Instruction
May 2010
Contents
Figures..................................................................................................................................... v
Tables..................................................................................................................................... vi
1. Introduction ......................................................................................................................
General Description ..................................................................................................................
Reference Documents ...............................................................................................................
Transmitter Identification .........................................................................................................
1
1
1
3
15
15
15
17
18
18
18
20
23
23
23
24
24
27
28
28
29
29
29
30
30
33
34
35
35
iii
Contents
37
38
39
39
39
39
40
4. Calibration ......................................................................................................................
General Calibration Notes ......................................................................................................
Calibration Setup ....................................................................................................................
Setup of Electronic Equipment ...........................................................................................
Field Calibration Setup ......................................................................................................
Bench Calibration Setup ....................................................................................................
Calibration Using a PC20 .......................................................................................................
Calibration Using a PC50 .......................................................................................................
Calibration Using a HART Communicator ............................................................................
Calibration Using the Optional Local Display ........................................................................
Zero Adjustment Using External Zero Button ....................................................................
Error Messages ......................................................................................................................
41
41
43
44
44
45
46
46
46
46
49
51
5. Configuration..................................................................................................................
Configurable Parameters .........................................................................................................
Configuration Using a PC20 ...................................................................................................
Configuration Using a PC50 ...................................................................................................
Configuration Using a HART Communicator ........................................................................
Configuration Using the Optional Local Display ....................................................................
Character Lists ........................................................................................................................
Error Messages ........................................................................................................................
53
53
54
54
54
54
64
65
6. Maintenance....................................................................................................................
Error Messages ........................................................................................................................
Parts Replacement ...................................................................................................................
Replacing the Terminal Block Assembly .............................................................................
Replacing the Electronics Module Assembly .......................................................................
Removing and Reinstalling a Housing Assembly ................................................................
Adding the Optional Display .............................................................................................
Replacing the Sensor Assembly ...........................................................................................
Rotating Process Covers for Venting .......................................................................................
67
67
67
67
68
69
70
70
72
Index .................................................................................................................................... 75
iv
Figures
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
3
4
7
16
17
18
19
19
20
21
21
22
23
23
23
24
24
24
26
27
28
29
30
30
31
33
33
34
37
38
40
44
45
46
48
49
57
58
59
69
71
72
72
Tables
1
2
3
4
5
6
7
8
9
10
11
1
9
12
40
47
51
53
55
64
64
65
vi
1. Introduction
General Description
The IDP10-T intelligent differential pressure transmitters measure the difference between two
pressures applied to opposite sides of a silicon strain gauge microsensor within the sensor
assembly. This microsensor converts differential pressure to a change in resistance. The resistance
change is then converted to a 4 to 20 mA or digital signal proportional to differential pressure or
to the square root of differential pressure. This measurement signal is transmitted to remote
receivers over the same two wires that supply power to the transmitter electronics. These wires
also carry two-way data signals between the transmitter and remote communication devices.
The transmitter allows direct analog connection to common receivers while still providing full
Intelligent Transmitter Digital Communications using a HART Communicator.
The transmitter is often used for measuring fluid flow rates across a primary device such as an
orifice plate, but can also be used for other types of differential pressure measurements such as
liquid level, interface level, or density measurements. The IDP10 can also be supplied with direct
connected or remote pressure seals to isolate the measuring element from corrosive or viscous
fluids.
For more detailed information on the principle of operation of the transmitter, refer to document
TI 037-096, available from Invensys.
Reference Documents
Table 1. Reference Documents
Document
Description
Dimensional Prints
DP 020-342
Dimensional Print PSFLT Pressure Seals
DP 020-343
Dimensional Print PSFPS and PSFES Pressure Seals
DP 020-345
Dimensional Print PSFAR Pressure Seals
DP 020-347
Dimensional Print PSTAR Pressure Seals
DP 020-349
Dimensional Print PSISR Pressure Seals
DP 020-351
Dimensional Print PSSCR Pressure Seals
DP 020-353
Dimensional Print PSSCT Pressure Seals
DP 020-354
Dimensional Print PSSSR Pressure Seals
DP 020-355
Dimensional Print PSSST Pressure Seals
DP 020-446
Dimensional Print IDP10, IDP25, and IDP50 Differential Pressure Transmitters
DP 022-335
Dimensional Print Model CO Compact Orifice
Parts Lists
PL 006-172
Parts List Model CO Compact Orifice
1. Introduction
Description
Parts List IDP10 Differential Pressure Transmitter
1. Introduction
Transmitter Identification
See Figure 1 for transmitter data plate contents. For a complete explanation of the Model
Number code, see the parts list. The firmware version is identified on the top line of the display
when VIEW DB (View Database) is selected in the top level structure (see Figure 2).
STYLE
MODEL CODE
SERIAL NUMBER
CALIBRATED RANGE
SUPPLY VOLTAGE
CUSTOMER TAG
MODEL
REFERENCE
AUX. SPEC.
SUPPLY
CUST. TAG
CAL. RANGE
ORIGIN
MWP
ST
1. Introduction
(measurement M1 or M2)
E
(measurement M2 or M1)
N
N
RERANGE
N
E
CONFIG
N
CALIB
N
VIEW DB
ON-LINE MODE
N
N
E
TST DSP
CANCEL
ON-LINE MODE
N
E
E
N
N = NEXT BUTTON
E = ENTER BUTTON
1. Introduction
Standard Specifications
Operative Limits
Influence
Operative Limits
D
E
Span Limits
P
0.12 and 7.5 kPa
0.5 and 30 inH20
12 and 750 mmH20
0.87 and 50 kPa
3.5 and 200 inH20
87 and 5000 mmH20
7.0 and 210 kPa
28 and 840 inH20
2.3 and 69 ftH20
0.07 and 2.1 MPa
10 and 300 psi
23 and 690 ftH20
0.7 and 21 MPa
100 and 3000 psi
Range Limits
P (a)
-7.5 and +7.5 kPa
-30 and +30 inH20
-750 and +750 mmH20
-50 and +50 kPa
-200 and +200 inH20
-5000 and +5000 mmH20
-210 and +210 kPa
-840 and +840 inH20
-69 and +69 ftH20
-0.21 and +2.1 MPa
-30 and +300 psi
-69 and +690 ftH20
-0.21 and +21 MPa
-30 and +3000 psi
(a)Negative values of differential pressure indicate a higher pressure on the low side of the sensor.
Positive values indicate a higher pressure on the high side of the sensor.
