NOTES

GENERAL
All dimensions are in mm unless otherwise specified.

TO POWER FACTOR CORRECTION UNIT

Drawing are not to scalled. only figured dimensions to be used


SAUNA KPLC METER
KPLC CUT OUTS

100 Ampere Sauna ConsumerUnit

Single pole 10 Amperes Reception & Sauna Lighting Sub - circuit

30 Amperes power Socket outlets sub circuit

10 Amperes single pole washroom lighting sub circuit

The contractor must check and verify all dimensions before


commencement of any work. Any discrepancies to be clarified
with the Project Architect.

10 Amperes single pole reception & sauna lighting sub sircuit

30 Amperes salon power socket outlet sub circuit

CONSTRUCTION

3 Phase 100 Amperes salon ,botique & candy shop Distribution Board
SALON & BOTIQUE KPLC METER
10 Amperes single pole candy shop lighting sub circuit
KPLC CUT OUTS

30 Amperes candy shop power socket sub circuit

10 Amperes single pole Botique lighting sub circuit

All slab at ground level to be cast over 1000 guage polythene


sheet on 50mm thick murram blinding on hardcore.

Power Factor
Correction Unit - PFCU
30 Amperes Botique power socket outlet sub circuit
10 Amperes single pole washroom lighting sub circuit
3 Phase 100 Amperes Banking Hall Distribution Board
BANKING HALL KPLC METER
10Amps Single pole Banking hall Lighting sub circuit

Ground Floor

Ground Floor sub-board

KPLC CUT OUTS

200AMCCB

200A TP MCCB

PARKING & DRIVE WAY KPLC METER


100Ampere Parking lot & drive way consumer unit
10Amps single pole corridor Lighting sub circuit
KPLC CUT OUTS

CIVIL

30 Amperes Banking Hall power Socket outlets

10 Amperes single Pole washroom lighting sub circuit

All soil under slab around and under foundation to be treated


for termite control.

30 Amperes corridor power Socket outlets

10 Amperes single pole washroom lighting sub circuit


10Amperes single pole Lounge Lighting sub circuit

All soil on cut embararkment to be stablized.The slope not to


exceed 45 degree.

30 Amperes Lounge Socket outlets

10Amperes single pole kitchen Lighting sub circuit

STRUCTURAL

30 Amperes kitchen socket Outlets

30 Amperes cooker socket outlet


HOUSE KPLC METER
KPLC CUT OUTS

100 Ampere House ConsumerUnit


10Amperes single pole Bedroom 1 Lighting sub circuit

All black cotton soil to be removed from all buildings and paved
surfaces

30 Amperes Bedroom 1 socket outlet

10Amperes single pole Bedroom 2 Lighting sub circuit

For all R.C work,refer to stuctural Engineer's details.

30 Amperes Bedroom 2 socket outlet

10Amperes single pole Bedroom 3 Lighting sub circuit

Depth of foundation to be detemined on site to S.E's aproval

30 Amperes Bedroom 3 socket outlet

10Amperes single pole Washroom Lighting sub circuit

KPLC METERS
KPLC CUT OUTS

10Amps Sp Gym/Aerobics Lighting sub circuit


Gym / Aerobics 6-way3-Phase Distribution Board

All walls to be reinforced with loop iron at every


every alternate course.

60Amps 3 phase Gym/Aerobics Socket outlets

MECHANICAL
Spare

All adjacent R.C. work and masonry walls to be tied with loop iron
Shunt Trip or Firemans switch

KPLC METERS
KPLC CUT OUTS

Restaurant 12-way 3-Phase Distribution


Board

10Amps Sp Restaurant Lighting sub circuit


40Amps 3 phase Restaurant Socket outlets

10Amps Sp Restaurant Washrooms Lighting sub circuit

ST / FS

All plumbing and drainage to comply with relevant local authority


at every alternate course.

10Amps Sp Office Lighting sub circuit

KPLC Metering CT chamber


30Amps single phase office Socket outlets

1250 Amperes Mains MCCB


Current Transformer
Tariff Meter
KPLC CUTOUT FUSES

PFC CT

10Amps Sp Cashiers Lighting sub circuit

1250A TPN MCCB

Incoming KPLC service line


fromTransformer

200A TP MCCB

First Floor

First Floor sub-board

SVP denotes soil vent pipe to be provided at the head of the


drainage system

30Amps single phase Cashiers Socket outlets


200AMCCB
10Amps Sp Kitchen Lighting sub circuit

CT

30Amps single phase Kitchen Socket outlets

Drains pass beneath buildings & driveways to be encased in


150mm concrete surround.

