Learning Outcome
When you complete this module you will be able to:
Describe the various feedwater control methods and devices used on low-pressure
steam boilers.
Learning Objectives
Here is what you will be able to do when you complete each objective:
1. Describe the operation of a feedwater float switch operating a valve and float
switch operating a pump.
2. Describe how condensate is collected and returned to the boiler.
3. Explain the purpose and function of heating boiler feedwater and condensate
piping connections.
1
INST 6005
INTRODUCTION
In low-pressure steam boilers there are several ways in which feedwater is
controlled to the boiler and many ways condensate is collected and returned to the
boiler. This module will cover some of the common methods that are in use today.
Figure 1
Basic Diagram of a Float Operated Low-Water Fuel Cut-Off
The three-wire (double-pole) switch (Fig. 2(a)) is used as a cut-off switch for the
fuel valve and as an alarm switch; the two-wire (single-pole) switch (Fig. 2(b))
controls the operation of either the feedwater pump or the feedwater control
valve.
Figure 2
Mercury Switches
2
INST 6005
Fig. 3 shows how a combined low-water fuel cut-off and feedwater control switch
controls the water level in a steam boiler.
Figure 3
Control of Water Levels in a Steam Boiler
At level A, the highest operating level of the water in the boiler, the feedwater
supply switch opens, stopping the power supply to either feedwater pump or
control valve, thus stopping feedwater supply to the boiler. When the water level
drops to level B, the control switch closes again and feedwater supply resumes.
Should the pump fail to start or should the water supply be insufficient to
maintain the level, the water level in the boiler would continue to drop. When it
reaches level C, the cut-off switch opens and cuts off the power to the fuel valve.
At the same time the alarm circuit is energized.
The boiler cannot be started up again unless the water is raised above level C, the
operating level of the cut-off switch.
The cut-off switch should open when the level in the glass (level C) shows at least
20 mm (approx. 3/4") of water. Levels B and A, the cut-in and cut-out levels of
the feedwater control switch, may vary depending on type and size of boiler used.
3
INST 6005
A basic sketch of a small steam boiler plant is shown in Fig. 4. The boiler supplies
steam to the various parts of the heating system where the steam gives up its heat
in the radiators, convectors, etc., and condenses. This steam condensate returns
from the heating system to the boiler room through the condensate return main
and collects in the condensate receiver from where it is pumped into the boiler by
the boiler feed pump. The diagram shows the combination low-water fuel cut-off
and pump control mounted at the right side of the boiler. The boiler is also
equipped with a second low-water cut-off device, which is required by code.
Figure 4
Basic Steam Plant
4
INST 6005
Figure 5
Float-Operated Low-Water Cut-Off with Feeder Valve
Since control of the feedwater supply is now the primary function of the cut-off
device, a second cut-off is again required by code.
5
INST 6005
BH1_fig6.gif
Figure 6
Low-Water Cut-Off Operating Electric Valve in Secondary Feedwater Supply
After the water level is raised, the switch breaks the circuit and the valve is closed
again. Should the supply of make-up water fail or be insufficient, the low-water
cut-off will stop the burner before the level drops to a dangerous point. A second
low-water cut-off device would also be required on this boiler.
Note that the auxiliary water supply should not open until the water level has
dropped well below the cut-in level of the feedwater pump. This allows for ample
space for fluctuations in water level without the necessity of feeding any make-up
water. The feeder valve should merely act as a stand-by for low water conditions.
BH1_fig7.gif
Figure 7
Feeder Valve On Secondary Water Supply Operated by Low-Water Cut-Off
FEEDWATER SUPPLY
In a steam heating system the boiler supplies the steam to the heating system. In
this system consisting of various pieces of heat exchange equipment (radiators,
convectors, unit heaters etc.) connected by supply and return piping, the steam
gives up its heat and condenses back to water forming what is commonly called
steam condensate. This condensate is then returned to the boiler to be converted
to steam again.
In this module, whenever mention is made of feedwater supplied to a lowpressure steam heating boiler, it should be understood that most, if not all, of the
feedwater is actually steam condensate returned from the heating system.
7
INST 6005
The condensate is fed into the boiler through a return or Hartford loop, Fig. 8. If
the condensate return line would be directly connected to the feed connection in
the lower part of the boiler, the possibility would exist that the steam pressure
would force the boiler water back into the return line should the check valve fail
to close, and the water level in the boiler could drop below the safe minimum
level.
Figure 8
Hartford or Return Loop
The Hartford loop prevents this. The return line is connected to the loop at the
height of the lowest safe water level. At that level the heights of the water in the
boiler and in the loop will be equal and the steam pressure above the water in
boiler and loop will be the same. Since water height and steam pressure in both
boiler and loop are balanced, no water can be forced out of the boiler and
sufficient water will cover the heating surfaces to prevent overheating.
8
INST 6005
BH1_fig9.gif
Figure 9
Feedwater Control by Float Switch in Condensate Tank
The system in Fig. 9 is not suitable for systems where the condensate return is not
steady. Heating systems with long horizontal condensate return lines, such as
those found in large shopping centres and warehouses, or systems with irregular
steam consumption have a tendency to accumulate large amounts of condensate,
since the steam supply is faster than the condensate return. This would cause a
low level in the boiler, the feeder valve would open up, and extra water would
flow into the boiler to make up for the condensate hung up in the system. But
when the condensate returns to the receiver, the pump will feed it all into the
boiler, since the float switch maintains a fairly steady level in the receiver. As a
result of the extra water fed into the boiler previously, the level in the boiler will
now become excessively high.
