DIRECCIN DE OPERACIN
NDICE
1.
2.
2.1.
INTRODUCCIN....................................................................................... 3
REQUERIMIENTOS PARA EL REPORTE DE INFORMACIN ........................... 3
EQUIPOS DE ADQUISICIN DE DATOS...................................................... 3
2.2.
2.3.
2.2.1.
2.2.2.
2.4.
2.5.
2.6.
VAS DE COMUNICACIN EN
2.8.
Prueba de Enlace:................................................................................. 6
Prueba Inicial: ...................................................................................... 6
Prueba Punto a Punto: .......................................................................... 6
COSTOS estimados INVOLUCRADOS.......................................................... 7
2.8.1.
Hosting ................................................................................................ 7
2.8.2.
Modificacin Base de Datos SCADA CDEC-SIC ......................................... 7
2.8.3.
Protocolo Serial: Dispositivo Mode ShaRE DEVICES ............................... 7
2.8.4.
Protocolo ICCP: LICENCIA SPECTRUM .................................................... 8
ANEXO 1.- CONFIGURACIN ENLACE TCP/IP ..............................................................10
ANEXO 2.PROTOCOLO ICCP: EJEMPLO CONFIGURACIN TABLAS BILATERALES ....11
ANEXO 3.CONFIGURACIN ENLACE SERIAL ........................................................14
ANEXO 4.PROTOCOLOS IEC 870-5-104/101 Y DNP3.0 TCP-IP/SERIAL: PERFILES ...15
ANEXO 5
PROTOCOLOS IEC 870-5-101 Y DNP3.0 SERIAL: DISPOSITIVO DERIVADOR 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
1. INTRODUCCIN
El presente documento complementa el Procedimiento DO Definicin de parmetros
tcnicos y para el envo de datos al SITR del CDEC-SIC y especifica las condiciones
tcnicas y administrativas para la conexin de los Coordinados al SITR del CDC.
PROTOCOLO TCP/IP
Ancho de Banda
128 kbps o Superior
128 kbps o Superior
Ancho de Banda
128 kbps o Superior
El enlace principal que el coordinado establezca entre sus instalaciones y el front end
del CDEC-SIC, deber llegar a las instalaciones del CPD de Synapsis ubicado en Av.
Eduardo Frei Montalva 2205 (ex Panamericana Norte), comuna de Independencia,
Santiago. En el caso de que el coordinado determine utilizar en forma adicional un
enlace de respaldo, el segundo enlace deber llegar a las instalaciones del CPD de
3 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
PROTOCOLO SERIAL
Ancho de Banda
1.200, 9.600 19.200 baudios
1.200, 9.600 19.200 baudios
4 de 19
CDEC-SIC
Direccin de Operacin
2.4.
Mayo de 2007
En el caso de tratarse de una conexin serial, la conectividad entre los equipos ser
habilitada y validada por las dos partes en conjunto, tanto por el coordinado como por
el CDEC-SIC a travs de Synapsis. Como paso previo a esta habilitacin, el
coordinado entregar un esquema de comunicaciones y definicin de parmetros de
los equipos RTU y el CDEC-SIC lo complementar con sus propios equipos,
direcciones y rutas. En base a esta informacin, el CDEC-SIC generar un diagrama
unificado con los equipos de ambos, el cual considerar los dispositivos que
conformarn la conectividad.
En el ANEXO 3 se muestra un ejemplo que describe un diagrama esquemtico de
comunicacin con los principales elementos que componen un enlace serial entre el
CDEC-SIC y un coordinado.
En el ANEXO 4 se encuentran los perfiles de los protocolos Seriales referidos.
En el caso de una conexin va RTU en protocolo DNP 3.0 Serial o IEC 870-5-101, el
CDEC-SIC indicar al coordinado el punto del Front-End del SCADA del CDEC-SIC
donde deber conectar un cable DB-25. A su vez, el coordinado deber considerar un
dispositivo derivador denominado Modem Sharing Device que permite utilizar la
redundancia del Front-End del Sistema SCADA del CDEC-SIC. En el ANEXO 5 se
presenta la descripcin tcnica del dispositivo y el pin-out del Terminal DB-25
necesario.
