SL No
Drawing/
Document Comment/ Recommendation (Aon Review #1)
Number
General:
N/A
M-803
M-803
Provide means of supervision for valves "chain and padlock" for all
isolation valves (OS&Y) in pump room
M-501
Fire pump room has small dimensions which will not be capable to
provide operational and maintenance space in the room.
M-501
M-501
M-501
A detailed plan is required for review for the fire pump room
including the piping system and diesel tank.
Sprinkler &
Standpipe
Systems
9
10
Relocate the landing valves to the main landing of the exit stairs
All Drawings and provide details for hose connection to match fire department
hoses.
General
Provide details for the fire hose cabinet and fire extinguishers
inside the cabinets.
11
12
All Drawings
13
M- 501
14
M-509
Provide sprinklers at the top of the stairs and under the first
accessible landing of each staircase
15
M-509
16
General
17
M-509
18
General
Special
suppression
systems
19
20
21
22
M-502
Provide additional design details for the clean agent systems and
CO2 systems. Cylinders capacity, hydraulic calc., nozzles
selection, piping distribution, room dimensions and if there is false
floor or false ceiling, control panel location, detection devices,
manual release station, maintenance switches.
M-502
General
General
23
M-510
24
General
Prepared
by
Checked by
Rev No.
Code Reference
AME Response
NOTED
General
General
NFPA 12 [2011]
section4.6.4.3 & NFPA
2001 [2012] section 4.1.3
Ok, done.
N/A
General
ML
PK
001