It should be noted that the boiler in Fig. 9 is also fitted with a Hartford loop. This
loop is also used on boilers equipped with non-positive displacement feedpumps,
such as a centrifugal pump, since failure of the check valve in the feed line could
allow the steam pressure to force the boiler water back into the tank via the pump,
creating a low water condition.
Fig. 10 shows a feed system commonly used to maintain a steady boiler water
level in spite of an irregular condensate return. The boiler is equipped with a
combination pump control low-water cut-off.
9
INST 6005
BH1_fig10.gif
Figure 10
Feedwater Control by Float Switch on Boiler
The float will follow the water level in the boiler and start and stop the feed pump
as required. This will assure a steady water level within close limits. Fluctuations
in the condensate return will only affect the level in the condensate receiver. A
make-up feeder is installed on the receiver to ensure that sufficient water is
available at all times to maintain the boiler water level and to prevent the pump
from running dry.
Although this system is quite reliable, there is still the possibility of developing a
low water condition in the boiler due to failure of the pump or its power supply
resulting in a shut-down by the low-water cut-off. This can be prevented by
installation of a secondary means of water supply controlled by a float-operated or
electrically controlled feeder valve as discussed earlier in this module.
In multiple boiler heating plants, the control of the water level in each boiler is
independent from the other boilers but the feedwater is usually supplied through a
common feedline by a single pump (Fig. 11). When one of the boilers requires
water, its float operated control switch closes, energizing the motorized valve in
the feedwater branch line to the boiler. As soon as this valve reaches the open
position, it closes an attached pump starting switch, and the condensate starts
flowing from the receiver to the boiler. When the water in the boiler reaches its
maximum level, the pump control switch opens the circuit, the motorized valve
closes and the pump stops.
10
INST 6005
Figure 11
Multiple Boiler System with Feedpump and Motorized Valves
If any of the other boilers requires feedwater while the pump is already feeding
into one boiler, its pump control switch will energize the motorized feedwater
valve on that boiler and the pump will then supply both boilers. Since the second
motorized valve also closes an attached pump starting switch, it will be the valve
closing last that will shut the feedwater pump down.
FEEDWATER CONNECTIONS
Condensate Receiver Tank Level Controllers
An important requirement of a well-designed boiler feedwater system is a
condensate receiver of adequate size together with a reliable method of make-up
water supply to the receiver. An undersized receiver may cause loss of
condensate, while an unreliable make-up feeder could result in boiler shut-downs
due to low water conditions if the boilers are not equipped with feeder valves.
As a general rule, the size of the receiver should be sufficient to hold a volume of
condensate equivalent to the water evaporated by the boiler in a 1/3 to 1/2 hour
period at normal load. The smaller size receiver may be used when the condensate
returns easily as in heating systems used in high-rise buildings. In systems
extended over a large area (factories, warehouses, etc.), condensate return will be
lengthy and the larger size tank should be used.
The make-up valve should have sufficient capacity to supply the water required at
the normal firing rate of the boiler. If a make-up valve of smaller capacity is used,
the valve is commonly installed in the upper part of the receiver, leaving a small
volume available for accumulation of condensate. Enough water will be stored in
the receiver to supply the feed to the pump during its operating cycle.
11
INST 6005
Figure 12
Receiver with Internal Float Make-Up Valve
An externally mounted float controller feeder valve is preferred on most
installations (Fig. 13). The float chamber is attached to the receiver by equalizing
lines which dampen the level fluctuations in the chamber resulting in a smooth
flow of make-up water.
Figure 13
Receiver with External Float Make-Up Valve
12
INST 6005
A large capacity receiver serving a multiple boiler plant requires a higher volume
of make-up water and thus a larger size feeder valve. The float controlled feeder
valve, as used in Fig. 13, serves then as a pilot valve actuating a high capacity
diaphragm valve in a make-up water line, as shown in Fig. 14.
Figure 14
Receiver with Float-Controlled Hydraulically Operated Make-Up Valve
City water is supplied on top of the diaphragm of the make-up valve and to the
float controlled valve through a small diameter control line which has a needle
valve to control the water flow. When the level in the receiver is normal and no
make-up is required, the float control valve is closed. The full pressure of the city
water will act on the diaphragm of the make-up valve keeping it closed. When the
level drops slightly below normal, the float control valve will open slightly,
bleeding some of the water out of the control line. With a restricted flow of water
through the needle valve, the bleed-off will cause the pressure in the control line
to drop which reduces the force on the diaphragm, allowing the make-up valve to
open slightly.
The lower the level in the receiver drops below normal, the more water the
control valve will bleed out of the control line and the lower the pressure in this
line will drop. This, in turn, allows the make-up valve to open more.
Fig. 15 shows an electric float control actuating a motorized valve in the make-up
water line to the receiver. This control is modulating, which means that it opens
up the make-up valve in proportion to the drop in water level in the receiver.
13
INST 6005
Figure 15
Receiver with Float-Controlled Electrically Operated Make-Up Valve
Some condensate receivers are equipped with a low-water cut-off switch. Should
the level in the receiver drop so low that the pump could lose suction, the switch
will cut off the power supply to the motor preventing damage to the pump.