2.5.
En el caso de que el coordinado requiera instalar equipos en dependencias del CDECSIC para habilitar una va de comunicacin, deber tener presente lo siguiente:
La administracin de los servicios de SITR del CDEC-SIC, se realizan a travs de un
contrato de outsourcing con SYNAPSIS IT LTDA, esto significa que los equipos
debern instalarse en un CPD de dicha empresa, ubicado en Panamericana Norte
2205, comuna de Independencia; y en caso de utilizar la redundancia (slo para
enlace TCP/IP) debern instalarse en el CPD de Synapsis IT LTDA., ubicado en Santa
Rosa 76, comuna de Santiago.
5 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
Con esta informacin, Synapsis gestionar los permisos correspondientes para que el
coordinado pueda ingresar al CPD y efectuar sus trabajos.
2.7.
PRUEBA DE ENLACE:
A nivel de capa de enlace se debe constatar que los equipos comuniquen verificando
rutas y permisos de los sistemas.
2.7.2.
PRUEBA INICIAL:
6 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
Nmero de Tags
N 25
25 < N 50
50 < N 80
80 < N 120
120 < N
10
12
14
20
28
25
40
68
84
Revisar
Caso a Caso
10
14
22
49
68
102
132
Revisar
Caso a Caso
Revisar
Caso a Caso
2.8.3.
7 de 19
CDEC-SIC
Direccin de Operacin
2.8.4.
Mayo de 2007
8 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
ANEXOS
ANEXO 1.-
ANEXO 2.-
ANEXO 3.-
ANEXO 4.-
ANEXO 5.-
9 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
OPCIONES:
IP UTR IEC104 Coordinado: AA.BB.CC.DD
IP UTR DNP3.0 Coordinado: AA.BB.CC.DD
IP Servidor ICCP Coordinado: AA.BB.CC.DD
Router
SCADA CDEC-SIC
Instalaciones CPD Synapsis
Router
CPD Principal:
Switch
Redes Externas
Firewall: 10.39.XX.ZZ
IP(gateway) que resuelve acceso a servidores ICCP
del CDEC-SIC para SCADA del COORDINADO
CPD Respaldo:
Santa Rosa 76,
Comuna Santiago, Santiago
Firewall
SCADA
LAN A
LAN B
UCS1
TCS1
UCS2
TCS2
Notas:
TCS:
UCS:
Firewall:
10 de 19
CDEC-SIC
Direccin de Operacin
ANEXO 2.-
Mayo de 2007
Valor
ICCP
MCS
400
400
15000
1y2
COORDINA
RALCO _DOMAIN
SCADA CDEC-SIC
18 seg.
8 seg.
10 seg.
SYNAPSIS
1996-08
DOMAIN_ COORDINA
DOMAIN_MCS
COORDINA
11
LOCAL_ COORDINA
REMOTE_ COORDINA
11 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
Parmetro
Nombre del Grupo
Reporte Peridico de Datos
Reporte por Excepcin de Datos
Intervalo de Chequeo de Integridad
Valor
Excpt_1
No Aplica
S
600 seg.
Parmetro
Nombre del Grupo
Reporte Peridico de Datos
Reporte por Excepcin de Datos
Periodicidad del Reporte de Datos
Valor
Perio_1
S
No Aplica
10 seg.
