Operation and instruction manual for ebrit multi

500.0

ebrit

500.0

HPL Electric & Power Pvt. Ltd.


1/21, Atma Ram Mansion, Asaf Ali Road, New Delhi-110002
Phone : 23234411, 23234811, 23236811; Fax : 23232639
E-Mail : hpl@hplindia.com, Website : www.hplindia.com
This document is not contractual, HPL Electric & Power Pvt. Ltd. reserves the
right to modify features without prior notice in view of continued improvements.

GCPK6EBRITMULTI485

500.0
VIF

AVG
MAX

TEST

SPCL SCRN

LOCK

PROG

CAL

HPL Electric & Power Pvt. Ltd.

ebrit multi

ebrit multi

In the CRC 16, the first OCTET Transmitted is LSB:


EXAMPLE : Development of CRC

Contents

1. General Information ........................................ 2


2. Programming .................................................. 4
3. Communication .... 6

Operation and Instruction Manual

16

Operation and Instruction Manual

ebrit multi

1. General Information

ebrit multi

Guide to CRC 16 Calculation :

1.1 Function:
This model of ebrit multi with RS485 provides communication facility on
RS485 MODBUS. Ebrit multi with RS485 works on a master slave
configuration, where the ebrit multi is the slave and the master can be
computer / PLC etc.
The following are also supplied with this model:
n=0

2 numbers 120 End-Of-Line resistance.

1.2 General Points:

MOVEMENT TO THE
RIGHT CRC 16

For standard configuration, RS485 serial link 2 wire is used to connect 255
ebrit multi with one RS232 port on the master (computer/PLC etc.) over a
distance of 1200 meters using MODBUS protocol.

No

CARRY OVER

Yes

1.3 Typical Network Architecture:

n=n+1

RS 232

RS 485

No
500.0

ebrit

500.0

ebrit

500.0

500.0

500.0
P

AVG
MAX

TEST

SPCL SCRN

LOCK

PROG

CAL

500.0

VIF

AVG
MAX

TEST

SPCL SCRN

LOCK

PROG

CAL

VIF

AVG
MAX

TEST

SPCL SCRN

LOCK

PROG

NEXT BYTE

CAL

No

Cables and RS485/232 converter, computer are not supplied with this
ebrit multi.

MESSAGE TERMINATED

Yes

END

Recommendation: Please use a shielded twisted pair cable for connection


A repeater should be used if one intends to exceed the cable distance of
over 1200 meters.
Operation and Instruction Manual

Yes

500.0

500.0

VIF

n>1

500.0

ebrit

Operation and Instruction Manual

15

ebrit multi

1.4 Connection Diagram:

Example : For CT Secondary Writting.


Slave
Address

Function
code

0x0005

0x0010

Higher
order
address

Low
order
address

0x05C1

Number
of word
high

ebrit multi

Number
of word
low

0x0001

No. of
byte

Data

0x0002

0x0005

CRC
High

CRC
low

RS485 Bus

0x791B
+RX -RX

3.4 Reset Parameters (Reset to Zero):


kW & kVA MD with Date Time

P
N

PARAMETER
kW MD

DECIMAL
ADDRESS

0x581

U
X

Address Table
HEX
ADDRESS

1409

No. OF
WORDS
2

RS 485

S1

L1

UNIT

L2

kW/1000

L3

I1
S2
S1

I2

S2

Example: For Resetting the kW MD


Slave
Address

Function
code

0x0005

0x0010

Higher
order
address

Low
order
address

0x0581

Number
of word
high

0x0002

No. of
byte

Data

0x0004

0x007B*

CRC
High

Master

S1

I3

Number
of word
low

RS485/232
Converter

S2

CRC
low

120
End-Of-Line
Resistance

0xEF68

+Rx -Rx
RS485

*007B i.e. 1234 is the Default Programming Password

Note: This serial communication requires 120 end-of-line resistance to be connected on first and
last device in an RS485 MODBUS network.
The End Of-Line resistance supplied with Emfis HT is to be connected between Rx- and Rx+ as
shown above.

1.5 RS485 configuration :

Operation and Instruction Manual

14

Baud Rate

Stop Bit

Byte size

8 Bit

Parity

None

Operation and Instruction Manual

4800 / 9600 / 19200 bps

ebrit multi

ebrit multi

Address Table

2. Programming
PARAMETER

To access / view the programming mode:


Keys

Instruction

Prog

Press Once

Display
pass
0---

Comment
You are now in programming
mode. Password has to be
Entered.

