www.kaltra.de
Environment-friendly
chilled water solution
Capacity range:
280-1350kW
R1234ze refrigerant
CENTRIFUGAL
HFO-1234ze
MICROCHANNEL
EC FANS
FREECOOLING
Available in 9 frame sizes, total 20 models with vast array of options and accessories
May 2016
Technology
Green refrigeration
An exceptionally energy ecient air-cooled chiller oering a wide span of cooling capacities and featuring a huge
array of standard accessories, including compressor economizers. Lightstream TURBO combines ultra ecient and
quiet centrifugal compressors and the latest fan technology applied in a modular V-form coil design. Microchannel
heat exchangers signicantly lift eciency, whilst the refrigerant charge is quite low.
Centrifugal compressors
EC fans
Flooded evaporators
The ooded evaporator used in Lightstream TURBO design enables to operate at the higher saturated evaporating temperature when
compared to many others evaporator types and allows to achieve higher cooling capacity with correspondingly higher eciency.
The refrigerant pool in the shell behaves as a ywheel, allowing the controls of the ooded evaporator to successfully track the varying
load of a batch process. In order to avoid preferential ows, Lightstreams evaporators has optimized tube geometry, ensuring optimal
refrigerant distribution.
www.kaltra.de
Unit identication
Lightstream TURBO
450
V4
Selection
A vast range of Lightstream TURBO models and options provides exibility, tailored precisely to the customer requirements allowing to design truly ecient cooling solutions for every application in any climate zone.
In a 24/7 world, keeping facilities up and running is critical, and we paid special attention to control and monitoring
functionality, as well as to operational reliability and ease of maintenance.
Enclosure
size
Length
mm
Width
mm
Height
mm
2375
Cooling
2250
2250
2375
2375
Nominal capacity
kW
F4
F5
7115
8235
2250
2250
2375
2375
F6
9355
2250
2375
Condenser size
F7
10475
2250
2375
F8
12715
2250
2375
F9
13835
2250
2375
Compressors
No. of compressors
General
Economizer (for compressors w/ economizer port)
Freecooling
MCHE epoxy e-coating
MCHE thermoguard
Airside
EC-fans
Fluidside
Pumping group (single/twin inline pumps) w/ heater
Refrigerant circuits
Gas leakage detection
Power and controls
Power factor correction
Electrical panel heater
GSM connectivity
Remote terminal
Standard feature
Option
Applications
Anti-vibration mounts
Anti-vibration springs
High-ambient kit
Low-ambient kit
Flowmeter
BMS connectivity
SNMP connectivity
Sequence management
Energy monitoring
CW 09
Features
CW 06
F series
Features
M series
18
FCW
series
2250
4875
5995
CW 12
3755
F2
F3
CW
15
M
series
F1
Mechanical only (M)
Freecooling (F)
Lightstream TURBO has been designed with attention to every detail to maximize its reliability, and ts ideally to the requirements of
mission-critical applications like data centers, telecom facilities and cleanrooms, and in every area where reliability is a key factor.
Due to its excellent eciency at part-load conditions, Lighstream TURBO is a brilliant economy solution for applications where the heat
load is not constant or expected to grow.
www.kaltra.de
Technical specications
Model
M300
V3/1
M350
V3/1
M450
V4/2
M550
V5/2
M650
V6/2
M750
V7/3
M850
V7/3
M950
V8/3
M1100
V9/4
M1250
V11/4
M1350
V12/4
Cooling capacity
kW
280
340
430
550
680
750
830
960
1080
1280
1350
Water ow rate
m/h
48
58
73
95
118
130
F2
F3
F4
F5
186
F7
232
F1
165
F6
220
F1
143
F5
F8
F9
kg
3240
3290
4300
5370
6025
7460
7625
8380
9715
11030
11690
Qty.
Capacity control
25100
25100
12100
12100
12100
8100
8100
8100
6100
6100
6100
Power input
kW
60.0
83.5
98.3
125.0
167.0
174.0
194.0
236.0
255.0
308.0
312.0
Max. current
150
150
300
300
300
450
450
450
600
600
600
Frame size
Net weight
Compressors
Quantity
oil-free centrifugal
Fans
EC
Quantity
Qty.
10
12
14
14
16
18
22
24
Airow
m/h
156000
156000
208000
260000
312000
364000
364000
416000
468000
572000
624000
Power input
kW
13.6
13.6
18.2
22.7
27.2
31.8
31.8
36.4
40.9
49.9
54.4
Max. current
26.4
26.4
35.2
44.0
52.8
61.6
61.6
70.4
79.2
96.8
105.6
m/h
2375
44.5
2375
30100
45150
45150
80225
80225
80225
150320
150320
150320
44.5
57.0
85.2
85.2
146.0
146.0
146.0
276.4
276.4
276.4
Evaporator
Water ow rate
Water volume
Refrigerant
Gas circuits
R1234ze
Qty.
kg
190
190
190
215
225
360
360
370
470
485
495
3.76
3.44
3.62
3.70
3.44
3.63
3.64
3.48
3.60
3.52
3.61
4.90
5.46
4.88
5.27
5.70
5.08
5.15
5.77
5.13
5.59
5.92
F450
V4/2
F550
V5/2
F650
V6/2
F750
V7/3
F850
V7/3
F950
V8/3
F1100
V9/4
F1250
V11/4
F1350
V12/4
Charge
Energy eciency
EER
kW/kW
ESEER (Eurovent)
Model
Cooling capacity
kW
430
550
660
760
830
960
1105
1280
1350
Freecooling capacity
kW
495
622
748
865
890
1020
1158
1392
1504
m/h
74
95
114
130
143
165
190
220
232
F2
F3
F4
F5
F5
F6
F7
F8
F9
kg
4860
6070
6885
8460
8625
9520
11000
12595
13395
Qty.
Capacity control
12100
12100
12100
8100
8100
8100
6100
6100
6100
Power input
kW
112.0
131.0
163.0
191.0
202.0
245.0
276.0
316.0
335.0
Max. current
300
300
300
450
450
450
600
600
600
Water ow rate
Frame size
Net weight
Compressors
Quantity
oil-free centrifugal
Fans
EC
Quantity
Qty.
10
12
14
14
16
18
22
24
Airow
m/h
190000
237500
285000
332500
332500
380000
427500
522500
570000
Power input
kW
19.8
24.7
29.7
34.6
34.6
39.6
44.6
54.5
59.4
Max. current
35.2
44.0
52.8
61.6
61.6
70.4
79.2
96.8
105.6
m/h
30100
57.0
45150
45150
80225
80225
80225
150320
150320
150320
85.2
85.2
146.0
146.0
146.0
276.4
276.4
276.4
Evaporator
Water ow rate
Water volume
Refrigerant
Gas circuits
R1234ze
Qty.
kg
190
215
225
360
360
370
470
485
495
3.18
3.46
3.33
3.28
3.40
3.28
3.33
3.36
3.33
4.62
5.07
5.52
4.84
5.12
5.50
5.08
5.43
5.60
www.kaltra.de
Charge
Energy eciency
EER
kW/kW
ESEER (Eurovent)
The development of Kaltra products and services is continuous and the information in this document may not be up to date.
It is important to check the current position with Kaltra at the address stated below:
E-mail: info@kaltra.de