12 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
= LOCAL_COORDINA
= 1 2 50 18
= 100
=2
=1
= 00000068
= 0001
= 0001
=0
=0
= REMOTE_ COORDINA
= 1 2 50 18
= 100
=2
=1
= 00000068
= 0001
= 0001
=0
=0
= ip servidor ICCP del COORDINADO
= TCP
13 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
SCADA CDEC-SIC
Dispositivo Comunicaciones
Por ejemplo: Mdem
Dispositivo Derivador
RAN1
RAN2
LAN A
LAN B
TCS1
TCS2
Notas:
TCS:
RAN:
14 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
15 de 19
CDEC-SIC
Direccin de Operacin
Mayo de 2007
Perfil
IEC-104-101.pdf
16 de 19
IEC-60870-5-101
______________________________________________________________________
1.1
Communication profiles
IEC-60870-5-101
______________________________________________________________________
Companion standard for basic telecontrol tasks
A1 - 1 Interoperability
The companion standard defined above presents sets of parameters and alternatives from which
subsets have to be selected to implement particular telecontrol systems. Certain parameter
values, such as the number of octets in the COMMON ADDRESS of ASDUs represent mutually
exclusive alternatives. This means that only one value of the defined parameters is admitted per
system. Other parameters, such as the listed set of different process information in command and
in monitor direction allow the specification of the complete set or subsets, as appropriate for given
applications. This clause summarizes the parameters of the previous clauses to facilitate a
suitable selection for a specific application. If a system is composed of equipment from different
manufacturers it is necessary that all partners agree on the selected parameters.
The selected parameters should be crossed in the white boxes.
Note: In addition, the full specification of a system may require individual selection of certain
parameters for certain parts of the system, such as the individual selection of scaling factors for
individually addressable measured values.
Note:
Functions which are not (yet) implemented in Siemens Spectrum System do not have the
check box " ". Further investigations are needed if they are required. Mandatory items are
marked by " ".
Parameters which are in addition or different to the TCS 101 are written in italic.
A1 - 1.1 Network Configuration
Configuration
Remark
Multipoint-Partyline
Ditto
Multipoint-Star
Ditto
Remark
Speed
100 bit/s
Remark
4 800 bit/s
200 bit/s
300 bit/s
19 200 bit/s
600 bit/s
38 400 bit/s
1 200 bit/s
56 000 bit/s
2 400 bit/s
64 000 bit/s
9 600 bit/s
IEC-60870-5-101
______________________________________________________________________
A1 - 1.3 Link Layer
Frame format FT 1.2, single character1(=E5) and the fixed time out interval are used exclusively
in this companion standard.
Link transmission procedure
Procedure
Remark
Balanced Transmission
Send / No reply in monitoring direction
Unbalanced Transmission
Number of Data Class 1 requests__
Number of Data Class 2 requests__
default: 2
default: 4
(only for unbalanced transmission relevant)
default: 255
Number of repeats_____
default: 2
Remark
not present
1 Octet
2 Octets
structured
unstructured
Remark
1 Octet
2 Octets
structured
unstructured
IEC-60870-5-101
______________________________________________________________________
Information Object Address
Description
Remark
1 Octet
2 Octets
3 Octets
structured
unstructured
Cause of Transmission
1 Octet
2 Octets
Test bit
Test bit is not evaluated in the Spectrum System
ASDU
Description
Remark
<1>
M_SP_NA_1
Single-point information
<2>
M_SP_TA_1
Single-point information
with time tag
<3>
M_DP_NA_1
Double-point
information
<4>
M_DP_TA_1
Double-point
information with time tag
<5>
M_ST_NA_1
Step position
information
<6>
M_ST_TA_1
Step position
information with time tag
<7>
M_BO_NA_1
Bitstring of 32 bit
<8>
M_BO_TA_1
<9>
M_ME_NA_1
Measured value,
normalized value
recommended type
<10>
M_ME_TA_1
Measured value,
normalized value with
time tag
<11>
M_ME_NB_1
IEC-60870-5-101
______________________________________________________________________
value
<12>
M_ME_TB_1
<13>
M_ME_NC_1
<14>
M_ME_TC_1
<15>
M_IT_NA_1
Integrated totals
<16>
M_IT_TA_1
<17>
M_EP_TA_1
Event of protection
equipment with time tag
( )
<18>
M_EP_TB_1
on request
( )
<19>
M_EP_TC_1
on request
<20>
M_PS_NA_1
Packed single-point
information with status
change detection
<21>
M_ME_ND_1
Measured value,
normalized value
without quality
descriptor
M_SP_TB_1
M_DP_TB_1
M_ST_TB_1
M_BO_TB_1
M_ME_TD_1
M_ME_TE_1
<36> := Measured value, short floating point value with time tag CP56Time2a
M_ME_TF_1
M_IT_TB_1
M_EP_TD_1
<39> := Packed start events of protection equipment with time tag CP56Time2a
M_EP_TE_1
M_EP_TF_1
IEC-60870-5-101
______________________________________________________________________
Cause of Transmission
CoT
Cause
Remark
<1>
periodic, cyclic
<2>
background scan
<3>
spontaneous
<5>
requested
<7>
activation confirmation
<9>
deactivation
confirmation
<10>
activation termination
<11>
return information
caused by a remote
command
<12>
return information
caused by a local
command
<20>
interrogated by general
interrogation
Description
Remark
<NT
not topical
<IV>
invalid
<OV>
overflow
<SB>
substituted
<BL>
blocked
Remark:
Invalid time tags are passed-on from process interface to the Communicator without change.