(b)Span Limit Code A not available with pressure seals.
1. Introduction
Psi
3625
MPa
100
Psi
14500
15
2175
60
8700
20
16
10
2900
2320
1500
70
64
40
11150
9280
6000
40
5800
100
14500
NOTE
Static pressure zero shift for all calibrated spans can be eliminated by readjusting the
zero output at nominal operating static pressure.
! CAUTION
1. Exceeding the maximum overrange pressure can cause damage to the transmitter
degrading its performance.
2. The transmitter could be nonfunctional after application of the proof pressure.
Elevated Zero and Suppressed Zero
For applications requiring an elevated or suppressed zero, the maximum span and the
upper and lower range limits of the transmitter can not be exceeded.
Sensor Fill Fluid
Silicone Oil (DC 200) or Fluorinert (FC-43)
1. Introduction
-80
30
Temperature C
60
90
120
140
120
100
80
60
40
20
-25
50
100
150
200
250
Temperature F
Position effect zero shift for all calibrated spans can be eliminated by readjusting
zero output after installation.
Approximate Mass
Without Process Connectors
With Process Connectors
With Optional 316 ss Housing
With Pressure Seals
Process Connections
IDP10 transmitters are connected to the process via a 1/4 NPT thread or any one of a
number of optional process connectors.
7
1. Introduction
1. Introduction
Supply Voltage
Power supply must be capable of providing 22 mA when the transmitter is configured for
4 to 20 mA output. Ripple of up to 2 V pp (50/60/100/120 Hz) is tolerable, but
instantaneous voltage must remain within specified range.
The supply voltage and loop load must be within specified limits. This is explained in
detail in Wiring on page 29. A summary of the minimum requirements is listed in
Table 2.
Table 2. Minimum Loop Load and Supply Voltage Requirements
Minimum Resistance
Minimum Supply Voltage
HART
Communication
250
17 V
No HART
Communication
0
11.5 V
mA Output (equivalent)
Output in Percent Flow (square root) or Pressure Units (linear). Percent Display in
Linear mode on local display is also supported.
1. Introduction
Electronic Damping
Failsafe Direction
Communications Format
Communication is based upon the FSK (Frequency Shift Keying) technique. The
frequencies are superimposed on the transmitter power/signal leads.
4 to 20 mA Output
The transmitter sends its differential pressure measurement to the loop as a continuous
4 to 20 mA dc signal. It also communicates digitally with the HART Communicator at
distances up to 3000 m (10 000 ft). Communication between the remote configurator
and the transmitter does not disturb the 4 to 20 mA output signal. Other specifications
are:
Data Transmission Rate:
4 - 20 mA Update Rate:
Output when Fail Low:
Output when Fail High:
Output when Underrange
Output when Overrange
Output when Offline:
1200 Baud
30 times/second
3.60 mA
21.00 mA
3.80 mA
20.50 mA
User configurable between
4 and 20 mA
10
1. Introduction
! WARNING
To maintain IEC IP66 and NEMA Type 4X protection, the unused conduit opening
must be plugged with the metal plug provided. Use a suitable thread sealant on both
conduit connections. In addition, the threaded housing covers must be installed.
Turn covers to seat the O-ring into the housing and then continue to hand tighten
until the cover contacts the housing metal-to-metal.
NOTE
1. These transmitters have been designed to meet the electrical safety description
listed in Table 3. For detailed information or status of testing laboratory
approvals/certifications, contact Invensys.
2. Wiring restrictions required to maintain electrical certification of the transmitter
are provided in Wiring on page 29.
11
1. Introduction
Application Conditions
Electrical
Safety Design
Code
KEMA 00ATEX2019X
Temperature Class T6, T85C,
Ta = -40 to +80C
SIRA 06ATEX2055X
Temperature Class T4,Ta = -40 to
+80C
12
1. Introduction
Application Conditions
Electrical
Safety Design
Code
(a) User must permanently mark (check off in rectangular block on data plate) one type of protection only (ia and
ib, d, or n). This mark cannot be changed once it is applied.
13
EN 50281-1-1: 1998
EN 60079-15: 2004
14
1. Introduction
2. Installation
! CAUTION
To avoid damage to the transmitter sensor, do not use any impact devices, such as an
impact wrench or stamping device, on the transmitter.
NOTE
Transmitter Mounting
The IDP Series differential pressure transmitter can be supported by the process piping or
mounted to a vertical or horizontal pipe or surface using the optional mounting bracket. See
figures below. For dimensional information, refer to DP 020-446.
NOTE
1. If the transmitter is not installed in the vertical position, readjust the zero output
to eliminate the position zero effect.
2. When structure codes 78/79 are used (pvdf inserts) with the IDP10 transmitters,
the process connection must be made directly to the pvdf inserts in the high and
low side process covers.
Process Mounting
With process mounting, the transmitter mounted to and supported by the process piping.
15
2. Installation
TRADITIONAL STRUCTURE
SEE
NOTE
LP1 STRUCTURE
LP2 STRUCTURE
SEE
NOTE
16
SEE
NOTE
2. Installation
M4A MANIFOLD
MB3 MANIFOLD
17
2. Installation
ADAPTER PLATE
AND GASKETS
MT3 MANIFOLD
MC3 MANIFOLD
18
2. Installation
APPROXIMATELY 3 IN
CLEARANCE REQUIRED
FOR ACCESS TO MOUNTING
BOLTS AND VENT SCREW.
BRACKET
VERTICAL DN 50 OR 2 IN PIPE
SHOWN. ROTATE U-BOLT 90
FOR MOUNTING TO HORIZONTAL
PIPE
VERTICAL PIPE
LP2 STRUCTURE
TRADITIONAL STRUCTURE
HORIZONTAL PIPE
LP2 STRUCTURE
TRADITIONAL STRUCTURE
19
2. Installation
HOLES FOR
U-BOLT AND
SURFACE
MOUNTING
ON FOUR
SIDES OF THIS
BRACKET LEG,
BOLTS TO MOUNT
TRANSMITTER
TO BRACKET
BOLTS TO MOUNT
TRANSMITTER TO
BRACKET
HOLES TO MOUNT TRANSMITTER
TO BRACKET OR FOR SURFACE
MOUNTING ON FOUR SIDES OF
THIS BRACKET LEG
20
2. Installation
VERTICAL PIPE
HORIZONTAL PIPE
Figure 10. Mounting a Transmitter with Traditional Structure Using a Universal Bracket
Figure 11. Vertical Pipe Mounting a Transmitter with LP2 Structure Using a Universal Bracket
21
2. Installation
Figure 12. Horizontal Mounting a Transmitter with LP2 Structure Using a Universal Bracket
22
2. Installation
PROCESS
COVER
DRAIN SCREW
OPTIONAL
SIDE VENT
SHOWN
PLUG
VENT SCREW
23
2. Installation
process covers. If the transmitter is connected with a length of impulse piping, such piping should
slope up to the transmitter for gas applications and down for liquid applications.
