Anda di halaman 1dari 70

Chapter 5.

Control Valve Selection

Liquid Sizing Sample Problem "1)2

Assume an installation that, at initial


plant start-up, will not be operating at
Fp ! $ C
1 % #K 2v
N2 d
& '(
2

maximum design capability. The lines


are sized for the ultimate system ca- where,
pacity, but there is a desire to install a
N2 = 890, from the Equation
control valve now which is sized only
Constants table
for currently anticipated requirements.
The line size is 8 inches, and a Class d = 3 in., from step 1
300 globe valve with an equal per-
centage cage has been specified. Cv = 121, from the flow coefficient
Standard concentric reducers will be table for a Class 300, 3 in. Globe
used to install the valve into the line. valve with equal percentage cage
Determine the appropriate valve size.
To compute !K for a valve installed
1. Specify the necessary variables re- between identical concentric reducers:
quired to size the valve:
#K ! K 1 % K 2
" Desired valve designClass 2
300 globe valve with equal percent- & 2
! 1.5 1 " d 2
D
'
age cage and an assumed valve size
of 3 inches. 2

" Process fluidliquid propane


&
(3) 2
! 1.5 1 " 2
(8)
'
" Service conditions ! 1.11
where,
q = 800 gpm
D = 8 in., the internal diameter of
P1 = 300 psig = 314.7 psia the piping so,
"1)2

$ & '(
P2 = 275 psig = 289.7 psia 2
F p ! 1 % 1.11 121
$P = 25 psi 890 3 2

T1 = 70!F ! 0.90
Gf = 0.50 4. Determine $Pmax (the Allowable
Sizing Pressure Drop.)
Pv = 124.3 psia
Based on the small required pressure
Pc = 616.3 psia drop, the flow will not be choked
($Pmax > $P).
2. Determine an N1 value of 1.0 from
the Equation Constants table. 5. Solve for Cv, using the appropriate
equation.
3. Determine Fp, the piping geometry q
factor. Cv !
#P1"P2
N 1F P Gf
Because it is proposed to install a
3-inch valve in an 8-inch line, it will be
necessary to determine the piping ge- ! 800
ometry factor, Fp, which corrects for (1.0)(0.90) #0.5
25

losses caused by fittings attached to


the valve. ! 125.7
117
Chapter 5. Control Valve Selection
6. Select the valve size using the flow ! 121.7
coefficient table and the calculated Cv
value.
This solution indicates only that the
The required Cv of 125.7 exceeds the 4-inch valve is large enough to satisfy
capacity of the assumed valve, which the service conditions given. There
has a Cv of 121. Although for this ex- may be cases, however, where a
ample it may be obvious that the next more accurate prediction of the Cv is
larger size (4 inches) would be the required. In such cases, the required
correct valve size, this may not always Cv should be redetermined using a
be true, and a repeat of the above new Fp value based on the Cv value
procedure should be carried out. obtained above. In this example, Cv is
121.7, which leads to the following re-
Assuming a 4-inch valve, Cv = 203. sult:
This value was determined from the
flow coefficient table for a Class 300,
4-inch globe valve with an equal per- "1)2
centage cage.
Recalculate the required Cv using an
Fp ! $ C
1.0 % #K 2v
N2 d
& '(
2

assumed Cv value of 203 in the Fp


calculation.
where, "1)2

#K ! K 1 % K 2 $
! 1.0 % 0.84 121.7
890 42
& '(
2

2
& 2
! 1.5 1 " d 2
D
'
! 0.97
2
&
! 1.5 1 " 16
64
'
The required Cv then becomes:
! 0.84
and q
Cv !
"1)2 N 1F p # P 1"P2

$ & '(
2 Gf
C
Fp ! 1.0 % #K 2v
N2 d

! 800
(1.0)(0.97) #0.5
"1)2

$
! 1.0 % 0.84 203
890 4 2
& '(
2 25

! 0.93 ! 116.2

and
Because this newly determined Cv is
q very close to the Cv used initially for
Cv !
N 1F p # P 1"P2
Gf
this recalculation (116.2 versus
121.7), the valve sizing procedure is
complete, and the conclusion is that a
800 4-inch valve opened to about 75-per-
! cent of total travel should be adequate
(1.0)(0.93) #0.5
25
for the required specifications.
118
Chapter 5. Control Valve Selection

Sizing Valves for Use either N7 or N9 if sizing the valve


for a flow rate in volumetric units (scfh
Compressible Fluids or m3/h). Which of the two constants
Following is a six-step procedure for to use depends upon the specified
the sizing of control valves for com- service conditions. N7 can be used
pressible flow using the ISA standard- only if the specific gravity, Gg, of the
ized procedure. Each of these steps is following gas has been specified
important and must be considered along with the other required service
during any valve sizing procedure. conditions. N9 can be used only if the
Steps 3 and 4 concern the determina- molecular weight, M, of the gas has
tion of certain sizing factors that may been specified.
or may not be required in the sizing
equation depending on the service Use either N6 or N8 if sizing the valve
conditions of the sizing problem. If it is for a flow rate in mass units (lb/h or
necessary for one or both of these siz- kg/h). Which of the two constants to
ing factors to be included in the sizing use depends upon the specified ser-
equation for a particular sizing prob- vice conditions. N6 can be used only if
lem, refer to the appropriate factor de- the specific weight, !1, of the flowing
termination section(s), which is refer- gas has been specified along with the
enced and located in the following other required service conditions. N8
text. can be used only if the molecular
weight, M, of the gas has been speci-
1. Specify the necessary variables re-
fied.
quired to size the valve as follows:
" Desired valve design (e.g. bal- 3. Determine Fp, the piping geometry
anced globe with linear cage); refer to factor. Fp is a correction factor that ac-
the appropriate valve flow coefficient counts for any pressure losses due to
table piping fittings such as reducers, el-
bows, or tees that might be attached
" Process fluid (air, natural gas, directly to the inlet and outlet connec-
steam, etc.) and tions of the control valves to be sized.
If such fittings are attached to the
" Appropriate service conditions valve, the Fp factor must be consid-
ered in the sizing procedure. If, how-
q, or w, P1, P2 or $P, T1, Gg, M, k, ever, no fittings are attached to the
Z, and !1 valve, Fp has a value of 1.0 and sim-
ply drops out of the sizing equation.
The ability to recognize which terms
are appropriate for a specific sizing
procedure can only be acquired Also, for rotary valves with reducers,
through experience with different Fp factors are included in the ap-
valve sizing problems. If any of the propriate flow coefficient table. For
above terms appear to be new or un- other valve designs and fitting styles,
familiar, refer to the Abbreviations and determine the Fp factors by using the
Terminology table for a complete defi- procedure for Determining Fp the Pip-
nition. ing Geometry Factor, which is located
in the section for Sizing Valves for Liq-
2. Determine the equation constant, uids.
N. N is a numerical constant con-
tained in each of the flow equations to
4. Determine Y, the expansion factor,
provide a means for using different
as follows:
systems of units. Values for these var-
ious constants and their applicable
units are given in the Equation Y!1" x
Constants table. 3F k x T
119
Chapter 5. Control Valve Selection
where, 5. Solve for the required Cv using the
appropriate equation:
Fk = k/1.4, the ratio of specific
heats factor For volumetric flow rate units

k = Ratio of specific heats " If the specific gravity, Gg, of the


gas has been specified:
x = $P/P1, the pressure drop ratio
q
Cv !
xT = The pressure drop ratio factor
for valves installed without at-
N7 Fp P1 Y # x
Gg T1 Z

tached fittings. More definitively,


xT is the pressure drop ratio re- " If the molecular weight, M, of the
quired to produce critical, or gas has been specified:
maximum, flow through the q
valve when Fk = 1.0 Cv !
N9 Fp P1 Y # x
M T1 Z
If the control valve to be installed has
fittings such as reducers or elbows at- For mass flow rate units
tached to it, then their effect is ac-
counted for in the expansion factor " If the specific weight, !1, of the
equation by replacing the xT term with gas has been specified:
a new factor xTP. A procedure for de-
termining the xTP factor is described in Cv ! w
the section for Determining xTP, the N 6F pY #x P 1 ! 1
Pressure Drop Ratio Factor.
" If the molecular weight, M, of the
gas has been specified:
Note
Cv ! w
Conditions of critical
pressure drop are real- N8 Fp P1 Y # x M
T1 Z
ized when the value of x
becomes equal to or ex- In addition to Cv, two other flow coeffi-
ceeds the appropriate cients, Kv and Av, are used, particular-
value of the product of ly outside of North America. The fol-
either Fk xT or Fk xTP at lowing relationships exist:
which point:
K v ! (0.865)(C v)
y!1" x ! 1 " 1)3 ! 0.667
3F k x T A v ! &2.40 X 10 "5'(C v)
Although in actual service, pressure 6. Select the valve size using the ap-
drop ratios can, and often will, exceed propriate flow coefficient table and the
the indicated critical values, this is the calculated Cv value.
point where critical flow conditions de-
velop. Thus, for a constant P1, de- Note
creasing P2 (i.e., increasing $P) will
not result in an increase in the flow Once the valve sizing
rate through the valve. Values of x, procedure is completed,
therefore, greater than the product of consideration can be
either FkxT or FkxTP must never be made for aerodynamic
substituted in the expression for Y. noise prediction. To de-
This means that Y can never be less termine the gas flow siz-
than 0.667. This same limit on values ing coefficient (Cg) for
of x also applies to the flow equations use in the aerodynamic
that are introduced in the next section. noise prediction tech-
120
Chapter 5. Control Valve Selection
nique, use the following mining Fp, the piping Geometry
equation: factor, which is contained in the
section for Sizing Valves for Liq-
C g ! 40 C v #x T uids.)

Determining xTP, the Compressible Fluid Sizing


Pressure Drop Ratio Sample Problem No. 1
Factor Determine the size and percent open-
If the control valve is to be installed ing for a Fisher Design V250 ball
with attached fittings such as reducers valve operating with the following ser-
or elbows, then their effect is ac- vice conditions. Assume that the valve
counted for in the expansion factor and line size are equal.
equation by replacing the xT term with
a new factor, xTP. 1. Specify the necessary variables re-
quired to size the valve:
"1

x TP !
xT
Fp
$2
x K Cv
1% T i
N5 d 2
& '(
2
" Desired valve designDesign
V250 valve

where, " Process fluidNatural gas

N5 = Numerical constant found in " Service conditions


the Equation Constants table
P1 = 200 psig = 214.7 psia
d = Assumed nominal valve size
Cv = Valve sizing coefficient from P2 = 50 psig = 64.7 psia
flow coefficient table at 100 per-
cent travel for the assumed $P = 150 psi
valve size
x = $P/P1 = 150/214.7 = 0.70
Fp = Piping geometry factor
T1 = 60!F = 520!R
xT = Pressure drop ratio for valves
installed without fittings at- M = 17.38
tached. xT values are included
in the flow coefficient tables Gg = 0.60
In the above equation, Ki, is the inlet k = 1.31
head loss coefficient, which is defined
as: q = 6.0 x 106 scfh
K i ! K 1 % K B1 2. Determine the appropriate equation
constant, N, from the Equation
where,
Constants table.
K1 = Resistance coefficient of up-
stream fittings (see the proce- Because both Gg and M have been
dure for Determining Fp, the given in the service conditions, it is
Piping Geometry Factor, which possible to use an equation containing
is contained in the section for either N7 or N9. In either case, the end
Sizing Valves for Liquids). result will be the same. Assume that
the equation containing Gg has been
KB1 = Inlet Bernoulli coefficient arbitrarily selected for this problem.
(see the procedure for Deter- Therefore N7 = 1360.
121
Chapter 5. Control Valve Selection
3. Determine Fp, the piping geometry 6. Select the valve size using the ap-
factor. Since valve and line size are propriate flow coefficient table and the
assumed equal, Fp = 1.0. calculated Cv value.
4. Determine Y, the expansion factor. The above result indicates that the
k valve is adequately sized (rated Cv =
Fk ! 2190). To determine the percent valve
1.40
opening, note that the required Cv oc-
! 1.31 curs at approximately 83 degrees for
1.40 the 8-inch Design V250 valve. Note
also that, at 83 degrees opening, the
! 0.94 xT value is 0.252, which is substantial-
It is assumed that an 8-inch Design ly different from the rated value of
V250 valve will be adequate for the 0.137 used initially in the problem.
specified service conditions. From the The next step is to rework the problem
flow coefficient table, xT for an 8-inch using the xT value for 83 degrees trav-
Design V250 valve at 100-percent el.
travel is 0.137.
The Fk xT product must now be recal-
x = 0.70 (This was calculated in culated.
step 1.)
x ! Fk x T
Since conditions of critical pressure
drop are realized when the calculated
value of x becomes equal to or ex- ! (0.94) (0.252)
ceeds the appropriate value of FkxT,
these values should be compared. ! 0.237
F kx T ! (0.94) (0.137) The required Cv now becomes:
! 0.129
q
Cv !
Because the pressure drop ratio, x =
0.70 exceeds the calculated critical
N7 Fp P1 Y # x
Gg T1 Z

value, FkxT = 0.129, choked flow con-


ditions are indicated. Therefore, Y = 6.0 x 10 6
0.667, and x = FKXT = 0.129. !
&1360'&1.0'&214.7'&0.667' # 0.237
(0.6)(520)(1.0)
5. Solve for required Cv using the ap-
propriate equation.
! 1118
q
Cv !
N7 Fp P1 Y # x
Gg T1 Z
The reason that the required Cv has
dropped so dramatically is attributable
The compressibility factor, Z, can be solely to the difference in the xT val-
assumed to be 1.0 for the gas pres- ues at rated and 83 degrees travel. A
sure and temperature given and Cv of 1118 occurs between 75 and 80
Fp = 1 because valve size and line degrees travel.
size are equal.
The appropriate flow coefficient table
So, indicates that xT is higher at 75 de-
grees travel than at 80 degrees travel.
6.0 x 10 6 Therefore, if the problem were to be
Cv !
&1360'&1.0'&214.7'&0.667' # 0.129
(0.6)(520)(1.0)
reworked using a higher xT value, this
should result in a further decline in the
! 1515 calculated required Cv.
122
Chapter 5. Control Valve Selection
Reworking the problem using the xT c. Service conditions
value corresponding to 78 degrees
travel (i.e., xT = 0.328) leaves: w = 125,000 lb/h

x ! Fk xT P1 = 500 psig = 514.7 psia


P2 = 250 psig = 264.7 psia
! (0.94) (0.328)
$P = 250 psi
! 0.308
x = $P/P1 = 250/514.7 = 0.49
and,
T1 = 500!F
q
Cv ! = 1.0434 lb/ft3 (from Proper-
N7 Fp P1 Y # x
Gg T1 Z
!1
ties of Saturated Steam table)

6.0 x 10 6 k= 1.28 (from Properties of Sat-


! urated Steam table)
(1360)(1.0)(214.7)(0.667) # 0.308
(0.6)(520)(1.0)
2. Determine the appropriate equation
constant, N, from the Equation
! 980 Constants table.
The above Cv of 980 is quite close to Because the specified flow rate is in
the 75 degree travel Cv. The problem mass units, (lb/h), and the specific
could be reworked further to obtain a weight of the steam is also specified,
more precise predicted opening; how- the only sizing equation that can be
ever, for the service conditions given, used is that which contains the N6
an 8-inch Design V250 valve installed constant. Therefore,
in an 8-inch line will be approximately
75 degrees open. N 6 ! 63.3
3. Determine Fp, the piping geometry
Compressible Fluid Sizing factor.
Sample Problem No. 2
"1)2
Assume steam is to be supplied to a
process designed to operate at 250
psig. The supply source is a header
Fp ! $ C
1 % #K 2v
N2 d
& '(
2

maintained at 500 psig and 500!F. A


6-inch line from the steam main to the where,
process is being planned. Also, make N2 = 890, determined from the
the assumption that if the required Equation Constants table
valve size is less than 6 inches, it will
be installed using concentric reducers. d = 4 in.
Determine the appropriate Design ED
valve with a linear cage. Cv = 236, which is the value listed
in the manufacturers Flow Co-
1. Specify the necessary variables re- efficient table for a 4-inch De-
quired to size the valve: sign ED valve at 100-percent to-
tal travel.
a. Desired valve designClass
300 Design ED valve with a linear and
cage. Assume valve size is 4 inch-
es. #K ! K 1 % K 2
2
b. Process fluidsuperheated
steam
& 2
! 1.5 1 " d 2
D
'
123
Chapter 5. Control Valve Selection

$ & '(
2
&
! 1.5 1 " 4 2
6
2
' & D
2
! 0.5 1 " d 2 '
2
% 1" d
D
4

! 0.463
Finally:
"1)2
& 6
2
! 0.5 1 " 4 2 '
2
$
% 1" 4
6
& '(
4

+ &
(1.0)(236)
' -.*
2

*
F p ! 1 % 0.463
, 890 (4)
2
! 0.96

! 0.95
where D = 6 in.
4. Determine Y, the expansion factor.
x so:
Y!1"
3F k x TP
"1
where,

Fk ! k
X TP ! 0.692 1
0.95
$ 1000
&4 '(
&0.69'&0.96' 236
2
2

1.40
! 0.67
1, 28
!
1.40
Finally:
! 0.91

x ! 0.49 (As calculated in step Y!1" x


1.) 3 F k x TP

Because the 4-inch valve is to be


installed in a 6-inch line, the xT term !1" 0.49
must be replaced by xTP. (3) (0.91) (0.67)
"1

x TP !
xT
Fp 2
$x K C
1 % T i 2v
N5 d
& '(
2
! 0.73

5. Solve for required Cv using the ap-


where, propriate equation.
N5 = 1000, from the Equation
Constants table Cv ! w
N6 FP Y #x P 1 ! 1
d = 4 in.
Fp = 0.95, determined in step 3
125, 000
Cv !
xT = 0.688, a value determined (63.3)(0.95)(0.73) #(0.49)(514.7)(1.0434)
from the appropriate listing in
the manufacturers Flow Coeffi-
cient table ! 176

Cv = 236, from step 3


6. Select the valve size using the ap-
and propriate manufacturers Flow Coeffi-
cient table and the calculated Cv val-
K i ! K 1 % K B1 ue.
124
Chapter 5. Control Valve Selection
Refer to the manufacturers Flow Co- that the calculated required Cv had
efficient tables for Design ED valves been small enough to have been han-
with linear cage. Because the as- dled by the next smaller size or if it
sumed 4-inch valve has a Cv of 236 at had been larger than the rated Cv for
100-percent travel and the next small- the assumed size, it would have been
er size (3 inches) has a Cv of only necessary to rework the problem
148, it can be surmised that the as- again using values for the new as-
sumed size is correct. In the event sumed size.

