Anda di halaman 1dari 10

CERTIFICATE OF COMPLIANCE

Certificate Number
Report Reference
Issue Date

Issued to:

This is to certify that


representative samples of

20150904E143112
E143112-20050405
2015-SEPTEMBER-04

SIEMENS AG
DF CP R&D V 3
WERNER-VON-SIEMENS-STRASSE 48
92224 AMBERG, GERMANY
Motor Controllers, Mechanically Operated and Solid-state
See Addendum Page
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.

Standard(s) for Safety:

Additional Information:

UL 60947-1 and CSA C22.2 NO. 60947-1-13 LOWVOLTAGE SWITCHGEAR AND CONTROLGEAR - PART
1: GENERAL RULES
UL 60947-4-1 and CSA C22.2 NO. 60947-4-1-14 LOWVOLTAGE SWITCHGEAR AND CONTROLGEAR - PART
4-1: CONTACTORS AND MOTOR-STARTERS ELECTROMECHANICAL CONTACTORS AND MOTORSTARTERS
See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 10

CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date

20150904E143112
E143112-20050405
2015-SEPTEMBER-04

This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.
Product Covered:
Solid-state motor controller, Type 3RW40 followed by 55, 56, 72, 73, 74, 75 or 76 followed by -2 or -6 followed by
AB or BB followed by 3 or 4 followed by 4 or 5.

Solid-state motor controller with braking function, Type 3RW4 followed by 2, followed by 11, followed
by -6, followed by R, followed by B, followed by 8, followed by 5. May be followed by additional suffix letters and/or
numbers.

Solid-state motor controller, Type 3RW44 followed by 22, 23, 24, 25, 26, 27, 34, 35, 36, 43, 44, 45, 46 or 47
followed by -2 or -6 followed by BC followed by 3 or 4 followed by 4, 5 or 6.

Accessories, fans, type 3RW4936-8VX40, 3RW4936-8VX30, 3RW4947-8VX40, 3RW4947-8VX30..


General:
These devices are solid - state motor controller for use in industrial applications. These devices allow smooth,
step less starting with the option of soft stopping. These devices are provided with an integrated solid-state
overload relay (class settings 3RW40: 10, 15, 20; class settings 3RW44: 5, 10, 15, 20, 30). The 3RW40AB provides the same options as the 3RW40BB but without an active bypass system. Its ratings are
lower than with an active bypass system.

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 2 of 10

CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date

20150904E143112
E143112-20050405
2015-SEPTEMBER-04

Ratings:
3RW40
3 ph Horsepower at 40 C surrounding air temperature
Type

200 V

230/240 V

3RW4055
3RW4056
3RW4072
3RW4073
3RW4074
3RW4075
3RW4076

40 hp
50 hp
75 hp
75 hp
75 hp
100 hp
150 hp

50 hp
60 hp
75 hp
75 hp
100 hp
125 hp
150 hp

460/480 V
100 hp
125 hp
150 hp
150 hp
200 hp
250 hp
350 hp

575/600 V

max FLA

125 hp
150 hp
201 hp
201 hp
250 hp
350 hp
450 hp

134 A
162 A
230 A
230 A
280 A
356 A
432 A

3RW4211-6RB85
3 ph Horsepower at 40 C surrounding air temperature
Type
3RW4211
3RW4211

200 V
-

230/240 V
-

460/480 V
60hp
-

575/600 V
60hp

max FLA
77 A
62 A

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 3 of 10

CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date

20150904E143112
E143112-20050405
2015-SEPTEMBER-04

3 ph Horsepower at 50C surrounding air temperature


Type

200 V

230/240 V

460/480 V 575/600 V

max FLA

3RW4055BB

30 hp

40 hp

75 hp

100 hp

117 A

3RW4055AB
3RW4056
3RW4072
3RW4073BB

25 hp
40 hp
60 hp
60 hp

30 hp
50 hp
75 hp
75 hp

60 hp
100 hp
150 hp
150 hp

75 hp
150 hp
200 hp
200 hp

88 A
145 A
205 A
205 A

3RW4073AB
3RW4074
3RW4075
3RW4076

40 hp
75 hp
100 hp
125 hp

40 hp
100 hp
125 hp
150 hp

100 hp
200 hp
250 hp
300 hp

100 hp
250 hp
300 hp
400 hp

124 A
248 A
315 A
385 A

3RW44
3 ph Horsepower at 40C surrounding air temperature
Type

200 V

230/240 V

3RW4422
3RW4423
3RW4424
3RW4425
3RW4426
3RW4427
3RW4434
3RW4435
3RW4436
3RW4443
3RW4444
3RW4445
3RW4446
3RW4447

7.5 hp
10 hp
10 hp
15 hp
20 hp
30 hp
30 hp
40 hp
50 hp
60 hp
75 hp
100 hp
100 hp
150 hp

10 hp
10 hp
15 hp
20 hp
25 hp
30 hp
40 hp
50 hp
60 hp
75 hp
100 hp
125 hp
125 hp
150 hp

460/480 V
15 hp
25 hp
30 hp
40 hp
60 hp
60 hp
75 hp
100 hp
125 hp
150 hp
200 hp
250 hp
250 hp
350 hp