VENT
SCREW
IN-LINE
PROCESS
CONNECTION
PROCESS
CONNECTION
VENT
SCREW
PROCESS
CONNECTION
DRAIN
SCREW
VENT &
DRAIN
SCREWS
24
2. Installation
The transmitters are shown below the level of the pressure connections at the pipe (usual
arrangement, except for gas flow without a seal liquid), and with filling tees in the lines to the
transmitter (for a seal liquid).
If the process fluid being measured must not come in contact with the transmitter, the transmitter
lines must be filled with a suitable seal liquid (see procedure in next section). In such a case, the
transmitter must be mounted below the level of the pressure connections at the pipe. With steam
flow, the lines are filled with water to protect the transmitter from the hot steam. The seal liquid
(or water) is added to the lines through the filling tees. To prevent unequal heads on the
transmitter, the tees must be at the same elevation and the transmitter must be mounted vertically
(as shown). If a seal liquid is not required, elbows can be used in place of the tees.
Tighten drain plugs and optional vent screws to 20 Nm (15 lbft). Tighten the four process
connector bolts to a torque of 61 Nm (45 lbft).
Note that the low and high pressure sides of the transmitter are identified by an L-H marking on
the side of the sensor above the warning label.
With medium viscosity seal liquids and/or long transmitter lines, larger valve sizes should be used.
NOTE
1. With a horizontal line, pressure connections at the pipe should be at the side of
the line. However, with gas flow without a seal liquid, connections should be at
top of line.
2. With a vertical line, flow should be upwards.
3. For liquid or steam flow, the transmitter should be mounted lower than the
pressure connections at the pipe.
4. For gas flow without a seal liquid, the transmitter should be mounted above the
pressure connections at the pipe; for gas flow with a seal liquid, the transmitter
should be mounted below the pressure connections.
5. Invensys recommends the use of snubbers in installations prone to high levels of
fluid pulsations.
25
2. Installation
DIRECTION OF
PRESSURE FLOW
TRANSMITTER
HIGH
PRESSURE
SIDE
FILLING TEES
26
2. Installation
PROCESS
SHUT OFF VALVES
FILLING TEES
LOW
PRESSURE
SIDE
DIRECTION OF
PRESSURE FLOW
TRANSMITTER
HIGH
PRESSURE
SIDE
PIPE OR TUBING
OPTIONAL
3-VALVE
MANIFOLD
27
2. Installation
! CAUTION
To prevent loss of seal liquid and contamination of process fluid, never open both
process shutoff valves and manifold shutoff valves if the bypass valve is open.
RETENTION CLIP
HOUSING
CUP
ANTI-ROTATION SCREW
OR RETENTION CLIP
CLIP
28
2. Installation
Cover Locks
Electronic housing cover locks, shown in Figure 22, are provided as standard with certain agency
certifications and as part of the Custody Transfer Lock and Seal option. To lock the covers,
unscrew the locking pin until approximately 6 mm (0.25 in) shows, lining up the hole in the pin
with the hole in the housing. Insert the seal wire through the two holes, slide the seal onto the
wire ends and crimp the seal
Wiring
The installation and wiring of your transmitter must conform to local code requirements.
! WARNING
ATEX requires that when the equipment is intended to be used in an explosive
atmosphere caused by the presence of combustible dust, cable entry devices and
blanking elements shall provide a degree of ingress protection of at least IP6X. They
shall be suitable for the conditions of use and correctly installed.
NOTE
29
2. Installation
EXTERNAL EARTH
(GROUND)
(+)
TRANSMITTER
SIGNAL
CONNECTIONS
()
(+)
(-)
HHT
CAL
30
2. Installation
Any combination of supply voltage and loop load resistance in the shaded area can be used. To
determine the loop load resistance (transmitter output load), add the series resistance of each
component in the loop, excluding the transmitter. The power supply must be capable of
supplying 22 mA of loop current.
1450
1400
1300
1200
V dc
LOAD (OHMS)
1100
24
30
32
1000
NOTES:
1. THE MINIMUM LOAD FOR THE HART COMMUNICATOR
IS 250 .
2. THE TRANSMITTER CAN FUNCTION WITH AN OUTPUT L
LESS THAN THE MINIMUM, PROVIDED THAT A REMOTE
CONFIGURATOR IS NOT CONNECTED TO IT. CONNECTIN
A REMOTE CONFIGURATOR WHILE OPERATING IN THIS
COULD CAUSE OUTPUT DISTURBANCES AND/OR COMM
CATION PROBLEMS.
OUTPUT LOAD,
900
800
700
600
500
MINIMUM LOAD
(SEE NOTE)
OPERATING AREA
400
300
200
100
0
0
10
20
30
11.5
40
42
SUPPLY VOLTAGE, V dc
31
2. Installation
3050 m (10,000 ft) using single pair cable and adhering to requirements of HART
physical layer implementation defined in HART Document HCF_SPEC-53. Use
CN=1 when calculating max. lengths.
NOTE
Do not run transmitter wires in same conduit as mains (ac power) wires.
3. If shielded cable is used, earth (ground) the shield at the power supply only. Do not
ground the shield at the transmitter.
4. Plug unused conduit connection with the 1/2 NPT, PG 13.5 or M20 metal plug
provided (or equivalent). To maintain specified explosionproof and dustignitionproof protection, plug must engage a minimum of five full threads for 1/2
NPT connections; seven full threads for M20 and PG 13.5 connections.
5. Connect an earth (ground) wire to the earth terminal in accordance with local
practice.
! CAUTION
If the signal circuit must be earthed (grounded), it is preferable to do so at the
negative terminal of the dc power supply. To avoid errors resulting from earth loops
or the possibility of short-circuiting groups of instruments in a loop, there should be
only one earth in a loop.
6. Connect the power supply and receiver loop wires to the + and terminal
connections.
7. Connect receivers (such as controllers, recorders, indicators) in series with power
supply and transmitter as shown in Figure 26.
