Relion 605 series

Feeder/Motor protection and control/


Relion 605 series
Relion 605 series

Feeder/Motor protection
REF601/REJ601/REM601
Optimized solution for protection and
control of utility and industrial installation

REF601/REJ601 and REM601 are members of ABBs The relay provides an optimized composition of protection,
Relion protection and control product family and its 605 monitoring and control functionality in one unit, with the best
series. These relays provide an optimized composition performance usability in its class and is based on ABBs in-
of protection, monitoring and control functionality in one depth knowledge of protection and numerical technology.
unit, with the best performance usability in their class.
The relay offers pre-configured functionality which facilitates
The relay REF601/REJ601 offers various application easy and fast commissioning of switchgear.
configurations for feeder protection and control while To emphasize the simplicity of relays usage, only application
REM601 offers application configurations for motor specific parameters need to be set within the relays intended
protection and control. area of application.

2 Feeder/Motor protection
Feeder / Motor and and
protection control/Feeder/Motor
control // Feederprotection | REF601/REJ601/REM601
/ Motor protection | REF601 / REJ601 / REM601
Highlights of REF601/REJ601 and REM601 Selectable characteristics for non-directional overcurrent
and earth fault protection according to IEC61255-3 and
Simple to handle and ready to use ANSI C37.112 with special RI inverse characteristics for
Multiple language support better coordination throughout distribution network
Option for conventional current transformers or Rogowski The input/output signal configuration can be easily altered
sensor inputs by local HMI or the protection and control IED manager
Possibility to control one circuit breaker via remote com- PCM600
munication or via the IEDs local HMI (human-machine Built-in test functionality shortens testing and commission-
interface) ing time
Wide range auxiliary supply Press-fit design for effort-less installations on panels
Optional communication protocol: Modbus and Three dedicated and five configurable LEDs indicate the
IEC60870-5-103 with add-on communication card facility status of relay and protection functions
at site
Detachable terminals with feature of CT shorting which aid
in the trouble shooting and repair
Facility to derive earth fault current internally in relay or
externally through residual or CBCT connection

/ REM601 | Feeder /| Feeder/Motor


REF601/REJ601/REM601
REF601 / REJ601 protection
Motor protection and control/Feeder/Motor
and control protection 3
// Feeder / Motor protection
Feeder protection and control REF601/
Feeder protection REJ601

REF601/REJ601 is a dedicated feeder protection and REF601/REJ601 provides main protection for overhead lines
control relay intended for the protection and control and cable feeders of distribution and sub-distribution net-
of utility and industrial power system, in primary and works. Further, inrush current stabilization function allows the
secondary distribution networks. relay to be used as main protection of distribution transform-
ers.
The compact size of REF601 makes it suitable for even
mounting on ABB circuit breaker VD4 and HD4. The relay with application configuration B offers, non-direction-
al over current and earth-fault protection.
REF601/REJ601 is available in three alternative
application configurations. The application configuration C additionally offers thermal over-
load protection for feeders, cables and transformers, phase
discontinuity protection and circuit breaker failure protection.

The application configuration D provides highest functionality


with incorporation of negative phase sequence protection and
multi shot auto-reclose functionality making relay suitable for
overhead line feeders.

REF601/ FEEDER PROTECTION AND CONTROL / FEEDER PROTECTION


REJ601
PROTECTION LOCAL HMI ADDITIONAL FUNCTIONS

- Sequence of events
- Analog fault data
Master Trip I
- IED self-supervision
Lockout relay
- User management
R
L

94/86
- Two setting group

b)
3I> 3I>> 3I>>> 3Ith> R
L

51 50-1 50-2 49
3I

b) b) b)
I2> I2/I1> 3I>/Io>BF
SUPERVISION COMMUNICATION
46 46PD 51BF/51NBF
1 0 1 0 0 0 1 1
Protocols: 1 0 1 1 0 0 1 0
MODBUS RTU 1 1 0 0 1 1 1 0
3I2f> TCS IEC 60870-5-103 1 0 1 1 0 1 1 0
68 TCM 1 0 1 0 0 0 1 1
1 0 1 1 0 0 1 0
Interfaces:
Serial: RS-485, 2 wire
Io