2.1 Enter the access code '1234 (default password) to access the programming
mode:
Keys

Instruction

Display

Scroll up

Press Once

pass
1---

Digit increment by 1.

Scroll down

Press Once

pass
10--

Moves one digit right.

Scroll up

Press Twice

pass
12--

Digit increment by 2.

Scroll down

Press Once

pass
120-

Moves one digit right.

HEX
ADDRESS

DECIMAL
ADDRESS

No. OF
WORDS

Unit

SECOND

0x5C7

1479

Sec

MINUTE

0x5C8

1480

Min

HOUR

0x5C9

1481

Hrs

DATE

0x5CA

1482

DD

MONTH

0x5CB

1483

MM

HEX
ADDRESS

DECIMAL
ADDRESS

No. OF
WORDS

Unit

0x5CC

1484

YY

CT RATIO

0x5C0

1472

CT SECONDARY

0x5C1

1473

0x5C2

1474

Comment

PARAMETER

YEAR

Scroll up

Press Thrice

pass
123-

Digit increment by 3.

Scroll down

Press Once

pass
1230

Moves one digit right.

pass
1234

Digit increment by 4.

pass
1234

Meter entered into


programming mode.

Scroll up
Prog

Press Four Time


Press Once

PT Ratio

Range and Default Value of Programming Parameter


PARAMETER
Primary

9995 in step of 5 for -/5

Secondary

-/1A or -/5A

Comment

110V

------

110V

Slave Address
Baud Rate

Default slave address.

-/5A

110/1.1//2.2/3.3/6.6//11/22/33/66/121/132 kV

PT Secondary

005
Operation and Instruction Manual

500

PT Ratio
PT Primary

Display

DEFAULT VALUE

2000 in step of 5 for -/1

2.2 Set Slave Address:


Instruction

RANGE
CT Ratio

If your password is correct 1234 (default password) you can see all setting parameters
using Scroll up/Scroll down button.

Keys

Amp

1 : Secondary 1
5 : Secondary 5

1-255

4800 / 9600 / 19.2 kbps

9600 bps

Table 1.0
4

Operation and Instruction Manual

13

ebrit multi
PARAMETER

HEX
ADDRESS

DECIMAL
ADDRESS

No. OF
WORDS

UNIT

ebrit multi

Prog

Press Once

Scroll up

Press Once

Scroll down

Press Once

Scroll up

Press twice

Scroll down

Press Once

Scroll up

Press thrice
Press Once

0--

SERIAL NUMBER

0x5BB

1467

POWER RATIO

0x5BD

1469

NETWORK SELECTION

0x5BF

1471

CT RATIO

0x5C0

1472

CT SECONDARY

0x5C1

1473

PT RATIO

0x5C2

1474

PT SECONDARY

0x5C3

1475

Volt

INTE. TIME FOR AVG. PARAMETERS

0x5C4

1476

Min

MD INTEGRATION TIME

0x5C5

1477

Min

Prog

SECOND

0x5C7

1479

Sec

2.3 Set Baud Rate (4800/9600/19200)

MINUTE

0x5C8

1480

Min

Keys

HOUR

0x5C9

1481

Hrs

DATE

0x5CA

1482

DD

MONTH

0x5CB

1483

MM

YEAR

0x5CC

1484

YY

Amp

1-1012120

Setting a new value.

Digit increment by 1.

Moves 1 digit to right.

Digit increment by 2.

Moves 1 digit to right.

Digit increment by 3.
125
Slave Address setting
completed successfully.

RTC

An example has been given using WINBUS32 S/w.


Example 1: To read Second, Minute & Hour.
Slave
Address

Function
code

0x0005

0x0003

Higher
order
address

Low
order
address

0x05C9

Number
of word
high

Number
of word
low

No. of
byte

0x0003

0x0006

No. Of
Word

No. of
Bytes

CRC
High

Instruction

Prog

Press Once

Scroll up

Press Once

Scroll up

Press Once

Scroll up

Press Once

Prog

Press Once

CRC
low
0xF5E3

Display

9600
4800
9600
19.2

Comment
Default Baud Rate.

Next.

Next.

Next.
Successfully set
New Baud Rate (19200).

3.3 Writing Parameters:


Writing Frame
Slave
Address

Function
Code

Address

Data

CRC 16

Function Code 16: For Writing, Maximum Word Length is 10 words.


