomenclature

Cooling Only Model

OUTDOOR UNIT
AMC-D Series Product Line Up
Classification

Others

1/2
1

X
5/8
1-1/8

A4MC-D Series Product Line Up


Classification

Others

1/2

5/8

1-1/8

Heatpump Models

4MSS

75ER

100ER

125ER

150ER

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X

7
X

X
X

X
X

Phase Sequencer

Check valve

With Brazed Type Ball Valve

Rivet "Made In Malaysia"

Gold Fin (NA549)

For Sequential Controller

Gas Pipe Size (in)

Liquid Pipe Size (in)

Gas Pipe Size (in)

X
X

Liquid Pipe Size (in)

With Brazed Type Ball Valve

X
X
X
X
X
X
X
X
X
X
X
X
X

With Accumulator

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

Gold Fin (NA549)

TXV

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

For Sequential Controller

Scroll-Copeland

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

Without Expansion Device

Compressor

CE Mark

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

Refrigerant
Control

Marking

With Auto HP/LP

Controller

With Contactor

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

Without Expansion Device

TXV

X
X
X
X
X
X
X
X
Refrigerant
Control

Compressor

Scroll-Copeland

FBAA
FCAA
FBAA
FCAA
FBAA
FCAA
FBAA
FCAA
Marking

150ER

CE Mark

125ER

With Auto HP/LP

Controller

100ER

FBAA
FBAB
FBAC
FCAA
FBAA
FBAB
FBAC
FCAA
FBAA
FBAB
FBAC
FCAA
FBAA
FBAB
FCAA

With Contactor

75ER
Nomenclature

MSS

Nomenclature

HEATPUMP MODLES

Outdoor Unit
AMC-ER Series Product Line Up
Classification

Others

1/2
1

5/8
1-1/8

5/8
1-3/8

5/8
1-3/8

A4MC-ER Series Product Line Up


Classification

Others

1/2

5/8

1-1/8

5/8

1-3/8

5/8

1-3/8

4. SPECIFICATIONS
General Data - Cooling Only (R22)
MODEL

INDOOR UNIT

ACC 75D

ACC 100D

OUTDOOR UNIT

AMC 75D

AMC 100D

Btu/h

75,000

95,000

21,960

27,820

8,471

10,822

16.3

NOMINAL CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE

R22 / INDOOR TXV

REFRIGERANT TYPE / CONTROL


SUPER HIGH

CFM / L/s

2420 / 1142

3150 / 1487

HIGH

CFM / L/s

2450 / 1156

3130 / 1477

MEDIUM

CFM / L/s

2000 / 944

2840 / 1340

LOW

CFM / L/s

1680 / 793

2240 / 1057

AIR FLOW

INDOOR UNIT

EXTERNAL STATIC PRESSURE (SH/H/M/L)


SOUND PRESSURE LEVEL (SH/H/M/L)
UNIT DIMENSION

PACKING DIMENSION

20 / 14 / 10 / 7 (196 / 137 / 98 / 69)

mmAq(Pa)
dBA

52 / 52 / 48 / 43

HEIGHT

mm/in

430 / 16.9

430 / 16.9

WIDTH

mm/in

1426 / 56.1

1655 / 65.2
826 / 32.5

DEPTH

mm/in

826 / 32.5

mm/in

612 / 24.1

612 / 24.1

WIDTH

mm/in

1535 / 60.4

1765 / 69.5

DEPTH

mm/in

974 / 38.3

974 / 38.3

kg/lb

92 / 203

119 / 262

mm/in

25.4 / 1.0

CONDENSATE DRAIN SIZE


AIR FLOW

dBA

64

HEIGHT

mm/in

1041 / 40.98

SOUND PRESSURE LEVEL

PACKING DIMENSION

WIDTH

mm/in

981 / 38.62

DEPTH

mm/in

981 / 38.62

HEIGHT

mm/in

1224 / 48.2

WIDTH

mm/in

1175 / 46.3

DEPTH

mm/in

UNIT WEIGHT

1150 / 45.3
170 / 374

kg/lb

REFRIGERANT CHARGE

SIZE

184 / 405
BRAZING

TYPE
PIPE CONNECTION

25.4 / 1.0
7000 / 3304

CFM / L/s

UNIT DIMENSION

55 / 54 / 52 / 48

HEIGHT

UNIT WEIGHT

OUTDOOR UNIT

19.4
380 - 415 / 3 / 50

V/Ph/Hz

LIQUID

mm/in

12.70 / 1/2

15.88 / 5/8

GAS

mm/in

25.40 / 1

28.57 / 1-1/8

kg/lb

6.7 / 14.77

10.5 / 23.15

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 26.7C DB / 19.4C WB INDOOR AND 35.0C DB / 23.9C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.

Electrical Data - Cooling Only (R22)


MODEL

INDOOR UNIT

ACC 75D

ACC 100D

OUTDOOR UNIT

AMC 75D

AMC 100D
INDUCTION

TYPE

CLASS B

INSULATION GRADE
POWER SOURCE
INDOOR MOTOR

220 - 240 / 1 / 50

V/Ph/Hz

RATED INPUT POWER

1061

RATED RUNNING CURRENT

4.51

5.79

MOTOR OUTPUT

750

1000

POLES

CLASS F

INSULATION GRADE
V/Ph/Hz

380 - 415 / 3 / 50

RATED INPUT POWER

600

RATED RUNNING CURRENT

1.2

MOTOR OUTPUT

350

POWER SOURCE

SCROLL

TYPE
INSULATION GRADE
POWER SOURCE
COMPRESSOR

4
INDUCTION

TYPE

OUTDOOR MOTOR

1254

N/A

N/A
380 - 415 / 3 / 50

V/Ph/Hz

CAPACITOR

NIL

RATED INPUT POWER

6810

8968

RATED RUNNING CURRENT

13.6

16.3

LOCKED ROTOR AMP.

95

125

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/230-94.

NIL

Components Data (R22)


MODEL

INDOOR UNIT

ACC 75D

OUTDOOR UNIT

AMC 75D

ACC 100D
ALC 100D
CENTRIFUGAL

TYPE
Q'TY
INDOOR FAN

INDOOR FAN
MOTOR

MATERIAL

ZINC COATED STEEL

ZINC COATED STEEL

DRIVE

DIRECT

DIRECT

DIAMETER

mm/in

228.6 / 9.0

228.6 / 9.0

LENGTH

mm/in

177.8 / 7.0

228.6 / 9.0
INDUCTION

TYPE
Q'TY
INDEX OF PROTECTION (IP)

N/A

N/A

TYPE

PROPELLER

Q'TY

1
ALUMINIUM

OUTDOOR FAN MATERIAL

DIRECT

DRIVE
DIAMETER

812.8 / 32.0

mm/in

INDUCTION

TYPE
OUTDOOR FAN
Q'TY
MOTOR
INDEX OF PROTECTION (IP)

1
N/A

N/A
SCROLL

TYPE
COMPRESSOR

OIL TYPE
OIL AMOUNT

cm

SONTEX 200 LT

SONTEX 200 LT

2513

3253
SEAMLESS COPPER

MATERIAL
TUBE

DIAMETER

mm/in

9.52 / 3/8

THICKNESS

mm/in

0.35 / 0.013

MATERIAL

INDOOR COIL
FIN

ALUMINIUM

ALUMINIUM

THICKNESS

mm/in

0.127 / 0.005

0.127 / 0.005

FACE AREA

m2/ft2

0.45 / 4.89

0.55 / 5.89

ROW

FIN PER INCH

12

14
SEAMLESS COPPER

MATERIAL
TUBE

DIAMETER

mm/in

THICKNESS

mm/in

9.52 / 3/8
0.35 / 0.013

MATERIAL

OUTDOOR COIL
FIN

ALUMINIUM

ALUMINIUM

THICKNESS

mm/in

0.127 / 0.005

0.127 / 0.005

FACE AREA

m2/ft2

2.29 / 24.72

2.29 / 24.72

ROW

FIN PER INCH

20

16
WASHABLE SARANET FILTER

TYPE
FILTRATION

SIZE

WIDTH

mm/in

665 / 26.1

780 / 30.7

HEIGHT

mm/in

345 / 13.9

345 / 13.9

pc

QUANTITY
INDOOR UNIT
CASING
OUTDOOR UNIT

MATERIAL

GALVANIZED MILD STEEL

FINSIHING

COLOUR

MATERIAL

ELECTRO GALVANIZED STEEL

FINISHING

EPOXY POLYESTER POWDER

COLOUR

WHITE

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

10

General Data - Heat pump (R22)


MODEL

INDOOR UNIT

ACC 75DR

OUTDOOR UNIT

ACC 100DR

AMC 75ER

AMC 100ER

Btu/h

75000

100000

21960

29280

Btu/h

84000

110000

NOMINAL COOLING CAPACITY


NOMINAL HEATING CAPACITY

24600

32210

NOMINAL TOTAL INPUT POWER (COOLING)

7356

10200

NOMINAL TOTAL INPUT POWER (HEATING)

7206

9800

13.6

17.9

13.3

NOMINAL RUNNING CURRENT (COOLING)


NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE

R22 / INDOOR & OUTDOOR TXV

REFRIGERANT TYPE / CONTROL


SUPER HIGH

CFM / L/s

2420 / 1142

3150 / 1487

HIGH

CFM / L/s

2450 / 1156

3130 / 1477

MEDIUM

CFM / L/s

2000 / 944

2840 / 1340

LOW

CFM / L/s

1680 / 793

2240 / 1057

AIR FLOW

INDOOR UNIT

EXTERNAL STATIC PRESSURE (SH/H/M/L)


SOUND PRESSURE LEVEL (SH/H/M/L)
UNIT DIMENSION

PACKING DIMENSION

20 / 14 / 10 / 7 (196 / 137 / 98 / 69)

mmAq(Pa)
dBA

52 / 52 / 48 / 43

HEIGHT

mm/in

430 / 16.9

430 / 16.9

WIDTH

mm/in

1426 / 56.1

1655 / 65.2
826 / 32.5

DEPTH

mm/in

826 / 32.5

mm/in

612 / 24.1

612 / 24.1

WIDTH

mm/in

1535 / 60.4

1765 / 69.5

DEPTH

mm/in

974 / 38.3

974 / 38.3

kg/lb

92 / 203

119 / 262

mm/in

25.4 / 1.0

CONDENSATE DRAIN SIZE


AIR FLOW

dBA

64

HEIGHT

mm/in

1041 / 40.98

SOUND PRESSURE LEVEL

PACKING DIMENSION

WIDTH

mm/in

981 / 38.62

DEPTH

mm/in

981 / 38.62

HEIGHT

mm/in

1224 / 48.2

WIDTH

mm/in

1175 / 46.3

DEPTH

mm/in

UNIT WEIGHT

1150 / 45.3
170 / 374

kg/lb

REFRIGERANT CHARGE

SIZE

184 / 405
BRAZING

TYPE
PIPE CONNECTION

25.4 / 1.0
7000 / 3304

CFM / L/s

UNIT DIMENSION

55 / 54 / 52 / 48

HEIGHT

UNIT WEIGHT

OUTDOOR UNIT

17.2
380 - 415 / 3 / 50

V/Ph/Hz

LIQUID

mm/in

12.70 / 1/2

15.88 / 5/8

GAS

mm/in

28.58 / 1-1/8

28.58 / 1-1/8

kg/lb

6.80 / 14.99

7.50 / 16.54

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7C DB / 19.4C WB INDOOR AND 35.0C DB / 23.9C WB OUTDOOR
b) HEATING - 21.1C DB INDOOR AND 8.3C DB / 6.1C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.

