2 0 GHC 10 CL 001 10GHC10BB001 07485-20-GHC-MDD-TRE-120 01 Not Low Level in South Demi Water Tank 1L 1200 mm Permissive & start order for one demi water pump Setting value measured from bottom of tank
2 0 GHC 10 CL 001 10GHC10BB001 07485-20-GHC-MDD-TRE-120 01 Low Level in South Demi Water Tank 2L 1000 mm Stop order for demi water pump operating Setting value measured from bottom of tank
2 0 GHC 10 CL 001 10GHC10BB001 07485-20-GHC-MDD-TRE-120 01 Low Low Level in South Demi Water Tank 3L 800 mm Trip order for demi water pump operating Setting value measured from bottom of tank
2 0 GHC 20 CP 001 20GHC20BR001 07485-20-GHC-MDD-TRE-120 01 Low Pressure on Pumps Discharge Header 1L 4 bar g Operating demi water pump run-out alarm
2 0 GHC 20 CF 001 20GHC20BR001 07485-20-GHC-MDD-TRE-120 01 Low flow on Pumps Discharge Header 1L 23 m3/h Recirculation valve control loop operating 09/12/2015 setting changed
2L 21 m3/h Low Low alarm 09/12/2015 new
Low Low Low alarm. Trip GHC Pump #1. GHC
3L 19 m3/h
Pump #2 starts
0 0 0 0 20 CF 001 20GHC20BR001 07485-20-GHC-MDD-TRE-120 01 High flow on Pumps Discharge Header 1H 52 m3/h High alarm
High High alarm. Trip GHC Pump #1. GHC Pump
2H 54 m3/h
#2 starts
Signal calculated as 20GHC20CP001 (barg)*10.2-
(10GHC10CL001(m) - diference of elevation between
0 2 0 GHC 20 CP 001 20GHC11/12 AP001 0 01 High Pump TDH 1H 49,0 m level nozzle and pressure transmitter elevation (3.5m
from insometric)
High alarm. 10/12/2015 new
Signal calculated as 20GHC20CP001 (barg)*10.2-
(10GHC10CL001(m) - diference of elevation between
0 2 0 GHC 20 CP 001 20GHC11/12 AP001 0 01 Low Pump TDH 1L 32,0 m level nozzle and pressure transmitter elevation (3.5m
from insometric)
Low alarm. 10/12/2015 new