8. Reinstall the cover onto the housing by rotating it clockwise to seat the O-ring into
the housing and then continue to hand tighten until the cover contacts the housing
metal-to-metal. If cover locks are present, lock the cover per the procedure described
in Cover Locks on page 29.
9. If wiring additional transmitters to the same power supply, repeat Steps 1 through 8
for each additional transmitter. The setup with multiple transmitters connected to a
single power supply is shown in Figure 27.
10. A HART Communicator or PC-Based Configurator can be connected in the loop
between the transmitter and the power supply as shown in Figures 26 and 27. Note
that a minimum of 250 must separate the power supply from the HART
Communicator or PC-Based Configurator.
32
2. Installation
NON-HAZARDOUS
LOCATION
INTRINSIC
SAFETY
BARRIER.
FIELD
TERMINALS
(a)
(b)
PC-BASED
CONFIGURATOR
INDICATOR
+
PLUG
UNUSED
CONDUIT
CONNECTION
+
POWER
SUPPLY
_
_
+
CONTROLLER
OR RECORDER
HART COMMUNICATOR(b)
POWER
SUPPLY
250
min.(a)
+
TRANSMITTER
250
min.(a)
+
TRANSMITTER
250
min.(a)
+
TRANSMITTER
Multidrop Communication
Multidropping refers to the connection of several transmitters to a single communications
transmission line. Communications between the host computer and the transmitters takes place
digitally with the analog output of the transmitter deactivated. With the HART communications
33
2. Installation
protocol, up to 15 transmitters can be connected on a single twisted pair of wires or over leased
telephone lines.
The application of a multidrop installation requires consideration of the update rate necessary
from each transmitter, the combination of transmitter models, and the length of the transmission
line. Multidrop installations are not recommended where Intrinsic Safety is a requirement.
Communication with the transmitters can be accomplished with any HART compatible modem
and a host implementing the HART protocol. Each transmitter is identified by a unique address
(1-15) and responds to the commands defined in the HART protocol.
Figure 28 shows a typical multidrop network. Do not use this figure as an installation diagram.
Contact the HART Communications Foundation, (512) 794-0369, with specific requirements
for multidrop applications.
HOST
MODEM
LOAD
POWER
SUPPLY
IDP10-T
IDP10-T
IDP10-T
IASPT transmitters with HART communication protocol are set to poll address 0
(POLLADR 0) at the factory, allowing them to operate in the standard point-topoint manner with a 4 to 20 mA output signal. To activate multidrop
communication, the transmitter address must be changed to a number from 1 to
15. Each transmitter must be assigned a unique number on each multidrop
network. This change deactivates the 4 to 20 mA analog output.
34
2. Installation
This procedure assumes that the process shutoff valves are open.
1. Make sure that both upstream and downstream manifold valves are closed.
2. Make sure that the bypass valve is open.
3. Slowly open the upstream manifold valve.
4. Close the bypass valve.
5. Slowly open the downstream manifold valve.
This procedure assumes that the process shutoff valves are open.
1. Close the downstream manifold valve.
2. Close the upstream manifold valve.
3. Open the bypass valve.
4. Carefully open the vent screw to release any residual pressure before disconnecting
lines.
! WARNING
When venting pressure from the transmitter, wear suitable protective equipment to
prevent possible injury from process material, temperature, or pressure.
35
36
2. Installation
34.5
INH2O
NEXT
ENTER
NEXT
PUSHBUTTON
ENTER
PUSHBUTTON
37
(measurement M1 or M2)
E
(measurement M2 or M1)
N
N
RERANGE
N
E
CONFIG
N
CALIB
N
VIEW DB
ON-LINE MODE
N
N
E
TST DSP
CANCEL
ON-LINE MODE
N
E
E
N
N = NEXT BUTTON
E = ENTER BUTTON
1. The decimal point may not be placed directly after the first digit. For example,
you can not enter a value as 1.2300; you must enter it as 01.230.
2. The decimal position is identified by flashing except at the position after the fifth
digit. At that position (representing a whole number), the decimal point is assumed.
5. The display advances to the next menu item.
38
Reranging
You can access the Rerange mode in the top level menu (see Figure 30). Entry to the Mode Select
menu is made (from normal operating mode) by pressing the Next button. The display reads
RERANGE. You can then adjust M1 URV and/or M1 LRV in the following two submenus.
NOTE
be zero.
ALL SEGMENTS ON
Error Messages
Table 4. Operation Error Messages
Parameter
Normal
Operation
Startup
40
Condition Tested
Write Protection
Enabled
Any non-On-line
Condition
Database OK or
corrupted
Error
Message
WR PROT
OFFLINE
INITERR
Action
Displays periodically to notify user
that unit is in Write Protect.
Notifies user of a non-On-line
condition.
User should perform SET GDB
procedure. See SET GDB: on
page 63.
4. Calibration
NOTE
1. For best results in applications where high accuracy is required, rezero the
transmitter output once it has stabilized at the final operating temperature.
2. Zero shifts resulting from position effects and/or static pressure effects can be
eliminated by rezeroing the transmitter output.
3. When checking the zero reading of a transmitter operating in the square root
mode, return the output to the linear mode. This eliminates an apparent
instability in the output signal. Return the transmitter output to the square root
mode after the zero check is complete.
4. After calibrating transmitters operating with a 4 to 20 mA (or 1 to 5 V dc)
output signal, check the underrange and overrange output values to ensure that
they extend beyond 4 and 20 mA (or 1 and 5 V dc) respectively.
When either CAL LRV or CAL URV is initiated from the local pushbuttons, the
transmitter expects that the differential pressure applied at the time the button is
pressed is equal to the LRV or URV value respectively.
This function trims the internal digital value of differential pressure; that is, it
performs a calibration based on the application of accurate differential pressures
equal to the values entered for LRV and URV in the transmitter database.
This function also sets the 4 and 20 mA output points; that is, the 4 and 20 mA
points correspond to the values of LRV and URV in the database.
41
4. Calibration
The reranging function is accomplished by entering new database values for LRV
and URV.
Reranging does not affect the calibration of the transmitter; that is, it does not
affect the optimization of the internal digital value of differential pressure over a
specific calibrated range.
If the reranged LRV and URV are not within the calibrated range, the measured
values may not be as accurate as when they are within the calibrated range.
If the transmitter is in square root mode for flow rate measurement, the URV in the
database is displayed as the flow rate URV when the view database (VIEW DB)
function is used. However, the LRV and URV in pressure units can be displayed by
selecting the reranging (RERANGE) function. LRV is always zero when the
transmitter is configured for square root mode.