CONTROL a) MEASUREMENT

Object Ctrl 2) - 3I - 3 Phase current


- Io - Neutral current
CB 1
- - Thermal level b)

Io 1)
Check availability of binary inputs/outputs
- Operation counter
from technical documentation - I2 - Negative phase sequence current c)
Io> Io>> 2)
Control and indication function for
51N 50N primary object
Analog interface types 1)

c) Current transformer 4
O I
79 1) Conventional transformer version:
Conventional transformer inputs - 4 Nos.
Sensor version:
Sensor inputs - 3 Nos.
Conventional transformer inputs - 1 No.

REMARKS
Calculated
value
Io

Functional overview of the application configuration of REF601/REJ601

4 Feeder/Motor protection
Feeder / Motor and and
protection control/Feeder/Motor
control // Feederprotection | REF601/REJ601/REM601
/ Motor protection | REF601 / REJ601 / REM601
Motor protection and control/Motor
protection REM601

REM601 is a dedicated motor protection and control relay REM601 provides protection to motor during starting and
intended for the protection and control of asynchronous running condition. The relay with application configuration
motors in manufacturing and process industry. The relay B offers, thermal overload protection, short-circuit protection,
can be used for three phase motors in all conventional startup supervision, negative phase sequence protection and
contactor or circuit breaker controlled motor drives. loss-of-phase protection. The relay also incorporates sensi-
tive earth fault protection, under current protection and circuit
REM601 is available in two alternative application breaker failure protection.
configurations.
The emergency restart feature helps to keep essential critical
motors running by allowing motor start up even though start
inhibit is activated.

The application configuration C additionally offers breaker


control functionality.

REM601 MOTOR PROTECTION AND CONTROL / MOTOR PROTECTION

PROTECTION LOCAL HMI ADDITIONAL FUNCTIONS

- Sequence of events
- Analog fault data
Master Trip I
- IED self-supervision
Lockout relay
- User management
R
L

94/86
- Two setting group
- Emergency restart
- Provision of speed switch input

3I> 3I>> I2>> R


L

49M 51 50-1 46R


3I

I2> I2/I1> Is t>, n<


SUPERVISION COMMUNICATION
46 46PD 14/48/66
1 0 1 0 0 0 1 1
Protocols: 1 0 1 1 0 0 1 0
MODBUS RTU 1 1 0 0 1 1 1 0
3I>>> 3I< 3I>/Io>B TCS IEC 60870-5-103 1 0 1 1 0 1 1 0
50LR 37 51BF/51NBF TCM 1 0 1 0 0 0 1 1
1 0 1 1 0 0 1 0
Interfaces:
Serial: RS-485, 2 wire
Io

CONTROL a) MEASUREMENT

Object Ctrl 2) - 3I - 3 Phase current


- Io - Neutral current
CB 1 - I2 - Negative phase sequence current
- - Thermal level
Io 1)
Check availability of binary inputs/outputs - Operation counter
from technical documentation - Motor running time
Io> Io>> 2)
Control and indication function for
51N 50N primary object
Analog interface types 1)

Current transformer 4
1) Conventional transformer version:
Conventional transformer inputs - 4 Nos.
Sensor version:
Sensor inputs - 3 Nos.
Conventional transformer inputs - 1 No.

REMARKS
Calculated
value
Io

Functional overview of the application configuration of REM601

/ REM601 | Feeder /| Feeder/Motor


REF601/REJ601/REM601
REF601 / REJ601 protection
Motor protection and control/Feeder/Motor
and control protection 5
// Feeder / Motor protection
REF601/REJ601 Application configuration
Description Application configuration
Non-directional overcurrentand
Non-directional overcurrent Non-directional
non-directionalovercurrent and non-directional earth-fault protection
earth-fault protection B
Non-directional overcurrent and non-directional earth-fault protection, thermal overload protection
for feeders, cable and transformers, phase-discontinuty protectiontion C
Non-directional overcurrent and non-directional earth-fault protection, thermal overload protection
for feeders, cable and transformers, phase-discontinuty protectiontion, negative phase-sequence D
protection, auto recloser