11

Electrical Data - Heat pump (R22)


MODEL

INDOOR UNIT

ACC 75DR

ACC 100DR

OUTDOOR UNIT

AMC 75ER

AMC 100ER
INDUCTION

TYPE

CLASS B

INSULATION GRADE
POWER SOURCE
INDOOR MOTOR

220 - 240 / 1 / 50

V/Ph/Hz

RATED INPUT POWER

1061

RATED RUNNING CURRENT

4.51

5.79

MOTOR OUTPUT

750

1000

POLES

CLASS F

INSULATION GRADE
V/Ph/Hz

380 - 415 / 3 / 50

RATED INPUT POWER

600

RATED RUNNING CURRENT

1.2

350

POWER SOURCE

MOTOR OUTPUT

SCROLL

TYPE
INSULATION GRADE
POWER SOURCE
COMPRESSOR

4
INDUCTION

TYPE

OUTDOOR MOTOR

1254

N/A

N/A
380 - 415 / 3 / 50

V/Ph/Hz

CAPACITOR

NIL

NIL

RATED INPUT POWER (COOLING)

5695

8346

RATED INPUT POWER (HEATING)

5545

7966

RATED RUNNING CURRENT (COOLING)

10.9

14.8

RATED RUNNING CURRENT (HEATING)

10.6

14.1

LOCKED ROTOR AMP.

95

125

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.

12

Components Data (R22)


MODEL

INDOOR UNIT

ACC 75DR

ACC 100DR

OUTDOOR UNIT

AMC 75ER

AMC 100ER
CENTRIFUGAL

TYPE
Q'TY
INDOOR FAN

INDOOR FAN
MOTOR

MATERIAL

ZINC COATED STEEL

ZINC COATED STEEL

DRIVE

DIRECT

DIRECT

DIAMETER

mm/in

228.6 / 9.0

228.6 / 9.0

LENGTH

mm/in

177.8 / 7.0

228.6 / 9.0
INDUCTION

TYPE
Q'TY

INDEX OF PROTECTION (IP)

N/A

N/A
PROPELLER

TYPE

Q'TY

ALUMINIUM

OUTDOOR FAN MATERIAL

DIRECT

DRIVE
DIAMETER

812.8 / 32.0

mm/in

INDUCTION

TYPE
OUTDOOR FAN
Q'TY
MOTOR
INDEX OF PROTECTION (IP)

1
N/A

N/A
SCROLL

TYPE
COMPRESSOR

OIL TYPE

Sontex 200 LT

OIL AMOUNT

cm3

3253
SEAMLESS COPPER

MATERIAL
TUBE

DIAMETER

mm/in

9.52 / 3/8

THICKNESS

mm/in

0.35 / 0.013

MATERIAL

INDOOR COIL
FIN

ALUMINIUM

ALUMINIUM

THICKNESS

mm/in

0.127 / 0.005

0.127 / 0.005

FACE AREA

m2/ft2

0.45 / 4.89

0.55 / 5.89

ROW

FIN PER INCH

12

14

SEAMLESS INNER GROOVED COPPER

MATERIAL
TUBE

DIAMETER

mm/in

9.52 / 3/8

THICKNESS

mm/in

0.35 / 0.013

MATERIAL

OUTDOOR COIL
FIN

ALUMINIUM

SIZE

ALUMINIUM

THICKNESS

mm/in

0.127 / 0.005

0.127 / 0.005

FACE AREA

2.29 / 24.72

2.29 / 24.72

m /ft

ROW

FIN PER INCH

20

16
WASHABLE SARANET FILTER

TYPE
FILTRATION

Sontex 200 LT

2513

WIDTH

mm/in

665 / 26.1

780 / 30.7

HEIGHT

mm/in

345 / 13.9

345 / 13.9

pc

QUANTITY
INDOOR UNIT
CASING
OUTDOOR UNIT

MATERIAL

GALVANIZED MILD STEEL

FINSIHING

N/A

COLOUR

N/A

MATERIAL

ELECTRO GALVANIZED STEEL

FINISHING

EPOXY POLYESTER POWDER

COLOUR

WHITE

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

13

Safety Devices
MODEL

INDOOR UNIT

ACC 75D

ACC 100D

OUTDOOR UNIT

AMC 75D

AMC 100D

AUTO RESET

AUTO RESET

HIGH PRESSURE SWITCH


SAFETY DEVICE

LOW PRESSURE SWITCH

TYPE
SETTING

426 psi OFF

426 psi OFF

TYPE

AUTO RESET

AUTO RESET

SETTING

PHASE SEQUENCER

18 psi OFF

18 psi OFF

AVAILABLE

AVAILABLE

DISCHARGE THERMOSTAT SETTING

130 C

130

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

MODEL

INDOOR UNIT

ACC 75DR

ACC 100DR

OUTDOOR UNIT

AMC 75ER

AMC 100ER

AUTO RESET

AUTO RESET

HIGH PRESSURE SWITCH


SAFETY DEVICE

LOW PRESSURE SWITCH

TYPE
SETTING

426 psi OFF

426 psi OFF

TYPE

AUTO RESET

AUTO RESET

SETTING

PHASE SEQUENCER

7 psi OFF

7 psi OFF

AVAILABLE

AVAILABLE

DISCHARGE THERMOSTAT SETTING

130 C

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

14

130

General Data - Cooling Only (R407C)


MODEL

INDOOR UNIT

ACC 75D

ACC 100D

OUTDOOR UNIT

A4MC 75D

A4MC 100D

Btu/h

75000

100000

NOMINAL CAPACITY

21980

29310

NOMINAL TOTAL INPUT POWER

8892

10833

NOMINAL RUNNING CURRENT

16.0

POWER SOURCE

R407C / INDOOR TXV

REFRIGERANT TYPE / CONTROL


SUPER HIGH

CFM / L/s

2520 / 1189

3070 / 1449

HIGH

CFM / L/s

2320 / 1095

2620 / 1237

MEDIUM

CFM / L/s

2095 / 989

2350 / 1109

CFM / L/s

1660 / 783

2150 / 1015

AIR FLOW

LOW
INDOOR UNIT

EXTERNAL STATIC PRESSURE (SH/H/M/L)


SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION

PACKING DIMENSION

dBA

52 / 52 / 48 / 43

mm/in

430 / 16.9

430 / 16.9

WIDTH

mm/in

1426 / 56.1

1655 / 65.2

DEPTH

mm/in

826 / 32.5

826 / 32.5

mm/in

612 / 24.1

612 / 24.1

WIDTH

mm/in

1535 / 60.4

1765 / 69.5

DEPTH

mm/in

974 / 38.3

974 / 38.3

kg/lb

92 / 203

119 / 262

mm/in

25.4 / 1.0

AIR FLOW

dBA

64

HEIGHT

mm/in

1041 / 40.98

SOUND PRESSURE LEVEL

PACKING DIMENSION

WIDTH

mm/in

981 / 38.62

DEPTH

mm/in

981 / 38.62

HEIGHT

mm/in

1224 / 48.2

WIDTH

mm/in

1175 / 46.3

DEPTH

mm/in

UNIT WEIGHT

1150 / 45.3

kg/lb
TYPE

REFRIGERANT CHARGE

SIZE

25.4 / 1.0
7000 / 3304

CFM / L/s

UNIT DIMENSION

55 / 54 / 52 / 48

HEIGHT

CONDENSATE DRAIN SIZE

OUTDOOR UNIT

20 / 14 / 10 / 7 (196 / 137 / 98 / 69)

mmAq(Pa)

HEIGHT

UNIT WEIGHT

PIPE CONNECTION

19.0
380 - 415 / 3 / 50

V/Ph/Hz

170 / 374

184 / 405

BRAZING

BRAZING

LIQUID

mm/in

12.70 / 1/2

15.88 / 5/8

GAS

mm/in

25.40 / 1

28.57 / 1-1/8

kg/lb

7.00 / 15.43

7.80 / 17.20

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 26.7C DB / 19.4C WB INDOOR AND 35.0C DB / 23.9C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.

15

Electrical Data - Cooling Only (R407C)


MODEL

INDOOR UNIT
OUTDOOR UNIT

ACC 75D

ACC 100D

A4MC 75D

A4MC 100D
INDUCTION

TYPE

CLASS B

INSULATION GRADE
POWER SOURCE
INDOOR MOTOR

220 - 240 / 1 / 50

V/Ph/Hz

RATED INPUT POWER

1061

RATED RUNNING CURRENT

4.51

5.79

MOTOR OUTPUT

750

1000

POLES

INDUCTION
CLASS F

INSULATION GRADE
V/Ph/Hz

380 - 415 / 3 / 50

RATED INPUT POWER

600

RATED RUNNING CURRENT

1.2

MOTOR OUTPUT

350

POWER SOURCE

SCROLL

TYPE
INSULATION GRADE
POWER SOURCE
COMPRESSOR

TYPE

OUTDOOR MOTOR

1254

N/A

N/A
380 - 415 / 3 / 50

V/Ph/Hz

CAPACITOR

NIL

NIL

RATED INPUT POWER

7231

8979

RATED RUNNING CURRENT

13.34

15.82

LOCKED ROTOR AMP.

95

125

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.

16

Components Data (R407C)


MODEL

INDOOR UNIT
OUTDOOR UNIT

ACC 75D

ACC 100D

A4MC 75D

A4MC 100D
CENTRIFUGAL

TYPE
Q'TY
INDOOR FAN

INDOOR FAN
MOTOR

MATERIAL

ZINC COATED STEEL

ZINC COATED STEEL

DRIVE

DIRECT

DIRECT

DIAMETER

mm/in

228.6 / 9.0

228.6 / 9.0

LENGTH

mm/in

177.8 / 7.0

Q'TY

INDEX OF PROTECTION (IP)

N/A

N/A
PROPELLER

TYPE

Q'TY

ALUMINIUM

OUTDOOR FAN MATERIAL

DIRECT

DRIVE
DIAMETER

812.8 / 32.0

mm/in

INDUCTION

TYPE
OUTDOOR FAN
Q'TY
MOTOR
INDEX OF PROTECTION (IP)

1
N/A

N/A
SCROLL

TYPE
COMPRESSOR

OIL TYPE

SONTEX 200 LT

OIL AMOUNT

cm3

MATERIAL
TUBE

FIN

FIN

SEAMLESS COPPER

mm/in

9.52 / 3/8

9.52 / 3/8

mm/in

0.35 / 0.013

0.35 / 0.013

ALUMINIUM
mm/in

0.127 / 0.005

0.127 / 0.005

FACE AREA

0.45 / 4.89

0.55 / 5.89

m /ft

ROW

FIN PER INCH

12

14

S. I. G. C.

SEAMLESS COPPER

DIAMETER

mm/in

9.52 / 3/8

9.52 / 3/8

THICKNESS

mm/in

0.35 / 0.013

0.35 / 0.013

ALUMINIUM

SIZE

ALUMINIUM

THICKNESS

mm/in

0.127 / 0.005

0.127 / 0.005

FACE AREA

2.29 / 24.72

2.29 / 24.72

ROW

FIN PER INCH

20

m /ft

16
WASHABLE SARANET FILTER

TYPE
FILTRATION

ALUMINIUM

THICKNESS

MATERIAL

OUTDOOR COIL

3253

S. I. G. C.

THICKNESS

MATERIAL
TUBE

SONTEX 200 LT

2513

DIAMETER
MATERIAL

INDOOR COIL

228.6 / 9.0
INDUCTION

TYPE

WIDTH

mm/in

665 / 26.1

780 / 30.7

HEIGHT

mm/in

345 / 13.9

345 / 13.9

pc

QUANTITY
INDOOR UNIT
CASING
OUTDOOR UNIT

MATERIAL

GALVANIZED MILD STEEL

FINSIHING

COLOUR

MATERIAL

ELECTRO GALVANIZED STEEL

FINISHING

EPOXY POLYESTER POWDER

COLOUR

WHITE

17

General Data - Heat pump (R407C)


INDOOR UNIT

ACC 75DR

ACC 100DR

OUTDOOR UNIT

A4MC 75ER

A4MC 100ER

Btu/h

75000

100000

21980

29310

Btu/h

84000

110000

24620

32240

NOMINAL TOTAL INPUT POWER (COOLING)

7827

11040

NOMINAL TOTAL INPUT POWER (HEATING)

