PUMP FLOW RATE CALCULATION

Hazard
Assumed Maximum Area of Operation(AMAO) as per TAC
No. of sprinklers provided as per AMAO
Sprinkler size (As per Table no. 33 of TAC Norms)
Mean Value of K- Factor for 15mm (As per Table no. 34 of TAC
Norms)
Minimum pressure at any discharging sprinkler (As per Table no.
28 of TAC Norms)
Flow rate of unit sprinkler
Flow rate for total 42 no. of Sprinklers as per AMAO
Flow rate
Available pump as per Table No.9 of TAC
Delivery pressure of Pump as per TAC

PRESSURE DROP CALCULATION


(HAZEN WILLIAMS FORMULA)
Flow
Pipe Diameter
Total Length including equivalent length
Pressure drop per meter
Pressure drop due to friction
Minimum pressure at any discharging sprinkler (As per Table no. 28 of
TAC Norms)
Minimum pressure at remotest hydrant point
Pressure Loss due to elevation change (12M)
Pressure required at pump room
Pressure required at pump room

PRESSURE DROP CALCULATION FOR REMOTEST HYDRANT


(HAZEN WILLIAMS FORMULA)
Flow
Pipe Diameter
Total Length including equivalent length
Pressure drop per meter
Pressure drop due to friction
Minimum pressure at any discharging sprinkler (As per Table no.
28 of TAC Norms)
Pressure required at pump room
Delivery pressure of Pump as per Table No.9 of TAC

ULATION
Ordinary
360
42
15

sq. mtr.
nos.
mm

80

0.35

bar

47.33
1987.80
119.27
127
7

LPM
LPM
m3/hr
m3/hr
Kg/cm2

171
150
1842
0.002733
5.03

m3/hr.
mm
m
bar/m
bar

0.35

bar

3.4
1.4
10.19
10.40

bar
bar
bar
kg/cm2

MULA)

OTEST HYDRANT
RMULA)
171
150
855
0.002733
2.336715

m3/hr
mm
m
bar/m
bar

0.35

bar

2.69

LPM
Kg/cm2

166
103
272

146
166
25
10
10
10
10
10
10
10
948
100
1048
1624

576