2.
Abstract In this paper the design and evaluation of an optimized interval robust controller applied to the problem of speedgovernor is presented. The literature describes the parameters of the linearized model of a hydraulic turbine generator system
change according to the water level in the forebay, resulting in degradation of performance of a conventional speed-governor. To
address this problem, an optimal robust controller is investigated able to maintain acceptable dynamic performance throughout
the range of permissible operating points. Performance tests were carried out experimentally in a 10 kVA synchronous generator
located at the Laboratory of Control and Power Systems of UFPA. The results confirmed the good performance of the optimal
robust controller, whom was able to maintain acceptable performance across the operating range, with a minor performance degradation compared with a conventional controller.
Keywords Speed-governing, interval robust control, hydraulic turbines, application in electrical systems.
Resumo Neste artigo, apresentado o projeto e avaliao de um controlador robusto intervalar otimizado aplicado ao problema de regulao de velocidade. descrito na literatura que os parmetros do modelo linearizado de um sistema turbina hidrulica-gerador variam de acordo com o nvel de gua no reservatrio em usinas hidreltricas, implicando em uma degradao de desempenho de um regulador de velocidade convencional. Para lidar com este problema, investigado um controlador robusto otimizado capaz de manter o desempenho dinmico aceitvel, em toda a faixa de pontos de operao admissveis. Os testes de d esempenho foram realizados experimentalmente, em um gerador sncrono de 10 kVA localizado no Laboratrio de Controle e Sistemas de Potncia da UFPA. Os resultados confirmam o bom desempenho do controlador robusto timo, que foi capaz de manter
um desempenho aceitvel em vrias alturas do nvel do reservatrio, apresentando uma menor degradao de desempenho em
comparao com o controlador convencional.
Palavras-chave Regulador de velocidade, controle robusto intervalar, turbinas hidrulicas, aplicao em sistemas eltricos.
1 Introduo
Em sistemas de hidrogerao de energia eltrica, um
dos componentes fundamentais o Regulador de
Velocidade (RV). O controle de velocidade das turbinas hidrulicas efetuado pelo RV um processo
complexo que influenciado, principalmente, pelas
dinmicas hidrulica e eletromecnica do gerador.
Tratando-se da dinmica hidrulica, um dos parmetros que mais influencia a dinmica do sistema a
altura da queda hidrulica. A altura da queda hidrulica representada pela diferena entre os nveis do
reservatrio e da turbina. Sabe-se que o desempenho
das turbinas hidrulicas influenciado pelas caractersticas da coluna de gua que alimenta a turbina
Kundur (1994). Essa influncia ocorre devido ao
princpio fsico que envolve a hidrogerao, que o
aproveitamento da energia potencial gravitacional da
gua contida em uma represa elevada ou proveniente
de uma queda d'gua natural. Portanto, torna-se necessrio o projeto de RV's que mantenham o desempenho desejado diante de incertezas representadas
por uma faixa de valores nos parmetros do modelo
da planta. Neste estudo, a variao do nvel do reser-
CARGAS
PAINEL DE
CONTROLE
PAINEL DA LT
TRANSFORMADOR
GRUPO MOTOR-GERADOR
9kVA
1200rpm
Rendimento
Tenso de Armadura
Corrente de Armadura
Tenso de Campo
Corrente de Campo
9/11
400V
27,5A
300V
1,5A
3 Modelagem do Sistema
Nesta seo ser demonstrada a modelagem matemtica utilizada, onde constam duas plantas do sistema
em estudo. Uma para o projeto do controlador levando-se em considerao um ponto de operao fixo, j
a outra planta modelada fazendo-se a variao do
ponto de operao, representado por um intervalo
real Lordelo (2004).
2.1 Modelagem No-Intervalar da Planta
Na equao (1) fornecida a funo de transferncia
da turbina hidrulica a partir de uma modelagem na
qual feita a linearizao de sua dinmica fixada em
torno de um ponto de operao (Kundur, 1994). A
razo entre a variao da abertura do distribuidor e o
sinal de controle do RV fornece a funo de transferncia do servoposicionador G ( s ) , conforme a
u (s)
Equao (2). O balanceamento do sistema representado pela Equao (3), onde: r (s) a velocidade
angular no rotor da mquina; H a constante de
inrcia; Pm a potncia mecnica desenvolvida pela
CONVERSOR
CC-CC
MOTOR
CC
CIRCUITO
GATE-DRIVER
TRANSDUTOR
E
CONDICIONADOR
PWM
ADC
Pm ( s)
1 Tw s
0,5Tw s
G ( s)
(1)
G ( s )
1
u ( s)
tg s 1
(2)
RAT
Linha de
Transmisso
Banco de
Lmpadas
FREQUENCMETRO
Firmware
CONDICIONAMENTO
DIGITAL DO SINAL
DE CORRENTE
IC
CONDICIONAMENTO
DIGITAL DO SINAL
DE CONTROLE
CALCULO DA
VELOCIDADE
EM PU
Ia
Pm
CONTROLE DE
POTNCIA
Pm*
DINMICA DA
TURBINA E DO
SERVOPOSICIONADOR
REF
habilita
SEQUNCIA DE
PARTIDA
INTERFACE
RS232
u0
REGULADOR DE
VELOCIDADE
C.F.