IEC-60870-5-101
______________________________________________________________________
Process information in control direction
Type
Ident
ASDU
Description
<45>
C_SC_NA_1
Single command
<46>
C_DC_NA_1
Double command
<47>
C_RC_NA_1
<48>
C_SE_NA_1
<49>
C_SE_NB_1
<50>
C_SE_NC_1
<51>
C_BO_NA_1
Bitstring of 32 bits
Remark
<70>
M_EI_NA_1
End of initialization
ASDU
Description
Remark
<100>
C_IC_NA_1
Interrogation command
<101>
C_CI_NA_1
Counter interrogation
command
not supported
not supported
<102>
C_RD_NA_1
Read command
<103>
C_CS_NA_1
Clock synchronization
command
<104>
C_TS_NA_1
Test command
not supported
<105>
C_RP_NA_1
not supported
IEC-60870-5-101
______________________________________________________________________
Parameter in Control Direction
Type
Ident
ASDU
Description
Remark
( )
<110>
P_ME_NA_P
q KPA=1
KPA=2
KPA=3/4
Parameter of measured
value, normalized value
- threshold - smoothing
factor - low / high limit
on request
( )
<111>
P_ME_NB_1
KPA=1
KPA=2
KPA=3/4
Parameter of measured
value, scaled value
- threshold - smoothing
factor - low / high limit
ditto
( )
<112>
P_ME_NC_1
Parameter of measured
value, short floating point
value
- threshold - smoothing
factor - low / high limit
ditto
Parameter activation
- act / deact of cyclic
transmission
not supported
KPA=1
KPA=2
KPA=3/4
<113>
P_AC_NA_1
QPA=3
ASDU
Description
<120>
F_FR_NA_1
File ready
<121>
F_SR_AN_1
Section ready
<122>
F_SC_NA_1
<123>
F_LS_NA_1
Last section
<124>
F_AF_NA_1
<125>
F_SG_NA_1
Segment
<126>
F_DR_TA_1
Directory
Remark
not implemented
Note:
Source or destination of the file transfer is a directory of the process controlling DAS server.
Preparation or evaluation of the file contents on any other Spectrum server is subject of extra
effort.
IEC-60870-5-101
______________________________________________________________________
A1 - 1.5 Basic Application Functions
General Interrogation
Type
Ident
ASDU
Description
Remark
<100>
C_IC_NA_1
(QOI=20)
global G I
<100>
C_IC_NA_1
(QOI=21)
group 1
not supported
<100>
C_IC_NA_1
(QOI=22)
group 2
ditto
etc.
group 3
ditto
group 4
ditto
group 5
ditto
group 6 ...
16
ditto
ditto
Remark
not supported
arbitrary
QOC
Description
Remark
<0>
no additional definition
<1>
<2>
<3>
Persistent output
not supported
IEC-60870-5-101
______________________________________________________________________
(others to be defined)
IEC-60870-5-101
______________________________________________________________________
Counter Interrogation Commands
Type
Ident
ASDU
Description
Remark
<101>
C_CI_NA_1.
