Anda di halaman 1dari 4

INTERLOCKING TEST FORM

Revision :
Form No :
0
SUBCONTRACTO PROJECT :PLTU 2x100 MW CFSPP
:
R Lampung
DESCRIPTION : DRAWING No. :
LOCATION : REPORT No. : Date :

#2 Boiler Feed Water Pump


Result Remark
No Item
Good Failed
Alarm Test of Boiler Feed Water Pump
Hidraulic Coupling
One or more bearing temperature coupling is H,
1
90 C
20LAG20CT201
20LAG20CT202
20LAG20CT203
20LAG20CT204
20LAG20CT205
20LAG20CT206
Outgoing transmission oil temperature is H, 90
2
C
20LAV20CT301
3 Outgoing transmission oil pressure is L, 0.08MPa
20LAV20CP101
4 After filter outgoing oil pressure is L, 0.12MPa
20LAV20CP111
Incoming transmission oil temperature is H, 90
5
C
20LAV20CT311
Motor
BFP motor free and bearing temperature is H, 75
1
C
20LAK20CT205 Page13
BFP motor driving and bearing temperature is H,
2
75 C
20LAK20CT204

Tested Responsible Witness By Supervised by


by by
ADHI KARYA KIT SUM CONSULTAN PLN
T COMM.TEAM
Signature
Print
name
Date
INTERLOCKING TEST FORM

Revision :
Form No :
0
SUBCONTRACTO PROJECT :PLTU 2x100 MW CFSPP
:
R Lampung
DESCRIPTION : DRAWING No. :
LOCATION : REPORT No. : Date :

BFP motor stator winding temperature is H, 125


3
C
20LAC20CT211
20LAC20CT212
20LAC20CT213
Pump
1 BFP input and bearing temperature is H, 85 C
20LAK20CT201
2 BFP free and bearing temperature is H, 85 C
20LAK20CT202
3 BFP driving and bearing temperature is H, 85 C
20LAK20CT203
4 Pump vibration 5.5 mm/s
20LAK20CY101

Trip Condition Test of Boiler Feed Water Pump


Hidraulic BFP
One or more sleeve bearing temperature is HH,
1
95 C
20LAG20CT201
20LAG20CT202
20LAG20CT203
OR
AND 20LAG20CT204
20LAG20CT205
20LAG20CT206
20LAV20CT301, 90C

Page13
Outgoing transmission oil temperature is HH, 95
2
C
20LAV20CT301
3 After filter outgoing oil pressure is L, 0.1MPa
20LAV20CP111

Tested Responsible Witness By Supervised by


by by
ADHI KARYA KIT SUM CONSULTAN PLN
T COMM.TEAM
Signature
Print
name
Date
INTERLOCKING TEST FORM

Revision :
Form No :
0
SUBCONTRACTO PROJECT :PLTU 2x100 MW CFSPP
:
R Lampung
DESCRIPTION : DRAWING No. :
LOCATION : REPORT No. : Date :

Motor
1 Motor free and Bearing temperature is HH, 80 C
20LAK20CT205
Motor driving and Bearing temperature is HH, 80
2
C
20LAK20CT204
3 Motor Stator bearing temperature is HH, 130 C
20LAC20CT211
20LAC20CT212
20LAC20CT213
Pump
1 BFP input end bearing temperature is HH, 90 C
20LAK20CT201
2 BFP free end bearing temperature is HH, 90 C
20LAK20CT202
3 BFP driving end bearing temperature is HH, 90 C
20LAK20CT203
4 BFP vibration is HH, 6.5 mm/s
20LAK20CY101
Pressure Differential at strainer inlet BFP is H,
5
0.06 Mpa
20LAB20DP001
Other
BFP running, flow is less than minimum flow
1 value (25% rated value) and re-cycle valve is
closed, 10s delay.
Page13
2 Daerator level is LL, <1000mm
Permissive Start BFP
AND Coupling Lube Oil Normal
Recirculation valve open
Outlet Valve close

Tested Responsible Witness By Supervised by


by by
ADHI KARYA KIT SUM CONSULTAN PLN
T COMM.TEAM
Signature
Print
name
Date
INTERLOCKING TEST FORM

Revision :
Form No :
0
SUBCONTRACTO PROJECT :PLTU 2x100 MW CFSPP
:
R Lampung
DESCRIPTION : DRAWING No. :
LOCATION : REPORT No. : Date :

Jury Pump Running


Deaerator level Normal
Coupling in the smallest position
No Trip Condition
Sequence Start
1 Close Outlet valve
2 Close Desuperheater valve
3 Start feedwater Pump Auxilary
4 Make coupling is smallest location < 5%
5 Send signal to MCS
6 Open Recirculation valve
7 Start BFP
8 Open outlet valve
9 Release coupling
Sequence Stop
1 Start Aux Oil Pump
2 Signal to MCS
3 Close outlet valve
4 Close Desuperheater Valve
5 Stop BFP
6 Close Recirculation valve

Page13

Tested Responsible Witness By Supervised by


by by
ADHI KARYA KIT SUM CONSULTAN PLN