Anda di halaman 1dari 10

Trends in Electrical Engineering

Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

Investigation of DC link Capacitor Failures in DFIG based Wind Energy


Conversion System
Ali M. Eltamaly* & Ammar Anwar Khan

King Saud University, Riyadh, Saudi Arabia

Abstract

This paper presents the effects of DC link electrolytic capacitor failure of DFIG based wind
energy conversion system (WECS). The degradation of electrolytic capacitor can lead to the
failure of DC link. As DFIG based WECS utilize low power converter, so there is a need to
explore the effects of capacitor failure. This failure (short circuit of capacitor or open circuit)
leads to the power outages, high machine currents, high transient currents in rotor circuit, low
terminal voltage of the generator and increase in generator speed. For this purpose aggregated
model of DFIG is implemented in the MATLAB/ Simulink to study the effects of DC link
capacitor short/open circuit on different parameters of system.
Author for Correspondence
Keywords: DFIG, DC link failure, capacitor short circuit, stator flux orientation, capacitor open
circuit.

*Author for Correspondence E-mail: eltamaly@ksu.edu.sa Mob: +966553334130

I. INTRODUCTION

DFIG proves itself as one of the successful decreased by more than 25% [5]. It has been
generator topologies for wind energy reported in many researches that electrolytic
conversion systems due to its variable speed capacitors are the weakest link in power
operation and low power rating three phase electronic converters [7-12]. The failure of
AC/DC/AC converter. AC/DC/AC PWM DC link electrolytic capacitor can lead to
converters are widely used in motor drives, either short circuit or open circuit of DC link
wind power generation [1], unified power while remaining the converters intact. The
quality conditioners [2] etc. These capacitor degradation is due to the effects of
converters usually consist of DC link of thermal, electrical, mechanical and
array of electrolytic capacitors as energy environmental stresses and there can be any
buffer. Electrolytic capacitors are preferred reason of its failure. The primary failure
due to their large capacitance per volume mechanism is the evaporation of electrolytic
and low cost per capacitance. However they solution and its loss through end seal.
are sensitive to temperature, frequency and Temperature rise accelerates the evaporation
have low reliability [3-4]. The lifetime of rate. This evaporation leads to the decrease
electrolytic capacitor is usually shorter than in capacitance and increase in ESR
the other components of the converter. (equivalent series resistance) which
Reference [1] reported that 72% of the increases the losses. Thus the degradation
power supplies failures were due to process continues till the capacitor fails.
electrolytic capacitor failures. The Other modes of failures are mentioned as
capacitors are considered to be over when, [7]:
with the passage of time, their capacitance is

STM Journals 2011. All Rights Reserved. 12


Trends in Electrical Engineering
Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

1. Rupturing or explosion of capacitor due to asynchronous generator which generates


excessive internal pressure (when normal the power to feed the grid. In case of
operating ranges are exceeded). doubly fed induction generator, it has a low
2. Open/short circuit failures due to repeated power converter in its rotor side circuit to
mechanical stress on the leads or control the slip speed. Fig. 1 shows the
capacitor. general representation of a DFIG based
3. Corrosion of leads due to cleaner, wind farm.
adhesive, coating material (mainly for Power
r
Grid side
Grid
PCB mounted capacitors), or other foreign transformer
G Wind
material.
Tm
Despite the importance of electrolytic
capacitors, the related research is very
limited in the field of switch mode power Grid Side Rotor Side
Converter Converter
supplies, drives and wind energy conversion
systems. There a need to study the effects of Fig. 1: Schematic of interconnection of
failure of DC link electrolytic capacitor and DFIG with electric utility.
also to estimate the remaining life or degree
of degradation of capacitor. One of the a. Aerodynamic Model of wind turbine
common methods to estimate the life of The power exploited by wind turbine from
capacitor is monitoring the ESR as reported the wind is given by [15]:
in [10]. As the DC linked capacitor
1
converters are installed inside the systems, Pm C p R 2u 3 (1)
so they make it difficult to detach the 2
component and measure the degradation of
the capacitor. Also it is very difficult to It means that as wind speed changes, the
monitor manually of off-shore or on-shore pitch angle or tip speed ratio is so adjusted
wind turbines having high towers. to utilize maximum power contained in
References [13] and [14] explored the wind. The tip speed ratio is the ratio
capacitance and online condition monitoring between the tip speed R to the wind speed
of the electrolytic capacitors. This paper u. This tip speed ratio is defined as [15]:
R
deals with the study of results of DC link (2)
electrolytic capacitor failure on the DFIG u
system. High and comparatively low power
converters are widely used in DFIG, The power coefficient Cp is the function of
permanent magnet synchronous generator or tip speed ratio and the pitch angle and it
induction generator based wind energy given by [16]:
conversion systems. A 9MW wind farm is c
5
c
aggregated modeled in MATLAB/Simulink C p ( , ) c1 ( 2 c3 c 4 )e i c6 (3)
to study the effect of lumped model of DC i
link electrolytic capacitor failure. The next
sections discuss in details about the And i is given as:
modeling, control, effects of DC link failure 1 1 c
38 (4)
and simulation results. i c7 1
II. WIND ENERGY SYSTEM MODEL
The coefficients from c1 to c8 are defined as
Wind energy system consists of wind in Ref. [16].
turbine that is connected to synchronous or
STM Journals 2011. All Rights Reserved. 13
Trends in Electrical Engineering
Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