125
Representative Sizing Coefficients for SinglePorted Globe Style Valve Bodies

126
Rated
Valve Size Port Dia.
Valve Plug Style Flow Characteristic Travel CV FL XT FD
(inches) (in.)
(in.)
1/2 Post Guided Equal Percentage 0.38 0.50 2.41 0.90 0.54 0.61
3/4 Post Guided Equal Percentage 0.56 0.50 5.92 0.84 0.61 0.61
Micro Form! Equal Percentage 3/8 3/4 3.07 0.89 0.66 0.72
1/2 3/4 4.91 0.93 0.80 0.67
1 3/4 3/4 8.84 0.97 0.92 0.62
Cage Guided Linear 1 5/16 3/4 20.6 0.84 0.64 0.34
Equal Percentage 1 5/16 3/4 17.2 0.88 0.67 0.38
MicroForm! Equal Percentage 3/8 3/4 3.20 0.84 0.65 0.72
1/2 3/4 5.18 0.91 0.71 0.67
Chapter 5. Control Valve Selection

1 1/2 3/4 3/4 10.2 0.92 0.80 0.62


Cage Guided Linear 1 7/8 3/4 39.2 0.82 0.66 0.34
Equal Percentage 1 7/8 3/4 35.8 0.84 0.68 0.38
Cage Guided Linear 2 5/16 1 1/8 72.9 0.77 0.64 0.33
2
Equal Percentage 2 5/16 1 1/8 59.7 0.85 0.69 0.31
Cage Guided Linear 3 7/16 1 1/2 148 0.82 0.62 0.30
3
Equal Percentage 136 0.82 0.68 0.32
Cage Guided Linear 4 3/8 2 236 0.82 0.69 0.28
4
Equal Percentage 224 0.82 0.72 0.28
Cage Guided Linear 7 2 433 0.84 0.74 0.28
6
Equal Percentage 394 0.85 0.78 0.26
Cage Guided Linear 8 3 846 0.87 0.81 0.31
8
Equal Percentage 818 0.86 0.81 0.26
Representative Sizing Coefficients for Rotary Shaft Valves
Valve Size Degrees of Valve
Valve Style Cv FL XT FD
(inches) Opening
1 VNotch Ball Valve 60 . 15.6 0.86 0.53
90 34.0 0.86 0.42
1 1/2 VNotch Ball Valve 60 28.5 0.85 0.50
90 77.3 0.74 0.27
2 VNotch Ball Valve 60 59.2 0.81 0.53
90 132 0.77 0.41
High Performance Butterfly Valve 60 58.9 0.76 0.50 0.49
90 80.2 0.71 0.44 0.70
3 VNotch Ball Valve 60 120 0.80 0.50 0.92
90 321 0.74 0.30 0.99
High Performance Butterfly Valve 60 115 0.81 0.46 0.49
90 237 0.64 0.28 0.70
4 VNotch Ball Valve 60 195 0.80 0.52 0.92
90 596 0.62 0.22 0.99
High Performance Butterfly Valve 60 270 0.69 0.32 0.49
90 499 0.53 0.19 0.70
6 VNotch Ball Valve 60 340 0.80 0.52 0.91
90 1100 0.58 0.20 0.99
High Performance Butterfly Valve 60 664 0.66 0.33 0.49
90 1260 0.55 0.20 0.70
8 VNotch Ball Valve 60 518 0.82 0.54 0.91
90 1820 0.54 0.18 0.99
High Performance Butterfly Valve 60 1160 0.66 0.31 0.49
90 2180 0.48 0.19 0.70
10 VNotch Ball Valve 60 1000 0.80 0.47 0.91
90 3000 0.56 0.19 0.99
High Performance Butterfly Valve 60 1670 0.66 0.38 0.49
90 3600 0.48 0.17 0.70
Chapter 5. Control Valve Selection

(continued)

127
Representative Sizing Coefficients for Rotary Shaft Valves (continued)

128
Valve Size Degrees of Valve
Valve Style Cv FL XT FD
(inches) Opening
12 VNotch Ball Valve 60 1530 0.78 0.49 0.92
90 3980 0.63 0.25 0.99
High Performance Butterfly Valve 60 2500 0.49
90 5400 0.70
16 VNotch Ball Valve 60 2380 0.80 0.45 0.92
90 8270 0.37 0.13 1.00
High Performance Butterfly Valve 60 3870 0.69 0.40
90 8600 0.52 0.23
Chapter 5. Control Valve Selection
Chapter 5. Control Valve Selection

Actuator Sizing Total force required = A + B + C + D


Actuators are selected by matching
the force required to stroke the valve A. Unbalance Force
with an actuator that can supply that
force. For rotary valves a similar pro- The unbalance force is that resulting
cess matches the torque required to from fluid pressure at shutoff and in
stroke the valve with an actuator that the most general sense can be ex-
will supply that torque. The same fun- pressed as:
damental process is used for pneu-
matic, electric, and electrohydraulic Unbalance force = net pressure differ-
actuators. ential X net unbalance area

Frequent practice is to take the maxi-


Globe Valves mum upstream gauge pressure as the
net pressure differential unless the
The force required to operate a globe
process design always ensures a
valve includes:
back pressure at the maximum inlet
! Force to overcome static unbal- pressure. Net unbalance area is the
ance of the valve plug port area on a single seated flow up
design. Unbalance area may have to
! Force to provide a seat load take into account the stem area de-
pending on configuration. For bal-
! Force to overcome packing fric- anced valves there is still a small un-
tion balance area. This data can be
obtained from the manufacturer. Typi-
! Additional forces required for cal port areas for balance valves flow
certain specific applications or up and unbalanced valves in a flow
constructions down configuration are listed below;
Typical Unbalance Areas of Control Valves
Unbalance Area
Unbalance Area
Port Diameter Single seated
Balanced Valves
unbalanced valves
1/4 .028 ---
3/8 0.110 ---
1/2 0.196 ---
3/4 0.441 ---
1 0.785 ---
1 5/16 1.35 0.04
1 7/8 2.76 0.062
2 5/16 4.20 0.27
3 7/16 9.28 0.118
4 3/8 15.03 0.154
7 38.48 0.81
8 50.24 0.86

129
Chapter 5. Control Valve Selection
CLASS V (METAL SEAT FOR OPTIMUM PER-
FORMANCE AND LIFE IN BOILER FEEDWATER
SERVICE.

1000

900

800 CLASS V (METAL SEAT WITH


CSEAL TRIM)

700
REQUIRED SEAT LOAD (LB PER LINEAL INCH)

600

500

CLASS V (METAL SEAT)


400

300

CLASS IV
200

CLASS III

100
CLASS II

0
0 1000 2000 3000 4000 5000 6000

A22224 SHUTOFF PRESSURE DROP, PSI

Figure 5-3. Minimum Required Seat Load for Metal-Seated Valves for
Improved Seat Life for Class II-V and Recommended Seat Load for
Optimum Performance in Boiler Feedwater Service

Leak Class Recommended Seat Load


Class I As required by user specification, no factory leak test required
Class II 20 pounds per lineal inch of port circumference
Class III 40 pounds per lineal inch of port circumference
Standard (Lower) Seat only40 pounds per lineal inch of port circumference
(up through a 4-3/8 inch diameter port)
Class IV
Standard (Lower) Seat only80 pounds per lineal inch of port circumference
(larger than 4-3/8 inch diameter port)
Metal Seatdetermine pounds per lineal inch of port circumference from
Class V
figure 5-3
Class VI Metal Seat300 pounds per lineal inch of port circumference

B. Force to Provide Seat Load quirements. Use the following guide-


Seat load, usually expressed in lines to determine the seat load
pounds per lineal inch of port circum- required to meet the factory accep-
ference, is determined by shutoff re- tance tests for ANSI/FCI 70-2 and IEC
130
Chapter 5. Control Valve Selection
534-4 leak classes II through VI. See C. Packing Friction
table for recommended seat load.
Packing friction is determined by stem
Because of differences in the severity size, packing type, and the amount of
of service conditions, do not construe compressive load placed on the pack-
these leak classifications and corre- ing by the process or the bolting.
sponding leakage rates as indicators Packing friction is not 100% repeat-
of field performance. To prolong seat able in its friction characteristics. Live
life and shutoff capabilities, use a loaded packing designs can have sig-
higher than recommended seat load. nificant friction forces especially if
See Figure 5-3 for suggested seat graphite packing is used. The table
loads. If tight shutoff is not a prime below lists typical packing friction val-
consideration, use a lower leak class. ues.

131
Chapter 5. Control Valve Selection

Typical Packing Friction Values


PTFE PACKING GRAPHITE
STEM SIZE
CLASS RIBBON/
(INCHES) Single Double FILAMENT
5/16 All 20 30 ---
125 ---
150 125
250 ---
3/8 300 38 56 190
600 250
900 320
1500 380
125 ---
150 180
250 ---
300 230
1/2 50 75
600 320
900 410
1500 500
2500 590
125 ---
150 218
5/8 250 63 95 ---
300 290
600 400
125 ---
150 350
250 ---
300 440
3/4 75 112.5
600 660
900 880
1500 1100
2500 1320
300 610
600 850
1 900 100 150 1060
1500 1300
2500 1540
300 800
600 1100
1-1/4 900 120 180 1400
1500 1700
2500 2040
300 1225
600 1725
2 900 200 300 2250
1500 2750
2500 3245
Values shown are frictional forces typically encountered when using standard packing flange bolt torquing procedures.

D. Additional Forces ing from seals; or special seating


forces for soft metal seals as an ex-
Additional forces may be required to ample. The manufacturer should ei-
stroke the valve such as: bellow stiff- ther supply this information or take it
ness; unusual frictional forces result- into account when sizing an actuator.
132
Chapter 5. Control Valve Selection

Actuator Force Calculations maximum air supply exceeds the mini-


mum air supply available.
Pneumatic diaphragm actuators pro-
vide a net force with the additional air The manufacturer normally takes re-
pressure after compressing the spring sponsibility for actuator sizing and
in air to close, or with the net precom- should have methods documented to
pression of the spring in air to open. check for maximum stem loads.
This may be calculated in pounds per Manufacturers also publish data on
square inch of pressure differential. actuator thrusts, effective diaphragm
areas, and spring data.
For example: Suppose 275 lbf. is re-
quired to close the valve calculated
following the process described earli- Rotary Actuator Sizing
er. An air-to-open actuator with 100
square inches of diaphragm area and In selecting the most economical ac-
a bench set of 6 to 15 psig is one tuator for a rotary valve, the determin-
available option. The expected operat- ing factors are the torque required to
ing range is 3 to 15 psig. The precom- open and close the valve and the
pression can be calculated as the dif- torque output of the actuator.
ference between the lower end of the This method assumes the valve has
bench set (6 psig) and the beginning been properly sized for the application
of the operating range (3 psig). This 3 and the application does not exceed
psig is used to overcome the precom- pressure limitations for the valve.
pression so the net precompression
force must be;
Torque Equations
3 psig X 100 sq. in. = 300 lbf.
Rotary valve torque equals the sum of
This exceeds the force required and is a number of torque components. To
an adequate selection. avoid confusion, a number of these
have been combined and a number of
Piston actuators with springs are calculations have been performed in
sized in the same manner. The thrust advance. Thus, the torques required
from piston actuators without springs for each valve type can be repre-
can simply be calculated as: sented with two simple and practical
equations.
(Piston Area)(Minimum Supply
Pressure) = Available Thrust
Breakout Torque
(be careful to maintain compatibility of TB = A(!Pshutoff) + B
units)

In some circumstances an actuator Dynamic Torque


could supply too much force and TD = C(!Peff)
cause the stem to buckle, to bend suf-
ficiently to cause a leak, or to damage The specific A, B, and C factors for
valve internals. This could occur be- each valve design are included in fol-
cause the actuator is too large or the lowing tables.

133
Chapter 5. Control Valve Selection

Typical Rotary Shaft Valve Torque Factors


VNotch Ball Valve with Composition Seal
VALVE A C
VALVE MAXIMU
SHAFT
SIZE, Composition B 60 70 M TD,
DIAMETER,
INCHES Bearings Degrees Degrees LBF"IN.
INCHES
2 1/2 0.15 80 0.11 0.60 515
3 3/4 0.10 280 0.15 3.80 2120
4 3/4 0.10 380 1.10 18.0 2120
6 1 1.80 500 1.10 36.0 4140
8 1-1/4 1.80 750 3.80 60.0 9820
10 1-1/4 1.80 1250 3.80 125 9820
12 1-1/2 4.00 3000 11.0 143 12,000
14 1-3/4 42 2400 75 413 23,525
16 2 60 2800 105 578 23,525
18 2-1/8 60 2800 105 578 55,762
20 2-1/2 97 5200 190 1044 55,762

High Performance Butterfly Valve with Composition Seal


MAXIMUM TORQUE,
VALVE SHAFT C
INCH-POUNDS
SIZE, DIAMETER A B
Breakout
INCHES INCHES 60# 75# 90# Dynamic TD
TB
3 1/2 0.50 136 0.8 1.8 8 280 515
4 5/8 0.91 217 3.1 4.7 25 476 1225
6 3/4 1.97 403 30 24 70 965 2120
8 1 4.2 665 65 47 165 1860 4140
10 1-1/4 7.3 1012 125 90 310 3095 9820
12 1-1/2 11.4 1422 216 140 580 4670 12,000

Maximum Rotation ton actuators, reflect this changing le-


ver length.
Maximum rotation is defined as the
angle of valve disk or ball in the fully
open position. Non-Destructive Test
Normally, maximum rotation is 90 de- Procedures
grees. The ball or disk rotates 90 de- Successful completion of specific non-
grees from the closed position to the destructive examinations is required
wide open position. for valves intended for nuclear service
and may be required by codes or cus-
Some of the pneumatic spring-return tomers in non-nuclear applications,
piston and pneumatic spring-and-dia- particularly in the power industry.
phragm actuators are limited to 60 or Also, successful completion of the ex-
75 degrees rotation. aminations may permit uprating of
ASME Standard Class buttwelding
For pneumatic spring-and-diaphragm end valves to a Special Class rating.
actuators, limiting maximum rotation The Special Class rating permits use
allows for higher initial spring com- of the butt-welding end valves at high-
pression, resulting in more actuator er pressures than allowed for Stan-
breakout torque. Additionally, the ef- dard Class valves. Procedures re-
fective length of each actuator lever quired for uprating to the Special
changes with valve rotation. Published Class are detailed in ASME Standard
torques, particularly for pneumatic pis- B16.34.
134
Chapter 5. Control Valve Selection
While it is not feasible to present com- the applicable light source. (Some de-
plete details of code requirements for velopers require use of an ultraviolet
non-destructive examinations, this or black light to expose defective
book will summarize the principles areas). If defects are discovered and
and procedures of four major types of repaired by welding, the piece must
non-destructive examinations defined be re-examined after repair.
in ANSI, ASME, and ASTM standards.

Radiographic (Volumetric)
Magnetic Particle (Surface) Examination
Examination
Radiography of control valve parts
Magnetic particle examination can be works on the principle that X-rays and
used only on materials which can be gamma rays will pass through metal
magnetized. The principle includes objects which are impervious to light
application of a direct current across a rays and will expose photographic film
piece to induce a magnetic field in the just as light rays will. The number and
piece. Surface or shallow subsurface intensity of the rays passing through
defects distort the magnetic field to the metal object depend on the densi-
the extent that a secondary magnetic ty of the object. Subsurface defects
field develops around the defect. If a represent changes in density of the
magnetic powder, either dry or sus- material and can therefore be
pended in liquid, is spread over the photographed radiographically. The
magnetized piece, areas of distorted piece to be inspected is placed be-
magnetic field will be visible, indicat- tween the X-ray or gamma ray source
ing a defect in the piece in the area of and the photographic film. Detail and
distortion. After de-magnetizing the contrast sensitivity are determined by
piece by reversing the electric current, radiographing one or more small flat
it may be possible to weld repair the plates of specified thickness at the
defect (normal procedure with cast- same time the test subject is exposed.
ings) or it may be necessary to re- The small flat plate, called a penetra-
place the piece (normal procedure meter, has several holes of specified
with forgings and bar stock parts). Af- diameters drilled in it. Its image on the
ter repair or replacement, the magnet- exposed film, along with the valve
ic particle examination must be re- body or other test subject, makes it
peated. possible to determine the detail and
contrast sensitivity of the radiograph.

