Electrical power transformer is a static device which transforms electrical energy from one circuit
to another without any direct electrical connection and with the help of mutual induction between
two windings. It transforms power from one circuit to another without changing its frequency but
may be in different voltage level. This is a very short and simple definition of transformer, as
we will go through this portion of tutorial related to electrical power transformer, we will
understand more clearly and deeply "what is transformer ?" and basic theory of transformer.
The working principle of transformer is very simple. It depends upon Faraday's law of
electromagnetic induction. Actually, mutual induction between two or more winding is responsible
for transformation action in an electrical transformer.
According to these Faraday's laws, "Rate of change of flux linkage with respect to time is directly
proportional to the induced EMF in a conductor or coil".
Say you have one winding which is supplied by an alternating electrical source. The alternating
current through the winding produces a continually changing flux or alternating flux that surrounds
the winding. If any other winding is brought nearer to the previous one, obviously some portion of
this flux will link with the second. As this flux is continually changing in its amplitude and direction,
there must be a change in flux linkage in the second winding or coil. According to Faraday's law of
electromagnetic induction, there must be an EMF induced in the second. If the circuit of the later
winding is closed, there must be an current flowing through it. This is the simplest form of
electrical power transformer and this is the most basic of working principle of transformer. For
better understanding, we are trying to repeat the above explanation in a more brief way here.
Whenever we apply alternating current to an electric coil, there will be an alternating flux
surrounding that coil. Now if we bring another coil near the first one, there will be an alternating
flux linkage with that second coil. As the flux is alternating, there will be obviously a rate of change
in flux linkage with respect to time in the second coil. Naturally emf will be induced in it as per
Faraday's law of electromagnetic induction. This is the most basic concept of the theory of
transformer.
There are three limbs side by side in a core of transformer. One phase winding is wound in one
limb. The voltage induced in different phases depends upon the respective position of the limb in
the core. The voltage induced in different phases of transformer in respect to neutral terminals
given in the table below.
AN BN
Generally there are two similar higher readings on two outer limb phases on transformer core and
one lower reading on the centre limb phase, in case of three phase transformers. An agreement to
within 30% of the measured exciting current with the previous test is usually considered
satisfactory. If the measured exciting current value is 50 times higher than the value measured
during factory test, there is likelihood of a fault in the winding which needs further analysis.
Why the Transformers are tested at double the rated frequency which never happens practically?
DVDF (Double voltage and double frequency) test is popular test conducted on the
Transformer before it is commissioned. In this test double the rated voltage and double the rated
frequency is applied to the Transformer under test and observed for its withstand capability usually
for 1 min. Double voltage is applied to test the Transformer withstand capability for higher voltages
which are sometimes occur in the form of lightning surges and faults on the transformer. But,
practically, no transformer is subjected to double the rated frequency as the frequency variations
are not allowed beyond 0.5% by the power supply grid controlling authority. In such a case, is it
essential to test the transformer at 200% i.e. double the rated frequency conditions?
When alternating electrical source is applied to the primary winding of the transformer, it
draws magnetizing current which produces alternating flux in the core of the transformer. This flux
links both primary and secondary windings and due its alternating nature EMF is induced across
both windings and Erms can be deduced by the equation.
What is Vacuum Drying of Power Transformer? Why is it required and How it is done?
Here in this article we will address vacuum drying process/method , principle of vacuum dryer of
power transformers and how it is done.
Insulation materials are those materials that act as a barrier for electricity conduction. Insulation
materials or simply electrical insulation is of prime importance in area of utility of Electric
appliances, be it a home appliance operating on 110VAC/230VAC or an industrial equipment
operating on 380VAC/415VAC or electrical high voltage devices like the transformers, transmission
lines, circuit breakers and like.
As the power levels scale up, the internal insulation levels of devices, (say like insulation between
two phases, phase to ground insulation etc.) become more crucial and decisive factor for the life of
the device. Devices like transformers and motor-generators require a good insulation for robust
electrical performance.
Water is abundantly present in the atmosphere in form of water vapour. Insulation material like
paper, insulating oils, wood etc. have natural tendency to absorb water. Water is a good conductor
of electricity and if absorbed by the insulation of the device weakens the insulation.
When a device with a weak insulation is put in operation, the electric pressure (voltage) may break
the insulation barrier for the current resulting in heavy inrush of electric current which the device
may not be able to withstand and eventually break down. In case the device happens to be a part
of the system, this may result in failure of the system.
We thus need to ensure a proper insulation of the electrical devices to assure non-failure of the
devices.
How can we ascertain a good insulation? What are parameters that decide that the insulation is
Insulating materials say like a plastic handle of electric iron, rubber shoes of wire-man, insulating
oils in a transformer or say chemicals used in motor windings, all of them require three properties
to be defined as good insulators.
First property of the insulator is its resistance offered to the electrical current. The higher the
resistance better is the insulation. Second property, the dielectric strength or breakdown strength
of insulation, defines strength of the insulation to withstand electric pressure the stress that is
developed in the insulation. The third property, the dielectric constant, or the dielectric power
factor or also called tan delta, states the amount of electrical energy consumed by the insulator
itself in order to act as a barrier to the electrical potential.
By judging these three properties, one can evaluate the quality of insulation.
