Anda di halaman 1dari 4

HFO-1234ze

www.kaltra.de

Kaltra Innovativtechnik GmbH


Max-Reger-Str. 44 90571 Schwaig Deutschland

Environment-friendly
chilled water solution
Capacity range:
280-1350kW

Shown: Lighstream TURBO F450 V4/2

Class A energy eciency


with EER up to 3.76

Microchannel condensing coils


improve heat exchange and increase energy eciency, thus reducing power bills

Centrifugal oil-free compressors


enable major cost savings and environmental benets

R1234ze refrigerant

with zero ozone-depletion potential and a low global-warming potential

Lightstream TURBO chillers


Ultra-ecient air-cooled chillers with centrifugal oil-free centrifugal compressors and microchannel condensing coils

CENTRIFUGAL

HFO-1234ze

MICROCHANNEL

EC FANS

FREECOOLING

Available in 9 frame sizes, total 20 models with vast array of options and accessories
May 2016

Technology

Green refrigeration
An exceptionally energy ecient air-cooled chiller oering a wide span of cooling capacities and featuring a huge
array of standard accessories, including compressor economizers. Lightstream TURBO combines ultra ecient and
quiet centrifugal compressors and the latest fan technology applied in a modular V-form coil design. Microchannel
heat exchangers signicantly lift eciency, whilst the refrigerant charge is quite low.

Centrifugal compressors

Compact and lightweight two-staged centrifugal oil-free compressors with


built-in variable frequency drive delivers high eciency at full load and extraordinarily high eciency at part-load conditions. It operates with low-GWP
R1234ze refrigerant which takes the environmental leadership while achieving
the best energy performance levels. Oil-free compressor design eliminates the
eciency losses due to the use of oil circulating in the compressor and suppresses the need for oil management accessories.
Compressor soft-start draws only 2 amps and reduces mechanical stress, as well
as the electrodynamic stresses on the power cables and electrical distribution
network, extending the lifespan of the system.

EC fans

Lighstream TURBOs new intelligent fan system consisting of the proled,


sickle-shaped axial fans, multifunctional air guide vanes and diusers - provides
maximum exibility, lowest possible sound emission and highest energy
eciency. Modern EC motor technology does not provide savings only during
full-load operation - it is exactly when operating under partial load that EC
motors lose much less of their eciency.
Frost protection and thermal management ensures stable operation under
extreme ambient conditions.

Microchannel condensing coils


All-aluminium microchannel condensing coils used in Lighstream TURBO design
allows to achieve a number of advantages, including low airside pressure drops,
higher heat transfer rate, and closer approach temperatures. The end result is
up to 40% higher energy eciency in comparison to n/tube coil design.
Smaller coil face, its thin design, up to 50% less weight, and less refrigerant
charge translate to lower cost.
Due to the all-aluminium construction, microchannel condensing coils are
subject to signicantly less galvanic corrosion than traditional n/tube design, in
that there are no dissimilar metals.

Flooded evaporators

The ooded evaporator used in Lightstream TURBO design enables to operate at the higher saturated evaporating temperature when
compared to many others evaporator types and allows to achieve higher cooling capacity with correspondingly higher eciency.
The refrigerant pool in the shell behaves as a ywheel, allowing the controls of the ooded evaporator to successfully track the varying
load of a batch process. In order to avoid preferential ows, Lightstreams evaporators has optimized tube geometry, ensuring optimal
refrigerant distribution.

www.kaltra.de

Key data & features

Unit identication
Lightstream TURBO

450

V4

Selection

A vast range of Lightstream TURBO models and options provides exibility, tailored precisely to the customer requirements allowing to design truly ecient cooling solutions for every application in any climate zone.
In a 24/7 world, keeping facilities up and running is critical, and we paid special attention to control and monitoring
functionality, as well as to operational reliability and ease of maintenance.

Enclosure
size

Length
mm

Width
mm

Height
mm
2375

Cooling

2250
2250

2375
2375

Nominal capacity

kW

F4
F5

7115
8235

2250
2250

2375
2375

F6

9355

2250

2375

Condenser size

No. of V-form condensers

F7

10475

2250

2375

F8

12715

2250

2375

F9

13835

2250

2375

Compressors

No. of compressors

General
Economizer (for compressors w/ economizer port)
Freecooling
MCHE epoxy e-coating
MCHE thermoguard
Airside
EC-fans
Fluidside
Pumping group (single/twin inline pumps) w/ heater
Refrigerant circuits
Gas leakage detection
Power and controls
Power factor correction
Electrical panel heater
GSM connectivity
Remote terminal

Standard feature
Option

Applications

Anti-vibration mounts
Anti-vibration springs
High-ambient kit
Low-ambient kit

Guide vanes for fans

Flowmeter

High-ecient refrigerant lter

BMS connectivity
SNMP connectivity
Sequence management
Energy monitoring

CW 09

Features

CW 06

F series

Features

M series

Package & options

18
FCW
series

2250

4875
5995

CW 12

3755

F2
F3

CW
15
M
series

F1
Mechanical only (M)
Freecooling (F)