Operation and Instruction Manual

12

Operation and Instruction Manual

ebrit multi

ebrit multi

3. Communication

PARAMETER

The MODBUS used by the ebrit multi involves a dialogue using a Master - Slave
structure. The mode of communication is the RTU (Remote Terminal Unit) using
hexadecimal characters of at least 8 bit.

MD Read or Reset

HEX
ADDRESS

DECIMAL
ADDRESS

No. OF
WORDS

kW MD

0x581

1409

kW

kW MD MINUTE

0x583

1411

Min

kW MD HOUR

0x584

1412

Hrs

kW MD DATE

0x585

1413

DD

kW MD MONTH

0x586

1414

MM

Function Code 3: For Reading Maximum Word length is 40 words.


For 3 Phase 4 Wire

kW MD YEAR

0x587

1415

YY

Address Table

kVA MD

0x588

1416

kVA

kVA MD MINUTE

0x58A

1418

Min

kVA MD HOUR

0x58B

1419

Hrs

0x58C

3.1 Reading Parameters


The Standard Reading Communication frame consists of
Device
address

Function
Code

INSTANTANEOUS
PARAMETER

Address

HEX
ADDRESS

Data

DECIMAL
ADDRESS

CRC16

No. OF
WORDS

UNIT

R-PHASE TO NEUTRAL VOLTAGE

0x552

1362

Volt/10

Y-PHASE TO NEUTRAL VOLTAGE

0x554

1364

Volt/10

kVA MD DATE

B-PHASE TO NEUTRAL VOLTAGE

0x556

1366

Volt/10

R-PHASE CURRENT

0x558

1368

Amp/1000

Y-PHASE CURRENT

0x55A

1370

Amp/1000

B-PHASE CURRENT

0x55C

1372

Amp/1000

PHASE TO PHASE VOLTAGE (R-Y)

0x55E

1374

Volt/10

PHASE TO PHASE VOLTAGE (Y-B)

0x560

1376

Volt/10

PHASE TO PHASE VOLTAGE (B-R)

0x562

1378

Volt/10

1380

kW/1000

ACTIVE POWER (R-PHASE)

0x564

ACTIVE POWER (Y-PHASE)

0x566

1382

kW/1000

ACTIVE POWER (B-PHASE)

0x568

1384

kW/1000

ACTIVE POWER

Operation and Instruction Manual

0x56A

1386

kW/1000

UNIT

1420

DD

kVA MD MONTH

0x58D

1421

MM

kVA MD YEAR

0x58E

1422

YY

ACTIVE ENERGY

0x58F

1423

kWh

APPARENT ENERGY

0x591

1425

kVAh

REACTIVE ENERGY LAG

0x593

1427

kVArh

REACTIVE ENERGY LEAD

0x595

1429

kVArh

AVERAGE ACTIVE POWER

0x5A3

1443

kW/10

AVERAGE APPARENT POWER

0x5A5

1445

kVA/10

AVERAGE REACTIVE POWER

0x5A7

1447

kVAr/10

MAXIMUM ACTIVE POWER

0x5B5

1461

kW/10

MAXIMUM APPARENT POWER

0x5B7

1463

kVA/10

MAXIMUM REACTIVE POWER

0x5B9

1465

kVAr/10

Operation and Instruction Manual

11

ebrit multi

3.2 Reading Parameters

ebrit multi
PARAMETER

HEX
ADDRESS

DECIMAL
ADDRESS

No. OF
WORDS

UNIT

APPARENT POWER (R-PHASE)

0x56C

1388

kVA/1000

APPARENT POWER (Y-PHASE)

0x56E

1390

kVA/1000

Function Code 3: For Reading Maximum Word length is 40 words.

APPARENT POWER (B-PHASE)

0x570

1392

kVA/1000

For 3 Phase 3 Wire

APPARENT POWER

0x572

1394

kVA/1000

REACTIVE POWER (R-PHASE)

0x574

1396

kVAr/1000

REACTIVE POWER (Y-PHASE)

0x576

1398

kVAr/1000

REACTIVE POWER (B-PHASE)

0x578

1400

kVAr/1000

The Standard Reading Communication frame consists of


Device
address

Function
Code

Address

Data

CRC16

Address Table
INSTANTANEOUS
PARAMETER

HEX
ADDRESS

DECIMAL
ADDRESS

No. OF
WORDS

UNIT

R-PHASE CURRENT

0x558

1368

Amp/1000

REACTIVE POWER

0x57A

1402

kVAr/1000

Y-PHASE CURRENT

0x55A

1370

Amp/1000

POWER FACTOR (R-PHASE)