7827

9279

NOMINAL RUNNING CURRENT (COOLING)

13.9

19.0

NOMINAL RUNNING CURRENT (HEATING)

13.9

MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY

POWER SOURCE

R407C / INDOOR & OUTDOOR TXV

REFRIGERANT TYPE / CONTROL


SUPER HIGH

CFM / L/s

2520 / 1189

3070 / 1449

HIGH

CFM / L/s

2320 / 1095

2620 / 1237

MEDIUM

CFM / L/s

2095 / 989

2350 / 1109

LOW

CFM / L/s

1660 / 783

2150 / 1015

AIR FLOW

INDOOR UNIT

EXTERNAL STATIC PRESSURE (SH/H/M/L)


SOUND PRESSURE LEVEL (SH/H/M/L)
UNIT DIMENSION

PACKING DIMENSION

20 / 14 / 10 / 7 (196 / 137 / 98 / 69)

mmAq(Pa)

52 / 52 / 48 / 43

dBA
mm/in

430 / 16.9

430 / 16.9

WIDTH

mm/in

1426 / 56.1

1655 / 65.2
826 / 32.5

DEPTH

mm/in

826 / 32.5

HEIGHT

mm/in

612 / 24.1

612 / 24.1

WIDTH

mm/in

1535 / 60.4

1765 / 69.5

DEPTH

mm/in

974 / 38.3

974 / 38.3

kg/lb

92 / 203

119 / 262

mm/in

25.4 / 1.0

25.4 / 1.0

CONDENSATE DRAIN SIZE


AIR FLOW

7000 / 3304

CFM / L/s
dBA

64

HEIGHT

mm/in

1041 / 40.98

SOUND PRESSURE LEVEL


UNIT DIMENSION

PACKING DIMENSION

WIDTH

mm/in

981 / 38.62

DEPTH

mm/in

981 / 38.62

HEIGHT

mm/in

1224 / 48.2

WIDTH

mm/in

1175 / 46.3

DEPTH

mm/in

UNIT WEIGHT

1150 / 45.3
170 / 374

kg/lb

REFRIGERANT CHARGE

SIZE

184 / 405
BRAZING

TYPE
PIPE CONNECTION

55 / 54 / 52 / 48

HEIGHT

UNIT WEIGHT

OUTDOOR UNIT

19.6
380 - 415 / 3 / 50

V/Ph/Hz

LIQUID

mm/in

12.70 / 1/2

15.88 / 5/8

GAS

mm/in

28.58 / 1-1/8

28.58 / 1-1/8

kg/lb

7.00 / 15.43

7.80 / 17.20

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7C DB / 19.4C WB INDOOR AND 35.0C DB / 23.9C WB OUTDOOR
b) HEATING - 21.1C DB INDOOR AND 8.3C DB / 6.1C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.

18

Electrical Data - Heat pump (R407C)


MODEL

INDOOR UNIT
OUTDOOR UNIT

ACC 75DR

ACC 100DR

A4MC 75ER

A4MC 100ER
INDUCTION

TYPE

CLASS B

INSULATION GRADE
POWER SOURCE
INDOOR MOTOR

220 - 240 / 1 / 50

V/Ph/Hz

RATED INPUT POWER

1061

RATED RUNNING CURRENT

4.51

5.79

MOTOR OUTPUT

750

1000

POLES

CLASS F

INSULATION GRADE
V/Ph/Hz

380 - 415 / 3 / 50

RATED INPUT POWER

600

RATED RUNNING CURRENT

1.2

MOTOR OUTPUT

350

POWER SOURCE

SCROLL

TYPE
INSULATION GRADE
POWER SOURCE
COMPRESSOR

4
INDUCTION

TYPE

OUTDOOR MOTOR

1254

N/A

N/A
380 - 415 / 3 / 50

V/Ph/Hz

CAPACITOR

NIL

RATED INPUT POWER (COOLING)

6045

9186

RATED INPUT POWER (HEATING)

6045

7425

RATED RUNNING CURRENT (COOLING)

11.1

15.9

RATED RUNNING CURRENT (HEATING)

11.1

16.5

LOCKED ROTOR AMP.

95

125

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.

19

NIL

Components Data (R407C)


MODEL

INDOOR UNIT
OUTDOOR UNIT

ACC 75DR

ACC 100DR

A4MC 75ER

A4MC 100ER
CENTRIFUGAL

TYPE
Q'TY
INDOOR FAN

INDOOR FAN
MOTOR

MATERIAL

ZINC COATED STEEL

ZINC COATED STEEL

DIRECT

DIRECT
228.6 / 9.0

DRIVE
DIAMETER

mm/in

228.6 / 9.0

LENGTH

mm/in

177.8 / 7.0

228.6 / 9.0
INDUCTION

TYPE
Q'TY
INDEX OF PROTECTION (IP)

N/A

N/A
PROPELLER

TYPE

Q'TY

ALUMINIUM

OUTDOOR FAN MATERIAL

DIRECT

DRIVE
DIAMETER

812.8 / 32.0

mm/in

INDUCTION

TYPE

OUTDOOR FAN
Q'TY
MOTOR
INDEX OF PROTECTION (IP)

1
N/A

N/A
SCROLL

TYPE
COMPRESSOR

OIL TYPE

SONTEX 200 LT

OIL AMOUNT

cm3

MATERIAL
TUBE

DIAMETER
THICKNESS

FIN

9.52 / 3/8

9.52 / 3/8

mm/in

0.35 / 0.013

ALUMINIUM

FIN

mm/in

0.127 / 0.005

0.127 / 0.005

FACE AREA

m2/ft2

0.45 / 4.89

0.55 / 5.89

ROW

FIN PER INCH

12

14

S. I. G. C.

SEAMLESS COPPER

DIAMETER

mm/in

9.52 / 3/8

9.52 / 3/8

THICKNESS

mm/in

0.35 / 0.013

0.35 / 0.013

ALUMINIUM

SIZE

ALUMINIUM

THICKNESS

mm/in

0.127 / 0.005

0.127 / 0.005

FACE AREA

m2/ft2

2.29 / 24.72

2.29 / 24.72

ROW

FIN PER INCH

20

16
WASHABLE SARANET FILTER

TYPE
FILTRATION

ALUMINIUM

THICKNESS

MATERIAL

OUTDOOR COIL

SEAMLESS COPPER

0.35 / 0.013

MATERIAL
TUBE

3253

S. I. G. C.
mm/in

MATERIAL

INDOOR COIL

SONTEX 200 LT

2513

WIDTH

mm/in

665 / 26.1

780 / 30.7

HEIGHT

mm/in

345 / 13.9

345 / 13.9

pc

QUANTITY
INDOOR UNIT
CASING
OUTDOOR UNIT

MATERIAL

GALVANIZED MILD STEEL

FINSIHING

COLOUR

MATERIAL

ELECTRO GALVANIZED STEEL

FINISHING

EPOXY POLYESTER POWDER

COLOUR

WHITE

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

20

Safety Devices
MODEL

INDOOR UNIT
OUTDOOR UNIT
HIGH PRESSURE SWITCH

SAFETY DEVICE

LOW PRESSURE SWITCH

TYPE

ACC 75D

ACC 100D

A4MC 75D

A4MC 100D

AUTO RESET

AUTO RESET

SETTING

426 psi OFF

426 psi OFF

TYPE

AUTO RESET

AUTO RESET

SETTING

PHASE SEQUENCER

18 psi OFF

18 psi OFF

AVAILABLE

AVAILABLE

DISCHARGE THERMOSTAT SETTING

130 C

130

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

MODEL

INDOOR UNIT
OUTDOOR UNIT
HIGH PRESSURE SWITCH

SAFETY DEVICE

LOW PRESSURE SWITCH

TYPE

ACC 75DR

ACC 100DR

A4MC 75ER

A4MC 100ER

AUTO RESET

AUTO RESET

SETTING

426 psi OFF

426 psi OFF

TYPE

AUTO RESET

AUTO RESET

SETTING

PHASE SEQUENCER

7 psi OFF

7 psi OFF

AVAILABLE

AVAILABLE

DISCHARGE THERMOSTAT SETTING

130 C

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

21

130

5. OPERATING RANGE
Ensure the operating temperature is in allowable range.

Cooling only

Outdoor temp. (CDB)

54

High ambient
unit

46

Standard
point

35

Caution :
The use of your air conditioner
outside the range of working
temperature and humidity can
result in serious failure.

19

Low ambient kit

-5
24

15

Indoor temp. (CWB)

Heatpump
Cooling

Heating
54

Outdoor temp. (CDB)

Outdoor temp. (CWB)

18

Standard
point

-9

High ambient
unit

46

Standard
point

35

19

Low ambient kit

-5
15

21

27

15

Indoor temp. (CDB)

24

Indoor temp. (CWB)

Note :
Standard operating range.

With High ambient unit. (Optional item)


Please refer to local dealer for unit of this specification.

With Low ambient kit. (Optional item)


Please refer to local dealer for unit of this specification.

22

6. SOUND DATA

Ext. Static
(mmAq)
20
14
10
7

Speed

Ext. Static
(mmAq)
20
14
10
7

Speed

SH
Hi
Me
Lo

SH
Hi
Me
Lo

Microphone position:

125
52
51
48
43

ACC 75D/DR
1/1 Octave sound Pressure Level (dB, reference 20 Pa)
250
500
1000
2000
4000
8000
49
49
48
45
40
33
49
48
47
44
40
33
46
46
45
40
34
26
40
42
38
36
30
19

Overall
(dBA)
52
52
48
43

Noise
Criteria
47
46
44
37

125
60
59
55
55

ACC 100D/DR
1/1 Octave sound Pressure Level (dB, reference 20 Pa)
250
500
1000
2000
4000
8000
54
51
51
49
44
37
52
50
50
48
42
36
51
49
47
44
38
31
47
47
43
40
33
26

Overall
(dBA)
55
54
52
48

Noise
Criteria
50
49
46
43

1.4m below the centre of the unit.


(Tested with 2m length duct at the air discharge outlet and air return inlet)

23

NC CURVES
ACC 75D/DR NC CURVES

70

Sound Pressure Level (dB, ref 20Pa)

60

50

NC-50
SH FAN

NC-45

HI FAN

40

NC-40

ME FAN

NC-35

LO FAN
30

NC-30
NC-25

20

NC-20

10

0
125

250

500

1000

2000

4000

8000

Octave-band Frequency (Hz)

ACC 100D/DR NC CURVES

70

60

Sound Pressure Level (dB, ref 20Pa)

SH FAN
50

NC-50

HI FAN

NC-45

ME FAN

NC-40

40

LO FAN

NC-35
NC-30

30

NC-25
20

NC-20

10

0
125

250

500

1000

Octave-band Frequency (Hz)

24

2000

4000

8000

5.
5.
7.PERFORMANCE
PERFORMANCE
PERFORMANCETABLE
TABLE
TABLE
Interpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity,
SC at those temperatures which are not stated out in the table.
Example:
Model: ACC 75D AMC 75D
Indoor Condition: 23C DB, 15C WB
Outdoor Condition: 37C DB
Solution:
Overall
Based on the Performance table on Pg. 29,
1. Refer to the Indoor DB column,
- 23C is located between 20C and 24C (Thus, Interpolation need to be applied)
2. Refer to the Indoor WB column,
- 15C only available in the case of Indoor DB = 20C. (Thus, Extrapolation between 16C
WB and 17C WB during 24C indoor DB is required)
3. Refer to the Outdoor DB column,
- 37C is located between 35C and 40C. (Thus, Interpolation need to be applied)
Please follow the steps below in order to get the required capacity.