Liquid Penetrant (Surface) Radiography can detect such casting


Examination defects as gas and blowholes, sand
inclusions, internal shrinkage, cracks,
This examination method permits hot tears, and slag inclusions. In cast-
detection of surface defects not visible ings for nuclear service, some defects
to the naked eye. The surface to be such as cracks and hot tears are ex-
examined is cleaned thoroughly and pressly forbidden and cannot be re-
dried. The liquid penetrant dye, either paired. The judgment and experience
water or solvent soluble, is applied by of the radiographer is important be-
dipping, brushing, or spraying, and al- cause he must compare the radio-
lowed time to penetrate. Excess pene- graph with the acceptance criteria
trant is washed or wiped off (depend- (ASTM reference radiographs) to de-
ing on the penetrant used). The termine the adequacy of the casting.
surface is again thoroughly dried and When weld repairs are required, the
a developer (liquid or powder) is ap- casting must be radiographed again
plied. Inspection is performed under after the repair.
135
Chapter 5. Control Valve Selection

Ultrasonic (Volumetric) FLOW

Examination
P1 P2
This method monitors sound wave re-
flections from the piece being in- RESTRIC-
spected to determine the depth and TION
VENA
size of any defects. Ultrasonic ex- A3444/IL CONTRACTA
amination can detect foreign materials
and discontinuities in fine-grained
metal and thus lends itself to volumet-
ric examination of structures such as Figure 54. Vena Contracta Illustration
plate, bar, and forgings. The test is
normally conducted either with a spe- tion, there is a necking down, or con-
cial oil called a coupler or under water traction, of the flow stream. The mini-
to ensure efficient transmission of mum crosssectional area of the flow
sound waves. The sound waves are stream occurs just downstream of the
generated by a crystal probe and are actual physical restriction at a point
reflected at each interface in the piece called the vena contracta, as shown in
being tested, that is, at each outer figure 54.
face of the piece itself and at each
face of the damaged or malformed in- To maintain a steady flow of liquid
ternal portion. These reflections are through the valve, the velocity must
received by the crystal probe and dis- be greatest at the vena contracta,
played on a screen to reveal the loca- where cross sectional area is the
tion and severity of the defect. least. The increase in velocity (or ki-
netic energy) is accompanied by a
substantial decrease in pressure (or
Cavitation and Flashing potential energy) at the vena contrac-
ta. Further downstream, as the fluid
Choked Flow Causes Flashing stream expands into a larger area, ve-
and Cavitation locity decreases and pressure in-
creases. But, of course, downstream
The IEC liquid sizing standard calcu- pressure never recovers completely to
lates an allowable sizing pressure equal the pressure that existed up-
drop, !Pmax. If the actual pressure stream of the valve. The pressure dif-
drop across the valve, as defined by ferential (!P) that exists across the
the system conditions of P1 and P2, is valve is a measure of the amount of
greater than !Pmax then either flash- energy that was dissipated in the
ing or cavitation may occur. Structural valve. Figure 55 provides a pressure
damage to the valve and adjacent pip- profile explaining the differing perfor-
ing may also result. Knowledge of mance of a streamlined high recovery
what is actually happening within the valve, such as a ball valve, and a
valve will permit selection of a valve valve with lower recovery capabilities
that can eliminate or reduce the ef- due to greater internal turbulence and
fects of cavitation and flashing. dissipation of energy.
The physical phenomena label is used Regardless of the recovery character-
to describe flashing and cavitation be- istics of the valve, the pressure differ-
cause these conditions represent ac- ential of interest pertaining to flashing
tual changes in the form of the fluid and cavitation is the differential be-
media. The change is from the liquid tween the valve inlet and the vena
state to the vapor state and results contracta. If pressure at the vena con-
from the increase in fluid velocity at or tracta should drop below the vapor
just downstream of the greatest flow pressure of the fluid (due to increased
restriction, normally the valve port. As fluid velocity at this point) bubbles will
liquid flow passes through the restric- form in the flow stream. Formation of
136
Chapter 5. Control Valve Selection
FLOW

P2

P1 P2
HIGH
RECOVERY

P2
LOW W2843/IL
RECOVERY
A3444/IL
Figure 57. Typical Appearance of
Cavitation Damage
Figure 55. Comparison of Pressure
Profiles for High and Low Recovery
Valves
On the other hand, if downstream
pressure recovery is sufficient to raise
the outlet pressure above the vapor
pressure of the liquid, the bubbles will
collapse, or implode, producing cavi-
tation. Collapsing of the vapor bubbles
releases energy and produces a noise
similar to what one would expect if
gravel were flowing through the valve.
If the bubbles collapse in close prox-
imity to solid surfaces in the valve, the
energy released will gradually tear
W2842/IL
away the material leaving a rough,
Figure 56. Typical Appearance of cinderlike surface as shown in figure
Flashing Damage 57. Cavitation damage may extend
to the adjacent downstream pipeline,
if that is where pressure recovery oc-
curs and the bubbles collapse. Ob-
viously, high recovery valves tend to
bubbles will increase greatly as vena be more subject to cavitation, since
contracta pressure drops further be- the downstream pressure is more like-
low the vapor pressure of the liquid. At ly to rise above the liquids vapor
this stage, there is no difference be- pressure.
tween flashing and cavitation, but the
potential for structural damage to the
Valve Selection for Flashing
valve definitely exists.
Service
If pressure at the valve outlet remains As shown in figure 56, flashing dam-
below the vapor pressure of the liquid, age is characterized by a smooth, pol-
the bubbles will remain in the down- ished appearance of the eroded sur-
stream system and the process is said faces. To review, flashing occurs
to have flashed. Flashing can produce because P2 is less than Pv. P2 is the
serious erosion damage to the valve pressure downstream of the valve and
trim parts and is characterized by a is a function of the downstream pro-
smooth, polished appearance of the cess and piping. Pv is a function of
eroded surface, as shown in figure the fluid and operating temperature.
56. Flashing damage is normally Therefore, the variables that define
greatest at the point of highest veloc- flashing are not directly controlled by
ity, which is usually at or near the seat the valve. This further means there is
line of the valve plug and seat ring. no way for any control valve to pre-
137
Chapter 5. Control Valve Selection
vent flashing. Since flashing cannot Valve Selection for Cavitation
be prevented by the valve the best Service
solution is to select a valve with prop-
er geometry and materials to avoid or Cavitation damage is characterized by
minimize damage. a rough, cinderlike appearance of
the eroded surface as shown in figure
5-7. It is distinctly different from the
In general erosion is minimized by: smooth, polished appearance caused
by the erosion of flashing. The pre-
! preventing or reducing the par- vious section describes how cavitation
ticle (liquid droplets in this case) im- occurs when the vena contracta pres-
pact with the valve surfaces sure is less than Pv, and P2 is greater
than Pv. Cavitation can be treated by
several means.
! making those surfaces as hard
as possible The first is to eliminate the cavitation
and thus the damage by managing
the pressure drop. If the pressure
! lowering the velocity of the ero- drop across the valve can be con-
sive flow trolled such that the local pressure
never drops below the vapor pres-
sure, then no vapor bubbles will form.
Selecting a valve with as few fluid di- Without vapor bubbles to collapse,
rectional changes as possible pro- there is no cavitation. To eliminate
vides the least number of particle im- cavitation the total pressure drop
pacts. Sliding-stem angle valves are across the valve is split, using multi-
traditional solutions which provide ple-stage trims, into smaller portions.
such a flow path. Some rotary valves, Each of these small drops keeps its
such as eccentric rotary plug, and V vena contracta pressure above the
ball valves, also offer straightthrough vapor pressure so no vapor bubbles
flow paths. Valves with expanded flow are formed.
areas downstream of the throttling
point are beneficial because the ero- The second method does not elimi-
sive velocity is reduced. For those nate the cavitation but rather mini-
areas where the fluid must impact the mizes or isolates the damage much
valve surfaces, at the seating surfaces the same as with flashing solutions.
for example, choose materials that are This method aims to isolate the cavi-
as hard as possible. Generally the tation from valve surfaces and to
harder the material the longer it will harden those surfaces that the cavita-
resist erosion. tion does impact.

Fluids that are both flashing and cor- A third method is to change the sys-
rosive can be especially troublesome. tem in a manner to prevent the
Flashing water in a steel valve is an causes of cavitation. If the P2 can be
example of the synergistic result of raised enough so that the vena con-
both corrosion and erosion. The water tracta pressure does not fall below the
causes corrosion of steel and the vapor pressure, that is the valve is no
flashing causes erosion of the result- longer choked, then cavitation will be
ant, soft, oxide layer; these combine avoided. P2 can be raised by moving
to create damage worse than either the valve to a location that has more
individual mechanism would. The static head on the downstream side.
solution in this case is to prevent the Applying an orifice plate or similar
corrosion by selecting, as a minimum, backpressure device can also raise
a low-alloy steel. P2 at the valve; the downside is the
138
Chapter 5. Control Valve Selection
potential for the cavitation to transfer termine the particular noise generat-
from the valve to the orifice plate. ing mechanism in the valve. There are
five defined regimes dependent on the
relationship of the vena contracta
Noise Prediction pressure and the downstream pres-
sure. For each of these regimes an
Aerodynamic acoustic efficiency is defined and cal-
culated. This acoustic efficiency es-
Industry leaders use the International tablishes the fraction of the total
Electrotechnical Commission standard stream power, as calculated in Step 1,
IEC 534-8-3: Industrial-process con- which is noise power. In designing a
trol valvesPart 8: Noise Consider- quiet valve, lower acoustic efficiency
ationsSection 3: Control valve aero- is one of the goals.
dynamic noise prediction method.
This method consists of a mix of ther- 3Convert acoustic power to
modynamic and aerodynamic theory sound pressure. The final goal of the
and some empirical information. The IEC prediction method is determina-
design of the method allows a noise tion of the sound pressure level at a
prediction for a valve based only on reference point outside the valve
the measurable geometry of the valve where human hearing is a concern.
and the service conditions applied to Step 2 delivers acoustic power, which
the valve. There is no need for specif- is not directly measurable. Acoustic or
ic empirical data for each valve design sound pressure is measurable and
and size. Because of this pure analyti- therefore has become the default ex-
cal approach to valve noise prediction pression for noise in most situations.
the IEC method allows an objective Converting from acoustic power to the
evaluation of alternatives. sound pressure uses basic acoustic
theory.
The method defines five basic steps
4Account for the transmission
to a noise prediction:
loss of the pipewall and restate the
1Calculate the total stream power sound pressure at the outside sur-
in the process at the vena contrac- face of the pipe. Steps 1 through 3
ta. The noise of interest is generated are involved with the noise generation
by the valve in and downstream of the process inside the pipe. There are
vena contracta. If the total power dis- times when this is the area of interest,
sipated by throttling at the vena con- but the noise levels on the outside of
tracta can be calculated, then the frac- the pipe are the prime requirement.
tion that is noise power can be The method must account for the
determined. Since power is the time change in the noise as the reference
rate of energy, a form of the familiar location moves from inside the pipe to
equation for calculating kinetic energy outside the pipe. The pipe wall has
can be used. The kinetic energy equa- physical characteristics, due to its ma-
tion is 1/2 mv2 where m is mass and v terial, size, and shape, that define
is velocity. If the mass flow rate is sub- how well the noise will transmit
stituted for the mass term, then the through the pipe. The fluid-borne
equation calculates the power. The noise inside the pipe must interact
velocity is the vena contracta velocity with the inside pipe wall to cause the
and is calculated with the energy pipe wall to vibrate, then the vibration
equation of the First Law of Thermo- must transmit through the pipe wall to
dynamics. the outside pipe wall, and there the
outside pipe wall must interact with
2Determine the fraction of total the atmosphere to generate sound
power that is acoustic power. The waves. These three steps of noise
method considers the process condi- transmission are dependent on the
tions applied across the valve to de- noise frequency. The method repre-
139
Chapter 5. Control Valve Selection
sents the frequency of the valve noise plant noise levels or exceed worker
by determining the peak frequency of exposure levels.
the valve noise spectrum. The method
also determines the pipe transmission Noise Control
loss as a function of frequency. The
method then compares the internal In closed systems (not vented to at-
noise spectrum and the transmission- mosphere), any noise produced in the
loss spectrum to determine how much process becomes airborne only by
the external sound pressure will be transmission through the valves and
attenuated by the pipe wall. adjacent piping that contain the flow-
stream. The sound field in the flow-
5Account for distance and calcu- stream forces these solid boundaries
late the sound pressure level at the to vibrate. The vibrations cause distur-
observers location. Step 4 delivers bances in the ambient atmosphere
the external sound pressure level at that are propagated as sound waves.
the outside surface of the pipe wall. Noise control employs either source
Again, basic acoustic theory is applied treatment, path treatment, or both.
to calculate the sound pressure level Source treatment, preventing or atte-
at the observers location. Sound pow- nuating noise at its source, is the most
er is constant for any given situation, desirable approach, if economically
but the associated sound pressure and physically feasible.
level varies with the area the power is
spread over. As the observer moves Recommended cage-style source
farther away from the pipe wall, the treatment approaches are depicted in
total area the sound power is spread figure 5-8. The upper view shows a
over increases. This causes the cage with many narrow parallel slots
sound pressure level to decrease. designed to minimize turbulence and
provide a favorable velocity distribu-
tion in the expansion area. This eco-
nomical approach to quiet valve de-
Hydrodynamic sign can provide 15 to 20 dBA noise
Noticeable hydrodynamic noise is reduction with little or no decrease in
usually associated with cavitation. The flow capacity.
traditional description of the sound is The lower view in figure 5-8 shows a
as rocks flowing inside the pipe. This two-stage, cage-style trim designed
association of hydrodynamic noise for optimum noise attenuation where
with cavitation is reflected in the vari- pressure drop ratios (!P/P1) are high.
ous prediction methods available
today. The methods account for one To obtain the desired results, restric-
noise characteristic for liquids in non- tions must be sized and spaced in the
choked flow situations and another primary cage wall so that the noise
characteristic in choked, cavitating generated by jet interaction is not
flow situations. greater than the summation of the
noise generated by the individual jets.
There are a variety of situations where This trim design can reduce the valve
the fluid is a two-phase mixture. noise by as much as 30 dBA. The fi-
These include liquid-gas two-phase nal design shown uses a combination
fluids at the inlet of the valve, flashing of several noise reduction strategies
fluids, and fluids that demonstrate out- to reduce valve noise up to 40 dBA.
gassing due to throttling. Noise pre- Those strategies are:
diction methods for these cases are
not yet well established. Test results ! Unique passage shape reduces
and field surveys of installed multi- the conversion of total stream power
phase systems indicate these noise generated by the valve into noise
levels do not contribute to overall power.
140
Chapter 5. Control Valve Selection
splitting the total pressure drop be-
tween the control valve and a fixed re-
striction (diffuser) downstream of the
valve can be effective in minimizing
noise. To optimize the effectiveness of
a diffuser, it must be designed (special
shape and sizing) for each given
installation so that the noise levels
generated by the valve and diffuser
are equal. Figure 5-9 shows a typical
installation.
Control systems venting to atmo-
W1257/IL
sphere are generally very noisy be-
cause of the high pressure ratios and
high exit velocities involved. Dividing
the total pressure drop between the
actual vent and an upstream control
valve, by means of a vent diffuser,
quiets both the valve and the vent. A
properly sized vent diffuser and valve
combination, such as that shown in
figure 5-10, can reduce the overall
system noise level as much as 40
dBA.
W6980/IL

Source treatment for noise problems


Figure 5-8. Valve Trim Design for
associated with control valves han-
Reducing Aerodynamic Noise
dling liquid is directed primarily at
eliminating or minimizing cavitation.
Because flow conditions that will pro-
! Multistage pressure reduction duce cavitation can be accurately pre-
divides the stream power between dicted, valve noise resulting from cavi-
stages and further reduces the acous- tation can be eliminated by application
tic conversion efficiency. of appropriate limits to the service
conditions at the valve by use of
! Frequency spectrum shifting re- break-down orifices, valves in series,
duces acoustic energy in the audible etc. Another approach to source treat-
range by capitalizing on the transmis- ment is using special valve trim that
sion loss of the piping. uses the series restriction concept to
eliminate cavitation as shown in figure
! Exit jet independence is main- 5-11.
tained to avoid noise regeneration due
to jet coalescence. A second approach to noise control is
that of path treatment. The fluid
! Velocity management is accom- stream is an excellent noise transmis-
plished with expanding areas to ac- sion path. Path treatment consists of
commodate the expanding gas. increasing the impedance of the trans-
mission path to reduce the acoustic
! Complementary body designs energy communicated to the receiver.
prevent flow impingement on the body
wall and secondary noise sources. Dissipation of acoustic energy by use
of acoustical absorbent materials is
For control valve applications operat- one of the most effective methods of
ing at high pressure ratios (!P/P1 > path treatment. Whenever possible
0.8) the series restriction approach, the acoustical material should be lo-
141
Chapter 5. Control Valve Selection

W2618/IL

Figure 5-9. Valve and Inline Diffuser Combination

W2673/IL

W2672/IL
Figure 5-11. Special Valve
Figure 5-10. Valve and Vent Design to Eliminate Cavita-
Diffuser Combination tion

cated in the flow stream either at or boundaries. Where high mass flow
immediately downstream of the noise rates and/or high pressure ratios
source. In gas systems, inline silenc- across the valve exist, inline silencers,
ers effectively dissipate the noise such as that shown in figure 5-12, are
within the fluid stream and attenuate often the most realistic and economi-
the noise level transmitted to the solid cal approach to noise control. Use of
142
Chapter 5. Control Valve Selection

W1304/IL

Figure 5-12. Typical In-Line Silencer

absorption-type inline silencers can


provide almost any degree of attenua-
tion desired. However, economic con-
siderations generally limit the insertion
loss to approximately 25 dBA.
Noise that cannot be eliminated within
the boundaries of the flow stream W6851/IL

must be eliminated by external treat-


Figure 5-13. Globe Style Valve
ment. This approach to the abatement
with Noise Abatement Cage for
of control valve noise suggests the
Aerodynamic Flow
use of heavy walled piping, acoustical
insulation of the exposed solid bound-
aries of the fluid stream, use of insu-
lated boxes, buildings, etc., to isolate
the noise source.
Path treatment such as heavy wall
pipe or external acoustical insulation
can be an economical and effective
technique for localized noise abate-
ment. However, noise is propagated
for long distances via the fluid stream
and the effectiveness of the heavy
wall pipe or external insulation ends
where the treatment ends.

