Anda di halaman 1dari 4

Worldwide

www.tyco-fire.com
Contacts

Model ESFR-17
16.8 K-factor Upright Sprinkler
Early Suppression, Fast Response
General when sizing system piping and posi-
tioning the system piping with respect
Description to the ceiling.
Applications for the TYCO ESFR Sprin-
TYCO Model ESFR-17 Upright Sprin- klers are expanding beyond currently
klers are Early Suppression, Fast recognized installation standards. For
Response (ESFR) sprinklers having a information on research fire tests that
nominal K-factor of 16.8 (Ref. Figure 1). may be acceptable to an authority
They are suppression mode sprinklers having jurisdiction, contact Tyco Fire
that are especially advantageous as a Protection Products (TFPP) Technical
means of eliminating in-rack sprinklers Services.
when protecting high-piled storage.
Model ESFR-17 Sprinklers are primarily NOTICE
used for ceiling-only sprinkler protec- The Model ESFR-17 Upright Sprinklers
tion of (but not limited to) the following described herein must be installed and
storage applications: maintained in compliance with this doc-
ument, as well as with the applicable
most encapsulated or non-encap-
standards of the National Fire Protec-
sulated common materials including
tion Association (NFPA), in addition to
cartoned, unexpanded plastics
the standards of any authorities having
cartoned, expanded plastics
some storage arrangements of
jurisdiction (e.g., FM Global). Failure to
do so may impair the performance of Technical
rubber tires and roll paper these devices.
The owner is responsible for main-
Data
For more specific criteria, refer to Table Approvals
A in this technical data sheet as well as taining their fire protection system
and devices in proper operating con- FM Approved
the applicable design standard. CE Certified (Certificate of Conformity
dition. Contact the installing contrac-
The Model ESFR-17 Upright Sprin- tor or product manufacturer with any 1725-CPD-H0012)
klers provide the system designer with questions. Maximum Working Pressure
an upright option to the traditional 175 psi (12,1 bar)
pendent ESFR Sprinklers. With a K-fac- In all cases, the appropriate NFPA or
tor of 16.8, Model ESFR-17 Sprinklers FM Global installation standard must Pipe Thread Connections
provide system designers with hydrau- be referenced to ensure applicabil- 3/4 Inch NPT or ISO 7-R 3/4
lic and sprinkler placement options not ity and to obtain complete installa-
Discharge Coefficient
presently available to traditional ESFR tion guidelines. The general guidelines
K=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)
Sprinklers having a K-factor of 14.0. In in this data sheet are not intended to
provide complete installation criteria. Temperature Ratings
particular, the Model ESFR-17 Upright 165F (74C) and 212F (100C)
Sprinklers are designed to operate at
substantially lower-end head pressures
compared to ESFR Sprinklers with 14.0
Sprinkler Finish
Natural Brass
K-factors. This feature offers flexibility Identification Physical Characteristics
Number (SIN)
Frame Brass
Deflector Copper
Compression Screw Stainless Steel
IMPORTANT TY7126 Hook MONEL
Strut MONEL
Always refer to Technical Data Link Assembly Solder, Nickel
Sheet TFP700 for the INSTALLER Button Brass
WARNING that provides cautions Sealing Assembly. . Beryllium Nickel w/TEFLON
with respect to handling and instal- Ejection Spring INCONEL
Deflector Nut Brass
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4 APRIL 2015 TFP316


TFP316
Page 2 of 4

2-9/16" DIA.
(65,0 mm)
10 TEMPERATURE
RATING

Components: 2
1 - Frame
2 - Deflector 3
3 - Compression
WRENCH
Screw
4 FLATS
4 - Hook THERMAL
5 - Strut 3-5/8" SENSING
6 - Link Assembly 5 (92,1 mm) ELEMENT
7 - Button
8 - Sealing
Assembly 6 1/2"
9 (12,7 mm)
9 - Ejection Spring
10 - Deflector Nut NOMINAL 1-5/8"
8 MAKE-IN (41,3 mm)