The stator reactive power as:


b. Modeling of DFIG
3
A fifth-order state space model of DFIG and Qs (vqsids vdsiqs ) (19)
second order drive train model is given 2
below [17]. All electrical variables and
parameters are referred to the stator. This is And electrical angle is:
v
indicated by the subscripts in the machine e e dt tan 1
equations given below. The subscripts used v
are defined as follows:
d : d-axis quantities c. Rotor-Side Converter Control
q : q- axis quantities By aligning the d-axis of the reference
r : rotor quantities frame (stator flux orientation) along with
s : stator quantities the grid voltage position vqs=0 and vds=Vs
l : leakage inductance quantities the active and reactive power can be
d obtained by using (18) and (19):
vqs Rsi qs qs eds (5) 3
dt Ps (vdsids ) (20)
d 2
vds Rsi ds ds eqs (6) 3
dt Qs (vdsiqs ) (21)
d 2
vqr Rr i qr qr (e r )dr (7)
dt
And iqs can be obtained as:
d
vdr Rr i dr dr (e r )qr (8) i L
dt iqs qr m (22)
3 Ls
Te P(dsiqs qsids ) (9)
2
Using (22) in (21):
3L
The fluxes are given as: Qs m (vdsiqr ) (23)
qs Lsiqs Lmiqr (10) 2 Ls
ds Lsids Lmidr (11)
From (23) it can be noticed that the stator
qr Lr iqr Lmiqs (12) reactive power Qs can be controlled by the
dr Lr idr Lmids (13) q-axis rotor current iqr. The reference for
Ls Lls Lm (14) the torque can be obtained from:
L
Lr Llr Lm (15) Te m (qsidr dsiqr ) (24)
Ls
d
m (16)
dt By using stator flux orientation control and
d 1 assuming ds=0:
(Te F Tm ) (17)
dt 2H L
Te m (qsidr ) (25)
Ls
The stator active power can be defined as
[19];
The value of qs can be obtained from (6)
3
Ps (vdsids vqsiqs ) (18) as:
2 v Rs ids
qs ds (26)
e

STM Journals 2011. All Rights Reserved. 14


Trends in Electrical Engineering
Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

Equations (23) and (25) give the references in DC link of converter makes it vulnerable
for iqr and idr respectively to independently to periodic degradation. This degradation of
control active and reactive power of the capacitor over the passage of years or loose
stator. link may result in short circuit or open
circuit of capacitor in the DC link. If the
d. Grid-Side Converter Control
capacitor is short circuited it will make the
The main function of the GSC is to control DC voltage as zero in the rotor and grid
the DC link voltage and to control active and side converter controllers. These controllers
reactive power from the DC link to the gird depend on Vdc for determining the
through grid side converter. If the dc modulation index for active power, reactive
voltage, Vdc is greater than its reference power and DC link voltage control. In case
value Vdc* this means that more power must of DC link short circuit, the GSC will try to
be moved from the DC link to electric utility charge the capacitor in order to raise the
via grid-side converter. The DC link voltage voltage of capacitor; hence it will exchange
is controlled by using stator voltage more power from the grid. On the other
orientation control [19]. This scheme hand, the firing sequences of the switches
permits independent control of the DC link are also dependent upon the DC link
voltage and reactive power. The active and voltage. The modulation indices of rotor
reactive power from the GSC to electric side convertor and grid side convertors are
utility is obtained from the following: determined by taking into account the DC
3
Pgc (vdsidgc vqsiqgc) (27) link voltage. Equation (31) gives the
2 relation that is used for determining the
3 modulation indices of RSC and GSC.
Qgc (vqsidgc vdsiqgc) (28)
2 2