1st Step

2nd Step

3rd Step

Find TC, SC for


(a) Indoor: 24C DB, 15C WB
Outdoor: 35C DB

Find TC, SC for


(a) Indoor: 23C DB, 15C WB
Outdoor: 35C DB

Find TC, SC for


(a) Indoor: 23C DB, 15C WB
Outdoor: 37C DB

(b) Indoor: 24C DB, 15C WB


Outdoor: 40C DB

(b) Indoor: 23C DB, 15C WB


Outdoor: 40C DB

Extrapolation of Indoor WB

Interpolation of Indoor DB

25

Interpolation of Outdoor DB

Details:
1st Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 24C DB, 15C WB
Outdoor Condition: 35C DB
Indoor DB
C

Indoor WB
C

24

15
16
17

Outdoor DB, C
35
TC (kW)
SC (kW)
x1
20.229
20.744

y1
15.040
14.517

Total capacity, TC
x1 = 19.713kW (Same as Total capacity at 20C Indoor DB / 15C Indoor WB & 35C Outdoor WB)*

Sensible capacity, SC
Extrapolation Method:
14.517kW - y 1
17 C - 15 C

17 C - 16 C

14.517kW - 15.040kW

y1 = 15.563kW

(b) Indoor Condition: 24C DB, 15C WB


Outdoor Condition: 40C DB
Indoor DB
C

Indoor WB
C

24

15
16
17

Outdoor DB, C
40
TC (kW)
SC (kW)
x2
18.776
19.366

y2
13.808
13.463

Total capacity, TC
x 2 = 18.186kW (Same as Total capacity at 20C Indoor DB / 15C Indoor WB & 40C Outdoor WB)*

Sensible capacity, SC
Extrapolation Method:
13.463kW - y 2
17 C - 15 C

17C - 16 C

13.463kW - 13.808kW

y 2 = 14.153kW

* This is due to 2 different conditions with same WB temperature, will have the same level of enthalpy. For
more details, please refer to psychrometrics chart

26

2nd Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23C DB, 15C WB
Outdoor Condition: 35C DB
Indoor DB
C

Indoor WB
C

20
23
24

15
15
15

Outdoor DB, C
35
TC (kW)
SC (kW)
19.173
x3
19.173

11.110
y3
15.563

Total capacity, TC
x 3 = 19.173kW (Same as Total capacity at 20C Indoor DB / 15C Indoor WB & 35C Outdoor WB)*

Sensible capacity, SC
Interpolation Method:
24 C - 20 C 15.563kW - 11.110kW

24C - 23 C

15.563kW - y 3

y 3 = 14.450kW

(b) Indoor Condition: 23C DB, 15C WB


Outdoor Condition: 40C DB
Indoor DB
C

Indoor WB
C

20
23
24

15
15
15

Outdoor DB, C
40
TC (kW)
SC (kW)
18.186
x4
18.186

9.698
y4
14.153

Total capacity, TC
x 4 = 18.186kW (Same as Total capacity at 20C Indoor DB / 15C Indoor WB & 40C Outdoor WB)*

Sensible capacity, SC
Interpolation Method:
24 C - 20 C 14.153kW - 9.698kW

24C - 23 C

14.153kW - y 1

y 4 = 13.039kW

* This is due to 2 different conditions with same WB temperature will have the same level of enthalpy. For
more details, please refer to psychrometrics chart

27

3rd Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23C DB, 15C WB
Outdoor Condition: 37C DB
Indoor DB
C

Indoor WB
C

23

15

TC (kW)
19.713

35

Outdoor DB, C
37
SC (kW)
TC (kW)
SC (kW)
14.450

Total capacity, TC
Interpolation Method:
40 C - 35 C 18.186kW - 19.713kW

40C - 37 C

18.186kW - x

x = 19.102kW

Sensible capacity, SC
Interpolation Method:
40 C - 35 C 13.039kW - 14.450kW

40C - 37 C

13.039kW - y

y = 13.886kW

28

TC (kW)
18.186

40

SC (kW)
13.039

R22 MODELS
(COOLING ONLY)
MODEL : ACC 75D / AMC 75D
ID DBC ID WBC

20

24

28

30

15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24

20
TC(kW) SC(kW)
24.294 15.345
24.586 14.284
24.586 18.738
24.877 17.677
25.169 16.616
25.461 15.555
25.750 14.484
25.169 21.069
25.461 20.008
25.750 18.938
26.038 17.860
26.325 16.783
26.612 15.706
26.899 14.629
25.750 21.164
26.038 20.087
26.325 19.010
26.612 17.933
26.899 16.855

25
TC(kW) SC(kW)
22.767 13.934
23.133 13.052
23.133 17.505
23.500 16.623
23.866 15.742
24.233 14.860
24.572 13.887
23.866 20.195
24.233 19.313
24.572 18.341
24.893 17.308
25.214 16.274
25.535 15.241
25.856 14.208
24.572 20.567
24.893 19.534
25.214 18.501
25.535 17.468
25.856 16.435

Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
21.240 12.522 19.713 11.110
21.681 11.819 20.229 10.587
21.681 16.273 20.229 15.040
22.122 15.570 20.744 14.517
22.563 14.867 21.260 13.993
23.004 14.164 21.775 13.469
23.393 13.290 22.215 12.693
22.563 19.321 21.260 18.447
23.004 18.618 21.775 17.923
23.393 17.744 22.215 17.147
23.748 16.755 22.603 16.202
24.103 15.766 22.992 15.257
24.458 14.777 23.381 14.313
24.813 13.788 23.770 13.368
23.393 19.971 22.215 19.374
23.748 18.982 22.603 18.429
24.103 17.993 22.992 17.484
24.458 17.004 23.381 16.539
24.813 16.015 23.770 15.595

40
TC(kW) SC(kW)
18.186 9.698
18.776 9.354
18.776 13.808
19.366 13.463
19.956 13.119
20.546 12.774
21.036 12.096
19.956 17.572
20.546 17.228
21.036 16.550
21.459 15.649
21.882 14.749
22.304 13.848
22.727 12.948
21.036 18.777
21.459 17.876
21.882 16.976
22.304 16.075
22.727 15.174

46
TC(kW) SC(kW)
16.354 8.004
17.033 7.875
17.033 12.329
17.713 12.199
18.392 12.070
19.072 11.940
19.622 11.380
18.392 16.523
19.072 16.394
19.622 15.833
20.085 14.986
20.549 14.138
21.012 13.291
21.476 12.443
19.622 18.060
20.085 17.213
20.549 16.365
21.012 15.518
21.476 14.670

25
TC(kW) SC(kW)
28.908 18.136
29.695 17.179
29.695 22.464
30.483 21.507
31.270 20.549
32.057 19.592
32.801 18.482
31.270 25.835
32.057 24.877
32.801 23.767
33.515 22.555
34.230 21.343
34.944 20.131
35.659 18.919
32.801 26.410
33.515 25.198
34.230 23.986
34.944 22.774
35.659 21.562

Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
27.224 16.650 25.540 15.163
28.046 15.906 26.396 14.634
28.046 21.192 26.396 19.919
28.868 20.448 27.253 19.390
29.690 19.705 28.109 18.861
30.512 18.962 28.966 18.332
31.251 17.930 29.700 17.378
29.690 24.991 28.109 24.146
30.512 24.247 28.966 23.617
31.251 23.215 29.700 22.663
31.935 21.990 30.354 21.425
32.618 20.765 31.007 20.186
33.302 19.539 31.660 18.948
33.986 18.314 32.314 17.709
31.251 25.858 29.700 25.306
31.935 24.632 30.354 24.067
32.618 23.407 31.007 22.829
33.302 22.182 31.660 21.590
33.986 20.957 32.314 20.352

40
TC(kW) SC(kW)
23.856 13.676
24.747 13.362
24.747 18.647
25.638 18.332
26.529 18.017
27.420 17.702
28.150 16.825
26.529 23.302
27.420 22.988
28.150 22.111
28.773 20.859
29.396 19.608
30.018 18.356
30.641 17.105
28.150 24.753
28.773 23.502
29.396 22.250
30.018 20.999
30.641 19.747

46
TC(kW) SC(kW)
21.835 11.892
22.767 11.835
22.767 17.120
23.700 17.062
24.632 17.004
25.565 16.946
26.290 16.163
24.632 22.290
25.565 22.232
26.290 21.448
26.876 20.181
27.462 18.914
28.048 17.646
28.634 16.379
26.290 24.091
26.876 22.824
27.462 21.556
28.048 20.289
28.634 19.022

MODEL : ACC 100D / AMC 100D


ID DBC ID WBC

20

24

28

30

15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24

20
TC(kW) SC(kW)
30.592 19.623
31.345 18.451
31.345 23.736
32.098 22.565
32.851 21.393
33.603 20.222
34.351 19.034
32.851 26.679
33.603 25.507
34.351 24.319
35.096 23.120
35.841 21.922
36.586 20.723
37.331 19.524
34.351 26.962
35.096 25.763
35.841 24.564
36.586 23.365
37.331 22.166

29

R22 MODELS
(HEATPUMP)
MODEL : ACC 75DR / AMC 75ER

COOLING MODE
ID DBC ID WBC

20

24

28

30

15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24

20
TC(kW) SC(kW)
24.294 15.345
24.586 14.284
24.586 18.738
24.877 17.677
25.169 16.616
25.461 15.555
25.750 14.484
25.169 21.069
25.461 20.008
25.750 18.938
26.038 17.860
26.325 16.783
26.612 15.706
26.899 14.629
25.750 21.164
26.038 20.087
26.325 19.010
26.612 17.933
26.899 16.855

25
TC(kW) SC(kW)
22.767 13.934
23.133 13.052
23.133 17.505
23.500 16.623
23.866 15.742
24.233 14.860
24.572 13.887
23.866 20.195
24.233 19.313
24.572 18.341
24.893 17.308
25.214 16.274
25.535 15.241
25.856 14.208
24.572 20.567
24.893 19.534
25.214 18.501
25.535 17.468
25.856 16.435

Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
21.240 12.522 19.713 11.110
21.681 11.819 20.229 10.587
21.681 16.273 20.229 15.040
22.122 15.570 20.744 14.517
22.563 14.867 21.260 13.993
23.004 14.164 21.775 13.469
23.393 13.290 22.215 12.693
22.563 19.321 21.260 18.447
23.004 18.618 21.775 17.923
23.393 17.744 22.215 17.147
23.748 16.755 22.603 16.202
24.103 15.766 22.992 15.257
24.458 14.777 23.381 14.313
24.813 13.788 23.770 13.368
23.393 19.971 22.215 19.374
23.748 18.982 22.603 18.429
24.103 17.993 22.992 17.484
24.458 17.004 23.381 16.539
24.813 16.015 23.770 15.595

HEATING MODE
ID DBC

15
17
19
21
23
25
27

-9
TC(kW) SC(kW)
15.812 15.812
15.621 15.621
15.431 15.431
15.240 15.240
15.149 15.149
15.058 15.058
14.967 14.967

-6
TC(kW) SC(kW)
17.812 17.812
17.640 17.640
17.468 17.468
17.296 17.296
17.149 17.149
17.002 17.002
16.855 16.855
FROST REGION

-5
TC(kW)
18.478
18.313
18.147
17.981
17.816
17.650
17.485

SC(kW)
18.478
18.313
18.147
17.981
17.816
17.650
17.485

Outdoor WBC
6
TC(kW) SC(kW)
25.812 25.812
25.414 25.414
25.017 25.017
24.619 24.619
24.564 24.564
24.510 24.510
24.455 24.455

30

12
TC(kW)
29.812
29.546
29.280
29.014
28.748
28.482
28.217

40
TC(kW) SC(kW)
18.186 9.698
18.776 9.354
18.776 13.808
19.366 13.463
19.956 13.119
20.546 12.774
21.036 12.096
19.956 17.572
20.546 17.228
21.036 16.550
21.459 15.649
21.882 14.749
22.304 13.848
22.727 12.948
21.036 18.777
21.459 17.876
21.882 16.976
22.304 16.075
22.727 15.174

