Anda di halaman 1dari 6

VAF & kWh

Meters

Quick and easy


installation

Meter for all electrical


panels

Power energy
monitoring

01

VAF & kWh Meters


Functions and characteristics

The DM6XXX & EM1XXX series are available in four different


versions, each to best fit specific applications

DM 6XXX / EM 1XXX Series

DM6100

VAF, PF meter with 1.0% accuracy

DM6100

VAF, PF meter with 0.5% accuracy

DM6300

VAF, PF meter with port & 1.0% accuracy

DM6300

VAF, PF meter with port & 0.5% accuracy

EM1000

Energy meter with pulse output & 1.0% accuracy

EM1000

Energy meter with pulse output & 0.5% accuracy

EM1200

Energy meter with RS485 port & 1.0% accuracy

EM1200

Energy meter with RS485 port & 0.5% accurcay

Applications
Energy billing
Load balancing and optimization
Electrical load monitoring
Gensets, test benches, and laboratories

Backlit LCD display

Smart line indicators

Main characteristics
Fast in line view:

Elegant single row, backlit LCD display


Three parameters, name and value at one glance
Direct reading of primary values - no multiplication factor
Kilo, mega and giga indications with autoscaling capability
User selectable default display page and lock
High Resolution

RMS values: Three digit


Integrated values: Energy values, nine digit (2 digits after decimal)
Intuitive function keys

Four smart keys for easy navigation, display pages expand


vertically, much like the directory or explorer tree displayed on
any computer
Auto-scrolling

Allows you to monitor a group of parameters sequentially without


any manual key operation.
Rear view

Secure settings

Unique password protection for the set-up parameters.


Smart line indicators

Helps to check the presence of input voltage (healthy phase)


Universal aux supply

The ConzervTM DM6XXX & EM1XXX series meter offers all


the basic measurement capabilities required to monitor an
electrical installation in 96 x 96 mm units
Characterized by their rugged construction, compact size,
and low installation costs, these state-of-the-art meters are
ideal for control panels, motor control centers and genset
panels

Wide aux range 44-277V ac/dc


Communicaton

Optional RS 485 communication port with Modbus RTU. Can


be integrated with various Schneider SCADA softwares (IONTM
Enterprise, Power LogicTM SCADA, VijeoTM Citect and Vista)
and also third party SCADA / BMS for Energy & Building
management studies

02

VAF & kWh Meters


Functions and characteristics

Selection guide

Selection Guide

DM6100 / DM6300

EM1000 / EM1200

Class 1.0/ 0.5

Class 1.0/ 0.5

General
Use on LV and HV systems
Accurancy

Instantaneous RMS values


Voltage - LL & LN

VLL V12 V23 V31 VLN V1 V2 V3

Line current

A A1 A2 A3

Frequency

Power factor

PF PF1 PF2 PF3

Active power (per


phase and total)*

W W1 W2 W3

Active energy*

Wh

Run hours

Run.h

On hours

On.h

Interupts count

INTR

Active energy

Wh

Run hours

Run.h

On hours

On.h

Interupts count

INTR

Integrated values

Old integ values

Communication
(EM1000)

Pulse output
RS 485 (Modbus
protocol)

(DM 6300)

*Apparent / Reactive power & energy parameters are optional

Part Numbers
VAF meter

Part number

DM6100 Class 1.0 accuracy

30002567

DM6100 Class 0.5 accuracy

30002569

DM6300 Class 1.0 accuracy with RS485

30002566

DM6300 Class 0.5 accuracy with RS485

30002570

kWh meter
EM1000 Class 1.0 accuracy with POP

30002568

EM1000 Class 0.5 accuracy with POP

30002571

EM1200 Class 1.0 accuracy with RS 485

30002565

EM1200 Class 0.5 accuracy with RS 485

30002572

1. Remove mounting clamps from the digital meter.


2. Gently slide the digital meter through the cut-out.
3. Put the mounting clamps back in the digital meter
and tighten the mounting clamp screws.