REM601 Application configuration


Description Application configuration
Motor protection without breaker control functionality B
Motor protection with breaker control functionality C

Supported functions, codes and symbols


Related products REJ601/ REJ601/ REF601 REM601 REM601
REF601 REF601
Functionality ANSI IEC B C D B C
Protection
Non-directional overcurrent protection, low-set stage 51 3I>
Non-directional overcurrent protection, high-set stage 50-1 3I>>
Non-directional overcurrent protection, instantaneous stage 50-2 3I>>> - -
Earth-fault protection, low-set stage 51N Io>
Earth-fault protection, high-set stage 50N Io>>
Three phase transformer inrush detector 68 3I2f> - -
Three phase thermal overload protection for feeders, cables
and distribution transformers 49 3Ith> - - -
Three phase thermal overload protection for motors 49 3Ith> - - -
Phase discountinuty protection 46PD I2/I1> - - -
Phase discountinuty / single phasing protection for motor 46PD I2/I1> - - -
Negative sequence overcurrent protection 46 I2> - -
Phase reversal protection 46R I2R> - - -
Under current protection 37 3I< - - -
Motor startup supervision, stalling protection with provision of 51LRS/
speed switch input, repetative start protection, restart inhibit 14/48/66 Ist n< - - -
Blocking / doubling during motor start up 68M - - -
Locked rotor protection 50-2 3I>>> - - -
Commulative startup time counter and restart inhibit function 66 - - -
Circuit breaker failure protection 51BF/ 3I>BF/
51NBF Io>BF -
Master trip 94/86 Master
Trip
Two setting group

Feeder / Motor
6 Feeder/Motor protection
protection and and control // Feederprotection
control/Feeder/Motor / Motor protection | REF601 / REJ601 / REM601
| REF601/REJ601/REM601
Supported functions, codes and symbols, continue
Related products REJ601/ REJ601/ REF601 REM601 REM601
REF601 REF601
Functionality ANSI IEC B C D B C
Control (function available in REF601)
Breaker control functionality I <-> O I <-> O
CB CB -
Auto reclosing, 4 shot
s 79 O -> I - - - -
Emergancy restart for motor ESTART ESTART - - -
Condition monitoring
Trip circuit supervision TCM TCS
Measurement
Three-phase current measurement 3I 3I
Residual current measurement In Io
Negative phase sequence current I2 I2 - -
Thermal level @ @ -
Operation counter - - -
Start-up time of latest motor startup - - - - -
Start-up current of latest motor startup - - - - -
Cumulative startup time counter - - - - -
Time to next possible motor startup - - - - -
Inputs / outputs
Analog inputs 4 / 3+1) 4 / 3+1) 4 / 3+1) 4 / 3+1) 4 / 3+1)
Binary inputs 4 4 4 4 4
Binary outputs 6 6 6 6 6
= Included

1) Conventional CT version - support for conventional current transformer input, sensor version - support for three current sensors and one conventional Io input (1A).

REF601 / REJ601 / REM601 | Feeder /| Feeder/Motor


REF601/REJ601/REM601 Motor protection and control
protection // Feeder / Motor protection
and control/Feeder/Motor protection 7
Contact us

Copyright 2014 ABB. All rights reserved.


information see
For more information, seeREF601/REJ601/REM601
REF601/REJ601/REM601 product guide or contact us:
Product Guide or contact us:

ABB India Limited,


Distribution Automation
Maneja Works
Vadodara 390013, India
Vadodara-390013, India
Phone: +91 265 2604386
Fax: +91 265 2638922

1MDS07202-YN Rev D September 2014


ABB Oy, Medium Voltage Products,
Distribution Automation
P.O. Box 699
FI-65101 Vaasa,
VAASA,Finland
Finland
Phone: +358 10 22 11
Fax: +358 10 22 41094

www.abb.com/mediumvoltage