Noise Summary
The amount of noise that will be gen-
erated by a proposed control valve
installation can be quickly and reason-
W6343/IL
ably predicted by use of industry stan-
dard methods. These methods are Figure 5-14. Ball Style Valve
available in computer software for with Attenuator to Reduce
ease of use. Such sizing and noise Hydrodynamic Noise
prediction tools help in the proper
selection of noise reduction equip-
ment such as shown in figures 5-13
and 5-14. Process facility require- deliver this are always being im-
ments for low environmental impact proved. For the latest in either equip-
will continue to drive the need for ment or prediction technology, contact
quieter control valves. The prediction the valve manufacturers representa-
technologies and valve designs that tive.
143
Chapter 5. Control Valve Selection

ENVIROSEAL DUPLEX

KALREZ
WITH
(KVSP 400) ZYMAXX
(KVSP
500)

E0936/IL

Figure 515. Application Guidelines Chart for 100 PPM Service

ENVIRO-SEAL!
PTFE and DUPLEX

KALREZ with
PTFE (KVSP400)

e0937/IL

Figure 516. Application Guidelines Chart for NonEnvironmental Service

Packing Selection
The following tables and figures 5-15 guidelines for sliding-stem and rotary
and 5-16 offer packing selection valves.

144
Packing Selection Guidelines for Sliding-Stem Valves
Maximum Pressure and Application Guideline for
Temperature Limits for Nonenvironmental Seal Service
Packing
Packing System 100 PPM Service(1) Service(1) Performance Life
Friction(2)
Index Index
Metric Imperial Metric Imperial
20.7 bar 300 psi
Single PTFE V-Ring 46 to 232!C 50 to 450!F Better Long Very low
18 to 93!C 0 to 200!F
Double PTFE V-Ring 46 to 232!C 50 to 450!F Better Long Low
ENVIRO-SEAL PTFE 46 to 232!C 50 to 450!F 46 to 232!C 50 to 450!F Best Very long Low
51.7 bar 750 psi
ENVIRO-SEAL Duplex 46 to 232!C 50 to 450!F Best Very long Low
46 to 232!C 50 to 450!F

KALREZ" with PTFE 24.1 bar 350 psig


40 to 204!C 40 to 400!F Best Long Low
(KVSP 400)(3) 4 to 204 40 to 400!F

KALREZ with ZYMAXX# 24.1 bar 350 psig


40 to 260!C 40 to 500!F Best Long Low
(KVSP 500)(3) 4 to 260!C 40 to 500!F
103 bar 1500 psi 207 bar 3000 psi
ENVIRO-SEAL Graphite ULF Best Very long Medium
7 to 315!C 20 to 600!F 198 to 371!C 325 to 700!F
103 bar 1500 psi 290 bar(4) 4200 psi(4)
HIGH-SEAL Graphite ULF Best Very long Medium
7 to 315!C 20 to 600!F 198 to 538!C 325 to 1000!F
Graphite Composite / HIGH-SEAL 290 bar(4) 4200 psi(4)
Better Very long Very high
Graphite 198 to 649!C(5) 325 to 1200!F(5)
290 bar 4200 psi
Braided Graphite Filament Good Moderate High
198 to 538!C(5) 325 to 1000!F(5)
290 bar 4200 psi
Graphite ULF Better Very long Medium
198 to 538!C 325 to 1000!F
1. The values shown are only guidelines. These guidelines can be exceeded, but shortened packing life or increased leakage might result. The temperature ratings apply to the actual packing
temperature, not to the process temperature.
2. See manufacturer for actual friction values.
3. The KALREZ pressure/temperature limits referenced in this bulletin are for Fisher valve applications only. DuPont Dow Elastomers LLC may claim higher limits.
4. Except for the 9.5 mm (3/8 inch) stem, 110 bar (1600 psi).
Chapter 5. Control Valve Selection

145
5. Except for oxidizing service, 198 to 371!C (325 to 700!F).
146
Packing Selection Guidelines for Rotary Valves
MAXIMUM PRESSURE AND
APPLICATION GUIDELINE FOR SEAL SERVICE
TEMPERATURE LIMITS FOR PACKING
PACKING SYSTEM NONENVIRONMENTAL SERVICE(1) PERFORMANCE LIFE
500 PPM SERVICE(1) FRICTION
INDEX INDEX
Metric Customary U.S. Metric Customary U.S.
103 bar 1500 psig
Single PTFE V-Ring Better Long Very low
46 to 232!C 50 to 450!F
103 bar 1500 psig 103 bar 1500 psig
ENVIRO-SEAL PTFE Superior Very long Low
46 to 232!C 50 to 450!F 46 to 232!C 50 to 450!F
KALREZ$ with PTFE (KVSP 24.1 bar 350 psig 51 bar 750 psig
Superior Long Very low
400) 4 to 204!C 40 to 400!F 40 to 204!C 40 to 400!F
Chapter 5. Control Valve Selection

KALREZ with ZYMAXX$ 24.1 bar 350 psig 51 bar 750 psig
Superior Long Very low
(KVSP 500) 4 to 260!C 40 to 500!F 40 to 260!C 40 to 500!F
103 bar 1500 psig 207 bar 3000 psig
ENVIRO-SEAL Graphite Superior Very long Moderate
18 to 315!C 20 to 600!F 198 to 371!C 325 to 700!F
103 bar 1500 psig
Graphite Ribbon Acceptable Acceptable High
198 to 538!C(2) 325 to 1000!F(2)
1. The values shown are only guidelines. These guidelines can be exceeded, but shortened packing life or increased leakage might result. The temperature ratings apply to the actual
packing temperature, not to the process temperature.
2. Except for oxidizing service, 198 to 371!C (325 to 700!F).
Chapter 6

Special Control Valves

As discussed in previous chapters, vice, and test requirements useful for


standard control valves can handle a control valves used in nuclear power
wide range of control applications. plant service.
The range of standard applications
can be defined as being encom- High Capacity Control
passed by: atmospheric pressure and
6000 psig (414 bar), 150!F (101!C) Valves
and 450!F (232!C), flow coefficient Generally, globe-style valves larger
Cv values of 1.0 and 25000, and the than 12-inch, ball valves over 24-inch,
limits imposed by common industrial and high performance butterfly valves
standards. Certainly, corrosiveness larger than 48-inch fall in the special
and viscosity of the fluid, leakage valve category. As valve sizes in-
rates, and many other factors demand crease arithmetically, static pressure
consideration even for standard ap- loads at shutoff increase geometrical-
plications. Perhaps the need for care- ly. Consequently, shaft strength, bear-
ful consideration of valve selection be- ing loads, unbalance forces, and
comes more critical for applications available actuator thrust all become
outside the standard limits mentioned more significant with increasing valve
above. size. Normally maximum allowable
pressure drop is reduced on large
This chapter discusses some special valves to keep design and actuator
applications and control valve modifi- requirements within reasonable limits.
cations useful in controlling them, de- Even with lowered working pressure
signs and materials for severe ser- ratings, the flow capacity of some
147
Chapter 6. Special Control Valves
assembly into the pipeline and remov-
al and replacement of major trim parts
require heavy-duty hoists. Mainte-
nance personnel must follow the
manufacturers instruction manuals
closely to minimize risk of injury.

Low Flow Control Valves


Many applications exist in laboratories
and pilot plants in addition to the gen-
eral processing industries where con-
trol of extremely low flow rates is re-
quired. These applications are
commonly handled in one of two
ways. First, special trims are often
available in standard control valve
bodies. The special trim is typically
made up of a seat ring and valve plug
that have been designed and ma-
W6119/IL
chined to very close tolerances to al-
low accurate control of very small
flows. These types of constructions
Figure 6-1. Large Flow Valve Body for can often handle Cvs as low as 0.03.
Noise Attenuation Service Using these special trims in standard
control valves provides economy by
reducing the need for spare parts in-
ventory for special valves and actua-
large-flow valves remains tremen- tors. Using this approach also makes
dous. future flow expansions easy by simply
replacing the trim components in the
Noise levels must be carefully consid- standard control valve body.
ered in all large-flow installations be-
Control valves specifically designed
cause sound pressure levels increase
for very low flow rates (figure 6-2) also
in direct proportion to flow magnitude.
handle these applications. These
To keep valve-originated noise within
valves often handle Cvs as low as
tolerable limits, large cast or fabri-
0.000001. In addition to the very low
cated valve body designs (figure 6-1)
flows, these specialty control valves
have been developed. These bodies,
are compact and light weight because
normally cage-style construction, use
they are often used in laboratory envi-
unusually long valve plug travel, a
ronments where very light schedule
great number of small flow openings
piping/tubing is used. These types of
through the wall of the cage and an
control valves are specially designed
expanded outlet line connection to
for the accurate control of very low
minimize noise output and reduce
flowing liquid or gaseous fluid applica-
fluid velocity.
tions.
Naturally, actuator requirements are
severe, and long-stroke, double acting High-Temperature Control
pneumatic pistons are typically speci-
fied for large-flow applications. The
Valves
physical size and weight of the valve Control valves for service at tempera-
and actuator components complicate tures above 450(F (232(C) must be
installation and maintenance proce- designed and specified with the tem-
dures. Installation of the valve body perature conditions in mind. At ele-
148
Chapter 6. Special Control Valves

B2560/IL

Figure 6-2. Special Control Valve Designed for Very Low Flow Rates

vated temperatures, such as may be used at temperatures up to 1200(F


encountered in boiler feedwater sys- (650(C).
tems and superheater bypass sys-
tems, the standard materials of control Extension bonnets help protect pack-
valve construction might be inade- ing box parts from extremely high
quate. For instance, plastics, elasto- temperatures. Typical trim materials
mers, and standard gaskets generally include cobalt based Alloy 6, 316 with
prove unsuitable and must be re- alloy 6 hardfacing and nitrided 422
placed by more durable materials. SST.
Metal-to-metal seating materials are
always used. Semi-metallic or lami-
nated flexible graphite packing materi- Cryogenic Service Valves
als are commonly used, and
spiral-wound stainless steel and flex- Cryogenics is the science dealing with
ible graphite gaskets are necessary. materials and processes at tempera-
tures below minus 150!F (101!C).
Cr-Mo steels are often used for the For control valve applications in cryo-
valve body castings for temperatures genic services, many of the same is-
above 1000(F (538(C). ASTM A217 sues need consideration as with high
Grade WC9 is used up to 1100(F temperature control valves. Plastic
(593(C). For temperatures on up to and elastomeric components often
1500(F (816(C) the material usually cease to function appropriately at tem-
selected is ASTM A351 Grade CF8M, peratures below 0!F (18!C). In
Type 316 stainless steel. For tempera- these temperature ranges, compo-
tures between 1000(F (538(C) and nents such as packing and plug seals
1500(F (816(C), the carbon content require special consideration. For plug
must be controlled to the upper end of seals, a standard soft seal will be-
the range, 0.04 to 0.08%. The come very hard and less pliable thus
9%Cr1%MoV materials, such as not providing the shut-off required
ASTM A217 grade C12a castings and from a soft seat. Special elastomers
ASTM A182 grade F91 forgings are have been applied in these tempera-
149
Chapter 6. Special Control Valves

A3449/IL

Figure 6-4. Inherent Valve


Characteristics

Materials of construction for cryogenic


W0667/IL
applications are generally CF8M body
and bonnet material with 300 series
Figure 6-3. Typical Extension Bonnet stainless steel trim material. In flash-
ing applications, hard facing might be
required to combat erosion.

tures but require special loading to


achieve a tight seal.
Customized
Packing is a concern in cryogenic ap- Characteristics and Noise
plications because of the frost that Abatement Trims
may form on valves in cryogenic ap-
plications. Moisture from the atmo- Although control valve characteristics
sphere condensates on colder sur- used in standard control valves (figure
faces and where the temperature of 6-4) meet the requirements of most
the surface is below freezing, the applications, often custom character-
moisture will freeze into a layer of istics are needed for a given applica-
frost. As this frost and ice forms on tion. In these instances, special trim
the bonnet and stem areas of control designs can be manufactured that
valves and as the stem is stroked by meet these requirements. For con-
the actuator, the layer of frost on the toured plugs, the design of the plug tip
stem is drawn through the packing can be modified so that as the plug is
causing tears and thus loss of seal. moved through its travel range, the
The solution is to use extension bon- unobstructed flow area changes in
nets (figure 6-3) which allow the pack- size to allow for the generation of the
ing box area of the control valve to be specific flow characteristic. Likewise,
warmed by ambient temperatures, cages can be redesigned to meet spe-
thus preventing frost from forming on cific characteristics as well. This is es-
the stem and packing box areas. The pecially common in noise abatement
length of the extension bonnet de- type trims where a high level of noise
pends on the application temperature abatement may be required at low
and insulation requirements. The cold- flow rates but much lower abatement
er the application, the longer the ex- levels are required for the higher flow
tension bonnet required. rate conditions.
150
Chapter 6. Special Control Valves

Control Valves for Nuclear mally cover these areas. Section III
does apply to materials used for pres-
Service in the USA sure retaining parts, to design criteria,
Since 1970, U.S. manufacturers and to fabrication procedures, to non-de-
suppliers of components for nuclear structive test procedures for pressure
power plants have been subject to the retaining parts, to hydrostatic testing,
requirements of Appendix B, Title 10, and to marking and stamping proce-
Part 50 of the Code of Federal Regu- dures. ASME Section III is revised by
lations entitled Quality Assurance Cri- means of semi-annual addenda,
teria for Nuclear Power Plants and which may be used after date of is-
Fuel Reprocessing Plants. The U.S. sue, and which become mandatory six
Nuclear Regulatory Commission en- months after date of issue.
forces this regulation. Ultimate re-
sponsibility of proof of compliance to Valves Subject to Sulfide
Appendix B rests with the owner of
the plant, who must in turn rely on the Stress Cracking
manufacturers of various plant com- NACE International is a technical soci-
ponents to provide documented evi- ety concerned with corrosion and cor-
dence that the components were rosion-related issues. NACE is re-
manufactured, inspected, and tested sponsible for a large number of
by proven techniques performed by standards, but by far the most influen-
qualified personnel according to docu- tial and well known is MR0175, for-
mented procedures. merly entitled Sulfide Stress Cracking
Resistant Metallic Materials for Oilfield
In keeping with the requirements of
Equipment. MR0175 was issued by
the Code of Federal Regulations,
NACE in1975 to provide guidelines for
most nuclear power plant components
the selection of materials that are re-
are specified in accordance with Sec-
sistant to failure in hydrogen sulfide
tion III of the ASME Boiler and Pres-
containing oil and gas production en-
sure Vessel Code entitled Nuclear
vironments. MR0175 has been so
Power Plant Components. All aspects
widely referenced that, throughout the
of the manufacturing process must be
process industry, the term NACE
documented in a quality control manu-
has become nearly synonymous with
al and audited and certified by ASME
MR0175. However, the situation
before actual manufacture of the com-
changed in 2003.
ponents. All subsequent manufactur-
ing materials and operations are to be MR0175 was modified significantly in
checked by an authorized inspector. a 2003 revision to cover chloride
All valves manufactured in accor- stress corrosion cracking in addition to
dance with Section III requirements sulfide stress cracking. Then, in late
receive an ASME code nameplate 2003, the document was reformatted
and an N stamp symbolizing accept- and released as a joint NACE/ISO
ability for service in nuclear power document called NACE MR0175/ISO
plant applications. 15156, Petroleum and Natural Gas
Industries Materials for Use in H2S
Section III does not apply to parts not Containing Environments in Oil and
associated with the pressureretain- Gas Production.
ing function, to actuators and acces-
sories unless they are pressure retain- In April 2003, NACE also released a
ing parts, to deterioration of valve new standard, MR0103, which is en-
components due to radiation, corro- titled, Materials Resistant to Sulfide
sion, erosion, seismic or environmen- Stress Cracking in Corrosive Petro-
tal qualifications, or to cleaning, paint- leum Refining Environments. This
ing, or packaging requirements. standard is essentially the refining in-
However, customer specifications nor- dustrys NACE MR0175. MR0103
151
Chapter 6. Special Control Valves
only addresses sulfide stress crack- " Nickel alloys generally provide
ing, and as such is similar in many re- the best resistance to SSC. Some
spects to the pre-2003 revisions of precipitation-hardenable nickel alloys
MR0175. Use of the MR0103 stan- are acceptable for use in applications
dard in the refining industry is acceler- requiring high strength and/or hard-
ating. ness up to 40 HRC.

Note that compliance with certain revi- " Chromium, nickel, and other
sions of NACE MR0175 or NACE types of plating offer no protection
MR0175/ISO 15156 is mandated by against SSC. Their use is allowed in
statute in some states and regions in sour applications for wear resistance,
the U.S.A. At this time, NACE but they cannot be used in an attempt
MR0103 is not mandated by any gov- to protect a non-resistant base materi-
erning bodies. al from SSC.

