A transformer tap changer allows control over the ratio of a transformers output voltage to its input voltage. It is a mechanical device
and one of a transformers few components with moving parts (others including pumps and fans). A tap changer changes the ratio
of transformation by adding or subtracting sections of tap windings to or from the HV or LV main windings of the transformer. A
tap changer may also be used to change configuration of the windings, as provided through the use of a de-energized tap changer
(DETC) one of two (2) classes of tap changers. A DETC must never be moved while a transformer is energized! However, the second
and arguably more indispensable tap changer class, that is, on-load tap changers (OLTC), allows for selection of a ratio change while
the transformer is in service. By varying the transformer ratio under load without interruption, OLTCs enable voltage regulation and/
or phase shifting.
Studies support the case for testing tap changers. [1] There are several tests available to assess the condition of and/or diagnose a
problem in a tap changer , including: exciting current, turns ratio, winding resistance, SFRA, dissolved gas analysis (DGA), continuity,
timing and dynamic measurements.
Static Measurements: Exciting current, turns ratio, winding resistance, and SFRA tests are performed while the OLTC (and DETC) is
stationary at each of a number of selected tap positions. With regard to tap changer diagnostics, these tests are valuable in assessing
the integrity of the additional portions of tap windings included in the measurement, the contacts (e.g., that movable and stationary
are not pitted, have no coking, are not loose, and are fully mating), and, in the case of reactive-type OLTCs, the condition of the
preventative autotransformer (PA), series autotransformer or series transformer, etc. Unlike a resistive-type OLTC, a reactive-type
OLTC uses the bridging position1 as a service position, so when performing a static measurement on an odd numbered tap position,
bridging components are included in the test circuit and are assessable. A resistive type OLTC never spends more than approximately
40 60 ms in a bridging state so when performing a static measurement, bridging components such as diverter resistors are not
included in the test circuit.
Dynamic Measurements (for OLTCs only): Continuity tests, timing tests and other dynamic measurements are performed during
the operation of the OLTC (i.e., while it is executing a tap change). Continuity checks, which verify that contacts make before others
break, have been in use for years. Dynamic measurements on OLTCs, including timing of the operation, are newer and gaining in
acceptance. Most experience with dynamic measurements are with resistive-type OLTCs, which are in widest use worldwide, as
opposed to reactive-type OLTCs, the predominant and widespread use of which is in North America. This bulletin addresses these
dynamic measurements.
A bridging position is a position whereby two consecutive taps are selected at the same time and some form of impedance, resistive
or reactive, is present to limit resulting circulating current.
1
Resistive type on-load tap-changers, common in Europe, Asia, Africa and South America, are connected to the HV winding of the
transformer. Reactive type on-load tap-changers, common in North America, are almost always connected to the LV side of the
transformer.
2
www.megger.com/tlm
Dynamic measurements of
on-load tap changers (OLTC)
Common for all methods of dynamic measurements on an OLTC is that a current is injected in the tap changer, either in one phase
or all phases, and during the operation of the tap changer, the current and/or the voltage is measured as a function of time. The
test current varies from about 0.1 A to a magnitude that is standard for winding resistance measurements, typically 1 to 10% of the
transformer windings rated current. The test may be performed at the same time as the winding resistance test or as a separate test.
Standard methods are:
nn
Continuity/break-before-make testing
nn
Dynamic measurements
Dynamic current/ripple (often called DRM)
Dynamic voltage (as a means to calculate dynamic resistance)
Dynamic resistance, DRM
The intention is to give a value that describes the conditions during operation and provide contact timing. For example, if the ripple
is uncharacteristically large, this indicates an increase in the resistance of the transition path and/or that the tap operation is slower
than it should be. [3] The percent ripple is plotted for each OLTC transition for all three phases (Figure 2).
Dynamic current measurements depend upon the test current and source impedance of the test set. The core must be saturated
and the current stable before representative and repeatable test results should be expected. If the test is performed at a current level
below saturation level, the inductance in the transformer winding is high and smoothes the current change. If the test is performed
at a current level at or above saturation level, the inductance is low and current level change will be higher [4].
www.megger.com/tlm
Dynamic measurements of
on-load tap changers (OLTC)
A method to reduce transformer inductance when performing tap changer measurements is to short-circuit the untested corresponding
LV (or HV) windings. This action is principally replacing the inductance of the winding with the short-circuit impedance. Inductance
is greatly reduced and changes in current can be measured more precisely. Meggers application note, Guide to Transformer Tap
Changer Testing, shows dynamic current measurements on a 30 MVA, 130/46 kV, YNyn0 transformer using different test currents
and with LV windings open and shorted [5], illustrating the inconsistency of the results given differing variables [6].
www.megger.com/tlm
Dynamic measurements of
on-load tap changers (OLTC)
change
The source impedance in this example is about 10 Ohm and we can see a small current change during the tap change (green trace
in Figure 5). Due to the inductance in the circuit (recalling that for this measurement the opposite or LV winding is left open), the
change in voltage measured across the HV winding (red trace in Figure 5) is rather large. This voltage is a sum of inductive and resistive
voltage and cannot be used for directly calculating the resistance in the circuit. However, the voltage measured across the LV winding
is purely inductive and if we use transformer model parameters to calculate the inductive voltage on the primary, we can deduct this
value from the measured HV winding voltage and calculate the resistance in the circuit. The result is given in figure 5.
www.megger.com/tlm
[1]
[2]
[3]
[4]
[5]
[6]
TLM2_Bulletin_DynamicResistanceOLTC_en_V02a - www.megger.com/tlm
The word Megger is a registered trademark
TLM Bulletins - Copyright Megger Limited, Dover, CT17 9EN, UK