Procedure M01
March 2007
23/0101205/WP/27820
Comment [JAG1]: To reinsert the
APPENDICES and TABLE INDEX
lists if deleted, use the Shortcut Keys or
Autotext
Contents
23/01012/05/27820
1. Ductwork and Air Distribution Systems
The design of ductwork and air distribution systems shall be in accordance with this Design Guide unless
otherwise approved by the Principal Engineer or Project Manager.
1.1.1 General
This technical procedure addresses the design of low velocity systems (less than 12.5 m/s).
High velocity systems are rarely used because of high pressure losses and consequent high energy
consumption. They are usually designed using the static regain method of calculation which is
documented in other literature. (i.e. ASHRAE handbooks).
Ductwork systems shall be designed with some flexibility to allow redistribution of air for tenancy
changes. The velocities and friction rates set our herein are therefore conservative and can be
exceeded when more air is required from an existing system or when building constraints etc prevent use
of the preferred rates.
The extent to which the recommended velocities and friction rates can be exceeded will depend on the
particular circumstances. Shaft velocities of 10 m/s and main duct velocities of 9 m/s in office ceiling
spaces have been used satisfactorily on some occasions but as a guide, they should be limited to
and 7.5 m/s respectively. Friction rates are generally limited by fan static pressure capability or air
balancing considerations.
Large air quantities will usually be governed by the velocity limit and smaller air quantities by the friction
limit. The changeover point will usually be at air quantities around 1000 to 3000 l/s. Thus ductwork
towards the end of runs will generally be designed by the equal friction method.
Reducing fittings are more expensive to fabricate than straight ductwork. They should be used
economically and it will be appropriate in most cases to allow for two or more take-offs before reducing
the duct size. As a general comment, fittings, which reduce one duct dimension, are cheaper and should
be used in preference to those which reduce both dimensions. (Note that modern laser cutting machines
can produce fittings which reduce both dimensions as cheaply as reducing one dimension however,
traditionally manufactured reducing fittings are expensive to manufacture).
Square ducts and ducts with low aspect ratios are more economical than those with a high aspect ratio
and should be used where practical. Aspect ratios of 7:1 should not be exceeded unless special
conditions apply.
Brickwork and blockwork plenums have been successfully used for car park exhaust systems but care is
needed in their construction. The plenum face needs to be reasonably smooth particularly in narrow
sections to avoid high friction losses and at least one face must be bagged or rendered to ensure that it
is airtight. A flexible joint should be used in the joint between the top of the plenum wall and the soffit of
the slab above. When using this type of construction ensure that the fan is capable of a speed or pitch
change if necessary to compensate for 10-20% leakage. Alternatively, Trilock or similar rigid wall
construction could be used.
Supply Air
Duct branch with more than one diffuser or register directly 6.0 1.0
connected.
Return Air
Riser Shafts
With return air grilles directly connected to the occupied 6.0 1.2
space.
Fresh Air
Duct to small system (<3000 l/s) where no fresh air fan is 6.0 0.5
used.
Exhaust Air
Toilet exhaust:
Existing offices with poorly sealed windows, with 0.5 to 1.0 l/s.m 2
wooden window frames, with leaky facades.
The major considerations in sizing grilles and louvres are pressure loss and noise generation. These are
controlled by limiting the air velocity through the grille.
The noise and pressure loss are greatly influenced by the form of grille used, eg an egg crate type grille
has a much lower pressure loss than a full chevron door grille at the same velocity.
A particular problem arises when grilles and louvres are provided by others. The Architect is usually
given sizes for outside air louvres based on free area of 55%. He then specifies a vertical sight proof
louvre with excellent weather proofing properties built like a three break eliminator with hooked edges.
The pressure drop at design velocity is large and can be a disaster if the intake is for equipment such as
a cooing tower. In such cases ensure that the type of louvre or grille to be used is known at the outset
and provide sizing information to suit the pressure drop characteristics.
The design velocities listed below are based on the types of grilles commonly used in projects i.e.:
Face velocities of up to 3.5 m/s can be used on intakes for stairwell pressurisation systems where the
grille type selected permits this velocity without excessive pressure drops.
Where internal lighting can shine through louvres or grilles at night, insects can be drawn into the
building (i.e. Bogong moths being drawn into Parliament House relief air louvres in huge numbers).
Insect screens should be used in lieu of bird screens in such applications as long as they are readily
accessible for cleaning.
The number of grille sizes used should be minimised for any particular project eg 0.1 m 2 minimum with
2.
size increments of 0.05 m
Preferably use one size of grille only for any particular project and at a maximum use two sizes. 150
150 is a good minimum size to standardise on (up to 55 l/s). Provide a grille over each toilet bowl and
urinal. Ensure that the design documents clarify that the 150 x 150 is open face size not overall size
inclusive of border.
Low-level grilles should be located where they are least susceptible to damage by reversing vehicles
(especially those with tow bars). This can usually be achieved by centering them on the marked dividing
lines between parking bays and preferably in line with columns. In some cases guard rails or bollards
may be advisable.
Refer to AS 1668.2 for additional requirements in relation to location sizing and installation height.