575/600 V
25 hp
30 hp
40 hp
50 hp
75 hp
75 hp
100 hp
125 hp
150 hp
200 hp
250 hp
300 hp
350 hp
450 hp

max FLA
29 A
36 A
47 A
57 A
77 A
93 A
113 A
134 A
162 A
203 A
250 A
313 A
356 A
432 A

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 4 of 10

CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date

20150904E143112
E143112-20050405
2015-SEPTEMBER-04

3 ph Horsepower at 50C surrounding air temperature


Type

200 V

3RW4422
3RW4423
3RW4424
3RW4425
3RW4426
3RW4427
3RW4434
3RW4435
3RW4436
3RW4443
3RW4444
3RW4445
3RW4446
3RW4447

230/240 V
7.5 hp
10 hp
10 hp
15 hp
20 hp
25 hp
30 hp
30 hp
40 hp
60 hp
60 hp
75 hp
100 hp
125 hp

Control voltage:
Auxiliary Contacts:

460/480 V
7.5 hp
10 hp
15 hp
15 hp
25 hp
30 hp
30 hp
40 hp
50 hp
60 hp
75 hp
100 hp
125 hp
150 hp

575/600 V max FLA

15 hp
20 hp
30 hp
30 hp
50 hp
60 hp
75 hp
75 hp
100 hp
150 hp
150 hp
200 hp
250 hp
300 hp

20 hp
30 hp
40 hp
40 hp
60 hp
75 hp
100 hp
100 hp
150 hp
150 hp
200 hp
250 hp
300 hp
400 hp

26 A
32.2 A
42 A
51 A
68 A
82 A
100 A
117 A
145 A
180 A
215 A
280 A
315 A
385 A

115 V up to 230 V ac
B300/R300

Short Circuit:
Type 3RW405BB: 10 kA, 600 V AC, max. Fuse
Type 3RW4055AB: 10 kA, 600 V AC, max. Fuse
Type 3RW407:
30 kA, 600 V AC, max. Fuse
Type 3RW4073AB: 10 kA, 600 V AC, max. Fuse
Type 3RW442:
10 kA, 600 V AC, max. Fuse
Type 3RW443:
10 kA, 600 V AC, max. Fuse
Type 3RW444:
30 kA, 600 V AC, max. Fuse

450 A, Class K5, Class J


350 A, Class K5, Class J
1200 A, Class L
450 A, Class RK5
300 A, Class K5, Class J
450 A, Class K5, Class J
1200 A, Class L

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 5 of 10

CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date

20150904E143112
E143112-20050405
2015-SEPTEMBER-04

Short Circuit Ratings Continued:

Model

Current, Voltage

Type 3RW4422:

100kA, 600 V AC, max. Fuse 50 A, Class RK5


max. Fuse 100 A, Class J
100kA, 600 V AC, max. Fuse 60 A, Class RK5
max. Fuse 120 A, Class J
100kA, 600 V AC, max. Fuse 80 A, Class RK5
max. Fuse 160 A, Class J
100kA, 600 V AC, max. Fuse 80 A, Class RK5
100kA, 600 V AC, max. Fuse 125 A, Class RK5
max. Fuse 250 A, Class J
100kA, 600 V AC, max. Fuse 150 A, Class RK5
max. Fuse 300 A, Class J
100kA, 600 V AC, max. Fuse 200 A, Class RK5
max. Fuse 400 A, Class J
100kA, 600 V AC, max. Fuse 200 A, Class RK5
max. Fuse 400 A, Class J
100kA, 600 V AC, max. Fuse 250 A, Class RK5
max. Fuse 500 A, Class J
100kA, 600 V AC, max. Fuse 300 A, Class RK5
max. Fuse 600 A, Class J
100kA, 600 V AC, max. Fuse 350 A, Class RK5

Type 3RW4423:
Type 3RW4424:
Type 3RW4425:
Type 3RW4426:
Type 3RW4427:
Type 3RW4434:
Type 3RW4055, 3RW4435:
Type 3RW4056, 3RW4436:
Type 3RW4443:
Type 3RW4072:
3RW4073:
3RW4444:
Type 3RW4074, 3RW4445:
Type 3RW4075, 3RW4446:
Type 3RW4076, 3RW4447:

100kA, 600 V AC,


100kA, 600 V AC,
100kA, 600 V AC,

Max Fuse Size

max. Fuse 450 A, Class RK5


max. Fuse 600 A, Class RK5
max. Fuse 700 A, Class L

3RW4211-6RB85
Type 3RW4211: 10kA, 480 V AC, when protected by self protected combination motor controller model 3RV104
.
Type 3RW4211: 10kA, 600 V AC, when protected by self protected combination motor controller model 3RV104
.