5. When the optional local display is used, the internal digital value of differential
pressure is sent directly to the indicator.
The display can show any measured differential pressure in selected units regardless of
the calibrated range and the values of LRV and URV (within the limits of the
transmitter and display).
If the measured differential pressure is outside the range established by the LRV and
URV values in the database, the display shows the measurement but also continually
blinks to indicate that the measurement is out of range. The mA current signal is
saturated at either the low or high overrange limit respectively but the display
continually shows the pressure.
The transmitter sets the output at 4 mA for the LRV and 20 mA for the URV.
The mA trim does not affect the calibration or the reranging of the transmitter and
does not affect the internal digital value of differential pressure or the transmission or
display of measured pressure.
The mA trim can be done with or without pressure applied to the transmitter.
7. Zeroing from the local display does not affect the span.
42
4. Calibration
When the transmitter is zeroed to compensate for installed position effect, the
transmitter can have either LRV differential pressure applied (CAL LRV) or zero
differential pressure applied (CAL AT0). If using a zero-based range, either method
produces the same result. However, if the range is not zero-based, it is advantageous to
have both methods available.
For example, consider a differential pressure transmitter having a range of 50 to 100
psig. If it is not feasible to vent the transmitter to atmosphere for zeroing (or to bypass
the high and low sides for zeroing), it can be zeroed while the LRV differential
pressure of 50 psi is applied by using the CAL LRV function. On the other hand, if
the transmitter has been installed but there is no pressure in the process line yet (or
the high and low sides can be connected by a bypass valve), it can be zeroed while
open to atmosphere (or bypassed) by using the CAL AT0 function.
a. Zeroing with LRV Pressure Applied (CAL LRV):
Before using this zeroing function, apply a differential pressure to the transmitter
equal to the value of LRV stored in the transmitter database.
When you zero the transmitter, the internal digital value of differential pressure is
trimmed to be equal to the value of LRV stored in the database and the mA
output set to 4 mA.
If zeroing is done when the applied differential pressure is different from the LRV
value in the database, the internal digital value of differential pressure is biased by
the difference in the values but the output is still set at 4 mA.
The CAL LRV and CAL URV function should be used when calibrating a
transmitter for a specific range with known input differential pressures applied for
the LRV and URV.
Make sure that the applied differential pressure is at zero. This means venting the
transmitter to atmosphere or opening a bypass valve to connect high and low
sides.
When you zero the transmitter, the internal digital value of the differential pressure is
trimmed to be equal to zero and the mA output set to an appropriate value such that
the mA output is a nominal 4 mA when the LRV pressure is applied later.
Calibration Setup
The following sections show setups for field or bench calibration. Use test equipment that is at
least three times as accurate as the desired accuracy of the transmitter.
NOTE
43
4. Calibration
POWER SUPPLY
(+)
()
() (+)
() (+)
If the transmitter is to be removed from the process for calibration, refer to Bench Calibration
Setupbelow.
For field calibration, an adjustable air supply and a pressure measuring device are required. For
example, a dead weight tester or an adjustable clean air supply and pressure gauge can be used.
The pressure source can be connected to the transmitter process connection with pipe fittings or
it can be connected to the vent screw assembly using a calibration screw. The calibration screw
has a Polyflo fitting and can be used for pressures up to 700 kPa (100 psi). It is available as
Foxboro Part Number F0101ES.
To set up the equipment, refer to Figure 33 and use the following procedure.
1. If the transmitter is in operation, follow the Taking a Differential Pressure
Transmitter Out of Operation on page 35.
! CAUTION
With liquid service, drain both sides of transmitter to avoid calibration errors.
2. If a calibration screw is being used, remove the vent screw and replace it with the
calibration screw. Connect the pressure source to the calibration screw using
6 x 1 mm or 0.250 inch tubing.
If a calibration screw is not being used, remove the entire vent screw assembly or drain
44
4. Calibration
plug (as applicable) from the high pressure side of the transmitter. Connect
calibration tubing using a suitable thread sealant.
3. Close the bypass valve opened in Step 1.
4. Complete the setup shown in Figure 33.
NOTE
For vacuum applications, connect the calibrating pressure source to the low pressure
side of the transmitter.
5. If calibrating the output signal, also connect equipment as shown in Figure 32.
BYPASS VALVE
SHUTOFF VALVES
CALIBRATING
PRESSURE
SOURCE
BLEEDER VALVES
(NEEDLE TYPE)
For vacuum applications, connect the calibrating pressure source to the low pressure
side of the transmitter.
If calibrating the output signal, also connect equipment as shown in Figure 32.
45
4. Calibration
BYPASS VALVE
SHUTOFF VALVES
CALIBRATING
PRESSURE
SOURCE
BLEEDER VALVES
(NEEDLE TYPE)
1. During calibration, a single change could affect several parameters. For this
reason, if an entry is entered in error, re-examine the entire database or use the
Cancel feature to restore the transmitter to its starting configuration and begin
again.
46
4. Calibration
Description
Calibrate at zero pressure.
Calibrate with pressure at 0% of transmitter range
(LRV).
CAL URV
Calibrate with pressure at 100% of transmitter range
(URV).
ADJ 4mA
Adjust nominal 4 mA output.
ADJ20mA
Adjust nominal 20 mA output.
CALDATE
Enter the calibration date.
ADJ 4mA causes the following four submenus.
A 4mA
Increase 4 mA output by large step.
A 4mA
Decrease 4 mA output by large step.
A 4mA
Increase 4 mA output by small step.
A 4mA
Decrease 4 mA output by small step.
ADJ 20mA causes the following four submenus.
Increase 20 mA output by large step.
A 20mA
A 20mA
Decrease 20 mA output by large step.
A 20mA
Increase 20 mA output by small step.
A 20mA
Decrease 20 mA output by small step.
NOTE
47
4. Calibration
CAL AT0
N
AT0 DONE
N
E
CAL LRV
N
LRV DONE
N
E
CAL URV
N
URV DONE
E = ENTER
N = NEXT
ADJ 4mA
E
A 4mA
N
A 4mA
N
A 4mA
E
A 4mA
E
E
A 4mA
A 4mA
A 4mA
N
A 4mA
ADJ20mA
E
A 20mA
N
A 20mA
N
N
A 20mA
N
A 20mA
N
A 20mA
E
E
A 20mA
E
E
A 20mA
E
E
E
A 20mA
CALDATE
(continued on next
figure)
Figure 35. Calibration Structure Diagram
48
4. Calibration
CALDATE
E
N
Display Day
Increment Day
E
N
Display Month
Increment Month
E
N
Display Year
Increment Year
E
CANCEL
N
SAVE
N
*If character is not the last position on the display line, advances to next character.