40Amps single phase Kitchen Cooker Socket outlets


Power Factor Correction Unit

10Amps Sp Store & Corridor lighting sub circuit

CT

Mechanical Interlock

The storm drain pipes to comply with BS 556 specification.

Banking Hall 4-ways 3-phase Distribution Board Spare


1250A TPN Main MCCB

KPLC METERS
KPLC CUT OUTS

10Amps Sp Banking Hall lighting sub circuit

Digital Multimeter

30Amps single phase Banking Socket outlets

Typical Supermarket 8-way 3-phase Distribution Board


KPLC METERS
KPLC CUT OUTS

1250A TPN MCCB

1250 Amperes Generator MCCB

R
L1

Y
L2

B
L3

10Amps Sp Supermarket lighting sub circuit

30Amps single phase Supermarket Socket outlets

Typical First Floor Circuit Distribution Plan

500 KvA,
415volts,
50 hZ
Standby Generator

Banking Hall 4-ways 3-phase Distribution Board


KPLC METERS
10Amps Sp Banking Hall lighting sub circuit

30Amps single phase Banking Socket outlets

Second Floor sub - board


200A TP MCCB

Second Floor
200AMCCB
All Offices or Shops 6-ways 3-phase Distribution Board

All underground foul and waste drain pipes shall be uPVC to


comply with BS 5255.
All inspection chambers covers and framing shall be cast iron.
Minimum slope in the drains pipes to be 1 in 100
No chases will be allowed for pipes. Sleeves will be allowed with
written approval of structural Eng's. No cutting of concrete without
All testing of pipes must be completed before plastering.
express approval of the Architect or structural Eng.

KPLC METERS
10Amps Sp Office or Shop lighting sub circuit

30Amps single phase Office /Shop Socket outlets

All mechnical works must be co-odinated with electrical and any


conflict must be clarified before work begin.

10Amps Sp Restaurant Lighting sub circuit


40Amps 3 phase Restaurant Socket outlets

PV denotes permanent ventilation

10Amps Sp Restaurant Washrooms Lighting sub circuit

10Amps Sp Office Lighting sub circuit

KPLC METERS
KPLC CUT OUTS

Restaurant 12-way 3-Phase Distribution


Board

ELECTRICALS

30Amps single phase office Socket outlets

10Amps Sp Cashiers Lighting sub circuit

All conduits must be laid before plastering

30Amps single phase Cashiers Socket outlets

10Amps Sp Kitchen Lighting sub circuit

30Amps single phase Kitchen Socket outlets

40Amps single phase Kitchen Cooker Socket outlets

Third Floor

200A TP MCCB

Third Floor sub-board

10Amps Sp Store & Corridor lighting sub circuit

200AMCCB

REVISIONS, ADDITIONS & ALTERATIONS

Spare
Offices 6-ways 1-phase Distribution Board
KPLC METERS
KPLC CUT OUTS

M
KPLC METERS

KPLC CUT OUTS

10Amps Sp office lighting sub circuit

NO. DATE

DESCRIPTION

BY

30Amps single phase Office Socket outlets

Typical Conference rooms 8-way 1-phase Distribution


Board
10Amps Sp Conference rooms lighting sub circuit

30Amps single phase Conference rooms Socket outlets

Typical Swimming pool & drive way ligting 6 ways Single phase 100 Amperes Consumer Unit

Swimming pool & parking sub- board


200A TP MCCB

Swimming Pool
200AMCCB

20Amps single phase Swimming pool Lighting sub-circuit

ARCHITECTS

Archismart creations ltd.


P.O.Box 101665-00101,
Nairobi

10Amps single phase Parking & Drive way Lighting sub-circuit

200A TP MCCB

Spare for future additions

architects, interior design, project managers

200A TP MCCB

200A TP MCCB

Spare for future additions

Spare for future additions

Spare for future additions

client

PERO LIMITED
PO BOX 60 - 00260
KISERIAN.

200A TP MCCB

project

PROPOSED ASHEY BUSINESS CENTRE


ON PLOT NO. LRs NGONG/ NGONG/ 11176 11180 KISERIAN, KAJIADO.

complete wiring circuit typical on each floor

project title

first floor
SCALE

DRAWN

1:100

JOB No.

2016/07

CHECKED

PMK

DRAWING NO

02

DATE
July. 2016
REVISION