..(FRZ=0)
no freeze or reset
not supported
...(FRZ=1)
ditto
...(FRZ=2)
ditto
...(FRZ=3)
counter reset
ditto
...(RQT=0)
no counter request
ditto
...(RQT=1)
ditto
...(RQT=2)
ditto
...(RQT=3)
ditto
...(RQT=4)
ditto
...(RQT=5)
ditto
Note:
all counter commands (freeze, reset) are to be carried out by the RTU. The transmission of the
counter messages is initialized by the RTU spontaneously after each freezing.
CDEC-SIC
Direccin de Operacin
Mayo de 2007
Anexo A_Perfil
IEC104.pdf
17 de 19
Valor por
Defecto
to
30 s
t1
15 s
t2
10 s
t3
30 s
Notas
Valor
Adoptado
Time-out de establecimiento de
conexin
Time-out de APDU del tipo send o
test
Time-out para confirmaciones en caso
de mensajes sin datos t2 < t1
Time-out para envo de tramas de tipo
S en caso de periodos largos de
inactividad t3 > t1
60 s
15 s
10 s
30 s
Rango de valores para todos los time-outs es de: 1 a 255 s, con una precisin de 1 s.
Nmero mximo de APDU tipo I y ltima confirmacin
Parmetro
Valor por
Defecto
12 APDUs
8 APDUs
Notas
Valor
Adoptado
12
8
Valor por
Defecto
2404
Notas
En todos los casos
Ethernet 802.3
Otras selecciones de RFC2200
Lista de documentos vlidos de RFC2200
1.- ______________________________
2.- ______________________________
3.- ______________________________
4.- ______________________________
Significado
Nemotcnico
<1>
<3>
M_SP_NA_1
M_DP_NA_1
<5>
Posicin de paso
M_ST_NA_1
<11>
M_ME_NB_1
<15>
<30>
<31>
Totales integrados
Estado digital simple con marca de tiempo extendida
Estado digital doble con marca de tiempo extendida
M_IT_NA_1
M_SP_TB_1
M_DP_TB_1
Causa de Transmisin
<20>
<20>
<3>
<20>
<3>
<20>
<3>
<3>
<3>
General Interrogation
General Interrogation
Spontaneous
General Interrogation
Spontaneous
General Interrogation
Spontaneous
Spontaneous
Spontaneous
Significado
Nemotcnico
<45>
Comando simple
C_SC_NA_1
<46>
Comando doble
C_DC_NA_1
<47>
C_RC_NA_1
<49>
C_SE_NB_1
Causa de Transmisin
<6> Activation
<8> Deactivation
<7> Activation Confirmation
<9> Deactivation Confirmation
<10> Activation Termination
<6> Activation
<8> Deactivation
<7> Activation Confirmation
<9> Deactivation Confirmation
<10> Activation Termination
<6> Activation
<8> Deactivation
<7> Activation Confirmation
<9> Deactivation Confirmation
<10> Activation Termination
<6> Activation
<8> Deactivation
<7> Activation Confirmation
<9> Deactivation Confirmation
<10> Activation Termination
Significado
Comando de interrogacin
Nemotcnico
C_IC_NA_1
Causa de Transmisin
<6> Activation
<8> Deactivation
<7> Activation Confirmation
<9> Deactivation
Confirmation
<10> Activation Termination
CDEC-SIC
Direccin de Operacin
Mayo de 2007
Perfil DNP3.pdf
18 de 19
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
The companion standard defined presents sets of parameters and alternatives from which subsets have to be selected to implement particular telecontrol systems. Certain parameter values, such as the number of octets in the
COMMON ADDRESS of ASDUs represent mutually exclusive alternatives. This means that only one value of the
defined parameters is admitted per system. Other parameters, such as the listed set of different process information in command and in monitor direction allow the specification of the complete set or subsets, as appropriate for
given applications. This clause summarizes the parameters of the previous clauses to facilitate a suitable selection
for a specific application. If a system is composed of equipment stemming from different manufacturers it is necessary that all partners agree on the selected parameters.
European projects have used a scheme called Double Channels. This method of redundancy is not supported.