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 6 of 10

CERTIFICATE OF COMPLIANCE
20150904E143112
E143112-20050405
2015-SEPTEMBER-04

Certificate Number
Report Reference
Issue Date

Short Circuit Ratings, standard fault


Type

3RW4422
3RW4423
3RW4424
3RW4425
3RW4426
3RW4427

Manual
Motor
Controller
3RV203
52
52
52
80
80
80

A
A
A
A
A
A

Circuit
Breaker
3RV1742

FLA

70
70
70
70
70
70

29
36
47
57
77
93

A
A
A
A
A
A

Short
Circuit

A
A
A
A
A
A

5
5
5
10
10
10

kA
kA
kA
kA
kA
kA

Voltage

600
600
600
600
600
600

V
V
V
V
V
V

Horse
Power

25
30
40
50
75
75

hp
hp
hp
hp
hp
hp

High Fault Current Ratings


Type

3RW4422
3RW4423
3RW4424
3RW4425
3RW4426
3RW4427

Manual
Motor
Controller
3RV203
32 A
52 A
52 A
-

Circuit
Breaker
3RV1742
35 A
70 A
70 A
-

FLA

29 A
36 A
47 A
-

Short
Circuit

Voltage

Horse
Power

10 kA
10 kA
10 kA
-

600 V
600 V
600 V
-

25 hp
30 hp
40 hp
-

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 7 of 10

CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date

20150904E143112
E143112-20050405
2015-SEPTEMBER-04

Nomenclature Breakdown:

3RW4
I
I.

2
II

11
III

6
IV

R
V

B
VI

8
VII

Basic Type
3RW4 - AC Semiconductor motor starter

II.
Device Type
2 - Soft starter
III.

Rated Operational Power


11 45kW / 60hp

IV.

Type of Terminals
6 - Bus bars for main circuit and screw terminals for control circuits

V.

Special Function
RWith bypass and breaking function

VI.

Phases Controlled
BTwo phases controlled

VII.

Rated Control Voltage


8Two control voltages

VIII.

Rated Operational Voltage


5400 V ac up to 600 V ac

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 8 of 10

5
VIII

CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date

20150904E143112
E143112-20050405
2015-SEPTEMBER-04

Nomenclature Breakdown:
3RW40 55
I
II

-2
III

BB 3 4
IV V VI

I - Basic type
3RW40 - AC Semiconductor motor starter
II - Size
55 - size S6, rated for 480 V and 50C / 75 hp, for BB Version, with bypass system
55 size S6, rated for 480 V and 50C / 60 hp, for AB Version, no bypass system
56 - size S6, rated for 480 V and 50C / 100 hp
72 - size S12, rated for 480 V and 50C / 150 hp
73 - size S12, rated for 480 V and 50C / 150 hp, for BB Version, with bypass system
73 size S12, rated for 480 V and 50C / 100 hp, for AB Version, no bypass system
74 - size S12, rated for 480 V and 50C / 200 hp
75 - size S12, rated for 480 V and 50C / 250 hp
76 - size S12, rated for 480 V and 50C / 300 hp
III

Type of Terminals
-2 Bus bars for main circuit and spring terminals for control circuits
-6 Bus bars for main circuit and screw terminals for control circuits

IV

Phases controlled and bypass


AB 2-phase controlled, no bypass-system
BB 2-phase controlled with bypass

Operating Voltage
3115 V ac
4230 V ac

VI

Rated Voltage
4200 up to 480 V ac
5460 up to 600 V ac

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 9 of 10

CERTIFICATE OF COMPLIANCE
Certificate Number
Report Reference
Issue Date

3RW44 22
I
II

-1
III

BC
IV

20150904E143112
E143112-20050405
2015-SEPTEMBER-04

3 4
V VI

I - Basic type
3RW44 - Solid-state motor controller, high functionality
II - Size
22 size 2, rated for 480 V and 50C / 15 hp
23 size 2, rated for 480 V and 50C / 20 hp
24 size 2, rated for 480 V and 50C / 30 hp
25 size 2, rated for 480 V and 50C / 30 hp
26 size 2, rated for 480 V and 50C / 50 hp
27 size 2, rated for 480 V and 50C / 60 hp
34 size 3, rated for 480 V and 50C / 75 hp
35 size 3, rated for 480 V and 50C / 75 hp
36 size 3, rated for 480 V and 50C / 100 hp
43 size 4, rated for 480 V and 50C / 150 hp
44 size 4, rated for 480 V and 50C / 150 hp
45 size 4, rated for 480 V and 50C / 200 hp
46 size 4, rated for 480 V and 50C / 250 hp
47 size 4, rated for 480 V and 50C / 300 hp
III

Type of Terminals
-1 Screw terminals for main circuit and control circuits
-2 Bus bars for main circuit and spring terminals for control circuits
-3 Screw terminals for main circuit and spring terminals for control circuits
-6 Bus bars for main circuit and screw terminals for control circuits

IV

Phases controlled and bypass


BC - 3-phase controlled with bypass

VII Operating Voltage


3115 V ac
4230 V ac
VIII Rated Voltage
4200 up to 480 V ac
5460 up to 600 V ac
6460 up to 600 V ac
Fans:
3RW4936-8VX40, 3RW4936-8VX30: for 3RW405, 3RW442, 3RW443
3RW4947-8VX40, 3RW4947-8VX30: for 3RW407, 3RW444

Bruce Mahrenholz, Director North American Certification Program


UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 10 of 10

Anda mungkin juga menyukai