UART
PC
IHM
Microcontrolador
Figura 2. Arquitetura do Sistema de Controle aplicado ao motor da Micromquina para Emular um sistema de Regulao de Velocidade de uma Unidade Hidrogeradora Nascimento Filho (2011)
2 Hr ( s) Pm ( s) Br ( s)
r ( s) 1 1 Tw s 1
u ( s)
2 Hs B 1 0,5Tw s t g s 1
(3)
(4)
Na Tabela 2 encontram-se os valores dos parmetros fsicos nominais do hidrogerador que, aps
serem substitudos na Equao (4), do origem
funo de transferncia da planta representada pela
Equao (5). Este modelo utilizado para o projeto
do controlador considerando-se um ponto de operao fixo.
Tabela 2. Parmetros fsicos da funo de transferncia da planta.
Parmetro Fsico
Valor do Parmetro
Tw
H
tg
1,54s
0,03482N.m/rad/s
4,29s
2,8s
1
1
s
H Tg Tw
G ( s)
1
2
B
s s
(5)
Tg Tw
2 H
0.08325s 0.05406
G ( s)
3
Tw
LPm
5/ 2
ag k p H 0
(6)
Sendo assim, optou-se por considerar uma variao da queda hidrulica H 0 , de 70% a 100% de sua
capacidade. A partir da Equao (6) obtm-se os
valores para a constante de tempo da turbina em
funo de H 0 . Com tais valores possvel definir os
intervalos reais mostrados nas equaes (7) e (8), os
quais representam as incertezas paramtricas do
sistema.
H0 [0.7, 1.0]
nP
x r0 r1 rnR1 s1 s2 xnS
(12)
a2
a1
an 3
an 2
a n 1
a2 a2 n 2
an 3
a n 1
a2 n 2
(7)
Tw [1.54, 3.756]
(8)
Para inserir tais incertezas paramtricas no sistema, so aplicados os valores da Equao (8) na
Equao (4), que resulta em uma funo de transferncia da planta intervalar Lordelo (2004).
(13)
xc
, tal que.
xc C S
(14)
max
M c ( I q T ) x y P ,
M c ( I q T ) x y P ,
M c ( I q T ) x y P ,
s.a M c ( I q T ) x y P ,
y ( I q T ) x y,
y ( I q T ) x y,
0.
REGIO
NO
CONVEXA
xc
2 (1 z 1 )
Ts (1 z 1 )
R( z 1 ) r0 r1 z 1 ... rnr z nr
(19)
(20)
(21)
T ( z ) R(1)
A Tabela 3 fornece os parmetros dos RV's
Convencional e timo digitais projetados,
Tabela 3. Parmetros dos Controladores Digitais
Parmetros
Controlador Fixo
Controlador
timo
r0
0,687759
0,388128
r1
-0,932407
-0,435118
r2
-0,361557
-0,249421
r3
0,936225
0.439554
r4
-0,322384
-0,134270
s1
-2,675232
-2,467008
s2
2,742134
2,264070
s3
-1,351504
-0,927360
s4
T
sP
0,284602
0,130298
0,007635
0,000381768
0,008870
0,000443549
(16)
5
Resultados Experimentais
6 Concluso
O teste de insero de carga realizado com o sistema de gerao operando de forma isolada, isto ,
alimentando unicamente as cargas conectadas nos
terminais do gerador sncrono de 10 kVA. Quando
atingida a velocidade nominal inserida no sistema
uma carga de 0,12 p.u., esta representa uma perturbao do tipo degrau positivo de carga.
Na Figura 5 so ilustradas as respostas do sinal
de velocidade e controle comparando o RV
Convencional com o RV timo. Aps a insero de
carga, nota-se que, para 100% da coluna de gua, os
dois controladores operam em condies satisfatrias
de desempenho tanto para a resposta da velocidade
quanto para o esforo de controle. Porm, quando
submetidos a 70% do nvel do reservatrio, os
controladores apresentam um tempo maior para
atingir o erro de regime nulo na resposta da
velocidade.
Contudo, destaca-se que o sinal de controle do
controlador timo, o qual capaz de regular a
velocidade com uma amplitude ligeiramente menor,
comparado com o sinal de controle do RV
Convencional.
Comparao entre o RV Convencional e o timo
1.1
0.65
0.6
1.05
0.55
Esforo de Controle (pu)
Velocidade (pu)
0.95
0.9
0.85
0.4
0.35
Convencional com Ho = 1 pu
Convencional com Ho = 0.7 pu
Otimo com Ho = 1.0 pu
Otimo com Ho = 0.7 pu
0.8
0.75
0.5
0.45
20
40
60
Tempo (s)
80
100
Convencional com Ho = 1 pu
Convencional com Ho = 0.7 pu
Otimo com Ho = 1.0 pu
Otimo com Ho = 0.7 pu
0.3
0.25
120
20
40
60
Tempo (s)
80
100
120
Velocidade (pu)
1.15
1.1
1.05
0.95
Convencional com Ho = 1 pu
Convencional com Ho = 0.7 pu
Otimo com Ho = 1.0 pu
Otimo com Ho = 0.7 pu
0.5
1.2
0.45
0.4
0.35
0.3
0.25
20
40
60
Tempo (s)
80
100
120
0.2