1RWH
7KHFKHFNER[HV\RXZLOOILQGEHORZKDYHWKHIROORZLQJPHDQLQJ
q
LPSOHPHQWHGE\6LHPHQV7HOHFRQWURO,QWHUIDFH
n/i
QRWLPSOHPHQWHGE\6LHPHQV7HOHFRQWURO,QWHUIDFH
VXEVHWVHOHFWHGIRUWKLVSURMHFWHPSW\FKHFNER[WREHUHSODFHGE\WKLVV\PERO
PDQGDWRU\
F-DA02-E-1.3.0.0
-1
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
1HWZRUN&RQILJXUDWLRQ
&RQILJXUDWLRQ
Point-to Point
Multipoint-Partyline
Multipoint-Star
5HPDUN
F-DA02-E-1.3.0.0
-2
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
3K\VLFDO/D\HU
7UDQVPLVVLRQ6SHHGFRPPRQIRUERWKGLUHFWLRQV
Unbalanced Interchange
Circuit V.24 / V.28 Standard
6SHHG
5HPDUN
6SHHG
5HPDUN
n/i
100 bit/s
4 800 bit/s
n/i
200 bit/s
9 600 bit/s
n/i
300 bit/s
19 200 bit/s
n/i
600 bit/s
n/i
38 400 bit/s
1 200 bit/s
n/i
56 000 bit/s
ditto
2 400 bit/s
n/i
64 000 bit/s
ditto
F-DA02-E-1.3.0.0
-3
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
'DWD/LQN/D\HU
The data link layer uses a standard variable length frame format as defined in the IEC 870-5-1 Transmission
Frame Formats document. The FT3 frame format class is well suited for data transmission between stations that
require medium information transfer rates and low residual error probability.
3URFHGXUH
5HPDUN
n/i
Unsolicited Responses
3.1
Function code Field Values of Control octet Sent from the primary station (PRM=1)
)XQFWLRQ )UDPH7\SH
&RGH
6HUYLFH)XQFWLRQ
)&9
%LW
User data
n/i
Not used
n/i
Not used
n/i
Not used
n/i
Not used
n/i
10
Not used
n/i
11
Not used
n/i
12
Not used
n/i
13
Not used
n/i
14
Not used
n/i
15
Not used
F-DA02-E-1.3.0.0
-4
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
3.2
Function code Field Values of Control octet Sent from the secondary station (PRM=0)
)XQFWLRQ )UDPH7\SH
&RGH
6HUYLFH)XQFWLRQ
CONFIRM
CONFIRM
n/i
Not used
n/i
Not used
n/i
Not used
n/i
Not used
n/i
Not used
n/i
Not used
n/i
Not used
n/i
Not used
n/i
10
Not used
11
n/i
12
Not used
n/i
13
Not used
14
15
RESPOND
F-DA02-E-1.3.0.0
-5
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
4.1
7UDQVSRUW/D\HU
Fragmentation for transport frames in receive direction
3URFHGXUH
5HPDUN
4.2
n/i
+255
-5
-1
=249
octets
octets
octet
octets
5HPDUN
F-DA02-E-1.3.0.0
-6
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
5.1
5.2
n/i
5.3
$SSOLFDWLRQ/D\HU
Fragmentation for application frames in receive direction
3URFHGXUH
5HPDUN
5HPDUN
Function codes
&RGH
)XQFWLRQ
7UDQVIHU)XQFWLRQ&RGHV
q
Confirm
Read
Write
&RQWURO)XQFWLRQ&RGHV
q
Select
Operate
Direct Operate
n/i
)UHH]H)XQFWLRQ&RGHV
q
Immediate Freeze
7UDQVIHU)XQFWLRQ&RGHV
n/i
n/i
10
n/i
11
F-DA02-E-1.3.0.0
-7
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
&RGH
n/i
12
)XQFWLRQ
Freeze and Time - No Acknowledgment
$SSOLFDWLRQ)XQFWLRQ&RGHV
n/i
13
Cold Restart
n/i
14
Warm Restart
n/i
15
n/i
16
Initialize Application
n/i
17
Start Application
n/i
18
Stop Application
&RQILJXUDWLRQ)XQFWLRQ&RGHV
n/i
19
Save Configuration
n/i
20
n/i
21
n/i
22
Assign Class
7LPH6\QFKURQL]DWLRQ)XQFWLRQ&RGHV
q
23
Delay Measurement
5HVHUYH
n/i
n/i
5HVSRQVH)XQFWLRQ&RGHV
q
129
Response
n/i
130