SC(kW)
29.812
29.546
29.280
29.014
28.748
28.482
28.217

15
TC(kW)
31.812
31.529
31.245
30.961
30.678
30.394
30.110

46
TC(kW) SC(kW)
16.354 8.004
17.033 7.875
17.033 12.329
17.713 12.199
18.392 12.070
19.072 11.940
19.622 11.380
18.392 16.523
19.072 16.394
19.622 15.833
20.085 14.986
20.549 14.138
21.012 13.291
21.476 12.443
19.622 18.060
20.085 17.213
20.549 16.365
21.012 15.518
21.476 14.670

SC(kW)
31.812
31.529
31.245
30.961
30.678
30.394
30.110

18
TC(kW)
33.812
33.511
33.210
32.908
32.607
32.306
32.004

SC(kW)
33.812
33.511
33.210
32.908
32.607
32.306
32.004

R22 MODELS
(HEATPUMP)
MODEL : ACC 100D / AMC 100ER

COOLING MODE
ID DBC ID WBC

20

24

28

30

15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24

20
TC(kW) SC(kW)
30.592 19.623
31.345 18.451
31.345 23.736
32.098 22.565
32.851 21.393
33.603 20.222
34.351 19.034
32.851 26.679
33.603 25.507
34.351 24.319
35.096 23.120
35.841 21.922
36.586 20.723
37.331 19.524
34.351 26.962
35.096 25.763
35.841 24.564
36.586 23.365
37.331 22.166

25
TC(kW) SC(kW)
28.908 18.136
29.695 17.179
29.695 22.464
30.483 21.507
31.270 20.549
32.057 19.592
32.801 18.482
31.270 25.835
32.057 24.877
32.801 23.767
33.515 22.555
34.230 21.343
34.944 20.131
35.659 18.919
32.801 26.410
33.515 25.198
34.230 23.986
34.944 22.774
35.659 21.562

Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
27.224 16.650 25.540 15.163
28.046 15.906 26.396 14.634
28.046 21.192 26.396 19.919
28.868 20.448 27.253 19.390
29.690 19.705 28.109 18.861
30.512 18.962 28.966 18.332
31.251 17.930 29.700 17.378
29.690 24.991 28.109 24.146
30.512 24.247 28.966 23.617
31.251 23.215 29.700 22.663
31.935 21.990 30.354 21.425
32.618 20.765 31.007 20.186
33.302 19.539 31.660 18.948
33.986 18.314 32.314 17.709
31.251 25.858 29.700 25.306
31.935 24.632 30.354 24.067
32.618 23.407 31.007 22.829
33.302 22.182 31.660 21.590
33.986 20.957 32.314 20.352

HEATING MODE
ID DBC

15
17
19
21
23
25
27

-9
TC(kW) SC(kW)
23.133 23.133
23.140 23.140
23.147 23.147
23.154 23.154
22.720 22.720
22.285 22.285
21.851 21.851

-6
TC(kW) SC(kW)
24.838 24.838
24.669 24.669
24.500 24.500
24.330 24.330
24.051 24.051
23.772 23.772
23.492 23.492
FROST REGION

-5
TC(kW)
25.406
25.178
24.951
24.723
24.495
24.267
24.039

SC(kW)
25.406
25.178
24.951
24.723
24.495
24.267
24.039

Outdoor WBC
6
TC(kW) SC(kW)
31.659 31.659
31.852 31.852
32.046 32.046
32.239 32.239
31.455 31.455
30.670 30.670
29.886 29.886

31

12
TC(kW)
35.069
34.756
34.444
34.131
33.818
33.505
33.192

40
TC(kW) SC(kW)
23.856 13.676
24.747 13.362
24.747 18.647
25.638 18.332
26.529 18.017
27.420 17.702
28.150 16.825
26.529 23.302
27.420 22.988
28.150 22.111
28.773 20.859
29.396 19.608
30.018 18.356
30.641 17.105
28.150 24.753
28.773 23.502
29.396 22.250
30.018 20.999
30.641 19.747

SC(kW)
35.069
34.756
34.444
34.131
33.818
33.505
33.192

15
TC(kW)
36.775
36.447
36.119
35.791
35.463
35.135
34.807

46
TC(kW) SC(kW)
21.835 11.892
22.767 11.835
22.767 17.120
23.700 17.062
24.632 17.004
25.565 16.946
26.290 16.163
24.632 22.290
25.565 22.232
26.290 21.448
26.876 20.181
27.462 18.914
28.048 17.646
28.634 16.379
26.290 24.091
26.876 22.824
27.462 21.556
28.048 20.289
28.634 19.022

SC(kW)
36.775
36.447
36.119
35.791
35.463
35.135
34.807

18
TC(kW)
38.480
38.137
37.794
37.451
37.108
36.765
36.422

SC(kW)
38.480
38.137
37.794
37.451
37.108
36.765
36.422

R407C MODELS
(COOLING ONLY)
MODEL : ACC 75D / A4MC 75D
ID DBC ID WBC

20

24

28

30

15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24

20
TC(kW) SC(kW)
24.294 15.345
24.586 14.284
24.586 18.738
24.877 17.677
25.169 16.616
25.461 15.555
25.750 14.484
25.169 21.069
25.461 20.008
25.750 18.938
26.038 17.860
26.325 16.783
26.612 15.706
26.899 14.629
25.750 21.164
26.038 20.087
26.325 19.010
26.612 17.933
26.899 16.855

25
TC(kW) SC(kW)
22.767 13.934
23.133 13.052
23.133 17.505
23.500 16.623
23.866 15.742
24.233 14.860
24.572 13.887
23.866 20.195
24.233 19.313
24.572 18.341
24.893 17.308
25.214 16.274
25.535 15.241
25.856 14.208
24.572 20.567
24.893 19.534
25.214 18.501
25.535 17.468
25.856 16.435

Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
21.240 12.522 19.713 11.110
21.681 11.819 20.229 10.587
21.681 16.273 20.229 15.040
22.122 15.570 20.744 14.517
22.563 14.867 21.260 13.993
23.004 14.164 21.775 13.469
23.393 13.290 22.215 12.693
22.563 19.321 21.260 18.447
23.004 18.618 21.775 17.923
23.393 17.744 22.215 17.147
23.748 16.755 22.603 16.202
24.103 15.766 22.992 15.257
24.458 14.777 23.381 14.313
24.813 13.788 23.770 13.368
23.393 19.971 22.215 19.374
23.748 18.982 22.603 18.429
24.103 17.993 22.992 17.484
24.458 17.004 23.381 16.539
24.813 16.015 23.770 15.595

40
TC(kW) SC(kW)
18.186 9.698
18.776 9.354
18.776 13.808
19.366 13.463
19.956 13.119
20.546 12.774
21.036 12.096
19.956 17.572
20.546 17.228
21.036 16.550
21.459 15.649
21.882 14.749
22.304 13.848
22.727 12.948
21.036 18.777
21.459 17.876
21.882 16.976
22.304 16.075
22.727 15.174

46
TC(kW) SC(kW)
16.354 8.004
17.033 7.875
17.033 12.329
17.713 12.199
18.392 12.070
19.072 11.940
19.622 11.380
18.392 16.523
19.072 16.394
19.622 15.833
20.085 14.986
20.549 14.138
21.012 13.291
21.476 12.443
19.622 18.060
20.085 17.213
20.549 16.365
21.012 15.518
21.476 14.670

25
TC(kW) SC(kW)
28.908 18.136
29.695 17.179
29.695 22.464
30.483 21.507
31.270 20.549
32.057 19.592
32.801 18.482
31.270 25.835
32.057 24.877
32.801 23.767
33.515 22.555
34.230 21.343
34.944 20.131
35.659 18.919
32.801 26.410
33.515 25.198
34.230 23.986
34.944 22.774
35.659 21.562

Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
27.224 16.650 25.540 15.163
28.046 15.906 26.396 14.634
28.046 21.192 26.396 19.919
28.868 20.448 27.253 19.390
29.690 19.705 28.109 18.861
30.512 18.962 28.966 18.332
31.251 17.930 29.700 17.378
29.690 24.991 28.109 24.146
30.512 24.247 28.966 23.617
31.251 23.215 29.700 22.663
31.935 21.990 30.354 21.425
32.618 20.765 31.007 20.186
33.302 19.539 31.660 18.948
33.986 18.314 32.314 17.709
31.251 25.858 29.700 25.306
31.935 24.632 30.354 24.067
32.618 23.407 31.007 22.829
33.302 22.182 31.660 21.590
33.986 20.957 32.314 20.352

40
TC(kW) SC(kW)
23.856 13.676
24.747 13.362
24.747 18.647
25.638 18.332
26.529 18.017
27.420 17.702
28.150 16.825
26.529 23.302
27.420 22.988
28.150 22.111
28.773 20.859
29.396 19.608
30.018 18.356
30.641 17.105
28.150 24.753
28.773 23.502
29.396 22.250
30.018 20.999
30.641 19.747

46
TC(kW) SC(kW)
21.835 11.892
22.767 11.835
22.767 17.120
23.700 17.062
24.632 17.004
25.565 16.946
26.290 16.163
24.632 22.290
25.565 22.232
26.290 21.448
26.876 20.181
27.462 18.914
28.048 17.646
28.634 16.379
26.290 24.091
26.876 22.824
27.462 21.556
28.048 20.289
28.634 19.022

MODEL : ACC 100D / A4MC 100D


ID DBC ID WBC

20

24

28

30

15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24

20
TC(kW) SC(kW)
30.592 19.623
31.345 18.451
31.345 23.736
32.098 22.565
32.851 21.393
33.603 20.222
34.351 19.034
32.851 26.679
33.603 25.507
34.351 24.319
35.096 23.120
35.841 21.922
36.586 20.723
37.331 19.524
34.351 26.962
35.096 25.763
35.841 24.564
36.586 23.365
37.331 22.166

32

R407C MODELS
(HEATPUMP)
MODEL : ACC 75DR / A4MC 75ER

COOLING MODE
ID DBC ID WBC

20

24

28

30

15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24

20
TC(kW) SC(kW)
24.294 15.345
24.586 14.284
24.586 18.738
24.877 17.677
25.169 16.616
25.461 15.555
25.750 14.484
25.169 21.069
25.461 20.008
25.750 18.938
26.038 17.860
26.325 16.783
26.612 15.706
26.899 14.629
25.750 21.164
26.038 20.087
26.325 19.010
26.612 17.933
26.899 16.855

25
TC(kW) SC(kW)
22.767 13.934
23.133 13.052
23.133 17.505
23.500 16.623
23.866 15.742
24.233 14.860
24.572 13.887
23.866 20.195
24.233 19.313
24.572 18.341
24.893 17.308
25.214 16.274
25.535 15.241
25.856 14.208
24.572 20.567
24.893 19.534
25.214 18.501
25.535 17.468
25.856 16.435

Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
21.240 12.522 19.713 11.110
21.681 11.819 20.229 10.587
21.681 16.273 20.229 15.040
22.122 15.570 20.744 14.517
22.563 14.867 21.260 13.993
23.004 14.164 21.775 13.469
23.393 13.290 22.215 12.693
22.563 19.321 21.260 18.447
23.004 18.618 21.775 17.923
23.393 17.744 22.215 17.147
23.748 16.755 22.603 16.202
24.103 15.766 22.992 15.257
24.458 14.777 23.381 14.313
24.813 13.788 23.770 13.368
23.393 19.971 22.215 19.374
23.748 18.982 22.603 18.429
24.103 17.993 22.992 17.484
24.458 17.004 23.381 16.539
24.813 16.015 23.770 15.595

HEATING MODE
ID DBC

15
17
19
21
23
25
27

-9
TC(kW) SC(kW)
15.812 15.812
15.621 15.621
15.431 15.431
15.240 15.240
15.149 15.149
15.058 15.058
14.967 14.967

-6
TC(kW) SC(kW)
17.812 17.812
17.640 17.640
17.468 17.468
17.296 17.296
17.149 17.149
17.002 17.002
16.855 16.855
FROST REGION