" Weld repairs and fabrication


Pre-2003 Revisions of MR0175 welds on carbon and low-alloy steels
The following statements, although must be properly processed to ensure
based on information and require- that they meet the 22 HRC maximum
ments in the pre-2003 revisions of hardness requirement in the base
MR0175, cannot be presented in the metal, heat-affected zone (HAZ), and
detail furnished in the actual standard weld deposit. Alloy steels require
and do not guarantee suitability for post-weld heat treatment, and post
any given material in hydrogen sul- weld heat treatment is generally used
fide-containing sour environments. for carbon steels as well.
The reader is urged to refer to the ac-
" Conventional identification
tual standard before selecting control
stamping is permissible in low stress
valves for sour service.
areas, such as on the outside diame-
ter of line flanges. Low-stress identifi-
" Most ferrous metals can become
cation stamping must be used in other
susceptible to sulfide stress cracking
areas.
(SSC) due to hardening by heat treat-
ment and/or cold work. Conversely,
" The standard precludes using
many ferrous metals can be heat
ASTM A193 Grade B7 bolting for ap-
treated to improve resistance to SSC.
plications that are considered ex-
posed. Use of SSC-resistant bolting
" Carbon and low-alloy steels materials (such as ASTM A193
must be properly heat treated to pro- Grade B7M) sometimes necessitates
vide resistance to SSC. A maximum to derating of valves designed origi-
hardness limit of HRC 22 applies to nally to use B7 bolting. For example,
carbon and low-alloy steels. in a Class 600 globe valve, 17-4PH
H1150 DBL bolting can be used to
" Austenitic stainless steels are avoid derating.
most resistant to SSC in the annealed
condition; some specific grades and
conditions of stainless steels are ac- NACE MR0175/ISO 15156
ceptable up to 35 HRC. NACE MR0175/ISO 15156 introduced
significant changes to the standard.
" Copper-base alloys are inherent- However, many end users continue to
ly resistant to SSC, but are generally specify NACE MR0175-2002, feeling
not used in critical parts of a valve that it adequately meets their needs in
without the approval of the purchaser providing good service life. The most
due to concerns about general corro- significant changes in NACE
sion. MR0175/ISO 15156 include:
152
Chapter 6. Special Control Valves
" The 17-4PH H1150 DBL bolting " The 2002 and older revisions of
that was previously used for fullrated MR0175 included environmental re-
exposed bolting in a Class 600 globe strictions on a few materials that were
valve is no longer allowed. continued in the latter editions.
MR0103 only deals with sulfide stress
" The revision addresses both sul- cracking. It does not impose environ-
fide stress cracking and chloride mental limits on any materials. Mate-
stress corrosion cracking. Prior ver- rials are either acceptable or not.
sions simply listed most materials as
acceptable or unacceptable. Because " Carbon steel base materials that
its scope was expanded to cover chlo- are classified as P-No. 1, group 1 or 2
ride stress corrosion cracking, the steels in the ASME Boiler and Pres-
new standard lists all corrosion-resist- sure Vessel Code are acceptable per
ant alloys as acceptable within limits, MR0103 without base metal hardness
referred to as environmental limits or requirements. P-No. 1 groups 1 and 2
environmental restrictions. These include WCC and LCC castings, A105
are typically expressed in terms of forgings, A516 Grade 70 plate, and
H2S partial pressure, maximum tem- the other common carbon steel pres-
perature, ppm chlorides, and the pres- sure vessel materials.
ence of free sulfur.
" MR0103 imposes welding con-
" 316 usage is still allowed but un- trols on carbon steels that are more
der very limited environmental condi- rigorous than those imposed by
tions. The impact, if strictly followed, MR0175-2002. MR0103 requires that
is that this material will find very little P-No. 1 carbon steels be welded per
use. another NACE document called
RP0472 Methods and Controls to
" The standard applies only to pe- Prevent In-Service Environmental
troleum production, drilling, gathering Cracking of Carbon Steel Weldments
and flow line equipment, and field in Corrosive Petroleum Refining Envi-
processing facilities to be used in H2S ronments. RP0472 imposes controls
bearing hydrocarbon service. It does that ensure both the weld deposit and
not apply to refineries. heat affected zone (HAZ) in a weld-
ment will be soft enough to resist sul-
" There is clear responsibility fide stress cracking. RP0472 invokes
placed on the buyer to specify the cor- actual hardness testing of weld de-
rect materials. The manufacturer is posits in production, although hard-
responsible for meeting the metallurgi- ness testing is waived if certain weld-
cal requirements of MR0175/ISO ing process/filler material
15156. combinations are employed. HAZ
hardness may be controlled by either
post-weld heat treatment (PWHT) or
NACE MR0103 by base material chemistry restrictions
As mentioned, NACE MR0103 is simi- such as imposing a maximum carbon
lar in many respects to the pre-2003 equivalent (CE).
revisions of NACE MR0175. Follow-
ing are the some major differences: " Like the 2003 and later revisions
of MR0175, MR0103 does not allow
" MR0103 utilizes different, refin- the use of S17400 double H1150 ma-
ery-based definitions for what consti- terial for bolting. This means that the
tutes a sour environment. The user is 17-4PH H1150 DBL bolting that was
responsible for imposing the require- previously used for full-rated exposed
ments of MR0103 when they are ap- bolting in a Class 600 valve is no lon-
plicable. ger allowed.
153
Chapter 6. Special Control Valves

154
Chapter 7

Steam Conditioning Valves

Steam conditioning valves include A desuperheater injects a controlled,


those in desuperheating, steam condi- predetermined amount of water into a
tioning, and turbine bypass systems, steam flow to lower the temperature of
covered in this chapter. the steam. To achieve this efficiently,
the desuperheater must be designed
and selected correctly for the applica-
tion. Although it can appear simplistic
Understanding in design, the desuperheater must in-
Desuperheating tegrate with a wide variety of complex
thermal and flow dynamic variables to
Superheated steam provides an ex- be effective. The control of the water
cellent source of energy for mechani- quantity, and thus the steam tempera-
cal power generation. However, in ture, uses a temperature control loop.
many instances, steam at greatly re- This loop includes a downstream tem-
duced temperatures, near saturation, perature sensing device, a controller
proves a more desirable commodity. to interpret the measured temperature
This is the case for most heattransfer relative to the desired set point, and
applications. Precise temperature the transmission of a proportional sig-
control is needed to improve heating nal to a water controlling valve/actua-
efficiency; eliminate unintentional su- tor assembly to meter the required
perheat in throttling processes; or to quantity of water.
protect downstream product and/or
equipment from heat related damage. The success or failure of a particular
One method to reduce temperature is desuperheater installation rests on a
the installation of a desuperheater. number of physical, thermal, and geo-
155
Chapter 7. Steam Conditioning Valves

B2567/IL

Figure 7-1. Desuperheater Installations

metric factors. Some of these are ob- ! Pipeline size


vious and some obscure, but all of
them have a varying impact on the ! Steam velocity
performance of the equipment and the
system in which it is installed. ! Equipment versus system turn-
down
The first, and probably the most im-
portant factor for efficient desuper- Installation orientation is an often
heater operation, is to select the cor- overlooked, but critical factor in the
rect design for the respective performance of the system. Correct
application. Desuperheaters come in placement of the desuperheater can
all shapes and sizes and use various have a greater impact on the opera-
energy transfer and mechanical tech- tion than the style of the unit itself. For
niques to achieve the desired perfor- most units, the optimum orientation is
mance within the limits of the system in a vertical pipeline with the flow di-
environment. Another section details rection up. This is contrary to most
the differences in the types of desup- installations seen in industry today.
erheaters available and expected per- Other orientation factors include pipe
formance. fittings, elbows, and any other type of
pipeline obstruction that exists down-
stream of the water injection point.
Technical Aspects of Figure 7-1 illustrates variations in the
Desuperheating installation of a desuperheater.

Some of the physical parameters that Spraywater temperature can have a


affect the performance of a desuper- significant impact on desuperheater
heating system include: performance. Although it goes against
logical convention, hightemperature
! Installation orientation water is better for cooling. As the
spraywater temperature increases,
flow and thermal characteristics im-
! Spraywater temperature
prove and impact the following:

! Spraywater quantity ! Surface tension


156
Chapter 7. Steam Conditioning Valves

B2568/IL

Figure 7-2. Spray Penetration

! Drop size distribution To perform a basic Cv calculation for


initial desuperheater sizing, it is re-
! Latent heat of vaporization quired that the resultant Qw(mass) is
converted to Qw(volumetric). When
! Vaporization rate using English units the conversion is
done as follows:
Improvements in all these areas, as a
Qw(mass) * 0.1247
result of increased spraywater tem- Qw(volumetric) ! pw
perature, improves the overall perfor-
mance of the system. Qw(volumetric) is in GPM and !w is
the density of the spraywater in Lbm/
The quantity of water to be injected Ft3. Based on this conversion, the siz-
will have a directly proportional effect ing can be completed with the follow-
on the time for vaporization. The heat ing Cv calculation for each set of
transfer process is time dependent conditions:
and, thus, the quantity of spraywater
will affect the time for complete vapor-
ization and thermal stability. C v ! Qw(volumetric) * %!Pdsh
SG

To determine the spraywater required Where SG is the specific gravity of the


(Qw) as a function of inlet steam flow spraywater and "Pdsh is the pressure
(Q1), perform a simple heat balance differential across the proposed de-
using the following equation: superheater.
When designing a new desuperheater
Qw(mass) ! Q1 * "H2
H1 # H2
# Hw
$ installation, another concern for prop-
er system performance is the pipeline
size. As the line size gets larger, more
Where Q is the mass flow in PPH and
attention must be paid to the penetra-
H is the individual enthalpy values at
tion velocity of the spray and the cov-
the inlet, outlet, and spraywater.
erage in the flow stream (figure 7-2).
When the calculation is performed as Some single-point, injection type de-
a function of outlet steam flow (Q2), superheaters have insufficient nozzle
that is, the combination of inlet steam energy to disperse throughout the en-
flow and desuperheating spraywater, tire cross sectional flow area of the
use the following equation: pipeline. As a result, the spray pattern
collapses and thermal stratification oc-
Qw(mass) ! Q2 * "Hw
H1 # H2
# H1
$ curs, that is, a sub-cooled center core
that is shrouded with superheated
157
Chapter 7. Steam Conditioning Valves
steam. This condition is normally elim- this is understood, it is obvious that a
inated after the flow stream has un- good desuperheater cannot overcome
dergone several piping directional the failings of a poor system. They
changes, but this is not always pos- must be evaluated on their own merits
sible within the limits of the control and weighted accordingly.
system or process. Proper placement
of high-energy, multi-nozzle units in Due to improved nozzle design
the larger pipelines normally prevents technology, pipe liners are rarely re-
the formation of thermal stratification. quired. Depending on the particulate
quality of the water source, in-line
The maximum and minimum velocity strainers may be required.
of the steam has a direct relationship The previous calculations and recom-
on the successful mixing of the water. mendations provide the necessary in-
The velocity directly affects the resi- formation to select the proper desup-
dence time available for the water to erheater design and size. This
mix with the steam. When the maxi- selection should be based on a variety
mum velocity is too high, there poten- of application considerations such as:
tially is not enough time for the water
to mix before it encounters a piping ! Minimum to maximum load re-
obstruction such as an elbow or tee. quirement rangeability
Ideal maximum velocity usually
! Minimum steam velocity
ranges from 150-250 feet per second
(4676 meters per second). When the ! Straight pipe length and temper-
minimum velocity is too low, turbu- ature sensor distance after the desup-
lence is reduced and then the water erheater
droplets tend to fall out of suspension
in the steam. As a rule, the minimum ! Steam pipe line size and
steam velocity in which water can re-
main suspended is approximately 30 ! Pressure differential between
feet per second (9 meters per sec- water and steam
ond). For applications with lower ve-
locities, proper mixing may be Typical Desuperheater
achieved with desuperheaters that of-
fer a venturi or atomizing steam.
Designs

One of the most over-used and mis- Fixed Geometry Nozzle Design
understood concepts in the area of The fixed geometry nozzle design (fig-
desuperheating is turndown. When ure 7-3) is a simple mechanically at-
applied to a final control element, omized desuperheater with single or
such as a valve, turndown is a simple multiple fixed geometry spray nozzles.
ratio of the maximum to the minimum It is intended for applications with
controllable flow rate. Turndown is nearly constant load changes (range-
sometimes used interchangeably with ability up to 5:1) and is capable of
rangeability. However, the exact proper atomization in steam flow ve-
meaning differs considerably when it locities as low as 14 feet per second
comes to actual performance compar- under optimum conditions. Standard
isons. installation of this type of unit is
through a flanged branch connection
A desuperheater is not a final control tee on a 6-inch or larger steam pipe
element, and as such, its performance line. This design is usually not avail-
is directly linked to its system environ- able for large Cv requirements. This
ment. The actual system turndown is unit requires an external water control
more a function of the system param- valve to meter water flow based on a
eters rather than based on the equip- signal from a temperature sensor in
ments empirical flow variations. Once the downstream steam line.
158
Chapter 7. Steam Conditioning Valves
try, back pressure activated spray
nozzles. Due to the variable geometry,
this unit can handle applications re-
quiring control over moderate load
changes (rangeability up to 20:1) and
is capable of proper atomization in
steam flow velocities as low as 14 feet
per second under optimum conditions.
Standard installation of this type of
unit is through a flanged branch con-
nection tee on an 8-inch or larger
steam pipe line. These units are avail-
able for large Cv requirements. This
design requires an external water con-
trol valve to meter water flow based
W7102/IL on a signal from a temperature sensor
in the downstream steam line.
Figure 7-3. Fixed Geometry
Nozzle Design

Self-Contained Design

The self-contained design (figure 7-5)


is also mechanically atomized with
one or more variable geometry, back
pressure activated spray nozzles. As
a special feature, this unit incorpo-
rates a water flow control element that
performs the function normally pro-
vided by an external water control
valve. This control element has a plug
that moves inside a control cage by
means of an actuator, which receives
a signal from a temperature sensor in
the downstream steam line. The water
flow then passes to the variable ge-
,'&%$"%#*+ ometry nozzle(s) and is atomized as it
enters the steam pipe line. Because of
the close coordination of the intrinsic
Figure 7-4. Variable Geometry control element and the variable ge-
Nozzle Design ometry nozzle(s), this unit can handle
applications requiring control over
moderate to high load changes
(rangeability up to 25:1). It offers prop-
er atomization in steam flow velocities
Variable Geometry Nozzle as low as 14 feet per second under
Design optimum conditions. Standard installa-
tion of this type of unit is through a
The variable geometry nozzle design flanged branch connection tee on an
(figure 7-4) is also a simple mechani- 8-inch or larger steam pipe line.
cally atomized desuperheater, but it These are available for moderate Cv
employs one or more variable geome- requirements.
159
Chapter 7. Steam Conditioning Valves

W6982-1 / IL

Figure 7-5. Self-Contained Design

omizing steam, usually twice the main


steam line pressure or higher, en-
counters the water in the spray nozzle
chamber where the energy of the ex-
panding atomizing steam is used to
atomize the water into very small
droplets. These smaller droplets allow
for faster conversion to steam and
permit the water to remain suspended
in a low steam velocity flow, thereby
allowing complete vaporization to oc-
cur. The steam atomized design,
therefore, can properly mix water into
steam flow velocities as low as
approximately 4 feet per second (1.2
W6311/IL
meters per second) under optimum
conditions. This design handles ap-
plications requiring very high load
Figure 7-6. Steam Assisted Design
changes (rangeability up to 50:1).
Standard installation of this type of
unit is through a flanged branch con-
Steam Atomized Design nection tee on an 8-inch or larger
The steam atomized design (figure steam pipe line. This design is avail-
7-6) incorporates the use of high-pres- able for moderate Cv requirements. It
sure steam for rapid and complete at- requires an external water control
omization of the spraywater. This is valve to meter water flow based on a
especially useful in steam pipe lines signal from a temperature sensor in
that have low steam velocity. The at- the downstream steam line. This sys-
160
Chapter 7. Steam Conditioning Valves

W6313-1/IL

Figure 7-7. Geometry-Assisted Wafer Design

tem also requires a separate on/off Understanding Steam


valve for the atomizing steam supply.
Conditioning Valves
A steam conditioning valve is used for
Geometry-Assisted Wafer the simultaneous reduction of steam
Design pressure and temperature to the level
required for a given application. Fre-
The geometry-assisted wafer design quently, these applications deal with
(figure 7-7) was originally developed high inlet pressures and temperatures
for small steam pipe line sizes of less and require significant reductions of
than 6-inch that were unable to ac- both properties. They are, therefore,
commodate an insertion style desup- best manufactured in a forged and
erheater. The unit is designed as a fabricated body that can better with-
wafer that is installed between two stand steam loads at elevated pres-
flanges in the steam pipe line. A re- sures and temperatures. Forged ma-
duced diameter throat venturi allows terials permit higher design stresses,
water to spray completely around the improved grain structure, and an in-
wafer and permits multiple points of herent material integrity over cast
spraying either through drilled holes or valve bodies. The forged construction
small nozzles. In addition, the venturi also allows the manufacturer to pro-
increases the steam velocity at the vide up to Class 4500, as well as in-
point of injection, which enhances at- termediate and special class ratings,
omization and mixing in steam flow with greater ease versus cast valve
velocities as low as approximately 10 bodies.
feet per second (3 meters per second)
under optimum conditions. It handles Due to frequent extreme changes in
applications requiring control over steam properties as a result of the
moderate load change (rangeability temperature and pressure reduction,
up to 20:1). It can be installed in the forged and fabricated valve body
steam pipe line sizes of 1-inch design allows for the addition of an
through 24-inch, and is available for expanded outlet to control outlet
moderate Cv requirements. This de- steam velocity at the lower pressure.
sign requires an external water control Similarly, with reduced outlet pres-
valve to meter water flow based on a sure, the forged and fabricated design
signal from a temperature sensor in allows the manufacturer to provide dif-
the downstream steam line. ferent pressure class ratings for the
161
Chapter 7. Steam Conditioning Valves
inlet and outlet connections to more
closely match the adjacent piping
Other advantages of combining the
pressure reduction and desuperheater
function in the same valve versus two
separate devices include:

! Improved spraywater mixing due


to the optimum utilization of the turbu-
lent expansion zone downstream of
the pressure reduction elements

! Improved rangeability

! Increased noise abatement due,


in part, to the additional attenuation of
noise as a result of the spraywater in-
jection

! In some designs, improved re-


sponse time due to an integrated
feedforward capability

! Ease of installing and servicing


only one device W8740-2A

Several available steam conditioning Figure 7-8. Steam Conditioning Valve


valve designs meet various applica-
tions. Typical examples of these fol-
low. options that yield efficient operation
over a wide range of conditions and
customer specified requirements.
Steam Conditioning
Valves The steam-conditioning valve shown
in figure 7-8) combines pressure and
Steam conditioning valves represent temperature control in a single valve.
state-of-the-art control of steam pres- Finite element analysis (FEA) and
sure and temperature by integrally computational fluid dynamic (CFD)
combining both functions within one tools were used in its development to
control element unit. These valves ad- optimize the valves operating perfor-
dress the need for better control of mance and overall reliability. The
steam conditions brought on by in- rugged design of this steam condition-
creased energy costs and more rigor- ing valve proves capable of handling
ous plant operation. Steam condition- full mainstream pressure drops, while
ing valves also provide better its flow-up configuration in conjunction
temperature control, improved noise with control valve noise abatement
abatement, and require fewer piping technology prevents the generation of
and installation restrictions than the excessive noise and vibration.
equivalent desuperheater and pres-
sure reduction station. The simplified trim configuration (fig-
ure 7-9) used in the steam condition-
Steam conditioning valve designs can ing valve accommodates rapid
vary considerably, as do the applica- changes in temperature, as experi-
tions they are required to handle. enced during a turbine trip. The cage
Each has particular characteristics or is case hardened for maximum life
162
Chapter 7. Steam Conditioning Valves

W8493-1

Figure 7-9. Cross-Section View of Steam ConditioningValve

and is allowed to expand during ther-


mally induced excursions. The valve
plug is continuously guided and uti-
lizes cobalt-based overlays both as
guide bands and to provide tight,
metal-to-metal shutoff against the
seat.