Typically, maintain 2200 mm clear headroom beneath ductwork run within carparks. However, note that
under AS/NZS 2890.1 Parking Facilities, Off-street Parking, reference is made to a new standard that is
in preparation (as at September 2004). AS/NZS 2890.6 Off-street Parking for People with Disabilities, will
require any vehicular path of travel to or from a parking space for people with disabilities to have a
headroom clearance of 2300 mm.
Balancing dampers shall be provided behind grilles. Grilles shall not be located opposite doorways or in
other locations where they can directly discharge out through doorways.
Where a grille has to be located opposite a doorway a grille that deflects the supply air shall be used with
the velocity reduced such that the pressure drop across the grille is in the region of 25-35 Pa.
2.7 Relief Air Grilles for On-floor Plant with Outside Air Cycle Operation
Face Velocity
The principal criteria for selection of diffusers and registers are Air Diffusion Performance Index (ADPI),
throw, noise and pressure loss. Drop is also important for register selection.
A grille consists of a frame enclosing a set of either vertical or horizontal blades (single deflection) or
both (double deflection or universal type).
A register is a grille in combination with a volume control device such as opposed blade dampers
(OBDs).
Air Diffusion Performance Index (ADPI) also affects selection of air terminals. Details of ADPI are
covered in ASHRAE Fundamentals Handbook. ADPI is related to the ratio of the air throw at 0.25 m
terminal velocity (0.5 m/s for ceiling slot diffusers), the cooling load within the air conditioned space, and
the characteristic room length L. (L = the distance from the diffuser to the nearest boundary wall in the
principle horizontal direction of the airflow. If no boundary wall, then half the distance between adjacent
diffusers plus the distance the diffused supply air and room air travels down to reach the occupied zone).
For variable air volume (VAV) systems, outlets must be selected to provide satisfactory air distribution at
both the maximum and minimum air flows. Linear air outlets, plaque diffusers and light air diffusers are
more suitable for varying air flows than some other outlets
3.1 Diffusers
Diffusers shall be selected from catalogue data taking note of maximum and minimum throw and noise
level.
Diffusers shall be sized so that minimum throws do not overlap each other or any wall or obstruction at
ceiling level and the maximum throw provides reasonable coverage of the area served. One, two and
three way blow diffusers can be used when the minimum throw is obstructed on one or more sides.
Alternatively, the same effect can be achieved by partially blanking the back of the diffuser face provided
that the reduced capacity of the diffuser is taken into account, eg a four way blow diffuser blanked to
provide two way blow can only handle 50% of its rated capacity.
Diffusers shall be provided complete with neck plates in accordance with the manufacturers selection
criteria.
Diffuser shall be provided complete with insulated cushion heads. Cushion heads shall be full diffuser
face size and not neck size (i.e. 600 x 600 say, not 225 x 225 neck size). Full size cushion heads provide
flexibility for fitout modifications by enabling simple changes to be made to the neck plates to suit altered
supply air quantities.
Flexible ductwork shall be connected horizontally into the side of the cushion head and not vertically onto
the top as vertical connections adversely affect the cushioning effect provided by the cushion head and
hence air throw from the diffuser.
The minimum diffuser throw is also affected by the ceiling height. The minimum throw can be reduced
by 1.0 metre for every metre of ceiling height above 2.7 m.
Noise problems can be experienced with louvre type diffusers where restricted ceiling space prevents
installation of diffuser spigot connections of adequate length.
Noise can be generated by air flowing obliquely across the top of the diffuser blades and can be
significantly reduced in existing installations by fitting split plastic tubing over the sharp leading edges.
Whilst this technique may be useful for reducing an existing problem the recommended procedure is to
install diffusers in accordance with standard specification as illustrated below.
Conventional square or circular type supply air diffusers are unsatisfactory for variable volume systems
which turn down below 40% maximum volume as they will normally dump supply air below this value.
Dumping occurs when the discharge velocity from the diffuser reduces to the point where the Coanda
effect is insufficient to hold the cold air stream against the ceiling.
The Coanda effect is the principle by which velocity pressure in the airstream causes a lowering of static
pressure thereby enabling the higher room static pressure to hold the cold airstream against the ceiling.
(The total pressures in the room and in the airstream are equal).
When the velocity is too low the cold air stream falls from the ceiling before sufficient room air has been
entrained and the result is a cold draught and uneven room temperatures. Refer to paragraph 3.3
Luminaire Air Diffusers.
Cooling load in air conditioned space within T0.25/L: 2.0 T0.25/L: 2.0
range of 35 to 160 w/m 2
(Range of 1.0 to 3.4) (Range of 1.4 to
3.2 Registers
Side blow registers shall be selected to have suitable throw and drop characteristic for the particular
application.
Throw shall be selected to adequately cover the area being served. As a general rule the throw is
adequate if it covers the required distance with the vertical blades set for a straight blow.
Drop shall be selected so the air stream does not fall into the occupied level (ie 2.0 m above floor level
before the air stream is substantially dissipated. Drop is a characteristic of side blow outlets because
they do not establish a Coanda effect by blowing air across the surface of the ceiling. It is often
expressed in catalogue data as minimum ceiling height and is affected by supply air temperature. The
colder the supply air, the greater the drop.
