ABB REUSE 090410 P0005 C02

exida Certification S.A. hereby confirms that the software library

OGP REUSE Solutions for AC 800M HI


used with the ABB AC 800M High Integrity Controller

ABB AS ATPA/AKU
Oslo, Norway

Has been assessed per the relevant requirements of

IEC 61508 Parts 1 - 7, and


IEC 61511Chapters 12.4.5 and 12.4.6
and meets the requirements providing a level of integrity to

Systematic Integrity : SIL 2 / SIL 3 Capable


Safety function
The OGP REUSE Solutions for AC 800M HI provides non-SIL, SIL 2 and SIL 3 compliant
application building blocks (Function Block Types and Control Module Types)
intended for Fire & Gas (F&G), Process Shutdown (PSD) and Emergency Shutdown
(ESD) application building, using the AC 800M HI Controller.
Application restrictions
The application building blocks must be properly integrated, configured and
validated in a Safety Application per the requirements in the Safety Manual.

Assessor

Certifying Assessor

Date: 11 Mar 2010

exida Certification SA, Nyon, Switzerland


Page 1 (2)

C E R T I F I C A T E / C E R T I F I C A T / Z E R T I F I K A T /

C E R T I F I C AT E

SIL 2 / SIL 3 Capability


The application building blocks marked SIL 1-2 and SIL 3 has met manufacturer design
process requirements of Safety Integrity Level (SIL) 2 and 3 respectively. These are intended
to achieve sufficient integrity against systematic errors of design by the manufacturer. A
safety application utilizing these application building blocks must not claim a Safety Integrity
Level higher than the statement.

SIL Verification:
The Safety Integrity Level (SIL) of Safety Functions provided by Safety Instrumented Systems
(SIS) utilizing application building blocks from OGP REUSE Solution for AC 800M HI must
be verified by an assessment of the safety application software and by a calculation of
PFH / PFDAVG considering the architecture, proof test interval, proof test effectiveness, any
automatic diagnostics, average repair time and the specific failure rates of all components
included in the SIS. Each part must be checked to assure compliance with minimum
hardware fault tolerance (HFT) requirements.

The following documents are mandantory part of this certificate:


Release
REUSE REV 7.1-1

REUSE REV 7.2-0

REUSE REV 7.4-0

REUSE REV 7.5-0

Document
ABB 0806-39-C R003 V1 R1 Assessment Report
Safety Manual AC800M REV7.1-1 version B
ABB 0904-10-C R007 V1 R1 Assessment Report
Safety Manual for REUSE AC 800M HI REV7.2-0 version ABB 0904-10-C R007 V1 R1 Assessment Report
Safety Manual for REUSE AC 800M HI REV7.4-0 SV5.0 SP2B version ABB 0904-10-C R007 V1 R1 Assessment Report
Safety Manual for REUSE AC 800M HI REV7.5-0 SV5.0 SP2C version -

The holder of this certificate


may use this mark.

exida Certification SA, Nyon, Switzerland


info@exidacert.ch
Page 2 (2)

C E R T I F I C A T E / C E R T I F I C A T / Z E R T I F I K A T /

Systematic Integrity: SIL 2 / SIL 3 Capable