**If character is the last position on the display line, advances to next menu item.
NOTE: Commentary about this diagram immediately follows.
Do not use CAL AT0 if pressure seals are used that are at different elevations from
the transmitter.
To use this feature:
49
4. Calibration
If the optional display is not present, the same functions can be accomplished by
depending on the length of time the external zero button is depressed. Press and
hold the button for 1 to 3 seconds for CAL AT0 or for 5 or more seconds for
CAL LRV. Therefore, if your LRV is zero, just depress the button for a few seconds.
However, if your LRV is not zero, use caution when using the external zero button
without the optional display because you must rely strictly on the length of time the
button is depressed to differentiate between CAL AT0 and CAL LRV.
Other possible messages are:
DISABLD if EX ZERO is configured EXZ DIS
IGNORED if the transmitter is not in the on-line mode.
WP ENAB if write protection jumper is in write protect position.
If additional rezeroing is required after Steps 1 and 2 have been accomplished, repeat
Step 2.
3. Relatch the external zero button by turning it 90 in a clockwise direction to prevent
accidental pressing of the button. Do not push the button in with the screwdriver
while doing this.
50
4. Calibration
Error Messages
Table 6. Calibration Error Messages
Parameter
Password
Protection
Write
Protection
ZERO
SPAN
M1 URV
M1 LRV
Condition Tested
Error
Message
User Action
Password
BAD PWD
Write protection
enabled
Internal offset too
large
Slope too large or too
small
M1URV > max
pressure in EGU
REJECT
BADZERO
BADSPAN
URV>FMX
URV<FMN
M1 URV = M1 LRV
LRV=URV
M1 turndown exceeds
limit
URV < 0 with M1 or
M2 SqRt
M1LRV > max
pressure in EGU
BADTDWN
URV<LRV
LRV>FMX
LRV<FMN
M1 URV = M1 LRV
LRV=URV
M1 turndown exceeds
limit
BADTDWN
51
52
4. Calibration
5. Configuration
Configurable Parameters
Table 7 lists all the configurable parameters and the factory default for the IDP10-T
Transmitters. The factory default values have been customized if the transmitter was ordered with
optional feature -C2. The table also shows which parameters are configurable with the integral vs.
remote configurators.
Table 7. IDP10-T Configurable Parameters
Configurable
with
Parameter
Descriptors
Tag Number
Descriptor
Message
Input
Calibrated Range
Capability
Measurement #1 EGUs
Measurement #2 Mode
(SV)
Measurement #2 EGUs
8 characters max
Tag Number
No
Yes
16 characters max
Tag Name
No
Yes
32 characters max
Inst Location
No
Yes
Yes
4 to 20 mA
Yes
Yes
Linear
Yes
Yes
Units of
Yes
Calibrated Range
Yes
Linear
Yes
Yes
Units of
Yes
Calibrated Range
Yes
Output
Measurement #1 Output 4 to 20 mA or Fixed
Current. Specify Poll
(PV)
Measurement #1 Mode
Factory
Default
Fail-safe
High
Enabled
None
Yes
Yes
Yes
Yes
Yes
Yes
Yes
53
5. Configuration
Capability
Factory
Default
0 - 15
0
Meas #1 EGU or % Lin Meas #1 EGU
Yes
No
(a) psi, inHg, ftH2O, inH2O, atm, bar, mbar, MPa, kPa, Pa, kg/cm2, g/cm2, mmHg, torr, mmH2O.
(b) Span Code A: 0 to 30 inH2O; Span Code B: 0 to 200 inH2O; Span Code C: 0 to 30 psi;
Span Code D: 0 to 300 psi; Span Code E: 0 to 3000 psi.
(c) gal/s, gal/m, gal/h, gal/d, Mgal/d, ft3/s, ft3/m, ft3/h, ft3/d, Igal/s, Igal/m, Igal/h, Igal/d, l/s, l/m, l/h, Ml/d, m3/s,
m3/m,
m3/h, m3/d, bbl/s, bbl/m, bbl/h, bbl/d, %flow.
(d) Square root with cutoff below 1% of calibrated pressure range or with linear below 4% of calibrated pressure
range.
(e) Measurement #2 can be displayed at any time by pressing the Enter button regardless of the local display
configuration. This reverts to Measurement #1 or % Lin (as configured) when power is cycled off and on.
54
5. Configuration
NOTE
1. You can configure most parameters using the local display. However, for more
complete configuration capability, use a HART Communicator or PC-Based
configurator.
2. During configuration, a single change can affect several parameters. For this
reason, if an entry is entered in error, re-examine the entire database or use the
Cancel feature to restore the transmitter to its starting configuration and begin
again.
Description
Poll Address: 0 - 15
External Zero: enable or disable
Temperature Sensor Failure Strategy: S2FATAL or
S2NOFTL
4 to 20 mA Output: forward or reverse
4 to 20 mA Output: fail mode output - low or high
4 to 20 mA Output in offline mode - last or user set
Damping: none, 1/4, 1/2, 1, 2, 4, 8, 16, or 32 seconds
Output: linear or type of square root(b)
Local Indicator Display in linear mode: in percent or
engineering units
User-Defined Engineering Units
Primary Upper Range Value
Primary Lower Range Value
Output: linear or type of square root
User-Defined Engineering Units
Display M1, M2, or Toggle between M1 and M2
Calibration Date
Enable password; no password, configuration only, or
configuration and calibration
User set configuration password (six characters)
User set calibration password (six characters)
Rewrite all calibration and configuration values with
default values
Initial Factory
Configuration
0
Enable
S2FATAL
Forward
High
USER MA
None
Linear
M1EGU
inH2O or psi
URL
0
Linear
Same as M1 EGU
M1
--NO PWD
-------
55
5. Configuration
Proceed to configure your transmitter by using the Next button to select your item and the Enter
button to specify your selection per the following three figures. At any point in the configuration
you can Cancel your changes and return to the on-line mode, or Save your changes.