-5
TC(kW)
18.478
18.313
18.147
17.981
17.816
17.650
17.485

SC(kW)
18.478
18.313
18.147
17.981
17.816
17.650
17.485

Outdoor WBC
6
TC(kW) SC(kW)
25.812 25.812
25.414 25.414
25.017 25.017
24.619 24.619
24.564 24.564
24.510 24.510
24.455 24.455

33

12
TC(kW)
29.812
29.546
29.280
29.014
28.748
28.482
28.217

40
TC(kW) SC(kW)
18.186 9.698
18.776 9.354
18.776 13.808
19.366 13.463
19.956 13.119
20.546 12.774
21.036 12.096
19.956 17.572
20.546 17.228
21.036 16.550
21.459 15.649
21.882 14.749
22.304 13.848
22.727 12.948
21.036 18.777
21.459 17.876
21.882 16.976
22.304 16.075
22.727 15.174

SC(kW)
29.812
29.546
29.280
29.014
28.748
28.482
28.217

15
TC(kW)
31.812
31.529
31.245
30.961
30.678
30.394
30.110

46
TC(kW) SC(kW)
16.354 8.004
17.033 7.875
17.033 12.329
17.713 12.199
18.392 12.070
19.072 11.940
19.622 11.380
18.392 16.523
19.072 16.394
19.622 15.833
20.085 14.986
20.549 14.138
21.012 13.291
21.476 12.443
19.622 18.060
20.085 17.213
20.549 16.365
21.012 15.518
21.476 14.670

SC(kW)
31.812
31.529
31.245
30.961
30.678
30.394
30.110

18
TC(kW)
33.812
33.511
33.210
32.908
32.607
32.306
32.004

SC(kW)
33.812
33.511
33.210
32.908
32.607
32.306
32.004

R407C MODELS
(HEATPUMP)
MODEL : ACC 100D / A4MC 100ER

COOLING MODE
ID DBC ID WBC

20

24

28

30

15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24

20
TC(kW) SC(kW)
30.592 19.623
31.345 18.451
31.345 23.736
32.098 22.565
32.851 21.393
33.603 20.222
34.351 19.034
32.851 26.679
33.603 25.507
34.351 24.319
35.096 23.120
35.841 21.922
36.586 20.723
37.331 19.524
34.351 26.962
35.096 25.763
35.841 24.564
36.586 23.365
37.331 22.166

25
TC(kW) SC(kW)
28.908 18.136
29.695 17.179
29.695 22.464
30.483 21.507
31.270 20.549
32.057 19.592
32.801 18.482
31.270 25.835
32.057 24.877
32.801 23.767
33.515 22.555
34.230 21.343
34.944 20.131
35.659 18.919
32.801 26.410
33.515 25.198
34.230 23.986
34.944 22.774
35.659 21.562

Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
27.224 16.650 25.540 15.163
28.046 15.906 26.396 14.634
28.046 21.192 26.396 19.919
28.868 20.448 27.253 19.390
29.690 19.705 28.109 18.861
30.512 18.962 28.966 18.332
31.251 17.930 29.700 17.378
29.690 24.991 28.109 24.146
30.512 24.247 28.966 23.617
31.251 23.215 29.700 22.663
31.935 21.990 30.354 21.425
32.618 20.765 31.007 20.186
33.302 19.539 31.660 18.948
33.986 18.314 32.314 17.709
31.251 25.858 29.700 25.306
31.935 24.632 30.354 24.067
32.618 23.407 31.007 22.829
33.302 22.182 31.660 21.590
33.986 20.957 32.314 20.352

HEATING MODE
ID DBC

15
17
19
21
23
25
27

-9
TC(kW) SC(kW)
23.133 23.133
23.140 23.140
23.147 23.147
23.154 23.154
22.720 22.720
22.285 22.285
21.851 21.851

-6
TC(kW) SC(kW)
24.838 24.838
24.669 24.669
24.500 24.500
24.330 24.330
24.051 24.051
23.772 23.772
23.492 23.492
FROST REGION

-5
TC(kW)
25.406
25.178
24.951
24.723
24.495
24.267
24.039

SC(kW)
25.406
25.178
24.951
24.723
24.495
24.267
24.039

Outdoor WBC
6
TC(kW) SC(kW)
31.659 31.659
31.852 31.852
32.046 32.046
32.239 32.239
31.455 31.455
30.670 30.670
29.886 29.886

34

12
TC(kW)
35.069
34.756
34.444
34.131
33.818
33.505
33.192

40
TC(kW) SC(kW)
23.856 13.676
24.747 13.362
24.747 18.647
25.638 18.332
26.529 18.017
27.420 17.702
28.150 16.825
26.529 23.302
27.420 22.988
28.150 22.111
28.773 20.859
29.396 19.608
30.018 18.356
30.641 17.105
28.150 24.753
28.773 23.502
29.396 22.250
30.018 20.999
30.641 19.747

SC(kW)
35.069
34.756
34.444
34.131
33.818
33.505
33.192

15
TC(kW)
36.775
36.447
36.119
35.791
35.463
35.135
34.807

46
TC(kW) SC(kW)
21.835 11.892
22.767 11.835
22.767 17.120
23.700 17.062
24.632 17.004
25.565 16.946
26.290 16.163
24.632 22.290
25.565 22.232
26.290 21.448
26.876 20.181
27.462 18.914
28.048 17.646
28.634 16.379
26.290 24.091
26.876 22.824
27.462 21.556
28.048 20.289
28.634 19.022

SC(kW)
36.775
36.447
36.119
35.791
35.463
35.135
34.807

18
TC(kW)
38.480
38.137
37.794
37.451
37.108
36.765
36.422

SC(kW)
38.480
38.137
37.794
37.451
37.108
36.765
36.422

8. OUTLINES AND DIMENSIONS


INDOOR UNIT
MODEL : AC C 75D/DR

Note: Dimension in mm
MODEL : ACC 100D/DR

Note: Dimension in mm
35

OUTDOOR UNIT
MODEL : AMC / A4MC 75 / 100 D/ER

Note: Dimension in mm

36

. REFRIGERANT
9.
REFRIGERANTCIRCUIT
CIRCUIT
MODEL : AC C 75/100D - AMC / A4MC 75/100D

MODEL : ACC 75/100DR - AMC / A4MC 75/100ER

37

10. WIRING DIAGRAMS


COOLING UNIT
MODEL : ACC 75/100D - AMC / A4MC 75/100D

38

MODEL : ACC 75/100DR - AMC / A4MC 75/100ER

39

11. INSTALLATION
PRELIMINARY SITE SURVEY

Electrical supply and installation is to conform to local authority's codes and regulations. (e.g. National Electricity Board).
Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply lines must be independent of
welding transformers which can cause high supply fluctuation. Ensure that the location is convenient for wiring and
piping.

INSTALLATION OF INDOOR UNIT

The indoor unit must be installed such that there is no short circuit of the cool discharge. Comply to the installation
clearance recommended. Do not put the indoor unit where there is direct sunlight on unit. Make sure the location is
suitable for piping and drainage. Precautions steps :

800.0

i) Use the hanger supplied with the unit.


ii) Ensure the support is strong enough to withstand the weight of the unit.

800.0

800.0

PIPINGS

Do not use contaminated or damaged copper tubings. If pipings, evaporator or condenser are exposed or
had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do
not remove plastic/rubber plugs/caps from fittings, tubings and coils until ready to connect suction or liquid
line into fittings.

OPERATIONAL CHECK

After all electrical wiring is completed and the system is charged with refrigerant, make sure unit is operating
properly. Check that:
a)
b)
c)
d)

Condenser fans are running, with warm air blowing off the condenser coil.
Evaporator blowers are running and discharging cool air.
Suction line inside condensing unit feels cool.
Liquid line inside condensing unit feels warm.

ELECTRICAL CONNECTION

As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for
field wiring regulations and ensure that these are complied with. Besides, observe the following general
precautions:
a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring
work.
b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit
breaker for over-current protection should be provided in the exclusive line.
c) The unit must be GROUNDED to prevent possible hazard due to insulation failure.
d) All wiring must be firmly connected.
e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan
motors.

40

SPECIAL PRE CAUTIONS WHEN DEALING WITH REFRIGERANT R40 7C UNIT


1) WHAT IS NEW REFRIGERANT R407C?

R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0) and thus
conformed to the Montreal Protocol regulation. It requires Polyol-ester oil (POE) oil for its compressor's
lubricant. Its refrigerant capacity and performance are about the same as the refrigerant R22.

2) COMPONENTS

Mixture weight composition R32(23%), R125(25%), R134a(52%)

3) CHARACT ERISTIC

R407C liquid and vapor components have different compositions when the fluid evaporates or
condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerant
mixture left in the system will change and subsequently affect the system performance. DO NOT add
new refrigerant to leaked system. It is recommended that the system should be evacuated thoroughly
before recharging with R407C.
When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or
liquid phase. Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder
or can. This is to make certain that only original composition of R407C is being charged into the
system.
POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22
compressor. Extra precaution must be taken not to expose the R407C system too long to moist air.

4) CHECK LIST BEFORE INSTAL LATION/SERVICING

Tubing
Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure to
temporarily cover the ends of the tubing prior to installation
Compressor oil
No additional charge of compressor oil is permitted.
Refrigerant
No other refrigerant other that R407C
Tools
Tools specifically for R407C only (must not be used for R22 or other refrigerant)
i)
Manifold gauge and charging hose
ii)
Gas leak detector
iii) Refrigerant cylinder/charging cylinder
iv) Vacuum pump c/w adapter
v)
Flare tools
vi) Refrigerant recovery machine

5) HANDLING AND INSTALL ATION GUIDELINES

Like R22 system, the handling and installation of R407C system are closely similar. All precautionary
measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and
thorough leak check and vacuuming are equally important requirements. However, due to zeotropic nature
of R407C and its hydroscopic POE oil, additional precautions must be taken to ensure optimum and
trouble-free system operation.
a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve
type. For a heat-pump system, install a two-way flow filter dryer along the liquid line.
b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to
moist air. Residual POE oil in the piping and components can absorb moisture from the air.

41

c) Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is
about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.

R32/R125/R134
23% / 25% / 52%
33% / 33% / 34%

Composition of R407C in vapour phase


is different from liquid phase.
f)

Normally, the R407C cylinder or can is being equipped with a dip pipe for liquid withdrawal. However, if
the dip pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.

Invert cylinder
without dip-pipe

Dip-pipe

Liquid
withdrawal

g) When servicing leak, the top up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made up of three different components, may have changed during the leak. Consequently, a top
up may not ensure that the R407C in the system is of original composition. This composition shift may
adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.

42

12. SERVICING AND MAINTENANCE

Warning
Disconnect from Main Supply before Servicing the air conditioner
The unit is designed to give a long life operation with minimum maintenance required. However, it should be
regularly checked and the following items should be given due attention.

Components
Air Filters

Maintenance Procedure
1. Clean with a vacuum cleaner, or by tapping lightly
and then washing in lukewarm water (below 40C)
With neutral soap.

Recommended Schedule
Every 2 weeks.
More frequently if required.

2. Rinse well to dry before re-installing.


3. Note : Never use petrol, thinner, benzene or any
other chemicals.
Indoor Unit

1. Clean away dirt or dust on grille or panel by wiping


with a soft cloth soaked in lukewarm (or cold)
water or neutral detergent solution.

Every 2 weeks.
More frequently if required.

2. Note: Never use petrol, thinner, benzene or any


other volatile chemicals, which may cause
plastic surface to deform.
Condensate Drain

1. Check and clean.

Every 3 months.

Indoor Fan

1. Check for unusual noise.

As necessary.

Indoor/Outdoor Coil

1. Check and remove dirt which are clogged between


fins.

Every month.

Pan & Pipe

2. Check and remove obstacles which hinder air flow


in and out of indoor/outdoor unit.
Electrical

1.

Check voltage, current and wiring.

Every month.
Every 2 months.

2. Check faulty contacts caused by loose connections,


foreign matters, etc.

Every 2 months.

Compressor

1. No maintenance needed if refrigerant circuit


remains sealed. However, check for refrigerant leak
at joints & fittings.