Substituting for Vqs in (27) and (28): m Vnom * 2 * 3 (31)


Vdc
3
Pgc (vdsidgc ) (29) The DC voltage is present in the
2 denominator of the equation and can
3 present the divide by zero error if the
Qgc (vdsiqgc) (30)
2 measured DC voltage by the sensors is 0V.
However, based upon above equation, the
It is clear from these two equations that the converters will try to achieve maximum
active and reactive powers can be controlled modulation indices. Same is the case with
independently by using the reference open circuit capacitor link. This will create
currents from (29) and (30). The decoupled the fluctuating DC link voltage in which
control is implemented in order to control grid side converter will try to stable the DC
the active and reactive power by rotor and link voltage and rotor side converter will
grid side converters. The reference values of try to generate the sequence for controlling
voltages obtained from reference values of the torque. Either of these problems leads
currents are fed to the PWM controllers to to the machine instability and machine
generate the required signals to operate the suffers from power outages, low terminal
converters. voltage, high currents (in case of DC link
short circuit) and high rotor speed. Next
III. DC LINK CAPACITOR FAILURE section deals with the simulation of both
Off-shore or on-shore wind turbines bear the cases and their results on machine
harsh environmental conditions. The incor- output parameters.
-poration of array of electrolytic capacitors

STM Journals 2011. All Rights Reserved. 15


Trends in Electrical Engineering
Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

IV. SIMULATION RESULTS


A 9MW aggregated model of DFIG based
wind farm is simulated in Simulink. The
simulation time 0.4s and DC link failures of
short circuit or open circuit occur at 0.2s.
The model starts simulation using steady
state values. Table 1 and Table 2 give the
pre-fault and during fault (short circuit and
open circuit) parameters of wind farm. The
whole wind farm is simulated as a single Fig. 3: Generator complete current during
block and only the effect of lumped DC short circuit of capacitor.
link short circuit capacitor is studied to see
the effects of this failure on the same
system. Grid is modeled as 2500MVA
short circuit capacity with X0/X1=3. The
generator generates at voltage level 575V
which is stepped up to 25kV and
transmitted to the connection point through
30km transmission line and finally
connected to the grid by a step up
transformer 25kV/132kV. Simulation is
performed by using ode45 in Simulink with Fig. 4: Generator active power during short
step size of 1 microsecond. Fig. 2 to Fig. 9 circuit of capacitor.
show the behavior of generator output
parameters during the short circuit of
capacitor. For simulation purposes, the
short circuit is applied by simply by
passing the capacitor with a zero resistance
link.

Fig. 5: Generator reactive power during


short circuit of capacitor.

Fig. 2: Generator terminal voltage during


short circuit of capacitor.

Fig. 6: Generator rotor currents during short


circuit of capacitor.
STM Journals 2011. All Rights Reserved. 16
Trends in Electrical Engineering
Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

in higher currents as shown in Fig. 7. Fig. 4


and Fig. 5 show the generator active and
reactive powers. After the DC link capacitor
short circuit, the generator loses its active
power generation and terminal voltage.
However the demand for reactive power is
increased. This is due to the disturbance in
the control of grid side converter. Fig. 9
shows the rotor speed. The rotor speed
Fig. 7: Grid side converter currents during fluctuates around its rated speed during the
short circuit of capacitor. short circuiting of capacitor.

Fig. 8: DC link voltage during short circuit Fig. 10: Generator terminal voltage during
of capacitor. open circuit of capacitor.

Fig. 9: Rotor speed during short circuit of


capacitor. Fig. 11: Generator complete currents during
open circuit of capacitor.
Fig. 2 shows the generator terminal voltage.
The simulation was run with steady state
and at t=0.2s, short circuit was applied. The
voltage of the generator reached to 0.4pu of
its original value. The generator currents
reached up to 2pu with the transient peak
reaching 3pu as shown in Fig. 3. The
increased generator currents will result in
increased rotor currents. The rotor currents
reached up to 1 pu (previously 0.8 pu) with
the transient peak touching 3pu as seen in Fig. 12: Generator active power during
Fig. 6. The grid side converter will try to open circuit of capacitor.
increase the DC link voltage and will result
STM Journals 2011. All Rights Reserved. 17
Trends in Electrical Engineering
Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