56
5. Configuration
POLLADR
N
EX ZERO
EXZ DIS
EXZ ENA
OUT FWD
E
OFFL MA
FAIL LO
FAIL HI
E
OUT REV
OUTFAIL
S2 NOFTL
NOTES:
S2 FATAL
N
LAST MA
USER MA
Display
Digit
E
15
S2 FAIL
OUT DIR(a)
Implement
Digit
N
E
DAMPING
N
NO DAMP
DAMP 1/4
DAMP 1/2
DAMP 32
E
N
E
M1 MODE
N
M1SQ<1C
M1 LIN
E
M1SQ<4L
E
Display Digit
**
M1SQ<nC
E
Increment Digit
5. Configuration
M1 DISP(a)
M1 EGU
LIN PCT
E
N
M1 EGU
gal/s
gal/m
gal/h
E
N
N
or
N
inH20
inHg
M1EOFF
M1EFAC
**
atm
E
Increment Digit
Display Digit
Increment Digit
E
**
Display Digit
M1 URV
%flow
Display Digit
**
Increment Digit
N
M1 LRV
N
M2 MODE
E
**
Display Digit
E
Increment Digit
Similar to M1 MODE
N
M2 EGU
N
DISPLAY
(continued on next figure)
Similar to M1 EGU
*If character is not the last position on the display line, advances to next character.
**If character is the last position on the display line, advances to next menu item.
5. Configuration
DISPLAY
SHOW M1
SHOW M2
CALDATE
TOGGLE
E
E
N
Increment Day
Display Day
E
N
Display Month
Increment Month
E
N
Increment Year
Display Year
E
E
ENA PWD
CFGONLY
NO PWDS
CFG PWD
N or E
**
Display
Character
E
*
CFG+CAL
CAL PWD
N or E
Increment
Character
Increment
Character
Display N
Character
E
**
*
Increment
Character
Display
Character
E
CFG PWD
N or E
E
SET GDB
N
CANCEL
CLEAR DB
N
Performs Reset
and returns
to ONLINE
N
SAVE
N
59
5. Configuration
60
5. Configuration
DAMPING:
To configure additional damping, go to DAMPING with the Next button and press
Enter. Use the NEXT button to select NO DAMP, DAMP 1/4, DAMP 1/2, DAMP 1,
DAMP 2, DAMP 4, DAMP 8, DAMP 16, or DAMP 32 and press Enter.
M1 MODE:
To configure the mode of the primary output (PV), go to M1 MODE with the Next
button and press Enter. Use the Next button to select M1 LIN (linear), M1SQ<1C
(square root with cutoff below 1% dp (M1 URV in linear units of dp), M1SQ<4L (square
root with linear below 4% of dp (M1 URV in linear units of dp), or M1SQ<nC (square
root with user configured cutoff specified between 0 and 20% of the flow upper range
value, M1 EFAC) and press Enter. You cannot configure this parameter as square root if
OUT DIR was configured as OUT REV or if M1LRV is not zero.
NOTE
61
5. Configuration
For a 200 inH2O transmitter with a measured range of 0 to 100 inH2O and displayed
range of 0 to 500 gal/m, M1EFAC = 500.
To edit the span in your configured flow units, press Enter at the prompt M1EFAC. Use
the procedure Entering Numerical Values on page 38 to edit this parameter.
M1 URV:
To edit the upper range value, press Enter at the prompt M1 URV. Use the procedure
Entering Numerical Values on page 38 section to edit this parameter.
M1 LRV:
Similar to M1URV immediately above.
NOTE
M1 LRV is bypassed if M1 MODE is configured as square root since M1 LRV must
be zero.
M2 MODE:
M2 is a secondary measurement (SV) that is read by the HART Communicator and can
be displayed on the optional display. You might use this feature to display M1 in flow
units and M2 in comparable pressure units. To configure this parameter, go to M2
MODE with the Next button and press Enter. Use the Next button to select M2 LIN
(linear), M2SQ<1C (square root with cutoff below 1% dp (M2 URV in linear units of
dp), M2SQ<4L (square root with linear below 4% of dp (M2 URV in linear units of dp),
or M2SQ<nC (square root with cutoff specified between 0 and 20% of the flow upper
range value, M2 EFAC) and press Enter.
M2 EGU:
Similar to M1 EGU.
DISPLAY:
To display M1, M2, or to toggle between M1 and M2, go to DISPLAY with the Next
button and press Enter. Use the Next button to select SHOW M1, SHOW M2, or
TOGGLE and press Enter.
CALDATE:
This is not a required entry but can be used for record-keeping or plant maintenance
purposes. To edit the calibration date, go to CALDATE with the Next button and press
Enter. You then can change the day, month, and year. The display shows the last date
with the day flashing. Use the Next button to step through the library of digits to select
the desired day, then press Enter. Repeat this process for the month and year.
ENA PWD:
To enable or disable the password feature, go to ENA PWD with the Next button and
press Enter. Use the Next button to select NO PWDS (password not required for either
calibration or configuration), CFGONLY (password required to configure but not to
calibrate), or CFG+CAL (passwords required to both configure and calibrate) and press
Enter.
If you selected CFG ONLY, the display changes to CFG PWD. Press either the Next or
Enter button. Use the Next button to step through the library of characters to select the
62
5. Configuration
desired first character, then press Enter. Your selection is entered and the second
character flashes. Repeat this procedure until you have created your password. If the
password has less than six characters, use blanks for the remaining spaces. When you have
configured the sixth space, the display advances to the next menu item.
If you selected CFG+CAL, the display changes to CAL PWD. To create the Calibration
password, press either the Next or Enter button. Use the Next button to step through the
library of characters to select the desired first character, then press Enter. Your selection is
entered and the second character flashes. Repeat this procedure until you have created
your password. If the password has less than six characters, use blanks for the remaining
spaces. When you have configured the sixth space, the display advances to CFG PWD.
Use the same procedure to create the configuration password.
NOTE
In normal operation, the CAL PWD allows access to only calibration mode. The
CFG PWD allows access to both configuration and calibration.
! CAUTION
Record your new password before saving changes to the database.
SET GDB:
If your transmitter database becomes corrupted and you receive an INITERR message
upon startup, this function enables you to rewrite all calibration and configuration values
with default values.
! CAUTION
Any calibration and configuration values that you have entered will be lost. Therefore,
SET GDB should not be selected if your transmitter is functioning normally.
63
5. Configuration
Character Lists
Table 9. Alphanumeric Character List
Character List*
@
, (comma)
A-Z (uppercase)
[
\
]
^
_ (underscore)
space
!
