5.6 All current carrying parts viz bus bars, terminals, washers and clips
shall be of copper, aluminium, brass or equally non-rusting materials,
properly tinned at joints.
5.7 All cables shall be provided with soldered or approved lugs or crimped
joints or any other approved means for connection.
5.8 Outgoing circuits shall be clearly marked in English and vernacular
indicating the department or place or item controlled.
5.9 All circuits shall preferably be arranged in symmetry.
5.10Where a distribution board or group of distribution boards are erected
in a room of a building isolated from the source of supply, or at a
distance from it, adequate means of control and isolation shall be
provided both near the board and at the origin of supply.
5.11Each outgoing circuit from a switchboard (excepting fuse distribution
boards) shall be separately controlled by a suitable automatic circuit
breaker or linked switch and cutouts.
NOTE: Fuses shall be throughout of HRC type irrespective of current
rating of the circuit.
5.12Detachable inspection covers shall preferably be provided to examine
connections.
5.13Woodwork shall not be permitted for mounting of, or construction of,
framework of any ironclad switch, control or distribution gear.
5.14Motors shall not be connected to lighting distribution boards.
5.15A maximum of Four exhaust fans and similar appliances, may be
installed on a circuit; provided, the rated output of each motor does
not exceed 600 watts.
5.16Temporary power wiring shall not be permitted.
5.17Looping of conductors and T-joints in power wiring shall not be
permitted.
5.18Overhead bus bar trunking system shall comply with the following: i)
ii)
iii)