The steam conditioning valve incorpo-


rates a spraywater manifold down-
stream of its pressure reduction stage.
The manifold features variable geom-
etry, backpressure activated spray
nozzles that maximize mixing and
quick vaporization of the spraywater. W8494-1

Figure 7-10. Variable Geometry, Back-


The spray nozzle (figure 7-10) was pressure Activated Spray Nozzle
developed originally for condenser
dump systems in which the down- ed nozzle at a critical point in the op-
stream steam pressure can fall below eration.
the saturation level. In these
instances, the spraywater may flash Spring loading of the valve plug within
and significantly change the flow char- the spray nozzle prevents any such
acteristic and capacity of the associat- changes by forcing the plug to close
163
Chapter 7. Steam Conditioning Valves

W8786-1

Figure 7-11. Steam Cooler

when flashing occurs. With flashing, stroke in less than two seconds while
the compressibility of the fluid maintaining highly accurate step re-
changes, and the nozzle spring will sponse.
force closure and re-pressurization of
the fluid leg. Once this is done, the When piping dictates, the steam con-
fluid will regain its liquid properties ditioning valve can be provided as
and reestablish flow to the condenser. separate components, allowing pres-
sure control in the valve body and
The steam conditioning valve injects temperature reduction in a down-
the spray water towards the center of stream steam cooler.
the pipeline and away from the pipe
wall. The number of injection points Steam Cooler
varies by application. With high differ-
entials in steam pressure, the outlet The steam cooler (figure 7-11) normal-
size of the valve increases drastically ly is used when an application re-
to accommodate the larger specific quires a separation of the pressure
volumes. Correspondingly, an in- reduction and desuperheating func-
creased number of nozzles are ar- tions. The steam cooler is equipped
ranged around the circumference of with a water supply manifold. The
the outlet, making for a more even manifold (multiple manifolds are pos-
and complete distribution of the spray sible) provides cooling water flow to a
water. number of individual spray nozzles
installed in the pipe wall of the outlet
The simplified trim arrangement in the section. The result is a fine spray in-
steam conditioning valve permits ex- jected radially into the high turbulence
tending its use to higher pressure of the axial steam flow. The combina-
classes (through ANSI Class 2500) tion of large surface area contact of
and operating temperatures. Its bal- the water and high turbulence in the
anced plug configuration provides steam make for very efficient mixing
Class V shutoff and a linear flow char- and rapid vaporization.
acteristic.

The steam conditioning valve typically


Steam Sparger
uses high-performance, pneumatic Steam spargers (figures 7-12 and
piston actuators in combination with a 7-13) are pressure-reducing devices
digital valve controller to achieve full used to safely discharge steam into a
164
Chapter 7. Steam Conditioning Valves
technology. Sparger design and instal-
lation are both key elements when
considering total system noise.

Understanding Turbine
Bypass Systems
The turbine bypass system has
evolved over the last few decades as
the mode of power plant operations
has changed. It is employed routinely
in utility power plants where opera-
tions require quick response to wide
swings in energy demands. A typical
day of power plant operation might
start at minimum load, increase to full
W7017-1
capacity for most of the day, rapidly
reduce back to minimum output, then
Figure 7-12. Steam Sparger with up again to full loadall within a
Drilled-Hole Noise Control Technology twenty-four hour period. Boilers, tur-
bines, condensers and other associat-
ed equipment cannot respond proper-
ly to such rapid changes without some
form of turbine bypass system.
The turbine bypass system allows op-
eration of the boiler independent of
the turbine. In the start-up mode, or
rapid reduction of generation require-
ment, the turbine bypass not only sup-
plies an alternate flow path for steam,
but conditions the steam to the same
pressure and temperature normally
produced by the turbine expansion
process. By providing an alternate
flow path for the steam, the turbine
bypass system protects the turbine,
boiler, and condenser from damage
that may occur from thermal and pres-
W8684-2 sure excursions. For this reason,
many turbine bypass systems require
Figure 7-13. Steam Sparger Utilizing extremely rapid open/close response
Multi-Stage Pressure Drop Technique times for maximum equipment protec-
tion. This is accomplished with an
electrohydraulic actuation system that
condenser or turbine exhaust duct. In provides both the forces and controls
addition, the steam sparger provides for such operation.
backpressure to the turbine bypass
valve, limits steam velocity and allows Additionally, when commissioning a
reduced pipe size between the bypass new plant, the turbine bypass system
valve and sparger. The design of the allows start-up and check out of the
sparger is critical to a properly func- boiler separately from the turbine.
tioning turbine bypass system. To ad- This means quicker plant start-ups,
dress flowinduced noise, steam which results in attractive economic
spargers can employ noise abatement gains. It also means that this closed
165
Chapter 7. Steam Conditioning Valves

2
1

6 4

3 5

Equipment: Equipment:

1. HP Turbine Bypass Steam Valves 4. LP Turbine Bypass Steam Valves


2. HP Turbine Bypass Control and Water Isolation Valves 5. LP Turbine Bypass Water Valves
3. EHS Electrohydraulic System 6. LP Turbine Bypass Steam Stop Valves (optional)
Electrical Control Logic 3. EHS Electrohydraulic system
Hydraulic Control Logic
Accumulators and Accumulator Power System
Hydraulic Power Unit
Control Cabinet
Piston Actuators and Proportional Valves
B2569 / IL
Figure 7-14. Turbine Bypass System

loop system can prevent atmospheric section located closer to the con-
loss of treated feedwater and reduc- denser. Regardless of the configura-
tion of ambient noise emissions. tion, however, a cost effective solution
is a fixed-orifice device (usually a
sparger) located downstream for final
Turbine Bypass System pressure reduction to minimize the
size of the outlet pipe to the con-
Components denser.
The major elements of a turbine by-
pass system (figure 7-14) are turbine
Turbine Bypass Water Control
bypass valves, turbine bypass water
control valves, and the electro-hydrau- Valves
lic system. These valves are required to control
the flow of the water to the turbine by-
pass valves. Due to equipment
Turbine Bypass Valves protection requirements, it is impera-
Whether for low-pressure or tive that these valves provide tight
high-pressure applications, turbine by- shutoff (Class V).
pass valves are usually the manifold
design steam conditioning valves pre-
Electro-Hydraulic System
viously described with tight shutoff
(Class V). Because of particular instal- This system is for actuating the
lation requirements these manifold de- valves. Its primary elements include
sign valves will occasionally be sepa- the actual hydraulic actuators, the hy-
rated into two parts: the draulic accumulator and power unit,
pressure-reducing portion of the valve and the control unit and operating
and then the outlet/manifold cooler logic.
166
Chapter 8

Installation and Maintenance

Control valve efficiency directly affects yields, quality products, maximum


process plant profits. The role a con- profits, and energy conservation.
trol valve plays in optimizing pro-
cesses is often overlooked. Many pro- Optimizing control valve efficiency de-
cess plant managers focus most pends on:
resources on distributed control sys- 1. Correct control valve selection for
tems and their potential for improving the application,
production efficiency. However, it is
the final control element (typically a 2. Proper storage and protection,
control valve) that actually creates the
3. Proper installation techniques, and
change in process variable. If the
valve is not working properly, no 4. An effective predictive maintenance
amount of sophisticated electronics at program.
the front end will correct problems at
the valve. As many studies have Control valve selection is covered in
shown, control valves are often ne- Chapter 5. The other three topics are
glected to the point that they become included in this chapter.
the weak link in the process control
scheme. Proper Storage and
Control valves must operate properly,
Protection
no matter how sophisticated the au- Proper storage and protection should
tomation system or how accurate the be considered early in the selection
instrumentation. Without proper valve process, before the valve is shipped.
operation you cannot achieve high Typically, manufacturers have packag-
167
Chapter 8. Installation and Maintenance
ing standards that are dependent
upon the destination and intended
length of storage before installation.
Because most valves arrive on site
some time before installation, many
problems can be averted by making
sure the details of the installation
schedule are known and discussed
with the manufacturer at the time of
valve selection. In addition, special
precautions should be taken upon re-
W1916/IL
ceipt of the valve at the final destina-
tion. For example, the valve must be
stored in a clean, dry place away from Figure 8-1. Install the Valve with the
any traffic or other activity that could Flow Arrow Pointing in the Direction of
damage the valve. the Process Flow

on the female threads because ex-


Proper Installation cess compound on the female threads
Techniques could be forced into the valve body.
Excess compound could cause stick-
Always follow the control valve ing in the valve plug or accumulation
manufacturers installation instructions of dirt, which could prevent good valve
and cautions. Typical instructions are shutoff.
summarized here.
Inspect the Control Valve
Read the Instruction Manual Although valve manufacturers take
steps to prevent shipment damage,
Before installing the valve, read the such damage is possible and should
instruction manual. Instruction manu- be discovered and reported before the
als describe the product and review valve is installed.
safety issues and precautions to be
taken before and during installation. Do not install a control valve known to
Following the guidelines in the manual have been damaged in shipment or
helps ensure an easy and successful while in storage.
installation. Before installing, check for and re-
move all shipping stops and protective
Be Sure the Pipeline Is Clean plugs or gasket surface covers. Check
inside the valve body to make sure no
Foreign material in the pipeline could foreign objects are present.
damage the seating surface of the
valve or even obstruct the movement Use Good Piping Practices
of the valve plug, ball, or disk so that
Most control valves can be installed in
the valve does not shut off properly.
any position. However, the most com-
To help reduce the possibility of a
mon method is with the actuator verti-
dangerous situation from occurring,
cal and above the valve body. If hori-
clean all pipelines before installing.
zontal actuator mounting is necessary,
Make sure pipe scale, metal chips,
consider additional vertical support for
welding slag, and other foreign materi-
the actuator. Be sure the body is
als are removed. In addition, inspect
installed so that fluid flow will be in the
pipe flanges to ensure a smooth gas-
direction indicated by the flow arrow
ket surface. If the valve has screwed
(figure 8-1) or instruction manual.
end connections, apply a good grade
of pipe sealant compound to the male Be sure to allow ample space above
pipeline threads. Do not use sealant and below the valve to permit easy re-
168
Chapter 8. Installation and Maintenance

Control Valve
Maintenance
Always follow the control valve
manufacturers maintenance instruc-
tions. Typical maintenance topics are
summarized here.
Optimization of control valve assets
depends on an effective maintenance
philosophy and program. Three of the
most basic approaches are:
A0274-1/IL

Reactive Action is taken after an


Figure 8-2. Tighten Bolts in a event has occurred. Wait for some-
Criss-cross Pattern thing to happen to a valve and then
repair or replace it.

moval of the actuator or valve plug for Preventive Action is taken on a


inspection and maintenance. Clear- timetable based on history; that is, try
ance distances are normally available to prevent something bad from hap-
from the valve manufacturer as certi- pening.
fied dimension drawings. For flanged Predictive Action is taken based on
valve bodies, be sure the flanges are field input using state-of-the-art,
properly aligned to provide uniform non-intrusive diagnostic test and
contact of the gasket surfaces. Snug evaluation devices or using smart
up the bolts gently after establishing instrumentation.
proper flange alignment. Finish tight-
Although both reactive and preventive
ening them in a criss-cross pattern
programs work, they do not optimize
(figure 8-2). Proper tightening will
valve potential. Following are some of
avoid uneven gasket loading and will
the disadvantages of each approach.
help prevent leaks. It also will avoid
the possibility of damaging, or even
Reactive Maintenance
breaking, the flange. This precaution
is particularly important when con- Reactive maintenance allows subtle
necting to flanges that are not the deficiencies to go unnoticed and un-
same material as the valve flanges. treated, simply because there is no
clear indication of a problem. Even
Pressure taps installed upstream and critical valves might be neglected until
downstream of the control valve are they leak badly or fail to stroke. In
useful for checking flow capacity or some cases, feedback from produc-
pressure drop. Locate such taps in tion helps maintenance react before
straight runs of pipe away from el- serious problems develop, but valves
bows, reducers, or expanders. This might be removed unnecessarily on
location minimizes inaccuracies re- the suspicion of malfunction. Large
sulting from fluid turbulence. valves or those welded in-line can re-
quire a day or longer for removal, dis-
Use1/4- or 3/8-inch (6-10 millimeters) assembly, inspection, and reinstalla-
tubing or pipe from the pressure con- tion. Time and resources could be
nection on the actuator to the control- wasted without solving the problem if
ler. Keep this distance relatively short the symptoms are actually caused by
and minimize the number of fittings some other part of the system.
and elbows to reduce system time lag.
If the distance must be long, use a Preventive Maintenance
valve positioner or a booster with the Preventive maintenance generally
control valve. represents a significant improvement.
169
Chapter 8. Installation and Maintenance
However, because maintenance valve maintenance work practices.
schedules have been able to obtain These digital devices significantly im-
little information on valves that are op- prove upon the fault detection and dis-
erating, many plants simply overhaul crimination aspects of traditional
all control valves on a rotating sched- maintenance programs.
ule. Such programs result in servicing
some valves that need no repair or For example, in-service diagnostics
adjustment and leaving others in the (figure 8-3) can detect problems with
system long after they have stopped instrument air quality, leakage and
operating efficiently. supply pressure restriction, and can
identify such valve problems as ex-
cessive friction and deadband as well
Predictive Maintenance as being out-of-calibration. When a
Today, plant operators often extend problem is identified, its severity is re-
the time between turnarounds to three ported, possible causes are listed and
or four years and even longer in order a course of action is given. These
to maximize process availability. diagnostics typically result in one of
These extended run times offer less three conditions:
opportunity for traditional, out-of-ser- ! No fault detected (green condi-
vice valve diagnostics. tion). The valve should remain in ser-
vice, and monitoring should continue.
The traditional maintenance process
consists of four distinct modes: ! A warning that a fault has been de-
Fault Detection A majority of valve tected, but control remains unaffected
(yellow condition). This is a predictive
maintenance effort is spent in monitor-
indication that the detected problem has
ing valves while in service to detect the potential to affect control and that
the occurrence of a fault. When a fault future maintenance should be planned.
is identified, the maintenance process
transitions to fault discrimination. ! An error report that a fault affecting
control has been detected (red condi-
Fault Discrimination During this tion). These faults generally require im-
mode, valve assets are evaluated to mediate attention.
determine the cause of the fault and
to establish a course of corrective ac- More specifically, in-service diagnos-
tion. tics oversee:
Process Recovery Corrective action
is taken to fix the source of the defect. Instrument Air Leakage
Air mass flow diagnostics measure
Validation In this final mode, valve instrument air flow through the control
assets are evaluated relative to either valve assembly. Because of multiple
asnew condition or the last estab- sensors, this diagnostic can detect
lished baseline condition. Once vali- both positive (supply) and negative
dated, the maintenance process re- (exhaust) air mass flow from the DVC.
turns to fault detection status. This diagnostic not only detects leaks
in the actuator or related tubing, but
also much more difficult problems. For
example, in piston actuators, the air
Using Control Valve mass flow diagnostic can detect leak-
Diagnostics ing piston seals or damaged O-rings.
The advent of micro-processor based
valve instruments with their in-service Supply Pressure
diagnostics capabilities has allowed The supply pressure diagnostic de-
companies to redesign their control tects control valve problems related to
170
Chapter 8. Installation and Maintenance

W7046/IL

Figure 8-3. Non-Intrusive Diagnostics Program for Predictive Maintenance

supply pressure. This in-service diag- feting by fluid forces. If the crossover
nostic will detect both low and high pressure is set too high, both cham-
supply pressure readings. In addition bers will be near supply, the pneumat-
to checking for adequate supply pres- ic forces will be roughly equal, the
sure, this diagnostic can be used to spring force will be dominant and the
detect and quantify droop in the air actuator will move to its spring-fail
supply during large travel excursions. position.
This is particularly helpful in identify-
ing supply line restrictions. Instrument Air Quality
The I/P and relay monitoring diagnos-
Travel Deviation and Relay tic can identify problems such as plug-
Adjustment ging in the I/P primary or in the I/P
nozzle, instrument diaphragm failures,
The travel deviation diagnostic is used I/P instrument O-ring failures, and I/P
to monitor actuator pressure and trav- calibration shifts. This diagnostic is
el deviation from setpoint. This diag- particularly useful in identifying prob-
nostic is useful in identifying a stuck lems from contaminants in the air sup-
control valve, active interlocks, low ply and from temperature extremes.
supply pressure or shifts in travel cal-
ibration.
In-Service Friction and Friction
The relay adjustment diagnostic is Trending
used to monitor crossover pressure The in-service friction and deadband
on double-acting actuators. If the diagnostic determines friction in the
crossover pressure is too low, the ac- valve assembly as it is controlled by
tuator loses stiffness, making the the control system. Friction diagnos-
valve plug position susceptible to buf- tics data is collected and trended to
171
Chapter 8. Installation and Maintenance
detect valve changes that affect pro-
cess control.