Every 6 months.

Compressor
Lubrication

1. Oil is factory charged. Not necessary to add oil if


circuit remains sealed.

No maintenance required.

Fan Motors
Lubrication

1. All motors pre-lubricated and sealed at factory.

No maintenance required.

PRE-START UP MAINTENANCE (AFTER EXTENDED SHUTDOWN)


-

Inspect thoroughly and clean indoor and outdoor units.


Clean or replace air filters.
Clean condensate drain line.
Clean clogged indoor and outdoor coils.
Check fan imbalance before operation.
Tighten all wiring connections and panels.
Check for refrigerant leakage.

43

The design concept of the Condensing Unit is such that all servicing can be done from the front and side of the unit.
Upon removal of front and side panel, all the electrical "terminal box", fan and motor assembly and compressor are easily
accessible.
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surfaces once
quarterly. However, if a unit is installed in area subjected to much oil, mist and dust, the coil must be regularly cleaned by
qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation. Otherwise, the
systems life span might be shortened.
CAUTION
When the compressor is to be stopped for a long time, the crankcase heater should be energized for at least
6 hours before start of operation.
Do not charge OXYGEN, ACETYLENE or other flammable and poisonous gases into the refrigeration cycle
when performing a leakage test or an airtight-test. These types of gases are extremely dangerous, because
explosion can occur.
It is recommended that nitrogen or refrigerant be charged for these types of tests.

CAUTION FOR USE

Bear the following points in mind to safeguard against malfunction and breakdown.
Do not stick rods or other objects through the air outlet during operation since this may result to damage or injury

The air conditioner must not re-start within 3 minutes after shutdown. (These models are equipped with a crankcase
heater with the compressor).

Make sure the air conditioner is properly grounded by checking the ground terminal.

MAINTENANCE

For superb performance and lasting durability, please do not forget to conduct proper and regular maintenance.
Cleaning The Outdoor Unit Heat Exchanger
If you use your air conditioner for prolonged period of time, the outdoor unit heat exchanger will become dirty
impairing its function and reducing the performance of the air conditioned. Consult your local dealer about the cleaning of
the heat exchanger.

44

13. TROUBLESHOOTING
When any air-conditioner malfunction is noted, immediately switch off the power supply to the unit, and
contact the local dealer, if necessary. Some simple troubleshooting tips are given below :

FAULT

CAUSE

1. Fan does not work 3 minutes after


starting

Protection against the frequent starting. Wait 3 or 4 minutes.

2. The air conditioning unit does not


work

Power failure or need to replace the fuse.


The power plug is disconnected.
Possibility of making a programming error in the controller.
If the fault persist after these verifications, contact your installer.

3. The air conditioning unit does not


blow sufficiently

The air filter is dirty.


The doors or windows are open.
The air entrance and exit are clogged.
The regulate temperature is not high enough.

4. The remote control light is deficient The batteries are discharge.


The batteries are not correctly inserted.
The assembly is not good.
5. Air discharge flow has a bad odor

This odor can be caused by cigarette smoke particles, perfume,


sweat, which stick to the coil.
Check if there is any moisture on the walls, garment, other.
Check the drain pan.

6. Condensation on the air grille of


indoor unit

This is due to air humidity after a long time of operation.

7. The water flow of air conditioning


unit

Check the condensate evacuation.

8. The air conditioning unit are noisy

Air flow noise : refrigerant fluid admission in evaporator.

The unit has a lower temperature point, increase the point and
operate at high speed.

45

FOR COOLING ONLY MODELS OR HEAT PUMP MODELS (COOLING CYCLE)


DIAGNOSIS BY FLOW CHART
The following chart are efficient checking procedures for troubleshooting when these fan-coil units, are
coupled with the condensing units using standard wiring. For dual circuited models, perform the procedures
for each circuit.

No Cooling
: Check

: Faulty

: Cause

Remedy

No Cooling ( Compresor Does Not Start )


Evaporator
Fan Motor

Stop

Unit Power
Supply

Running

Faulty

Fuse For
Operation
Circuit

Blown

Overcurrent
Relay For
Evaporator Fan

Tripped

Evaporator Fan
Contactor

No Voltage or Low Voltage

Get the Right Voltage

Single-Phase

Repair the Power Line

Components Shorted
Connections Loose
High Volage or Low Voltage
Single-Phase

Faulty

Coil Burned
Contact Faulty
Faulty Fan Motor
Defective Operation Switch

Condenser
Fan Motor

Repair or Replace The Components


Tighten The Connections
Get The Right Voltage
Check The Power Supply To The
Motor : Repair When Necessary

Change The Contactor


Repair The Contacts
Repair Or Change The Motor
Repair Or Replace The Switch

Stop
Overcurrent
Relay For
Condenser Fan

Tripped

High Voltage or Low Voltage


Single-Phase

Get The Right Voltage


Check The Power Supply To The
Motor : Repair When Necessary

Running
Condenser Fan
Contactor

Faulty

Coil Burnt
Contact Faulty
Fan Motor Faulty
Other Electrical Component Faulty

Compressor
Contactor

Faulty

Coil Burnt
Contact Faulty
Open Compressor Windings
Incorrect Wiring

46

Change The Contactor


Change The Contacts
Repair or Change The Motor
Repair or Change If Necessary

Change The Contactor


Repair The Contacts
Change The Compressor
Correct The Wiring

INSUFFICIENT COOLING
Insufficient Cooling

Compressor
Cycling

Cycling On

Dual Pressure
Switch

Tripping

High Discharge Pressure or Low


Suction Pressure
Clogged Capillary or Pressure
Switch
Switch Faulty

Running

Overcurrent
Relay For
Compressor

Tripping

High Voltage or Low Voltage


Single-Phase
High Discharge Pressure And
High Suction Pressure
Loose Connections

Discharge Gas
Thermostat or
Internal
Thermostat

Tripping

High Discharge Pressure And


Low Suction Pressure
Refrigerant Short Charge or
Refrigerant Leakage
High Suction Pressure
High Discharge Pressure or Low
Suction Pressure

See "High Discharge Pressure" or


"Low Suction Pressure"
Repair Clogging and Replace
The Switch If Required
Repair or Change If Necessary
Get The Right Voltage
Check The Power Line To The
Compressor : Repair When Necessary
See "High Discharge Pressure"
or "High Suction Pressure"
Tighten The Connections
See "High Discharge Pressure"
or "Low Suction Pressure"
Add Refrigerant. Repair
Leakage If Detected.
See "High Suction Pressure"
See "High Discharge Pressure"
or "Low Suction Pressure"

HIGH DISCHARGE PRESSURE


High Discharge
Pressure
Restricted
Condenser
Air Flow

Clogged Condenser Coil


Low Fan Speed

Condenser
Air Inlet
Temperature

High

Malfunction Of Fan Cycling


System
Circulating Air Flow
Overcharged Refrigerant
Non-Condensable Gas
Restricted Liquid Line
High Suction Pressure

Clean The Condenser


Check The Voltage And Get
The Right Voltage
Check The System And
Repair If Required
Secure Space For
Required Air Flow
Purge The Refrigerant
Purge The Gas
Remove The Restriction
See "High Suction Pressure"

LOW DISCHARGE PRESSURE


Low Discharge
Pressure

Condenser
Air Flow

Excessive

Malfunction Of Fan Cycling


System
Low Refrigerant Charge
Low Ambient Temperature

47

Check The System And Repair The


Components If Required
Add Refrigerant
See The Unit Working Range

HIGH SUCTION PRESSURE


High Suction
Pressure
Low

Evaporator
Air Inlet
Temperature

Excessive Fresh Air Intake

Reduce The Fresh Air Intake

Insufficient Duct Insulation

Reinforce The Duct Insulation

Defective Compressor Valve


Overcharged Refrigerant

Change Or Repair The Compressor


Purge The Refrigerant

LOW SUCTION PRESSURE


Low Suction Pressure

Evaporator
Air Flow

Restricted

Evaporator
Air Inlet
Temperature

Clogged Air Filter

Low

Clean The Air Filter

Restricted Duct

Remove The Restriction

Low Fan Speed

Adjust The Fan Speed

Short Cycling
Faulty Thermostat
Restricted Liquid LIne And
Suction Line
Low Refrigerant Charge
Low Discharge Pressure

Remove Obstacles To Air Circulation


Repair Or Replace If Necessary
Remove The Restriction
Add Refrigerant
See "Low Discharge Pressure"

NOISY OPERATION
Noisy Operation
Compressor

Noisy
Shipping
Bolt(s)

Noisy

Unremoved Shipping Bolt(s)


Overcharged Refrigerant

Liquid
Refrigerant
Backing Up

Low Suction Pressure


Worn Compressor Parts

Evaporator
Fan

Liquid Line

Noisy

Knocking Runner

Noisy

Strainer
Whistling

Worn Bearing

Remove The Bolt(s)


Purge The Refrigerant
See "Low Suction Pressure"
Replace Or Repair The Compressor
Fix The Runner Or Casing Properly
Change The Bearing

Partially Clogged

Clean The Dryer

Refrigerant Short Charge

Add Refrigerant

Loose Fixed Screws


Inadequate Duct Work

48

Tighten All Fixed Screws


Check Flexible Ducts

FOR HEAT PUMP MODELS


By means of pressure readings :

Too
High

PROBABLE CAUSE
A Little
High

Circuit

Normal

Too
Low

Data

A Little
Low

PRESSURE

High Side
Low Side

1. Overcharged with refrigerant.


2. Non-condensable gases in refrigerant circuit (e.g. oil).
3. Obstructed air-intake/discharge.
4. Short circuiting of hot air outdoor unit.
1. Poor compression/no compression (compressor defective.)
2. Check valve stick in open position.
3. Reversing valve leaking.
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air filter clogged/dirty (indoor unit).
4. Indoor fan locked.
5. Defective defrost control, outdoor coil freeze up (heating).
6. Outdoor fan locked (heating).
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked (heating).
4. Indoor filter clogged/dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air)
1. Air intake temperature of indoor unit too high.

High Side
Low Side
High Side
Low Side

High Side
Low Side

High Side
Low Side

BY MEANS OF DIAGNOSIS FLOW CHART


Generally, there are two kind of problems, i.e. starting failure and insufficient cooling/heating. "Starting Failure" is
caused by electrical defect while "Insufficient Cooling/Heating" is caused by improper application or defects in
refrigerant circuit.

i) DIAGNOSIS OF ELECTRIC CIRCUIT

No Cooling / Heating
Unit fail to start

Check power supply


- voltage
- phase
- frequency

Check settings of remote control box

Check power source cord

Check circuit breake & fuse

Fan fails to start

Compressor fails to start

Fan Motor Capacitor defective

Thermostat setting too high

Loose Connections,
Contactors

Protection Device Actuated

Irregular motor resistance ( )


& insulation (M )

Reset

Voltage supply not within range


Loose Connections,
Improper wiring
Compressor
Capacitor Defective

Check motor resistance ( ) and insulation (M )

Replace Fan Motor


Regular but fails
to start

Irregular

Compressor locked (to replace compressor)

Compressor Motor damaged ( to replace compressor)

49

The most common causes of air conditioner failure to start" are:


a) Voltage not within 10% of rated voltage.
b) Power supply interrupted.
c) Control settings improper.
d) Air conditioner is disconnected from main power source.
e) Fuse blown or circuit breaker off.

ii) DIAGNOSIS OF REFRIGERANT CIRCUIT / APPLICATION


There might be some cases where the unit starts running but does not perform satisfactory, i.e.
insufficient cooling. Judgement could be made by measuring temperature difference of indoor
unit's intake and discharge air as well as running current.

Insufficient Cooling
Unit Starts
Check air circulation

High heat load


Refrigerant circuit

Indoor/Outdoor coil dirty


(clogged)
Air filters dirty
Fan Malfunction
Obstruction at air inlet/outlet
of indoor/outdoor unit

Leakage

Excessive heat
source e.g. electric
kettle

Restriction e.g. at
strainer, capillary,
filter dryer, etc.