Lightstream TURBO has been designed with attention to every detail to maximize its reliability, and ts ideally to the requirements of
mission-critical applications like data centers, telecom facilities and cleanrooms, and in every area where reliability is a key factor.
Due to its excellent eciency at part-load conditions, Lighstream TURBO is a brilliant economy solution for applications where the heat
load is not constant or expected to grow.

www.kaltra.de

Technical specications
Model

M300
V3/1

M350
V3/1

M450
V4/2

M550
V5/2

M650
V6/2

M750
V7/3

M850
V7/3

M950
V8/3

M1100
V9/4

M1250
V11/4

M1350
V12/4

Cooling capacity

kW

280

340

430

550

680

750

830

960

1080

1280

1350

Water ow rate

m/h

48

58

73

95

118

130

F2

F3

F4

F5

186
F7

232

F1

165
F6

220

F1

143
F5

F8

F9

kg

3240

3290

4300

5370

6025

7460

7625

8380

9715

11030

11690

Qty.

Capacity control

25100

25100

12100

12100

12100

8100

8100

8100

6100

6100

6100

Power input

kW

60.0

83.5

98.3

125.0

167.0

174.0

194.0

236.0

255.0

308.0

312.0

Max. current

150

150

300

300

300

450

450

450

600

600

600

Frame size
Net weight
Compressors
Quantity

oil-free centrifugal

Fans

EC

Quantity

Qty.

10

12

14

14

16

18

22

24

Airow

m/h

156000

156000

208000

260000

312000

364000

364000

416000

468000

572000

624000

Power input

kW

13.6

13.6

18.2

22.7

27.2

31.8

31.8

36.4

40.9

49.9

54.4

Max. current

26.4

26.4

35.2

44.0

52.8

61.6

61.6

70.4

79.2

96.8

105.6

m/h

2375
44.5

2375

30100

45150

45150

80225

80225

80225

150320

150320

150320

44.5

57.0

85.2

85.2

146.0

146.0

146.0

276.4

276.4

276.4

Evaporator
Water ow rate

ooded shell and tube

Water volume

Refrigerant
Gas circuits

R1234ze
Qty.

kg

190

190

190

215

225

360

360

370

470

485

495

3.76

3.44

3.62

3.70

3.44

3.63

3.64

3.48

3.60

3.52

3.61

4.90

5.46

4.88

5.27

5.70

5.08

5.15

5.77

5.13

5.59

5.92

F450
V4/2

F550
V5/2

F650
V6/2

F750
V7/3

F850
V7/3

F950
V8/3

F1100
V9/4

F1250
V11/4

F1350
V12/4

Charge
Energy eciency
EER

kW/kW

ESEER (Eurovent)
Model

Cooling capacity

kW

430

550

660

760

830

960

1105

1280

1350

Freecooling capacity

kW

495

622

748

865

890

1020

1158

1392

1504

m/h

74

95

114

130

143

165

190

220

232

F2

F3

F4

F5

F5

F6

F7

F8

F9

kg

4860

6070

6885

8460

8625

9520

11000

12595

13395

Qty.

Capacity control

12100

12100

12100

8100

8100

8100

6100

6100

6100

Power input

kW

112.0

131.0

163.0

191.0

202.0

245.0

276.0

316.0

335.0

Max. current

300

300

300

450

450

450

600

600

600

Water ow rate
Frame size
Net weight
Compressors
Quantity

oil-free centrifugal

Fans

EC

Quantity

Qty.

10

12

14

14

16

18

22

24

Airow

m/h

190000

237500

285000

332500

332500

380000

427500

522500

570000

Power input

kW

19.8

24.7

29.7

34.6

34.6

39.6

44.6

54.5

59.4

Max. current

35.2

44.0

52.8

61.6

61.6

70.4

79.2

96.8

105.6

m/h

30100
57.0

45150

45150

80225

80225

80225

150320

150320

150320

85.2

85.2

146.0

146.0

146.0

276.4

276.4

276.4

ooded shell and tube

Evaporator
Water ow rate
Water volume

Refrigerant
Gas circuits

R1234ze
Qty.

kg

190

215

225

360

360

370

470

485

495

3.18

3.46

3.33

3.28

3.40

3.28

3.33

3.36

3.33

4.62

5.07

5.52

4.84

5.12

5.50

5.08

5.43

5.60

www.kaltra.de

Charge
Energy eciency
EER

kW/kW

ESEER (Eurovent)

Cooling media temperature 10/15C; 100% water


Ambient temperature 35C
Freecooling capacity for 0C

The development of Kaltra products and services is continuous and the information in this document may not be up to date.
It is important to check the current position with Kaltra at the address stated below:

Tel.: +49 911 715 320 21


Fax: +49 911 253 312 70
Kaltra Innovativtechnik GmbH

24/7 Service & Support Hotline:


+49 152 343 915 17

E-mail: info@kaltra.de

Max-Reger-Str. 44 90571 Schwaig Deutschland

2016 Kaltra Innovativtechnik GmbH