Unsolicited Messages
F-DA02-E-1.3.0.0
Confirm
-8
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
'DWD2EMHFWVDQG)XQFWLRQV
2EMHFW*URXS9DULDWLRQ
5HTXHVW)XQFWLRQ
4XDOLILHU D
5HVSRQVH
)XQFWLRQ
4XDOLILHUD
Read
01, 06
Response
n/i
Assign Class
01, 06
Response
Read
01, 06
Response
01, 06
Response
n/i
01, 06
Response
Read
01, 06
Response
n/i
Assign Class
01, 06
Response
01, 06
Response
n/i
01, 06
Response
Read
01, 06
Response
n/i
Assign Class
01, 06
Response
Select, Operate,
Direct Operate
28
Response
Echoes
Request
n/i
n/i
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
01, 06
Response
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
F-DA02-E-1.3.0.0
-9
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
2EMHFW*URXS9DULDWLRQ
5HTXHVW)XQFWLRQ
4XDOLILHUD
5HVSRQVH
)XQFWLRQ
4XDOLILHUD
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
01, 06
Response
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
01, 06
Response
01, 06
Response
01, 06
Response
01, 06
Response
01, 06
Response
F-DA02-E-1.3.0.0
- 10
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
2EMHFW*URXS9DULDWLRQ
4XDOLILHUD
5HTXHVW)XQFWLRQ
5HVSRQVH
)XQFWLRQ
4XDOLILHUD
Read
01, 06
Response
01, 06
Response
01, 06
Response
Read
01, 06
Response
Read
01, 06
Response
01, 06
Response
01, 06
Response
Response
Response
Response
Response
Select, Operate,
Direct Operate
28
Response
Echoes
Response
Select, Operate,
Direct Operate
28
Response
Echoes
Response
Write
07
Response
n/i
Read
Response
Read
Response
n/i
Delay Measurement 07
Response
07
Read
Response
Response
Response
Response
n/i
F-DA02-E-1.3.0.0
06
- 11
6,1$876SHFWUXP
,QWHURSHUDELOLW\/LVW'13IRU/HYHO
7HOHFRQWURO,QWHUIDFH7&,
2EMHFW*URXS9DULDWLRQ
q
n/i
n/i
n/i
n/i
n/i
n/i
n/i
n/i
n/i
n/i
n/i
5HTXHVW)XQFWLRQ
Write
4XDOLILHUD
00
5HVSRQVH
)XQFWLRQ
Response
4XDOLILHUD
00
F-DA02-E-1.3.0.0
- 12
CDEC-SIC
Direccin de Operacin
ANEXO 5
Mayo de 2007
ModemShare
Devices 56606668[1]
19 de 19
Doc. 56606668
Rev. 01
Page 1 of 7
M. Brown
_________________
Originator
M. Brown
____________________
Engineer
_________________
Checked
____________________
Approved
Revision Record
Rev ECO
01
Description
Initial Draft
Appd. Date
08/22/05
_______________________________________________________________________
Doc. 56606668
Rev. 01
Page 2 of 7
1.2
First Used On: OPPD project; also used as a general solution for RS232
line sharing by redundant CFE servers.
1.0
Requirements
2.1
Doc. 56606668
Rev. 01
Page 3 of 7
2.2
Circuit Schematic.
2.3
2.4
2.5
2.6
2.7
2.8
Power Supply
Port powered and optional external 12vdc powered. The optional external
12vdc power, if used, is connected at an RJ11-4 pin jack. A second RJ114 pin jack is internally connected in parallel with the first RJ11 jack, and
this provides a means to connect external power in a daisy-chain manner
between multiple devices. At each RJ11 jack, 2 adjacent pins on one side
of the connector are used for positive polarity, and the 2 adjacent pins on
the other side of the connector are used for negative polarity.