Fig. 17: Rotor speed during open circuit of


Fig. 13: Generator reactive power during
capacitor.
open circuit of capacitor.
Fig. 10 to Fig. 17 show the generator
characteristics during open circuiting of the
DC link electrolytic capacitor. Fig. 10
shows that after the DC link capacitor
failure, the generator terminal voltage
remained 1pu but it was distorted as seen in
figure. The generator current control was
lost and generator currents reached up to
0.2 pu as shown in Fig 11. The generator
Fig. 14: Rotors currents during open circuit lost its active power generation capability
of capacitor. as given in Fig. 12. Fig 13 shows the
reactive power of the generator. Due to
oscillating DC link voltage the reactive
power oscillated around 0MVar as desired
reactive power is 0MVar. Fig. 14 and Fig.
15 show the rotor and grid side converter
currents. Both dropped up to 0.5pu and
0.1pu respectively. Fig. 16 shows the DC
link voltage which fluctuates during the
fault. Fig. 17 shows the rotor increased
speed above the rated speed.
Fig. 15: Grid side converter currents during
open circuit of capacitor. From Fig. 2 to Fig. 17, it is seen that DC
link capacitor failure leads to power loss
and low generator terminal voltage, high
rotor speed and failure of rotor side and
grid side converters control. The effects of
failure conditions are serious when this
generator is considered to be a part of wind
farm. Low terminal voltage, high currents,
loss of active power and reactive power
fluctuation can bring disturbance to the
complete system. As DC link is represented
Fig. 16: DC link voltage during open circuit by a lumped capacitor in the simulation. In
of capacitor. reality, arrays of capacitors are used.
However, due to aging and deterioration
due to long time of service, they can suffer
STM Journals 2011. All Rights Reserved. 18
Trends in Electrical Engineering
Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

from either short circuit or open circuit IV. CONCLUSIONS


problem.
The behavior of DC link short and open
Table 1. States of the parameters at pre- circuit is simulated in Simulink to observe
fault and during fault (short circuit the output parameters of DFIG based wind
capacitor). energy conversion system. DC link of DFIG
Parameters Pre-fault During constitutes the array of electrolytic
states fault capacitors. Electrolytic capacitors degrade
Active power 9MW 0MW with the passage of long time. DC link
Reactive 0MVar -8MVar represents the weakest link in converter and
Power is vulnerable to either short circuit or open
Generator 1pu 0.4pu circuit. During the short circuiting of
terminal capacitor, the generator terminal voltage
voltage falls, its active power capability is lost with
Generator 1pu 2.1pu high rotor and stator currents. The grid side
current converter exchanges high currents than the
Rotor current 0.8pu 2pu nominal values. In open circuit condition, the
DC link 1150V 1150V active power capability is lost and currents
voltage controllers at RSC and GSC fail. Rotor speed
increases in both conditions. These
Grid side 0.3pu 1.2pu
conditions are serious for other wind turbines
converter
in the same wind farm. The disturbance in
current
one generator can make complete wind farm
Rotor speed 1.20pu 1.25
unstable. However there is a need to study
the behavior of single generator DC link
Table 2. States of the parameters at pre-
failure on other generators performance in
fault and during fault (open circuit
the wind farm.
capacitor).
Parameters Pre-fault During fault REFERENCES
states
Active power 9MW 2MW
1) Pena R., Clare J. & Asher G. M. Doubly
Reactive 0MVar Oscillates
fed induction generator using back-to-back
Power around
PWM converters and its application to
0MVar
variable speed wind-energy generation
Generator 1pu 1pu but
IEE Proceedings Electric Power
terminal distorted
Applications 1996. 143(3) 231241p.
voltage
2) Fujita H. & Akagi H. The unified power
Generator 1pu 0.25pu
quality conditioner: the integration of
current
series- and shunt-active filters IEEE
Rotor current 0.8pu 0.5pu Transactions on Power Electronics 1998.
DC link 1150V Oscillates 13(2) 315322p.
votlage around 3) Military Handbook 217 F. Reliability
1150V prediction of electronic equipment Feb.
Grid side 0.3pu 0.1pu 28, 1995.
converter 4) Matsushita Electronic Components Co.
current Technical guide of aluminum electrolytic
Rotor speed 1.20pu 1.26 capacitors Mar. 2, 2000.