Register throw and drop are affected by the registers aspect ratio and the setting of the direction control
blades.
A square register has the longest throw and drop whereas a long narrow register has a short throw and
drop. Thus a change of register aspect ratio can sometimes be used to overcome a problem of overblow
or underblow. For most applications the highest aspect ratio from the available standard sizes should be
used ie choose a 100 mm deep register rather than a 150 mm deep register where applicable.
The vertical direction control blades can be set for a straight blow or divergent blow. A divergent blow
shortens the throw and drop.
The other factor controlling throw and drop is register face velocity. Higher velocities produce longer
throws and slightly less drop. Face velocity should be between 1.5 and 2.5 m/s, based on 50% free grille
area.
Conventional registers are unsatisfactory for variable volume systems because they dump at low airflow.
Special registers are available which maintain a constant volume discharge through the bottom edge of
the register to prevent dumping when the upper section of the register reduces its volume.
The slot type diffuser has the advantage that due to the Coanda effect the slot will not dump supply air
even when turned down to below 20% design capacity. Below this design capacity some dumping may
occur but at this capacity the problem should not be great as the air quantity is very small. Dumping is
only likely to occur on start up in winter.
To minimise dumping it is important that variable volume outlets be selected to operate at near peak
design capacity to allow the maximum turn down before dumping occurs. This is more important in the
perimeter zones that the interior zones as the turn down is likely to be much greater on the perimeter.
Outlet Type Slot Width mm Slot Length mm Max Air Quanity l/s
Single 12 1020 45
Double 12 1020 75
Single 12 1400 50
Double 12 1400 75
Single 19 1020 55
Double 19 1020 85
Single 10 1400 60
Double 19 1400 85
The above figures are based on data supplied by Anemostat and will not necessarily apply directly to
other manufacturers products.
The standard luminaire air diffusers will only blow in one direction. Typically this is the direction back
towards the flexible duct connection. Where the flexibility of blowing in either or both directions is
required a more expensive type outlet can be provided to give this flexibility. Generally this flexibility is
not considered necessary.
Air quantities are selected for a room noise level of NC35 allowing a room attenuation of 8dB for an
absorbent room. Maximum airflow rates for specific manufacturers equipment should be based on
acoustic test data to achieve the desired room noise level.
Luminaire air diffusers should comply with AS 2946. The specification should include a requirement for
the electrical and mechanical contractors to provide a sample light fitting and single and double-sided
luminaire air diffusers for NATA certified acoustic testing. The specification should also detail installation
sequencing requirements to ensure full coordination amongst the contractors involved. Suggested
specification clause:
The electrical contractor shall provide luminaries in accordance with AS 2946, identical to
prototype luminaire provided for acoustic testing, and shall check each luminaire for full
compliance with all documented requirements.
The electrical contractor shall unpack each luminaire, inspect it for damage and, if undamaged,
provide suitable protection to prevent damage to finished surfaces, and position each luminaire
on the floor directly beneath its final ceiling location.
The mechanical contractor shall provide single and double luminaire air diffusers, check them
for damage and compliance with AS 2946 and, if undamaged, fit them securely to each
luminaire on the floor.
The electrical contractor shall install each combined luminaire/air diffuser in the false ceiling
suspension system, within 250 mm of the final position.
The mechanical contractor shall install flexible ductwork and connect each luminaire air diffuser
to the main supply duct spigot.
The electrical contractor shall connect power and control wiring to each luminaire.
The ceiling contractor shall install the ceiling tiles and adjust the final position of all luminaries
to meet the lighting layout requirements.
The electrical trade shall install fluorescent tubes in the luminaires to form a complete
luminaire/air diffuser installation.
4.1 Fans
When completing Fan Schedules, nominate the design air quantity and the static pressure and schedule
the size of each fan motor to satisfy 120% of the selected fan power requirement. This ensures that
installed fans have adequate spare electrical power available to suit the actual installed system (as
opposed to the system shown on the design documents) and a reasonable increase in fan duty if
required.
Scheduled fan static pressures and minimum motor kilowatts are provided for tendering purposes
only. They shall be adjusted by the contractor as necessary before ordering the fans to ensure that
the supplied equipment meets the requirements of the installed system duty. Fan motor sizes shall
be provided to have a minimum of 120 % of the power required by the fan for the installed system
duty.
4.2 Coils
Cooling Coils
- Maximum air velocity through the coil face area (to 2.5 m/s
prevent moisture carry over)
Heating Coils
Panel Type
High Efficiency:
Medium Efficiency:
High Efficiency:
Medium Efficiency:
- Motorised multi-blade damper sets for control of minimum outdoor air supply.
- Motorised multi-blade 2-position outdoor air dampers for control of tenants supplementary outdoor air.
- Manually adjustable dampers at spigot takeoffs serving outlets and registers mounted on the side of
ductwork.
SPLITTER DAMPERS
- Manually adjustable single or opposed blade dampers in branches other than parallel flow duct branch
takeoffs.