Other Examples
In-service custom diagnostics can be
configured to collect and graph any
measured variable of a smart valve.
Custom diagnostics can locate and
discriminate faults not detectable by
other means. Often, these faults are
complicated and require outside ex-
pertise. In such cases, data is col-
lected by local maintenance personnel
and is then sent to an expert for fur-
ther analysis, thus avoiding the costs
and delays associated with an on-site
visit.

Continued Diagnostics W0363/IL

Development
Overall, the process industries will Figure 8-4. Typical
continue to demand more and more Spring-and-Diaphragm Actuator
efficiency in terms of quality, yield and
reliability. Individually, producers will
continue to lengthen time between Actuator Diaphragm
turnarounds. These demands will lead Most pneumatic spring-and-dia-
to fewer and fewer maintenance man phragm actuators (figure 8-4) use a
hours being available for instrumenta- molded diaphragm. The molded dia-
tion repair. The inevitable answer to phragm facilitates installation, pro-
this shortfall will be future diagnostic vides a relatively uniform effective
developments that focus on in-ser- area throughout valve travel, and per-
vice, non-intrusive test and evaluation mits greater travel than could be pos-
capabilities. sible with a flat-sheet diaphragm. If a
The ability to evaluate valve perfor- flat-sheet diaphragm is used for emer-
mance via in-service diagnostics im- gency repair, replace it with a molded
proves turnaround planning as the in- diaphragm as soon as possible.
formation gathered can be used to
pinpoint valve maintenance that is Stem Packing
necessary as well as valves that are Packing (figure 8-5), which provides
healthy. the pressure seal around the stem of
a globe-style or angle-style valve
An answer is to utilize micro-proces- body, should be replaced if leakage
sor-based valve instrumentation that develops around the stem, or if the
evaluates the operating health of the valve is completely disassembled for
control valve assembly while the valve other maintenance or inspection. Be-
is in service. Data is collected without fore loosening packing nuts, make
intruding on normal process opera- sure there is no pressure in the valve
tions. The instrumentation analyzes body.
the information in real-time and pro-
vides maintenance recommendations Removing the packing without remov-
for each valve operating problem that ing the actuator is difficult and is not
it identifies. recommended. Also, do not try to
172
Chapter 8. Installation and Maintenance

Seat Rings
Severe service conditions can dam-
age the seating surface of the seat
ring(s) so that the valve does not shut
off satisfactorily. Grinding or lapping
the seating surfaces will improve shut-
off if damage is not severe. For se-
vere damage, replace the seat ring.

Grinding Metal Seats


The condition of the seating surfaces
of the valve plug and seat ring can
often be improved by grinding. Many
grinding compounds are available
commercially. For cage-style
constructions, bolt the bonnet or bot-
tom flange to the body with the gas-
kets in place to position the cage and
seat ring properly and to help align the
W2911/IL
valve plug with the seat ring while
grinding . A simple grinding tool can
Figure 8-5. Typical Valve be made from a piece of strap iron
Stem Packing Assemblies locked to the valve plug stem with
nuts.
On double-port bodies, the top ring
blow out the old packing rings by ap- normally grinds faster than the bottom
plying pressure to the lubricator hole ring. Under these conditions, continue
in the bonnet. This can be dangerous. to use grinding compound on the bot-
Also, it frequently does not work very tom ring, but use only a polishing
well as many packing arrangements compound on the top ring. If either of
have about half of the rings below the the ports continues to leak, use more
lubricator hole. grinding compound on the seat ring
that is not leaking and polishing com-
A better method is to remove the ac- pound on the other ring. This proce-
tuator and valve bonnet and pull out dure grinds down the seat ring that is
the stem. Push or drive the old pack- not leaking until both seats touch at
ing out the top of the bonnet. Do not the same time. Never leave one seat
use the valve plug stem because the ring dry while grinding the other.
threads could sustain damage.
After grinding, clean seating surfaces,
Clean the packing box. Inspect the and test for shutoff. Repeat grinding
stem for scratches or imperfections procedure if leakage is still excessive.
that could damage new packing.
Check the trim and other parts as ap- Replacing Seat Rings
propriate. After re-assembling, tighten Follow the manufacturers instruc-
body/bonnet bolting in a sequence tions. For threaded seat rings, use a
similar to that described for flanges seat ring puller (figure 8-6). Before try-
earlier in this chapter. ing to remove the seat ring(s), check
to see if the ring has been
Slide new packing parts over the stem
tack-welded to the valve body. If so,
in proper sequence, being careful that
cut away the weld.
the stem threads do not damage the
packing rings. Adjust packing by fol- On double-port bodies, one of the
lowing the manufacturers instructions. seat rings is smaller than the other.
173
Chapter 8. Installation and Maintenance

A2219/IL

A7097/IL

Figure 8-7. Bench Set Seating Force


Figure 8-6. Seat Ring Puller

On direct-acting valves
(push-down-to-close action), install
spring adjuster. For air-to-open
the smaller ring in the body port far-
ther from the bonnet before installing valves, the lower bench set deter-
the larger ring. On reverse-acting mines the amount of seat load force
valves (push-down-to-open action), available and the pressure required to
install the smaller ring in the body port begin valve-opening travel. For
closer to the bonnet before installing air-to-close valves, the lower bench
larger ring. set determines the pressure required
to begin valve-closing travel. Seating
Remove all excess pipe compound force is determined by pressure ap-
after tightening the threaded seat ring. plied minus bench set minus spring
Spot weld a threaded seat ring in
compression due to travel (figure 8-7).
place to ensure that it does not loos-
Because of spring tolerances, there
en.
might be some variation in the spring
angle. The bench set, when the valve
Bench Set is seated, requires the greatest accu-
Bench set is initial compression racy. Refer to manufacturers instruc-
placed on the actuator spring with a tions for adjusting the spring.

174
Chapter 9

Standards and Approvals

Control Valve Standards American Society of Mechanical


Engineers (ASME)
Numerous standards are applicable to
control valves. International and glob- B16.1, Cast Iron Pipe Flanges and
al standards are becoming increasing- Flanged Fittings
ly important for companies that partici- B16.4, Gray Iron Threaded Fittings
pate in global markets. Following is a
B16.5, Pipe Flanges and Flanged
list of codes and standards that have
Fittings (for steel, nickel-based alloys,
been or will be important in the design
and other alloys)
and application of control valves.
B16.10, Face-to-Face and End-to-End
Dimensions of Valves (see ISA
American Petroleum Institute standards for dimensions for most
(API) control valves)
Spec 6D, Specification for Pipeline B16.24, Cast Copper Alloy Pipe
Valves (Gate, Plug, Ball, and Check Flanges and Flanged Fittings
Valves) B16.25, Buttwelding Ends
598, Valve Inspection and Testing B16.34, Valves - Flanged, Threaded,
and Welding End
607, Fire Test for Soft-Seated B16.42, Ductile Iron Pipe Flanges and
Quarter-Turn Valves Flanged Fittings
609, Lug- and Wafer-Type Butterfly B16.47, Large Diameter Steel Flanges
Valves (NPS 26 through NPS 60)
175
Chapter 9. Standards and Approvals

European Committee for European Material Standards


Standardization (CEN) EN 10213-1, Technical conditions of
delivery of steel castings for pressure
European Industrial Valve purposes - Part 1: General
Standards EN 10213-2, Technical conditions of
EN 19, Marking delivery of steel castings for pressure
purposes - Part 2: Steel grades for
EN 558-1, Face-to-Face and use at room temperature and elevated
Centre-to-Face Dimensions of Metal temperatures
Valves for Use in Flanged Pipe
Systems - Part 1: PN-Designated EN 10213-3, Technical conditions of
Valves delivery of steel castings for pressure
purposes - Part 3: Steel grades for
EN 558-2, Face-to-Face and use at low temperatures
Centre-to-Face Dimensions of Metal
Valves for Use in Flanged Pipe EN 10213-4, Technical conditions of
Systems - Part 2: Class-Designated delivery of steel castings for pressure
Valves purposes - Part 4: Austenitic and
austeno-ferritic steel grades
EN 593, Butterfly valves
EN 10222-2, Technical conditions of
EN 736-1, Terminology - Part 1: Defi- delivery of steel forgings for pressure
nition of types of valves purposes - Part 2: Ferritic and
EN 736-2, Terminology - Part 2: martensitic steels for use at elevated
Definition of components of valves temperatures

EN 736-3 Terminology - Part 3: EN 10222-3, Technical conditions of


Definition of terms (in preparation) delivery of steel forgings for pressure
purposes - Part 3: Nickel steel for low
EN 1349, Industrial Process Control temperature
Valves (in preparation)
EN 10222-4, Technical conditions of
EN 12266-1,Testing of valves - Part 1: delivery of steel forgings for pressure
Tests, test procedures and purposes - Part 4: Fine grain steel
acceptance criteria (in preparation)
EN 10222-5, Technical conditions of
EN 12516-1, Shell design strength - delivery of steel forgings for pressure
Part 1: Tabulation method for steel purposes - Part 5: Austenitic
valves (in preparation) martensitic and austeno-ferritic
stainless steel
EN 12516-2, Shell design strength -
Part 2: Calculation method for steel
valves (in preparation) European Flange Standards
EN 1092-1, Part 1: Steel flanges PN
EN 12516-3, Shell design strength -
designated
Part 3: Experimental method (in
preparation) EN 1092-2 (September 1997), Part 2:
EN 12627, Butt weld end design (in Cast iron flanges PN designated
preparation) EN 1759-1, Part 1: Steel flanges
EN 12760, Socket weld end design (in Class designated (in preparation)
preparation)
EN 12982, End to end dimensions for Fluid Controls Institute (FCI)
butt welding end valves (in 70-2-1991, Control Valve Seat
preparation) Leakage
176
Chapter 9. Standards and Approvals

Instrument Society of America S75.20, Face-to-Face Dimensions for


(ISA) Separable Flanged Globe-Style
Control Valves (Classes 150, 300,
S51.1, Process Instrumentation and 600)
Terminology
S75.22, Face-to-Centerline
S75.01, Flow Equations for Sizing Dimensions for Flanged Globe-Style
Control Valves Angle Control Valve Bodies (Classes
S75.02, Control Valve Capacity Test 150, 300, and 600)
Procedures RP75.23, Considerations for
S75.03, Face-to-Face Dimensions for Evaluating Control Valve Cavitation
Flanged Globe-Style Control Valve
Bodies (Classes 125, 150, 250, 300, International Electrotechnical
and 600) Commission (IEC)
S75.04, Face-to-Face Dimensions for The majority of International Electro-
Flangeless Control Valves (Classes technical Commission (IEC) standards
150, 300, and 600) for control valves, several of which are
based on ISA standards. have been
S75.05, Terminology re-published as EN standards and uti-
S75.07, Laboratory Measurement of lize an EN prefix. The IEC encourages
Aerodynamic Noise Generated by national committees to adopt them
Control Valves and to withdraw any corresponding
national standards. IEC standards are
S75.08, Installed Face-to-Face increasingly being applied by
Dimensions for Flanged Clamp or manufacturers and purchasers. Below
Pinch Valves is a list of IEC industrial-process con-
trol valve standards (60534 series).
S75.11, Inherent Flow Characteristic
and Rangeability of Control Valves 60534-1, Part 1: Control valve
terminology and general
S75.12, Face-to-Face Dimensions for considerations
Socket Weld-End and Screwed-End
Globe-Style Control Valves (Classes 60534-2-1, Part 2: Flow capacity -
150, 300, 600, 900, 1500, and 2500) Section One: Sizing equations for
incompressible fluid flow under
S75.13, Method of Evaluating the installed conditions (based on ISA
Performance of Positioners with S75.01)
Analog Input Signals
60534-2-3, Part 2: Flow capacity -
S75.14, Face-to-Face Dimensions for Section Three: Test procedures
Buttweld-End Globe-Style Control (based on ISA S75.02)
Valves (Class 4500)
60534-2-4, Part 2: Flow capacity -
S75.15, Face-to-Face Dimensions for Section Four: Inherent flow
Buttweld-End Globe-Style Control characteristics and rangeability
Valves (Classes 150, 300, 600, 900, (based on ISA S75.11)
1500, and 2500)
60534-4, Part 4: Inspection and
S75.16, Face-to-Face Dimensions for routine testing
Flanged Globe-Style Control Valve
Bodies (Classes 900, 1500, and 2500) 60534-5, Part 5: Marking

S75.17, Control Valve Aerodynamic 60534-6-1, Part 6: Mounting details


Noise Prediction for attachment of positioners to control
valve actuators - Section One:
S75.19, Hydrostatic Testing of Control Positioner mounting on linear
Valves actuators
177
Chapter 9. Standards and Approvals
60534-6-2, Part 6: Mounting details SP-25, Standard Marking System for
for attachment of positioners to control Valves, Fittings, Flanges and Unions
valve actuators - Section Two: SP-44, Steel Pipe Line Flanges
Positioner mounting on rotary
actuators SP-67, Butterfly Valves
SP-68, High Pressure Butterfly Valves
60534-7, Part 7: Control valve data with Offset Design
sheet
60534-8-1, Part 8: Noise NACE International
considerations - Section One: NACE MR0175/ISO 15156, Petroleum
Laboratory measurement of noise and Natural Gas Industries
generated by aerodynamic flow Materials for Use in H2S-Containing
through control valves (based on ISA Environments in Oil and Gas
S75.07) Production
NACE MR0175-2002, Sulfide Stress
60534-8-2, Part 8: Noise
Corrosion Cracking Resistant Metallic
considerations - Section Two:
Materials for Oil Field Equipment
Laboratory measurement of noise
generated by hydrodynamic flow NACE MR0103, Materials Resistant to
through control valves Sulfide Stress Cracking in Corrosive
Petroleum Refining Envoronments
60534-8-3, Part 8: Noise
considerations - Section Three: Product Approvals for
Control valve aerodynamic noise
prediction method (based on ISA Hazardous (Classified)
S75.17) Locations
60534-8-4, Part 8: Noise References
considerations - Section Four:
Prediction of noise generated by Canadian Standards Association
hydrodynamic flow (CSA) Standards
C22.1, Canadian Electrical Code
(CEC)
International Standards
Organization (ISO) C22.2 No. 94-M91, Special Industrial
Enclosures
5752, Metal valves for use in flanged
pipe systems - Face-to-face and European Committee for
centre-to-face dimensions Electrotechnical Standardization
(CENELEC) Standards
7005-1, Metallic flanges - Part 1: Steel
flanges EN 50014, Electrical apparatus for
potentially explosive
7005-2, Metallic flanges - Part 2: Cast atmospheresGeneral requirements
iron flanges
Instrument Society of America
7005-3, Metallic flanges - Part 3: (ISA) Standards
Copper alloy and composite flanges S12.1, Definitions and Information
Pertaining to Electrical Instruments in
Hazardous (Classified) Locations
Manufacturers Standardization
Society (MSS) International Electrotechnical
SP-6, Standard Finishes for Contact Commission (IEC) Standards
Faces of Pipe Flanges and 60079-4, Electrical apparatus for
Connecting-End Flanges of Valves explosive gas atmospheres. Part 4:
and Fittings Method of test for ignition temperature
178
Chapter 9. Standards and Approvals
60529, Degrees of protection provided ! Explosionproof: A type of
by enclosures (IP Code) protection that utilizes an enclosure
that is capable of withstanding an ex-
National Electrical Manufacturers plosion of a gas or vapor within it and
Association (NEMA) Standards of preventing the ignition of an explo-
sive gas or vapor that may surround it
250, Enclosures for Electrical and that operates at such an external
Equipment (1000 Volts Maximum) temperature that a surrounding explo-
sive gas or vapor will not be ignited
National Fire Protection thereby.
Association (NFPA) Standards
! Intrinsically Safe: A type of
70, National Electric Code (NEC) protection in which the electrical
497M, Classification of Gases, Vapors equipment under normal or abnormal
and Dusts for Electrical Equipment in conditions is incapable of releasing
Hazardous (Classified) Locations sufficient electrical or thermal energy
to cause ignition of a specific hazard-
ous atmospheric mixture in its most
North American Approvals easily ignitable concentration.

The National Electric Code (NEC) in ! NonIncendive: A type of


the United States and the Canadian protection in which the equipment is
Electric Code (CEC) require that elec- incapable, under normal conditions, of
trical equipment used in hazardous causing ignition of a specified flam-
locations carry the appropriate ap- mable gas or vapor-in-air mixture due
proval from a recognized approval to arcing or thermal effect.
agency.
Nomenclature
Approval Agencies Approval agencies within North Ameri-
The three main approval agencies in ca classify equipment to be used in
North America are Factory Mutual hazardous locations by specifying the
(FM) and Underwriters Laboratories location as being Class I or II; Division
(UL) in the United States and Cana- 1 or 2; Groups A, B, C, D, E, F, or G;
dian Standards Association (CSA) in and Temperature Code T1 through
Canada. T6. These designations are defined in
the NEC and CEC, as well as the fol-
lowing paragraphs. The approval con-
Types of Protection sists of the type of protection and the
The types of protection commonly class, division, groups, and tempera-
used for instruments in North America ture, e.g. Class I, Division 1, Groups
are: A, B, C, D, T6.