(EM1200)

03

VAF & kWh Meters


Functions and characteristics

Electrical characteristics
True rms

Type of measurement
Voltage

+ 1.0% of reading for DM6XXX Cl 1.0 meter


+ 0.5% of reading for DM6XXX Cl 0.5 meter

Current

+ 1.0% of reading for DM6XXX Cl 1.0 meter


+ 0.5% of reading for DM6XXX Cl 0.5 meter

Power factor

+1.0% of reading for DM6XXX & EM1XXX Cl 1.0 meter


+0.5% of reading for DM6XXX & EM1XXX Cl 0.5 meter

Power

Active

+1.0% of reading for EM1XXX Cl 1.0 meter


+0.5% of reading for EM1XXX Cl 0.5 meter

Energy

Active

Class 1.0 as per IEC 62052-11 and 62053-21 for


EM1XXX Cl 1.0 meter
Class 0.5S as per IEC 62052-11 and 62053-22
for EM1XXX Cl 0.5 meter

Measurement
accuracy *

Data update rate


Input-voltage
Inputs
characteristics Measured voltage
Permisible overload

480VLL with full accuracy, 750VLL max

Burden

0.2 VA per phase max


45 to 65 Hz

Frequency
Input-current

CT ratings

Primary

1 A to 99.0 kA

Secondary

1A / 5 A

Impedance

50 mA to 6A
5A: 6A continuous
1A: 1.2 A continuous
< 0.1 ohm

Burden

0.2 VA per phase max

Measurement range
Permissible overload

DM 6XXX / EM 1XXX series meter panel cut-out


Auxiliary
supply
(control power)
Comm.

One second
V1, V2, V3, VN
80 to 480 VAC LL without PTs
Up to 999 kV with external PTs

44 to 277 Vac/dc
Burden

3 VA max

Pulse output ( EM 1000 )

24Vdc, Pulse width programmable from 50 to 500ms

RS 485

2 terminals, Modubus RTU, baudrate up to 19200 bps

Mechanical characteristics
Weight

0.500 kg (shipping), 0.400 kg (unpacked)

IP degree of protection

Front: IP 51; Rear: IP 40

Dimensions

Bezel: 96 x 96 mm
Depth: 80 mm behind bezel
Panel cutout: 92 x 92 mm

Environmental characteristics
Operating temperature

-10 to +60 C (14 to 140 F)

Storage temperature

-25 to +70 C (-13 to 158 F)

Humidity

5 to 95 % RH non-condensing

Altitude

2000 m

Measurement category

III

Pollution degree

Protection class

Electromagnetic compatibility
Electrostatic discharge

15 kV Air discharge, 8 kV contact discharge


IEC 61000-4-2

Fast transient

4 kV IEC 61000-4-4

Immunity to surge waves

4 kV IEC 61000-4-5

Impulse voltage

6 kV, 1.2/50 second


IEC 60060
CISPR22

Conducted and radiated emissions

Safety and standards


Construction

Self extinguishable V0 plastics;


Double insulation at user accessible area

* Refer user manual for more detials on accuracy

04

VAF & kWh Meters


Functions and characteristics

3-phase 4-wire star/wye connection

2-phase 3-wire connection

RS 485 communication
(DM6300/EM1200)
POP(EM1000)

RS 485 communication
(DM6300/EM1200)
POP(EM1000)

3-phase 3-wire delta connection

RS 485 communication
(DM6300/EM1200)
POP(EM1000)

3-phase 3-wire open delta connection

RS 485 communication
(DM6300/EM1200)
POP(EM1000)

Single phase connection

RS 485 communication
(DM6300/EM1200)
POP(EM1000)

Schneider Electric India Pvt Ltd


9th Floor, DLF Building No. 10,
Tower C, DLF Cyber City, Phase II
Gurgaon - 122 002, Haryana, India
Phone: +91 124 3940 400
Fax:
+91 124 4222 036
Document Number 998-4564_IN

Customer Care Number (toll free): 1800 180 1707 1800 103 0011
http://www.schneider-electric.com
This document has been
printed on recycled paper

May 2011

2011 Schneider Electric. All rights All Rights Reserved. Schneider Electric, ION, PowerLogic, Vijeo, Conzerv, and Make the most of your energy
are trademarks owned by Schneider Electric Industries SAS or its affiliated companies.

Make the most of your energySM

Anda mungkin juga menyukai