155
1506.2 1508.5 UNIFORM PLUMBING CODE
standard(s) referenced in Section 1506.3 and at an 1506.7 Unshielded couplings shall not be used to
independent testing agency acceptable to the connect non-combustible piping unless it can be
Administrative Authority. demonstrated that the fire resistive integrity of the
Exceptions: penetration is maintained.
1. Concrete, mortar, or grout may be used to
fill the annular spaces around cast iron, copper, 1507.0 Model Code References
or steel piping that penetrates concrete or 1507.1 ICBO Uniform Building Code (1997
masonry fire resistant rated assemblies. The edition), Chapters 5 and 6 for heights and areas and
nominal diameter of the penetrating item should occupancies, Chapter 7 for fire resistance ratings and
not exceed 6 inches (15.2 cm) and the opening firestop systems.
size should not exceed 144 sq. in. (929 sq. cm).
1507.2 BOCA National Building Code (1999
The thickness of concrete, mortar, or grout
edition), Chapters 5 and 6 for heights and areas and
should be the full thickness of the assembly or
occupancies, Chapter 7 for fire resistance ratings and
the thickness necessary to provide a fire
firestop systems.
resistance rating not less than the required fire
resistance rating of the assembly penetrated. , or 1507.3 SBCCI Standard Building Code (1997
edition), Chapters 5 and 6 for heights and areas and
2. The material used to fill the annular space
occupancies, Chapter 7 for fire resistance ratings and
shall prevent the passage of flame and hot gases
firestop systems.
sufficient to ignite cotton waste for the time
period equivalent to the fire resistance rating of 1507.4 NFPA 101, Life Safety Code (1997 edition),
the assembly when tested to standard(s) Chapter 6 for fire resistance ratings and firestop
referenced in Section 1506.3. systems.
1506.3 Penetrations shall be protected by an
approved penetration firestop system installed as 1508.0 Inspection Checklist
tested in accordance with ASTM E 119 or ASTM E 1508.1 General. The Administrative Authority shall
814, with a minimum positive pressure differential of obtain verification of compliance with this chapter
0.01 inch of water. Systems shall have an F rating of through the application of this checklist, the
at least 1 hour but not less than the required fire appropriate installation standards, construction
resistance rating of the assembly being penetrated. documents, specifications and manufacturers product
Systems protecting floor penetrations shall have a T information (if applicable) to determine required
rating of at least 1 hour but not less than the required details.
fire resistance rating of the floor being penetrated.
1508.2 The Administrative Authority having
Floor penetrations contained within the cavity of a
jurisdiction shall determine the type, size and
wall at the location of the floor penetration do not
quantity of penetrations to be inspected.
require a T rating. No T rating shall be required for
floor penetrations by piping that is not in direct 1508.3 The Administrative Authority having
contact with combustible material. jurisdiction shall determine the required F ratings (1,
2, 3, or 4 hour) and T ratings (0, 1, 2, 3, or 4 hour) for
1506.4 The penetration must meet any additional
the assembly being penetrated.
requirements for protection of the penetration in the
building code adopted by the Administrative 1508.4 The Administrative Authority having
Authority. When no building code has been adopted jurisdiction shall require documentation (drawings)
by the local Administrative Authority the of systems installed by the contractor. This could be
penetration requirements shall be as required in a tested system or a manufacturers engineered
NFPA 101, Life Safety Code. system judgement. Ask for product data sheets of
products used for identification.
1506.5 Prior to being concealed, piping penetrations
shall be inspected to verify compliance with the fire 1508.5 Examination
resistance rating prescribed in the building code or, 1508.5.1 External Examination. The assembly
in the absence of a building code NFPA 101, Life type, insulation type and thickness, type and
Safety Code. size of any sleeve, type and size of penetrant,
1506.6 When piping penetrates a rated assembly, size of opening, orientation of penetrant, annular
combustible piping shall not connect to non- space and rating shall be inspected for
combustible piping unless it can be demonstrated that compliance with the approved drawing
the transition complies with the requirements of submitted.
1506.3.
156
FIRESTOP PROTECTION FOR DWV AND STORMWATER APPLICATIONS 1508.5
157
UNIFORM PLUMBING CODE
158