stop sequence is initiated to bring the DC power down before blocking the
converters.
Start the simulation, open the RECTIFIER and INVERTER scopes (in the Data
Acquisition subsystem) and observe the DC line voltage on trace 1 (1pu = 500
kV) and the DC line current (reference and measured values) on trace 2 (1pu = 2
kA).
Start-up and Stop
In the Master Control, the converters are unblocked and started by ramping the
rectifier and inverter reference current.
At t = 0.02 s (i.e. when the converters at unblocked), the reference current is
ramped to reach the minimum value of 0.1 pu in 0.3 s (0.33 pu/s). At the end of
this first ramp (t = 0.32 s) the DC line is charged at its nominal voltage and DC
voltage reaches steady-state.
At t= 0.4 s, the reference current is ramped from 0.1 pu to 1 pu (2kA) in 0.18 s (5
pu/s). At the end of this starting sequence (t=0.58 s), the DC current reaches
steady state. The RECTIFIER then controls the current and the INVERTER controls
the voltage.
In steady-state, the alpha firing angles (trace 3) are 17.7 degrees and 144.5
degrees respectively on the RECTIFIER and INVERTER sides. Note that in the
detailed model these traces (16.5 for the rectifier and 143 for the inverter) are
not the measured firing delay angles but the corresponding orders from the
control regulators. In the detailed model, the firing angles are smaller because
the regulators must advance the firing orders by two time steps in order to
compensate for the delays introduced by interfacing of input AC voltages and
output firing pulses of the 12-pulse Firing Control block. The extinction angle
gamma value is an output of the average model. It is used at the INVERTER and
shown in trace 5. In steady-state, its value is 23 degrees.
The control mode of operation (an integer between 0 to 6) is shown in trace 4
(0= blocked; 1=Current control; 2=Voltage control; 3=Alpha minimum limitation;
4=Alpha maximum limitation; 5=Forced or constant alpha; 6=Gamma control).
At t = 1.4 s the Stop sequence is initiated by ramping down the current to 0.1 pu.
At t = 1.6 s a Forced-alpha at the Rectifier extinguishes the current and at the
Inverter the Forced-alpha brings down the DC voltage.
At t = 1.7 s the pulses are blocked in both converters.
Step response of current and voltage regulators
Verify in the Master Control that the "Enable Ref. Current Step" switch is in the
upper position. This switch is used to apply a step on the reference voltage. Also
verify that the Ref. Voltage Step is enabled in the Inverter Control. Start the
simulation.
At t=0.7 s, a -0.2 pu step is first applied on the reference current (decrease from
1 pu to 0.8 pu ) and at t=0.8 s, the reference current is reset to its 1 pu original
value. The current stabilizes in approximately 0.1 seconds. Steps are also applied
on the reference voltage of the inverter (-0.1 pu / +0.1 pu at t=1.0 s / 1.1s).
DC line fault at the rectifier
Deactivate the steps applied on the current reference and on the voltage
reference in the Master Control and in the inverter control respectively by setting
the switches in lower position.
The DC Fault protection (DCPROT) in the rectifier is activated by default. In the
DC Fault block, change to 1 the 100 multiplication factor in the Switching times
so that a fault is now applied at t = 0.7 s.
Reduce the Simulation stop time from 2 to 1.4 s. Open the FAULT scope to
observe the DC fault current. Restart the simulation.
At fault application the DC current quickly increases to 2.63 pu and the DC
voltage falls to zero at the rectifier. This DC voltages drop is seen by the Voltage
Dependent Current Order Limiter (VDCOL) which reduces the reference current to
0.3 pu at the rectifier. A DC current still continues to circulate in the fault.
At t = 0.77 s, the rectifier alpha firing angle is forced to 166 degrees by the DC
protection because a DC voltage drop is detected (VdL< 0.5 pu for more than 70
ms). The rectifier now operates in inverter mode. The DC line voltage becomes
negative and the energy stored in the line is returned to the AC network, causing
rapid extinction of the fault current at its next zero-crossing.
Alpha is released at t = 0.82 s and the normal DC voltage and current recover in
approximately 0.4 s.
AC line-to-ground fault at the inverter
In the DC Fault block, change the multiplication factor of 1 in the Switching times
to 100, so that the DC fault is now disabled. In the A-G Fault block, change to 1
the 100 multiplication factor in the Switching times so that a 6 cycles line-toground fault is now applied at t = 0.7 s.
The Low AC voltage detection (LACVD) subsystem in the rectifier and inverter
protections and the Commutation Failure Prevention Control (CFPREV) in the
inverter protection are activated by default.
Restart the simulation.
Note that the 120 Hz oscillations in the DC voltage and currents which are
normally observed during single-phase fault with a detailed model do not exist in
the average model. Indeed, only positive-sequence fundamental components of
AC quantities are significant in the average model. The VDCOL would not operate
during the fault. The system recovers in approximately 0.2 s after fault clearing
(see the measured DC power Pd).
Abnormal inverter operation resulting from a commutation failure malfunction
(CF) due to AC faults are not correctly represented by the average model
equations. To assist the user in identifying such a condition an alarm signal
(CF_alarm) is set whenever the onset of a CF is predicted.
Look at the CF_alarm signal at the inverter, triggered at t = 0.73 s. Open the
CF_alarm block (inside the HVDC_CONV_AVG block of the inverter model) to
examine the logic.
Look at the A_min_I signal of the PROTECTION INVERTER scope. This signal
monitors the Commutation Failure Prevention (CFPREV) output of the Inverter
Protection block. The A_min signal is used to decrease the delay angle limit in
order to increase the commutation margin during and after the fault.
Finally, deactivate the CFPREV protection by deselecting the "ON State" in the
CFPREV dialog box. Restart the simulation and observe the difference in recovery
time of the DC transmission.