Table of Contents
2
Page 5-6: Testing Carbon Pile Load Testers Amps (with adjustable
ammeter) using Independent Clamp-on Inductive Ammeter
Page 7-8: Testing Carbon Pile Load Testers Amps (with adjustable
ammeter) using ED-182 Accessory Clamp-on Inductive Ammeter
3
Charger (Series)
Charger (Parallel)
Battery Scales
4
Figure 1. Freas Hydrometer
Notes: Flush Calibrated Freas Hydrometer thoroughly with water several times
immediately after testing and prior to storage.
5
Figure 2. Variable Carbon Pile Calibration Adjustment
load Tester
6
4. Adjust Clamp-on Ammeter to select DC Amps.
5. Zero test clamp-on ammeter (if applicable)
6. Clamp ammeter loop around load testers positive or negative cable.
7. Adjust the load testers amp load as close to 200 amps as possible.
8. If load tester has not been previously used that day, conduct two repetitive load tests
(15 second discharges) @ 200 amps within one minute prior to calibration testing. If
load tester has been used, proceed directly to step 9
9. Apply and maintain 200 amps (3rd test) to battery. Once 200 amp load level has been
achieved, proceed to step 10
10. Compare and note clamp-on ammeter reading to the load amps being produced by
load tester. See Note
Note: If the digital clamp-on ammeter and load tester are both displaying approximately 200
amps or (190 amps- 210 amps), the load tester is within calibration. However; if the load
tester is illustrating 200 amps and the digital ammeter is displaying either low or high by
more than + or 10 amps (190amps to 210amps), adjust the small plastic adjustment
screw located on amps scale clockwise or counterclockwise to within calibration while
load test is in progress.
If the load tester cannot be properly adjusted to within above noted calibration, contact the
load testers manufacturer or Interstates Technical Services Dept. @ Home Office.
7
Testing Carbon Pile Load Tester (with adjustable ammeter)
using ED-18 V2 Accessory Clamp-on Inductive Ammeter
1. Use Good fully charged battery for testing (550 CCA or above)
2. Connect Load Tester to Negative and Positive battery terminals
3. Connect ED-182s primary leads to battery terminals. ED-182 should power up.
4. Plug in Accessory Clamp-on Ammeter into ED-182s accessory port.
5. On ED-182 main menu (8 Icons), select DMM and Press Enter
6. Select DC Amp/Volt Icon then Press Enter
7. Choose 700 amp level, Press Enter
8. Zero test clamp-on ammeter as prompted, press Enter
9. Clamp ED-182s ammeter loop around load testers positive or negative cable.
10. Adjust load testers current draw as close to 200 amps as possible.
8
11. If load tester has not been used previously that day, Conduct two repetitive load tests (15
second discharges @ 200 amps) within one minute prior to calibration test verification. If load
tester has been used within last 4 hours, proceed directly to step 12
Note: If the digital clamp-on ammeter and load tester are both displaying approximately 200
amps (190 amps- 210 amps), the load tester is within calibration. However; if the load
tester is on 200 amps and the digital ammeter is displaying either low or high by more
than + or 10 amps (190amps to 210amps), adjust the small plastic adjustment screw
located on amps scale clockwise or counterclockwise to within calibration while load test
is in progress.
If the load tester cannot be properly adjusted to within above noted calibration, contact the
load testers manufacturer or Interstates Technical Services dept. @ Home Office.
9
Testing Carbon-Pile Load Testers Voltmeter Accuracy
Monthly
Note: This test can be completed in conjunction with Load Tester Ammeter Verification Test
Calibration Adjustment
Figure 6. Carbon Pile Load Figure 7. TPI-190 (calibrated voltmeter)
Tester Voltmeter scale
Note: If the load testers voltmeter will not adjust to reflect the Calibrated voltmeters
voltage to + or - .1 volt, (1) send load tester to manufacturer for repairs or (2) use a
10
recalibrated Daily Use digital voltmeter in conjunction with load tester anytime load
testing batteries. See front cover illustration.
If the load tester cannot be properly adjusted to within above noted calibration, contact the
load testers manufacturer or Tech Services @ Interstates Home Office.
11
4. Connect Calibrated voltmeter to pos. and neg. battery terminals
5. Power up Daily Use voltmeter and select 20-volt scale (where applicable)
6. Connect Daily Use voltmeter to same battery terminals as Calibrated voltmeter.
7. Record any voltage difference in Daily Use voltmeter to Calibrated voltmeter.
8. Adjust Daily Use voltage calibration setting (if applicable) or apply removable sticker to
Daily Use voltmeter with voltage difference. See example below.
9. Number your warehouse Daily Use voltmeters and maintain records of voltage variation or
calibration required.
Note: If the working voltmeter has calibration accessibility, always follow voltmeter
manufacturers recommended calibration procedures. If the daily use voltmeter does not have
accessibility to calibrate, apply removable sticker to voltmeter with date and voltage variation.
Example: Calibrated Voltmeter displays 12.76 volts and Daily Use voltmeter displays 12.74
volts. Adjust (when applicable) or attach sticker to working voltmeter with + .02 volts. Add .02 to
every voltmeter test reading when using that Daily Use voltmeter.
#4
12
Testing Series charger to verify amp reading (analog ammeter
gauges only)
Annually
1. Connect Series charger to good batteries.
2. Turn on charger
3. Adjust charger to 5 amps or highest amp level available.
4. Connect clamp-on inductive ammeter (see figure 4 or 5) around one of the series charger
leads.
5. Power up amp clamp
6. Compare amp adjustment of charger to clamp-on digital ammeter reading.
7. Place removable sticker on charger noting amp difference. Example: If charger is displaying
5-amps and digital ammeter displays 4-amps, place sticker on charger faceplate indicating
charger is -1amp. If the charger is displaying 4 amps and digital displays 5 amps, place a + 1
amp sticker on charger. See Example below
13
Example of sticker with date and variance.
If chargers amp reading varies more than 1-amp, contact charger manufacturer or Interstate
Batteries Technical Services Dept. at Home Office.
Time: Annually
Note: Some parallel chargers will not allow any adjustment process.
14
Example of sticker with date and variance.
If chargers amp reading varies more than 1 amp, contact charger manufacturer or Interstate
Batteries Technical Services Dept. at Home Office.
Battery Scales
Annually
If you have any questions about the program, please call Gale Kimbrough @
15
Appendix
Batteries
16