0x57C

1404

0.01

B-PHASE CURRENT

0x55C

1372

Amp/1000

REACTIVE POWER (Y-PHASE)

0x57D

1405

0.01

PHASE TO PHASE VOLTAGE (R-Y)

0x55E

1374

Volt/10

POWER FACTOR (B-PHASE)

0x57E

1406

0.01

PHASE TO PHASE VOLTAGE (Y-B)

0x560

1376

Volt/10

SYSTEM POWER FACTOR

0x57F

1407

0.01

PHASE TO PHASE VOLTAGE (B-R)

0x562

1378

Volt/10

FREQUENCY

0x580

1408

Hz/100

1386

kW/1000

0x581

1409

kW

ACTIVE POWER

0x56A

MD Read or Reset

APPARENT POWER

0x572

1394

kVA/1000

kW MD

REACTIVE POWER

0x57A

1402

kVAr/1000

kW MD MINUTE

0x583

1411

Min

SYSTEM POWER FACTOR

0x57F

1407

0.01

kW MD HOUR

0x584

1412

Hrs

FREQUENCY

0x580

1408

Hz/100

kW MD DATE

0x585

1413

DD

Operation and Instruction Manual

10

kW MD MONTH

0x586

1414

MM

kW MD YEAR

0x587

1415

YY

kVA MD

0x588

1416

kVA

kVA MD MINUTE

0x58A

1418

Min

kVA MD HOUR

0x58B

1419

Hrs

Operation and Instruction Manual

ebrit multi
PARAMETER

HEX
ADDRESS

ebrit multi
PARAMETER

DECIMAL
ADDRESS

No. OF
WORDS

UNIT

1420

DD

MAXIMUM APPARENT POWER

HEX
ADDRESS

DECIMAL
ADDRESS

No. OF
WORDS

UNIT

0x5B7

1463

kVA/10

0x5B9

1465

kVAr/10

kVA MD DATE

0x58C

kVA MD MONTH

0x58D

1421

MM

MAXIMUM REACTIVE POWER

kVA MD YEAR

0x58E

1422

YY

SERIAL NUMBER

0x5BB

1467

ACTIVE ENERGY

0x58F

1423

kWh

POWER RATIO

0x5BD

1469

APPARENT ENERGY

0x591

1425

kVAh

NETWORK SELECTION

0x5BF

1471

REACTIVE ENERGY LAG

0x593

1427

kVArh

CT RATIO

0x5C0

1472

REACTIVE ENERGY LEAD

0x595

1429

kVArh

CT SECONDARY

0x5C1

1473

R-PHASE AVERAGE VOLTAGE

0x597

1431

Volt/10

PT RATIO

0x5C2

1474

Y-PHASE AVERAGE VOLTAGE

0x599

1433

Volt/10

PT SECONDARY

0x5C3

1475

Volt

Amp

B-PHASE AVERAGE VOLTAGE

0x59B

1435

Volt/10

INTE. TIME FOR AVG. PARAMETERS

0x5C4

1476

Min

R-PHASE AVERAGE CURRENT

0x59D

1437

Amp/1000

MD INTEGRATION TIME

0x5C5

1477

Min

Y-PHASE AVERAGE CURRENT

0x59F

1439

Amp/1000

RTC

B-PHASE AVERAGE CURRENT

0x5A1

1441

Amp/1000

SECOND

0x5C7

1479

Sec

AVERAGE ACTIVE POWER

0x5A3

1443

kW/10

MINUTE

0x5C8

1480

Min

AVERAGE APPARENT POWER

0x5A5

1445

kVA/10

HOUR

0x5C9

1481

Hrs

AVERAGE REACTIVE POWER

0x5A7

1447

kVAr/10

DATE

0x5CA

1482

DD

R-PHASE MAXIMUM VOLTAGE

0x5A9

1449

Volt/10

MONTH

0x5CB

1483

MM

Y-PHASE MAXIMUM VOLTAGE

0x5AB

1451

Volt/10

YEAR

0x5CC

1484

YY

B-PHASE MAXIMUM VOLTAGE

0x5AD

1453

Volt/10

R-PHASE MAXIMUM CURRENT

0x5AF

1455

Amp/1000

Y-PHASE MAXIMUM CURRENT

0x5B1

1457

Amp/1000

B-PHASE MAXIMUM CURRENT

0x5B3

1459

Amp/1000

MAXIMUM ACTIVE POWER

0x5B5

1461

Operation and Instruction Manual

kW/10

Operation and Instruction Manual