7 3/4" NPT

FIGURE 1
MODEL ESFR-17 UPRIGHT SPRINKLER, 16.8K
EARLY SUPPRESSION, FAST RESPONSE

Design System Type


Wet Pipe
FM Global
Centerline of Thermal Sensing

Criteria
Element-to-Ceiling Distance
Roof Construction Refer to FM Global 2-0 for Storage
Unobstructed or obstructed construc- Sprinklers.
The following general guidelines pro- tion (e.g., smooth ceiling, bar joists,
vided for the TYCO Model ESFR-17 beam and girder, and so forth) Obstructions below Upright ESFR
Upright Sprinklers may be used for Sprinklers, Including Branchlines
quick reference. Where the depths of the solid struc- Per the requirements of FM, obstruc-
tural members (e.g., beams and stem) tions below upright ESFR Sprinklers
The National Fire Protection Associa- exceed 12 inches (302 mm), install can be ignored as follows
tion (NFPA) and FM Global (FM Approv- ESFR Sprinklers in each channel
als) provide installation standards that formed by the structural members. open-web bar joists or trusses
must be used to properly design an having chords no more than 4
automatic sprinkler system utilizing Ceiling Slope inches (102 mm) wide
Early Suppression, Fast Response Maximum 2 inch rise for 12 inch run
(16.7%) bridging or wind bracing no more
(ESFR) Sprinklers. The guidelines pro- than 4 inches (102 mm) wide
vided by NFPA and FM Global may Maximum Coverage Area
differ; consequently, the appropriate 100 ft.2 (9,3 m2) individual pipes and conduit 4 inches
standard must be used for a given (102 mm) diameter or less 3 inch
installation. In some cases, the installation stan- [DN80] pipe size or less will not
dards permit a greater coverage area. require sprigs)
In all cases, the appropriate NFPA or
FM Global installation standard must Minimum Coverage Area individual groups of smaller pipe
be referenced to ensure applicabil- 64 ft.2 (5,8 m2) per or conduit having a total width of 4
ity and to obtain complete installation NFPA 13 / FM Global 2-0 inches or less
guidelines, since the following general Maximum Spacing
guidelines are not intended to provide
complete installation criteria.
12 feet (3,7 m) for building heights Operation
up to 30 feet (9,1 m)
The fusible link assembly is com-
In addition to this technical data sheet, 10 feet (3,1 m) for building heights prised of two link halves that are joined
the following data sheets describe greater than 30 feet (9,1 m) together by a thin layer of solder. When
other TYCO ESFR Sprinklers: the rated temperature is reached, the
Minimum Spacing
TFP312 8 feet (2,4 m) solder melts and the two link halves
Model ESFR-25 (TY9226) separate, activating the sprinkler and
K=25.2 Pendent Sprinkler Minimum Clearance to Commodity flowing water.
36 inches (914 mm)
TFP315
Model ESFR-17 (TY7226) NFPA 13
K=16.8 Pendent Sprinkler Deflector-to-Ceiling Distance
3 to 12 inches (76,2 to 304 mm)
TFP318
Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler
TFP316
Page 3 of 4

Storage Type NFPA FM Global

Open Frame (i.e., no solid shelves)


Refer to NFPA 13
Single, Double, Multiple-Row, or Portable Rack Storage of Refer to FM 2-0 and 8-9
Chapters 16 and 17
Class I-IV and Group A or B Plastics

Solid Pile or Palletized Storage of Refer to NFPA 13 Refer to FM 2-0 and 8-9
Class I-IV and Group A or B Plastics Chapters 14 and 15

Refer to NFPA 13
Idle Pallet Storage Refer to FM 2-0, 8-9, and 8-24
Chapter 12

Refer to NFPA 13
Rubber Tire Storage Refer to FM 2-0 and 8-9
Chapter 18

Roll Paper Storage Refer to Chapter 13 Refer to FM 8-21


(Refer to the standard) Chapter 19

Flammable/Ignitable Liquid Storage N/A Refer to FM 7-29


(Refer to the standard)

Aerosol Storage N/A N/A


(Refer to the standard)

Automotive Components in Portable Racks


N/A N/A
(Control mode only; refer to the standard)

N/A Not Applicable


TABLE A
MODEL ESFR-17 UPRIGHT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Installation Note: Install the Model ESFR-17