! Dust Ignitionproof: A type of Hazardous Location


protection that excludes ignitable
amounts of dust or amounts that
Classification
might affect performance or rating and Hazardous areas in North America
that, when installed and protected in are classified by class, division, and
accordance with the original design group.
intent, will not allow arcs, sparks or
heat otherwise generated or liberated Note
inside the enclosure to cause ignition
of exterior accumulations or atmo- The method of classify-
spheric suspensions of a specified ing locations as zones
dust. instead of divisions was
179
Chapter 9. Standards and Approvals
introduced into the 1996 ! Group A: Atmospheres con-
edition of the NEC as an taining acetylene.
alternate method, but it
is not yet in use. The ! Group B: Atmospheres con-
zone method is com- taining hydrogen, fuel and combus-
mon in Europe and tible process gases containing more
most other countries. than 30 percent hydrogen by volume,
or gases or vapors of equivalent haz-
Class: The Class defines the general ard such as butadiene, ethylene ox-
nature of the hazardous material in ide, propylene oxide, and acrolein.
the surrounding atmosphere.
! Group C: Atmospheres such as
! Class ILocations in which ethyl ether, ethylene, or gases or va-
flammable gases or vapors are, or pors of equivalent hazard.
may be, present in the air in quantities
sufficient to produce explosive or ignit- ! Group D: Atmospheres such as
able mixtures. acetone, ammonia, benzene, butane,
cyclopropane, ethanol, gasoline, hex-
! Class IILocations that are ane, methanol, methane, natural gas,
hazardous because of the presence of naphtha, propane, or gases or vapors
combustible dusts. of equivalent hazard.
! Class IIILocations in which ! Group E: Atmospheres contain-
easily ignitable fibers or flyings may ing combustible metal dusts, including
be present but not likely to be in sus- aluminum, magnesium, and their com-
pension in sufficient quantities to mercial alloy, or other combustible
product ignitable mixtures. dusts whose particle size, abrasive-
ness, and conductivity present similar
Division: The Division defines the hazards in the use of electrical equip-
probability of hazardous material be- ment.
ing present in an ignitable concentra-
tion in the surrounding atmosphere. ! Group F: Atmospheres contain-
See ISA S12.1 for more detailed defi- ing combustible carbonaceous dusts,
nitions. including carbon black, charcoal, coal,
or dusts that have been sensitized by
! Division 1: Locations in which other materials so that they present
the probability of the atmosphere be- an explosion hazard.
ing hazardous is high due to flam-
mable material being present continu- ! Group G: Atmospheres con-
ously, intermittently, or periodically. taining combustible dusts not included
in Group E or F, including flour, grain,
! Division 2: Locations that are wood, plastic, and chemicals.
presumed to be hazardous only in an
abnormal situation.
Temperature Code
Group: The Group defines the haz- A mixture of hazardous gases and air
ardous material in the surrounding at- may be ignited by coming into contact
mosphere. The specific hazardous with a hot surface. The conditions un-
materials within each group and their der which a hot surface will ignite a
automatic ignition temperatures can gas depend on surface area, tempera-
be found in Article 500 of the NEC ture, and the concentration of the gas.
and in NFPA 497M. Groups A, B, C
and D apply to Class I, and Groups E, The approval agencies test and estab-
F and G apply to Class II locations. lish maximum temperature ratings for
The following definitions are from the the different equipment submitted for
NEC. approval. Equipment that has been
180
Chapter 9. Standards and Approvals
tested receives a temperature code ment. The following is a list of the dif-
that indicates the maximum surface ferent temperature codes:
temperature attained by the equip-

Class 1 Division 1 Groups ABCD T4


Hazard Type Area Classification Gas or Dust Group Temperature Code

North American Temperature General Locations


Codes
! Type 3 (Dust-tight, Rain-tight,
TEMPER- MAXIMUM SURFACE or Ice-resistance, Outdoor enclo-
ATURE TEMPERATURE
sure): Intended for outdoor use pri-
CODE "C "F marily to provide a degree of protec-
T1 450 842 tion against rain, sleet, windblown
T2 300 572 dust, and damage from external ice
T2A 280 536 formation.
T2B 260 500
T2C 230 446 ! Type 3R (Rain-proof, Ice-re-
sistance, Outdoor enclosure): In-
T2D 215 419
tended for outdoor use primarily to
T3 200 392 provide a degree of protection against
T3A 180 356 rain, sleet, and damage from external
T3B 165 329 ice formation.
T3C 160 320
T4 135 275 ! Type 3S (Dust-tight,
T4A 120 248 Rain-tight, Ice-proof, Outdoor
T5 100 212
enclosure): Intended for outdoor use
primarily to provide a degree of
T6 85 185
protection against rain, sleet, wind-
blown dust, and to provide for opera-
tion of external mechanisms when ice
The NEC states that any equipment ladened.
that does not exceed a maximum sur-
face temperature of 100 "C (212 "F)
[based on 40 "C (104 "F) ambient ! Type 4 (Water-tight,
temperature] is not required to be Dust-tight, Ice-resistant, Indoor or
marked with the temperature code. outdoor enclosure): Intended for in-
Therefore, when a temperature code door or outdoor use primarily to pro-
is not specified on the approved appa- vide a degree of protection against
ratus, it is assumed to be T5. windblown dust and rain, splashing
water, hose-directed water, and dam-
age from external ice formation.

NEMA Enclosure Rating ! Type 4X (Water-tight,


Dust-tight, Corrosion resistant, In-
Enclosures may be tested to deter- door or outdoor enclosure): In-
mine their ability to prevent the in- tended for indoor or outdoor use pri-
gress of liquids and dusts. In the marily to provide a degree of
United States, equipment is tested to protection against corrosion, wind-
NEMA 250. Some of the more com- blown dust and rain, splashing water,
mon enclosure ratings defined in and hose-directed water, and damage
NEMA 250 are as follows. from external ice formation.
181
Chapter 9. Standards and Approvals
Hazardous (Classified) Locations nated with the prefix CSA ENC (for
Two of the four enclosure ratings for example, CSA ENC 4).
hazardous (classified) locations are
described as follows in NEMA 250: Intrinsically Safe Apparatus
Intrinsically safe apparatus must be
! Type 7 (Class I, Division 1,
installed with barriers that limit the
Group A, B, C or D, Indoor hazard-
electrical energy into the equipment.
ous location, Enclosure): For in-
Two methods determine acceptable
door use in locations classified as
combinations of intrinsically safe ap-
Class I, Division 1, Groups A, B, C or
paratus and connected associated ap-
D as defined in the NEC and shall be
paratus (for example, barriers) that
marked to show class, division, and
have not been investigated in such
group. Type 7 enclosures shall be ca-
combination: entity concept and sys-
pable of withstanding the pressures
tem parameter concept.
resulting from an internal explosion of
specified gases, and contain such an
explosion sufficient that an explosive Entity Concept
gas-air mixture existing in the atmo- The entity concept specifies four pa-
sphere surrounding the enclosure will rameters: voltage, current, capaci-
not be ignited. tance, and inductance. The length of
cable connecting intrinsically safe
! Type 9 (Class II, Division 1, equipment with associated equipment
Groups E, F or G, Indoor hazardous may be limited because of the energy
location, Enclosure): Intended for storing characteristics of cable. The
use in indoor locations classified as entity parameters are:
Class II, Division 1, Groups E, F and
G as defined in the NEC and shall be Vmax = maximum voltage that may
marked to show class, division, and safely be applied to the intrinsically
group. Type 9 enclosures shall be ca- safe apparatus.
pable of preventing the entrance of
Imax = maximum current which may
dust.
safely be applied to the terminals of
The above two NEMA ratings are the intrinsically safe apparatus
often misunderstood. For example, Ci = internal unprotected capacitance
the above definition of Type 7 is es- of the intrinsically safe apparatus that
sentially the same as that for explo- can appear at the terminals of the de-
sionproof. Therefore, when an ap- vice under fault conditions
proval agency approves equipment as
explosionproof and suitable for Class Li = internal unprotected inductance
I, Division 1, the equipment automati- of the intrinsically safe apparatus that
cally satisfies the Type 7 requirement; can appear at the terminals of the de-
however, the agency does not require vice under fault conditions
that the equipment be labeled Type 7.
Instead it is labeled as suitable for Barriers used with the intrinsically safe
Class I, Division 1. Similarly, Type 9 apparatus must meet the following
enclosures would be labeled as suit- conditions, which are noted on the
able for Class II, Division 1. loop schematic (control drawing).
Vmax must be greater than Voc or Vt
CSA Enclosure Ratings Imax must be greater than Isc or It
CSA enclosure ratings are defined in
CSA C22.2, No. 94. They are similar Ca must be less than (Ci + Ccable)
to the NEMA ratings and are desig- La must be less than (Li + Lcable)
nated as type numbers; for example,
Type 4. Previously they were desig- where:
182
Chapter 9. Standards and Approvals
Voc or Vt = maximum open circuit volt- Loop Schematic (Control
age, under fault conditions, of the as- Drawing)
sociated apparatus (barrier). For mul-
tiple associated apparatus, FM uses Article 504 of the NEC specifically re-
the maximum combination of voltage quires intrinsically safe and associat-
Vt in place of Voc. ed apparatus to have a control draw-
ing that details the allowed
interconnections between the intrinsi-
Isc or It = maximum short circuit cur-
cally safe and associated apparatus.
rent that can be delivered under fault
This drawing may also be referred to
conditions by the associated appara-
as a loop schematic. The drawing
tus. For multiple associated appara-
number is referenced on the appara-
tus, FM uses the combination of cur-
tus nameplate and is available to the
rent It in place of Isc
user. It must include the following in-
formation:
Ca = maximum capacitance that can
safely be connected to the associated ! Wiring diagram: The drawing
apparatus shall contain a diagram of the appara-
tus showing all intrinsically safe termi-
La = maximum inductance that can nal connections. For intrinsically safe
safely be connected to the associated apparatus, all associated apparatus
apparatus must be defined either by specific
equipment identification or by entity
Ccable = capacitance of connecting parameters.
cable
! Entity parameters: The entity
parameters (or system parameters in
Lcable = inductance of connecting case of CSA) shall be supplied in a
cable table showing allowable values for
each applicable Class and Group.
The entity parameters are listed on
the loop schematic (control drawing). ! Hazard location identification:
The entity concept is used by FM and A demarcation line shall be provided
UL and will be used by CSA if re- on the drawing to show the equipment
quested. in the hazardous location and the
non-hazardous location. The Class,
Division, and Group of the hazardous
CSA System Parameter Concept location should be identified.
The parametric concept is only used ! Equipment identification: The
by CSA. For an intrinsically safe appa- equipment shall be identified by mod-
ratus, the parameters are: el, part number, etc. to permit positive
identification.
! The maximum hazardous loca-
tion voltage that may be connected to ! Division 2: Division 2 installa-
the apparatus. tion requirements for FM approved
equipment shall be shown.
! The minimum resistance in
ohms of the barrier that may be con- Comparison of Protection
nected to the apparatus. Techniques

! CSA will also investigate specific Explosion-proof Technique:


barriers, which may be listed on the This technique is implemented by en-
loop schematic along with the para- closing all electrical circuits in hous-
metric rating. ings and conduits strong enough to
183
Chapter 9. Standards and Approvals
contain any explosion or fires that cuits and equipment to levels that are
may take place inside the apparatus. too low to ignite the most easily ignit-
able mixtures of a hazardous area.
Advantages of this Technique
Advantages of this Technique
! Users are familiar with this tech-
nique and understand its principles ! This technique offers lower cost.
and applications. No rigid metal conduit or armored
cable are required for field wiring of
! Sturdy housing designs provide the instrument.
protection to the internal components
of the apparatus and allow their ap- ! Greater flexibility is offered since
plication in hazardous environments. this technique permits simple compo-
nents such as switches, contact clo-
! An explosion-proof housing is sures, thermocouples, RTDs, and
usually weatherproof as well. other non-energy-storing instruments
to be used without certification but
Disadvantages of this Technique with appropriate barriers.
! Circuits must be de-energized or ! Ease of field maintenance and
location rendered nonhazardous be- repair are advantages. There is no
fore housing covers may be removed. need to remove power before adjust-
ments or calibration are performed on
! Opening of the housing in a haz- the field instrument. The system re-
ardous area voids all protection. mains safe even if the instrument is
damaged, because the energy level is
! Generally this technique re- too low to ignite most easily ignitable
quires use of heavy bolted or screwed mixtures. Diagnostic and calibration
enclosures. instruments must have the appropri-
ate approvals for hazardous areas.
Installation Requirements
Disadvantages of this Technique
! The user has responsibility for
following proper installation proce- ! This technique requires the use
dures. (Refer to local and national of intrinsically safe barriers to limit the
electrical codes.) current and voltage between the haz-
ardous and safe areas to avoid devel-
! Installation requirements are opment of sparks or hot spots in the
listed in Article 501 of the NEC or Ar- circuitry of the instrument under fault
ticle 18-106 of the CEC. conditions.
! All electrical wiring leading to the ! High energy consumption ap-
field instrument must be installed us- plications are not applicable to this
ing threaded rigid metal conduit, technique, because the energy is lim-
threaded steel intermediate metal ited at the source (or barrier). This
conduit, or Type MI cable. technique is limited to low-energy ap-
plications such as DC circuits,
! Conduit seals may be required electro-pneumatic converters, etc.
within 18 inches of the field instrument
to maintain the explosionproof rating Dust Ignition-proof Technique:
and reduce the pressure piling effect
on the housing. This technique results in an enclosure
that will exclude ignitable amounts of
dusts and will not permit arcs, sparks,
Intrinsically Safe Technique: or heat otherwise generated inside the
This technique operates by limiting enclosure to cause ignition of exterior
the electrical energy available in cir- accumulations or atmospheric sus-
184
Chapter 9. Standards and Approvals
pension of a specified dust on or near ods suitable for wiring in ordinary
the enclosure. locations.

Disadvantages of this Technique


Non-Incendive Technique:
! This technique is limited to Divi-
This technique allows for the incorpo- sion 2 applications only.
ration of circuits in electrical instru-
ments that are not capable of igniting ! This technique places constraint
specific flammable gases or on control room to limit energy to field
vapor-in-air mixtures under normal op- wiring (normal operation is open, short
erating conditions. or grounding of field wiring) so that
arcs or sparks under normal operation
Advantages of this Technique will not have enough energy to cause
ignition.
! This technique uses electronic
equipment that normally does not de- ! Both the field instrument and
velop high temperatures or produce control room device may require more
sparks strong enough to ignite the stringent labeling.
hazardous environment.

! There is lower cost than other European and Asia/Pacific


hazardous environment protection
techniques, because there is no need
Approvals
for explosionproof housings or ener-
gy limiting barriers. Approval Agencies
Some of the common approval agen-
! For nonincendive circuits, the cies in Europe and Asia/Pacific are
NEC permits any of the wiring meth- listed below:

Approval Agencies
Location Abbreviation Agency
British Approvals Service for Electrical Equipment in
United Kingdom BASEEFA
Flammable Atmospheres
Germany PTB Physikalische-Technische Bundesanstalt
France LCIE Laboratorie Central des Industries Electriques
Australia SAA Standards Association of Australia
Japan JTIISA Japanese Technical Institution of Industry Safety Association

CENELEC Approvals Types of Protection


The types of protection commonly
CENELEC is the acronym for Euro- used outside North America are:
pean Committee for Electrotechnical
Standardization. CENELEC standards
are applicable to all European Union Flameproof:
countries plus other countries that ! A type of protection in which an
choose to use them. A piece of equip- enclosure can withstand the pressure
ment that is successfully tested to the developed during an internal explo-
relevant CENELEC standard has CE- sion of an explosive mixture and that
NELEC approval. The testing may be prevents the transmission of the ex-
performed by any recognized testing plosion to the explosive atmosphere
laboratory in Europe. Approvals may surrounding the enclosure and that
be based on national standards, but operates at such an external tempera-
CENELEC approvals are preferred. ture that a surrounding explosive gas
185
Chapter 9. Standards and Approvals
or vapor will not be ignite there. This mal energy to cause ignition of a spe-
type of protection is similar to explo- cific hazardous atmospheric mixture in
sionproof. It is referred to by IEC as its most easily ignitable concentration.
Ex d. This type of protection is referred to
by IEC as Ex i.
Increased Safety:
Non-Incendive:
! A type of protection in which var-
ious measures are applied to reduce ! A type of protection in which the
the probability of excessive tempera- equipment is incapable, under normal
tures and the occurrence of arcs or conditions, of causing ignition of a
sparks in the interior and on the exter- specified flammable gas or
nal parts of electrical apparatus that vapor-in-air mixture due to arcing or
do not produce them in normal ser- thermal effect. This type of protection
vice. Increased safety may be used is referred to by IEC as Ex n.
with the flameproof type of protection.
This type of protection is referred to
by IEC as Ex e.
Nomenclature
Approval agencies that use the IEC
nomenclature (for example, BASE-
Intrinsically Safe:
EFA, LCIE, PTB, and SAA) classify
! A type of protection in which the equipment to be used in hazardous
electrical equipment under normal or locations by specifying the type of
abnormal conditions is incapable of protection, gas group, and tempera-
releasing sufficient electrical or ther- ture code as follows:
E Ex ia IIC T4
Types of Protection
Denotes Denotes Temperature
iaIntrinsic safety (2 faults Group
CENELEC Hazardous Code
allowed)
Approval Area
ibIntrinsic safety (1 fault
Approval
allowed)
dFlameproof
eIncreased safety
nType n (nonincendive)
(SAA only)
NType N (nonincendive)
(BASEEFA only)
For CENELEC approvals, the name- Hazardous Location
plate must also include the following Classification
symbol to indicate explosion protec-
tion: Hazardous locations outside North
America are classified by gas group
and zone.

Group
Electrical equipment is divided into
two groups. Group I covers electrical
equipment used in mines, and Group
II covers all other electrical equip-
This mark indicates compliance with ment. Group II is further subdivided
CENELEC requirements and is recog- into three subgroups: A, B, and C.
nized by all European Union member The specific hazardous materials with-
countries. in each group can be found in CENE-
186

Anda mungkin juga menyukai