Room overcrowded
with people

Compressor

Windows / doors
wide open

Less or no compression
(Low running current)

Satisfactory operation with temperature difference of


air intake & discharge of indoor unit 10C - 15C

Insufficient Heating
Unit Starts
Check air circulation

High heat load


Refrigerant circuit

Indoor/Outdoor coil dirty (clogged)

Leakage
Air filters dirty

Restriction e.g. at
strainer, capillary,
filter dryer, etc.

Fan Malfunction

Compressor

Obstruction at air inlet/outlet


of indoor/outdoor unit

Less or no compression
(Low running current)

Satisfactory operation with temperature difference of


air intake & discharge of indoor unit 16C - 25C

50

Windows / doors
wide open

14. EXPLODED VIEW AND PARTS LIST


MODEL: ACC 75D

No.
Description
1
Assy, Panel Front Base
2
Panel, Back Base
3
Assy, Drain Pan
4
Assy, Coil Tubing CC 75D
5
Cover, Coil Right
6
Cover, Coil Left
7
Flange, Filter Right
8
Flange, Filter Left
9
Rail, Filter (CC75D/DR)
10
Drain Pan Seperator
11
Assy, Panel Top
12
Flange, Filter T/B
13
Assy, Fan Deck
14
Panel, Side Ledt
15
Panel, Header Small Right
16
Panel, Side Big Right
17
Assy, Bracket Drain Pump Cover
18
Switch, Level
19
Assy. Terminal Box
20
Cover, Filter L/R
21
Hanger
Parts Not Shown in Diagram
Control Module
Valve, TXV

51

Part Number
A50014076024
A01014074050
A50019023584
A50024078270
A01014073369
A01014073370
A01014073811
A01014073810
A12014076976
A01014077402
A50014073371
A01014074120
A50034074053
A01014073368
A01014073366
A01014073365
A50014080406
A04069022966
A50044080388
A01014074119
A01014032372
A04089025212
A05019015343

MODEL: ACC 75DR

No.
Description
1
Assy, Panel Front Base
2
Panel, Back Base
3
Assy, Drain Pan
4
Assy, Coil Tubing CC 75DR
5
Cover, Coil Right
6
Cover, Coil Left
7
Flange, Filter Right
8
Flange, Filter Left
9
Rail, Filter (CC75D/DR)
10
Drain Pan Seperator
11
Assy, Panel Top
12
Flange, Filter T/B
13
Assy, Fan Deck
14
Panel, Side Ledt
15
Panel, Header Small Right
16
Panel, Side Big Right
17
Assy, Bracket Drain Pump Cover
18
Switch, Level
19
Assy. Terminal Box
20
Cover, Filter L/R
21
Hanger
Parts Not Shown in Diagram
Control Module
Valve, TXV

52

Part Number
A50014076024
A01014074050
A50019023584
A50024074055
A01014073369
A01014073370
A01014073811
A01014073810
A12014076976
A01014077402
A50014073371
A01014074120
A50034074053
A01014073368
A01014073366
A01014073365
A50014080406
A04069022966
A50044076981
A01014074119
A01014032372
A04089023681
A05019022121

MODEL: ACC 100D

No.
Description
1
Assy, Panel Front Base
2
Panel, Back Base
3
Assy, Drain Pan
4
Assy, Coil Tubing CC 100D
5
Cover, Coil Right
6
Cover, Coil Left
7
Flange, Filter Right
8
Flange, Filter Left
9
Rail, Filter (CC100D/DR)
10
Drain Pan Seperator
11
Assy, Panel Top
12
Flange, Filter T/B
13
Assy, Fan Deck
14
Panel, Side Ledt
15
Panel, Header Small Right
16
Panel, Side Big Right
17
Assy, Bracket Drain Pump Cover
18
Switch, Level
19
Assy. Terminal Box
20
Cover, Filter L/R
21
Hanger
Parts Not Shown in Diagram
Control Module
Valve, TXV
53

Part Number
A50014076025
A01014073346
A50019023585
A50024078271
A01014073369
A01014073370
A01014073811
A01014073810
A12014076977
A01014077402
A50014074594
A01014073812
A50034073347
A01014073368
A01014073366
A01014073365
A01014077181
A04069022966
A50044080388
A01014074119
A01014032372
A04089025212
A05019015344

MODEL: ACC 100DR

No.
Description
1
Assy, Panel Front Base
2
Panel, Back Base
3
Assy, Drain Pan
4
Assy, Coil Tubing CC 75D
5
Cover, Coil Right
6
Cover, Coil Left
7
Flange, Filter Right
8
Flange, Filter Left
9
Rail, Filter (CC75D/DR)
10
Drain Pan Seperator
11
Assy, Panel Top
12
Flange, Filter T/B
13
Assy, Fan Deck
14
Panel, Side Ledt
15
Panel, Header Small Right
16
Panel, Side Big Right
17
Assy, Bracket Drain Pump Cover
18
Switch, Level
19
Assy. Terminal Box
20
Cover, Filter L/R
21
Hanger
Parts Not Shown in Diagram
Control Module
Valve, TXV
54

Part Number
A50014076025
A01014073346
A50019023585
A50024073351
A01014073369
A01014073370
A01014073811
A01014073810
A12014076977
A01014077402
A50014074594
A01014073812
A50034073347
A01014073368
A01014073366
A01014073365
A50014080406
A04069001616
A50044076981
A01014074119
A01014032372
A04089023681
A5019022122

MODEL: AMC / A4MC 75D

55

MODEL: AMC / A4MC 75ER

56

AMC / A4MC 75D


No.
1
2

Description
Assy, Base Pan Main
Compressor
AMC 75D
A4MC 75D
3
Struc. Tube Support
4
Assy, Access Valve
AMC 75D
A4MC 75D
5
Support, Tube Liquid 1/2" Tube
6
Support, Tube Gas 1" Tube
7
Assy, Coil Left Main
8
Assy, Coil Right Main
9
Struc. Coil
10
Assy, Structure Back L
11
Assy, Structure Back R
12
Clamp, Tube Liquid 1/2" Tube
13
Clamp, Tube Gas 1" Tube
14
Structure, Front Left
15
Structure, Front Right
16
Cover, Terminal Board Back
17
Panel, Orifice
18
Motor
19
Fan Propeller, 32"
20
Fan Guard 32"
21
Panel, Service Top
22
Panel, Service Bottom
23
Assy, S. Hoisting Bracket
Parts Not Shown in Diagram
Pressure Switch
High Pressure Switch
Bracket, Fan Motor 32"
Phase Sequencer
Assy, Discharge Thermostat
Filter Drier

AMC / A4MC 75ER

Part Number
A50014045044

No.
1
2

Description
Assy, Base Pan Main
Compressor
AMC 75ER
A4MC 75ER
3
Accumulator
AMC 75ER
A4MC 75ER
4
Struc. Tube Support
5
Support, Tube Liquid 1/2" Tube
6
Support, Tube Gas 1" Tube
7
Assy, Access Valve
8
Assy, Coil Left Main
9
Assy, Coil Right Main
10
Struc. Coil
11
Assy, Structure Back L
12
Assy, Structure Back R
13
Clamp, Tube Liquid 1/2" Tube
14
Clamp, Tube Gas 1" Tube
15
Structure, Front Left
16
Structure, Front Right
17
Cover, Terminal Board Back
18
Panel, Service Top
19
Panel, Orifice
20
Motor
21
Fan Propeller, 32"
22
Fan Guard 32"
23
Panel, Service Bottom
24
Assy, S. Hoisting Bracket
Parts Not Shown in Diagram
Pressure Switch
High Pressure Switch
Bracket, Fan Motor 32"
Phase Sequencer
Assy, Discharge Thermostat
Filter Drier

A50049004676
A50049014526
A01014044386
A50054028348
A50054077736
A01014024023
A01014024026
A50024044767
A50024044769
A01014022392
A50014022910
A50014029795
A01014024030
A01014024033
A01014069646
A01014069647
A01014044214
A01014044211
A03039012606
A03019021351
A01029048691
A01014069644
A01014069645
A50014022906
A04109015400
A04109015136
A01024048601
A04089018834
A50044052922
A02164034987

57

Part Number
A50014046841
A50049004676
A50049014526
A02119004676
A02119015245
A01014044386
A01014024023
A01014024026
A50054028348
A50024052994
A50024052995
A01014022392
A50014022910
A50014029795
A01014024030
A01014024033
A01014069646
A01014069647
A01014044214
A01014069644
A01014044211
A03039012606
A03019021351
A01029048691
A01014069645
A50014022906
A04109015400
A04109015136
A01024048601
A04089018834
A50044052922
A02164034987

MODEL: AMC / A4MC 100D

58

MODEL: AMC / A4MC 100ER

59

AMC/A4MC 100D
No.
1
2

Description
Assy, Base Pan Main
Compressor
AMC 100D
A4MC 100D
3
Struc. Tube Support
4
Assy, Access Valve
5
Support, Tube Liquid 5/8" Tube
6
SupportT, Tube Gas 1-1/8" Tube
7
Assy, Coil Left Main
8
Assy, Coil Right Main
9
Struc. Coil
10
Assy, Structure Back L
11
Assy, Structure Back R
12
Clamp, Tube Liquid 5/8" Tube
13
Clamp, Tube Gas 1-1/8" Tube
14
Structure, Front Left
15
Structure, Front Right
16
Cover, Terminal Board Back
17
Panel, Orifice
18
Motor
19
Fan Propeller, 32"
20
Fan Guard 32"
21
Panel, Service Top
22
Panel, Service Bottom
23
Assy, S. Hoisting Bracket
Parts Not Shown in Diagram
Low Pressure Switch
High Pressure Switch
Bracket, Fan Motor 32"
Phase Sequencer
Assy, Discharge Thermostat

AMC / A4MC 100ER

Part Number
A50014045044

No.
1
2

Description
Assy, Base Pan Main
Compressor
AMC 100ER
A4MC 100ER
3
Accumulator
4
Struc. Tube Support
5
Support, Tube Liquid 5/8" Tube
6
SupportT, Tube Gas 1-1/8" Tube
7
Assy, Access Valve
8
Assy, Coil Left Main
9
Assy, Coil Right Main
10
Struc. Coil
11
Assy, Structure Back L
12
Assy, Structure Back R
13
Clamp, Tube Liquid 5/8" Tube
14
Clamp, Tube Gas 1-1/8" Tube
15
Structure, Front Left
16
Structure, Front Right
17
Cover, Terminal Board Back
18
Panel, Service Top
19
Panel, Orifice
20
Motor
21
Fan Propeller, 32"
22
Fan Guard 32"
23
Panel, Service Bottom
24
Assy, S. Hoisting Bracket
Parts Not Shown in Diagram
Pressure Switch
High Pressure Switch
Bracket, Fan Motor 32"
Phase Sequencer
Assy, Discharge Thermostat
Filter Drier

A50049004677
A50049014427
A01014046135
A50054028348
A01014023152
A01014024027
A50024044774
A50024044776
A01014022392
A50014022910
A50014029795
A01014023149
A01014024034
A01014069646
A01014069647
A01014044214
A01014044211
A03039012606
A03019021351
A01029048691
A01014069644
A01014069645
A50014022906
A50134056107
A04109015136
A01024048601
A04089018834
A50044052922

60

Part Number
A50014046841
A50049004677
A50049014427
A02119015246
A01014046135
A01014023152
A01014024027
A50054028348
A50024053124
A50024053125
A01014022392
A50014022910
A50014029795
A01014023149
A01014024034
A01014069646
A01014069647
A01014044214
A01014069644
A01014044211
A03039012606
A03019021351
A01029048691
A01014069645
A50014022906
A50014022906
A04109015136
A01024048601
A04089018834
A50044052922
A02164034987

While upmost care is taken in ensuring that all details in the publication are correct at time of going to press, we are constantly striving for