Doc. 56606668
Rev. 01
Page 4 of 7
2.10
Labeling
Permanently identify the device with the following information:
Siemens part number and revision (from this Document)
Vendor name, code or logo
Vendor part number or model number
Date code of Manufacture
Labeling method and format must be approved by the Siemens design
control organization via first article inspection. Any later changes by the
supplier to this method must also be approved prior to implementation.
2.11
Testing
The manufacturer must individually test each device. Evidence of
successful testing must be provided either individually or by lot.
Individually stamping the devices, or certificate of testing for a date code
lot, are examples of acceptable test evidence.
2.0
Vendor
See Authorized Vendor List (AVL) for approved vendor and vendor part
number. Do not rely on attached vendor data (if present) or other vendor
references contained in this document.
Doc. 56606668
Rev. 01
Page 5 of 7
Port
Name
Connector
Type
Port A
Port A
Port A
Port A
Port A
Port A
Port A
Port A
Port A
Port A
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
Port
Name
Connector
Type
Port B
Port B
Port B
Port B
Port B
Port B
Port B
Port B
Port B
Port B
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
RJ45-10 pin-Female
Connector
Designation
J1- 1
J1- 2
J1- 3
J1- 4
J1- 5
J1- 6
J1- 7
J1- 8
J1- 9
J1-10
Connector
Designation
J2- 1
J2- 2
J2- 3
J2- 4
J2- 5
J2- 6
J2- 7
J2- 8
J2- 9
J2-10
RS232
Signal Name
Ring
DSR
RTS-A
Shield
TXD-A
RXD
Signal Gnd
CTS
DTR-A
CD
RS232
Signal Name
Ring
DSR
RTS-B
Shield
TXD-B
RXD
Signal Gnd
CTS
DTR-B
CD
Doc. 56606668
Rev. 01
Page 6 of 7
Port
Name
Modem
Modem
Modem
Modem
Modem
Modem
Modem
Modem
Modem
Modem
Connector
Type
DB25-Male
DB25-Male
DB25-Male
DB25-Male
DB25-Male
DB25-Male
DB25-Male
DB25-Male
DB25-Male
DB25-Male
Connector
Designation
J3- 1
J3- 2
J3- 3
J3- 4
J3- 5
J3- 6
J3- 7
J3- 8
J3-20
J3-22
Port
Name
Connector
Type
Ext Power 1
Ext Power 1
Ext Power 1
Ext Power 1
RJ11-4 pin-Female
RJ11-4 pin-Female
RJ11-4 pin-Female
RJ11-4 pin-Female
J4- 1
J4- 2
J4- 3
J4- 4
12 VDC Positive
12 VDC Positive
12 VDC Negative
12 VDC Negative
Ext Power 2
Ext Power 2
Ext Power 2
Ext Power 2
RJ11-4 pin-Female
RJ11-4 pin-Female
RJ11-4 pin-Female
RJ11-4 pin-Female
J5- 1
J5- 2
J5- 3
J5- 4
12 VDC Positive
12 VDC Positive
12 VDC Negative
12 VDC Negative
Connector
Designation
RS232
Signal Name
Shield
TXD
RXD
RTS
CTS
DSR
Signal Gnd
CD
DTR
Ring
Power
Signal Name
Doc. 56606668
Rev. 01
Page 7 of 7
Mating
RJ45
10-pin
Plug
Pin
1
Pin
1
Pin
10
Pin
4
Mating
RJ11
4-pin
Plug
Viewed
From
Contact
Side
Viewed
From
Contact
Side
3.95 inch
0.7 in
0.165 inch
(Typical)
Modem
Port
Port A
RJ45-10 pin
Female
J1
Male screwlocks
DB25
Male
Port B
RJ45-10 pin
Female
J2
J3
Pin 1
1.3 inch Approx.
Side View
J4
Power 1
RJ11-4 pin
Female
J5
Power 2
RJ11-4 pin
Female
End View