STM Journals 2011. All Rights Reserved. 19


Trends in Electrical Engineering
Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

5) Hitachi AIC Inc. Estimated life of -tions Magazine Jan-Feb., 2002. 8(1). 16
aluminium electrolytic capacitors Tokyo, 20p.
Japan. 1999. 13) Michael L. Gasperi A Method for
6) Harada K., Katsuki A. & Fujiwara M. Predicting the Expected Life of Bus
Use of ESR for deterioration diagnosis of Capacitors IEEE Industry Applications
electrolytic capacitor IEEE Transactions Society Annual Meeting New Orleans,
on Power Electronics Oct., 1993. 8(4) Louisiana. Oct. 5-9, 1997.
355361p. 14) Lee D.C., Lee K. J., Seok J. K. et al.
7) Lee K.W., Kim M., Yoon J. et al. Online capacitance estimation of DC-
Condition Monitoring of DC-Link link electrolytic capacitors for three-
Electrolytic Capacitors in Adjustable- phase AC/DC/AC PWM converters using
Speed Drives, IEEE Transactions on recursive least squares method IEE
Industrial Applications, pp. 16061613, Proceedings Electric Power Applications
Sept./Oct. 2008. Nov., 2005. 152(6) 1503-1508p.
8) Gasperi M. L. Life prediction modeling 15) Ali M. Eltamaly Modeling of Wind
of bus capacitors in ac variable-frequency Turbine Driving Permanent Magnet
drives IEEE Transactions on Industry Generator with Maximum Power Point
Applications Nov./Dec. 2005. 41(6) 1430 Tracking System Journal of King Saud
1435p. University. Engineering Sciences. 2007.
9) Sankaran V. A., Rees F. L. & Avant C. S. 19(2) 223-228p.
Electrolytic Capacitor Life Testing and P 16) Heier S., Grid Integration of Wind
rediction Proceedings of IEEE IAS Energy Conversion Systems John Wiley
Annual Meeting Oct. 1997. 1058- 1065p. & Sons Ltd, 2nd Edition. ISBN
10) Layhani A., Venet P., Grellet G. et al. 0470868996. 2006.
Failure prediction of electrolytic 17) Krause P. C., Wasynczuk O. & Sudhoff
capacitors during operation of a switch- S. D., Analysis of Electric Machinery,
mode power supply IEEE Transactions book, IEEE Press. 2002.
on Power Electronics Nov. 1998. 13(6) 18) Vas P. Sensorless Vector and Direct
11991207p. Torque Control, Oxford science
11) Ondel O., Boutleux E. & Venet P. A Publications. ISBN 13: 9780198564652.
decision system for electrolytic capacitors 1998.
diagnosis Proceedings of IEEE PESC 19) Yao J., Li H., Liao Y. et al. An
June, 2004. 4360-4364P. Improved Control Strategy of Limiting
12) Venet P., Perisse F., El-Husseini M. H. the DC-Link Voltage Fluctuation for a
et al. Realization of a smart electrolytic Doubly Fed Induction Wind Generator
capacitor circuit IEEE Industry Applica- IEEE Transactions on Power Electronics
2008. 23(3) 1205-1213p.

STM Journals 2011. All Rights Reserved. 20


Trends in Electrical Engineering
Volume 1, Issue 1, May, 2011, Pages 12-21.

____________________________________________________________________________________________

APPENDIX
Nomenclature qr , dr Rotor q and d axis fluxes
Pm Mechanical power from wind r Angular velocity of the rotor
turbine m Rotor angular position
Air density (kg/m3) P Number of pole pairs
R Radius of the swept area by e Electrical angular velocity
the blades (m) ( * P )
u Velocity of the wind (m/sec) e Electrical rotor angular
Cp Power coefficient. position ( m * P )
Angular velocity of the shaft Te Electromagnetic torque
(rad/sec) Tm Shaft mechanical torque
Tip speed ratio J Combined rotor and load
Blades pitch angle inertia coefficient. Set to
nom Tip speed ratio associated with infinite to simulate locked
the maximum coefficient of rotor
performance H Combined rotor and load
Rs ,Lls Stator resistance and leakage inertia constant. Set to infinite
inductance to simulate locked rotor
Rr,Llr Rotor resistance and leakage F Rotor and load viscous friction
inductance coefficient
Lm Magnetizing inductance Ps, Qs Stator active and reactive
Ls , Lr Total stator and rotor power
inductances Pgc , Qgc Active and reactive power
vqs , iqs q axis stator voltage and from the GSC to electric
current utility.
vqr , iqr q axis rotor voltage and idgc , iqgc d and q-axes of current from
current GSC.
vds , ids d axis stator voltage and Vdc DC-link voltage
current
vqr , iqr d axis rotor voltage and
current
qs , ds Stator q and d axis fluxes

STM Journals 2011. All Rights Reserved. 21

View publication stats

Anda mungkin juga menyukai