Upright Sprinkler in the Upright posi- WRENCH
TYCO Model ESFR-17 Early Suppres- tion (Ref. Figure 2). RECESS
sion, Fast Response 16.8K Upright Step 1. With pipe thread sealant
Sprinklers must be installed in accor- applied, hand-tighten the sprinkler into
dance with this section. the sprinkler fitting. Do not apply pres-
sure to the Link Assembly, and handle
General Instructions the Model ESFR-17 Sprinkler only by
Avoid damage to the fusible Link the Frame arms.
Assembly during installation by using
the Frame arms only to handle the Step 2. Wrench-tighten the Model "FITTING SIDE"
sprinkler (i.e., do not apply pressure ESFR-17 Upright Sprinkler using only TOWARDS SPRINKLER
to the fusible Link Assembly) and by the W-Type 21 Sprinkler Wrench (Ref. FITTING
using the appropriate sprinkler wrench. Figure 2) and by fully engaging (seating) FIGURE 2
Failure to do so can lead to an unstable the wrench on the sprinkler wrench W-TYPE 21
link assembly and premature activation flats (Ref. Figure 1). SPRINKLER WRENCH
of the sprinkler. Damaged sprinklers Step 3. After installation, inspect the
must be replaced. Link Assembly of each Model ESFR-17
A leak-tight 3/4 inch NPT sprinkler Sprinkler for damage. In particular,
joint should be obtained by apply- verify that the Link Assembly and Hook
ing a minimum-to-maximum torque of are positioned as illustrated in Figure
10 to 20 lbs.-ft. (13,4 to 26,8 Nm). 1, and that the Link Assembly is not
Higher levels of torque can distort the bent, creased, or forced out of normal
sprinkler inlet with consequent leakage position in any way. Replace damaged
or impairment of the sprinkler. sprinklers.
TFP316
Page 4 of 4

Care and Limited Ordering


Maintenance Warranty Procedure
TYCO Model ESFR-17 Early Suppres- For warranty terms and conditions, visit Contact your local distributor for avail-
sion, Fast Response 16.8K Upright www.tyco-fire.com. ability. When placing an order, indicate
Sprinklers must be maintained and ser- the full product name and part number
viced in accordance with this section. (P/N).
Before closing a fire protection system Sprinkler Assemblies
main control valve for maintenance Specify: Model ESFR-17 Early Sup-
work on the fire protection system that pression, Fast Response 16.8K Upright
it controls, permission to shut down the Sprinklers (TY7126), (specify tempera-
affected fire protection system must be ture rating), with Natural Brass finish,
obtained from the proper authorities P/N (specify):
and notify all personnel who may be
165F (74C) . . . . . . . . . . . . . . P/N 58-447-1-165
affected by this action. 212F (100C) . . . . . . . . . . . . . P/N 58-447-1-214
Sprinklers which are found to be
leaking or exhibiting visible signs of Special Order
corrosion must be replaced. Sprinkler Assemblies with
Automatic sprinklers must never be ISO 7-1 Thread Connection
painted, plated, coated, or other- Specify: Model ESFR-17 Early Sup-
wise altered after leaving the factory. pression, Fast Response 16.8K Upright
Modified sprinklers must be replaced. Sprinklers (TY7126) with ISO 7-1 thread
Sprinklers that have been exposed to connection, (specify temperature
rating), with Natural Brass finish, P/N
corrosive products of combustion, but
(specify):
have not operated, should be replaced
if they cannot be completely cleaned 165F (74C) . . . . . . . . . . . . . . P/N 58-448-1-165
by wiping the sprinkler with a cloth or 212F (100C) . . . . . . . . . . . . . P/N 58-448-1-214
by brushing it with a soft bristle brush.
Sprinkler Wrench
Care must be exercised to avoid Specify: W-Type 21 Sprinkler Wrench,
damage to the sprinklers before, P/N 56-001-0-686
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installa-
tion Section).
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any authorities having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinkler systems are
recommended to be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
INCONEL and MONEL are trademark of Special Metals Corporation.
TEFLON is trademark of the DuPont Corporation.

Anda mungkin juga menyukai