#
$
%
&
(
)
*
+
.
/
0-9
:
;
<
>
=
?
*List only applies to Model 275 HART Communicator not to optional local display.
. (decimal point)
0 through 9
64
5. Configuration
Error Messages
Table 11. Configuration Error Messages
Parameter
Password
Protection
Write
Protection
M1 MODE
(being
changed to
square root)
M1EFAC
M1 URV
Condition Tested
Error Message
User Action
Password
BAD PWD
Write Protection
Enabled
M1 LRV 0
REJECT
LRVnot0
M1 URV < 0
URV<LRV
URV<LRV
M1EFAC < 0
-M1EFAC
M2EFAC < 0
-M2EFAC
M1EFAC = 0
0M1EFAC
M2EFAC = 0
0M2EFAC
M1EOFF 0 or
M2EOFF 0
BADEOFF
M1EFAC < 0
-M1EFAC
M1EFAC = 0
0M1EFAC
URV>FMX
URV<FMN
5. Configuration
Condition Tested
Error Message
LRV>FMX
LRV<FMN
M2EFAC
66
URV<LRV
M1EFAC < 0
-M1EFAC
M2EFAC < 0
-M2EFAC
M1EFAC = 0
0M1EFAC
M2EFAC = 0
0M2EFAC
M1EOFF 0 or
M2EOFF 0
BADEOFF
M2EFAC < 0
-M2EFAC
M2EFAC = 0
0M2EFAC
User Action
Entered pressure is greater than maximum
rated pressure of transmitter. Check entry.
Verify EGUs.
Entered pressure is less than minimum rated
pressure of transmitter. Check entry. Verify
EGUs.
Cannot set span to 0. Check entry. Check
M1 URV.
Check entry. Check M1 URV.
Square root mode with nonzero LRV is not
valid. Change M1 LRV to 0.
Square root mode with negative URV is not
valid. Change M1 URV to positive value.
Square root mode with URV < LRV is not
valid. Change M1 LRV to 0 and M1 URV to
positive value.
Negative M1 EFAC is not valid. Change
M1 EFAC to positive value.
Negative M2 EFAC is not valid. Change
M2 EFAC to positive value.
M1 EFAC = 0 is not valid. Change
M1 EFAC to positive value.
M2 EFAC = 0 is not valid. Change
M2 EFAC to positive value.
Square root mode with nonzero
M1 EOFF and M2 EOFF is not valid. Change
M1 EOFF and M2 EOFF to 0.
Negative M2 EFAC is not valid. Change
M2 EFAC to positive value.
M2 EFAC = 0 is not valid. Change
M2 EFAC to positive value.
6. Maintenance
! DANGER
For nonintrinsically safe installations, to prevent a potential explosion in a Division 1
hazardous area, de-energize transmitters before you remove threaded housing covers.
Failure to comply with this warning could result in an explosion resulting in severe
injury or death.
Error Messages
For error messages displayed on the HART Communicator refer to MI 020-366.
Parts Replacement
Parts replacement is generally limited to the electronics module assembly, housing assembly,
sensor assembly, terminal block assembly, cover O-rings, and optional display. For part numbers
relating to the transmitter and its options, see PL 009-005.
67
6. Maintenance
68
6. Maintenance
HOUSING ASSEMBLY
TO REMOVE ELECTRONICS
MODULE, REMOVE TWO
CROSS RECESS SCREWS.
6. Maintenance
8. If your housing has an anti-rotation screw, engage the screw until it touches the sensor
neck and back it off 1/8th turn. It is important that the screw is not touching the
sensor. Fill the screw recess with red lacquer (Foxboro Part Number X0180GS or
equivalent). The housing can then be rotated up to one full turn counterclockwise for
optimum access.
9. If your housing has a retention clip, insert the clip over the boss in the housing neck so
that the hole in the clip is aligned with the hole in the boss. Install the screw but do
not tighten. Rotate the housing up to one full turn counterclockwise for optimum
access. Tighten the retention clip screw and fill the screw recess with red lacquer
(Foxboro Part Number X0180GS or equivalent). The housing can still be rotated for
optimum access.
10. Reinstall the electronics module per Steps 6 through 9 in the previous procedure.
6. Maintenance
pressure for one minute. There should be no leakage of the test fluid through the
gaskets. If leakage occurs, retighten the cover bolts per Step 5 (or replace the gaskets)
and retest.
! CAUTION
Perform hydrostatic test with a liquid and follow proper hydrostatic test procedures.
PROCESS COVER
SENSOR
PROCESS COVER
GASKETS
71
6. Maintenance
BOTTOMWORKS WITH
PROCESS CONNECTOR
CODE 7
PVDF INSERTS
PROCESS CONNECTIONS
STANDARD
ORIENTATION
PROCESS COVERS
CONDENSED
LIQUID FREELY
DRAINS
INVERTED
PROCESS
COVERS
72
6. Maintenance
73
74
6. Maintenance
Index
C
Calibration 41
Using a HART Communicator 46
Using a PC20 46
Using a PC50 Configurator 46
Using the Local Display 46
Calibration Notes 41
Calibration Setup 43
Configuration 53
Using a HART Communicator 54
Using a PC20 Configurator 54
Using a PC50 Configurator 54
Using the Local Display 54
Cover Locks 29
D
Display, Positioning the 28
E
Error Messages
Calibration 51
Configuration 65
Operation 40
H
Housing, Positioning the 28
I
Identification 3
Installation 15
M
Maintenance 67
Mounting 15
O
Operation Via Local Display 37
75
Index
P
Parts Replacement 67
Piping, Installation of Flow Measurement 24
R
Reference Documents
Reranging 39
S
Seal Liquid, Filling the System with 27
Specifications
Product Safety 10
Standard 5
W
Wiring 29
Write Protect Jumper, Setting the 29
Z
Zero Adjustment Using External Zero Button 49
ISSUE DATES
DEC 2001
OCT 2003
APR 2004
FEB 2005
JUN 2005
FEB 2006
AUG 2006
OCT 2007
JUL 2008
MAY 2010
Vertical lines to the right of text or illustrations indicate areas changed at last issue date.
Invensys Operations Management
5601 Granite Parkway Suite 1000
Plano, TX 75024
United States of America
http://www.iom.invensys.com
Global Customer Support
Inside U.S.: 1-866-746-6477
Outside U.S.:1-508-549-2424 or contact
your local Invensys representative.
Email: support@invensys.com
Website: http://support.ips.invensys.com
0510