The parameters defined above which give evidence of good insulation are sharply affected by the
water content in the insulation material. Thus if are able to develop insulation that has least water
content we are able to achieve better insulation properties. Removal of water from the insulating
material is called the process of drying. Drying of insulation to some extent can be done by heating
the insulating material and vapourizing the water from the insulation. However, heating of
insulation material is limited activity as it may damage the physical and chemical properties of the
insulation material. In case of transformers, one cannot simply elevate temperature in order to
evaporate more and more water from the insulation. This damages the physical properties of the
transformer and also may be hazardous.
We have seen a generalized scenario of insulation and drying. In the discussion to follow we shall
now concentrate on drying of transformers.
How can we achieve drying without elevated heating of the insulation material for transformers?
Drying of insulation materials can be achieved at low temperature and low pressure levels. The
pressure levels and temperature levels for drying vary for distinct material. At low pressure or
under vacuum the rate of water vapour evaporation is accelerated if sufficient heat is provided to
the insulation material. Thus we can achieve a good drying of insulating material if the material is
suitably heated and subjected to vacuum.
What are the components/equipments used in vacuum drying process of power transformers?
Vacuum drying process requires a closed vacuum tight chamber, a heating system that can heat
the insulation in stipulated time, a vacuum system and a controlling mechanism. We shall discuss
these one by one below
Heating system:
Inside the oven, on the walls, tubes are provided wherein a hot fluid flows to transfer heat
to the object placed in the oven. This fluid is externally heated by electrical heaters or by
a gas/fuel fired boiler. A fan is provided in the oven to uniformly distribute the temperature
and accelerate the heating of the transformer insulation.
Vacuum System:
The vacuum system consists of vacuum pumps, condensers and booster pumps. The
vacuum pump and booster pumps evacuate the chamber and extract the moisture/gas (air)
from the chamber. Water cooled Condensers placed in series of the vacuum pumps aid in
condensing the water vapour extracted from the transformers insulation.
Controlling Mechanism:
With the advent of PLC and SCADA the whole process of drying can be monitored and
controlled to desired levels. Vacuum levels can be monitored and controlled. The
temperature level in the vacuum drying oven can be controlled. The time taken for drying,
amount of drying done and end of power transformer drying process can be determined
and monitored.
What is vacuum drying of transformers and how vacuum drying of transformers is done?
In the process of vacuum drying the insulation material of transformer, the transformer is placed in
vacuum drying oven. A vacuum drying oven consists of heating facility and a vacuum system to
develop low pressure in the oven/chamber. The transformer is first heated to a desired level. The
insulation material should be uniformly heated and its temperature should be elevated to
acceptable levels. After heating the material, it is subjected to vacuum. Vacuum in the oven is
developed by a vacuum system consisting of vacuum pumps. Due to low gas pressure in the
vicinity of the material, i.e. in the oven, the moisture absorbed by the insulation is released and
extracted by the vacuum system. The vacuum system consists of the water condensation system
where this water vapour can be condensed and also measured.
(b) property of the material to release water also called the diffusion coefficient,
(c) difference of pressure exerted by the water vapour on the insulation and surrounding area (i.e.
inside of the oven) and
Instrument Transformers
Next
Instrument Transformers are used in AC system for measurement of electrical quantities i.e.
voltage, current, power, energy, power factor, frequency. Instrument transformers are also
used with protective relays for protection of power system. Basic function of Instrument
transformers is to step down the AC System voltage and current. The voltage and current level of
power system is very high. It is very difficult and costly to design the measuring instruments for
measurement of such high level voltage and current. Generally measuring instruments are
designed for 5 A and 110 V.
The measurement of such very large electrical quantities, can be made possible by using the
Instrument transformers with these small rating measuring instruments. Therefore these
instrument transformers are very popular in modern power system.
1. The large voltage and current of AC Power system can be measured by using small rating
measuring instrument i.e. 5 A, 110 120 V.
2. By using the instrument transformers, measuring instruments can be standardized. Which
results in reduction of cost of measuring instruments. More ever the damaged measuring
instruments can be replaced easy with healthy standardized measuring instruments.
3. Instrument transformers provide electrical isolation between high voltage power circuit and
measuring instruments. Which reduces the electrical insulation requirement for measuring
instruments and protective circuits and also assures the safety of operators.
4. Several measuring instruments can be connected through a single transformer to power
system.
5. Due to low voltage and current level in measuring and protective circuit, there is low power
consumption in measuring and protective circuits.
Current transformer is used to step down the current of power system to a lower level to make it
feasible to be measured by small rating Ammeter (i.e. 5A ammeter). A typical connection diagram
of a current transformer is shown in figure below.
Primary
of C.T. is having very few turns. Sometimes bar primary is also used. Primary is connected in
series with the power circuit. Therefore, sometimes it also called series transformer. The
secondary is having large no. of turns. Secondary is connected directly to an ammeter. As the
ammeter is having very small resistance. Hence, the secondary of current transformer operates
almost in short circuited condition. One terminal of secondary is earthed to avoid the large voltage
on secondary with respect to earth. Which in turns reduce the chances of insulation breakdown
and also protect the operator against high voltage. More ever before disconnecting the ammeter,
secondary is short circuited through a switch S as shown in figure above to avoid the high voltage
build up across the secondary.
Potential transformer is used to step down the voltage of power system to a lower level to make is
feasible to be measured by small rating voltmeter i.e. 110 120 V voltmeter. A typical connection
diagram of a potential transformer is showing figure below.
Primary
of P.T. is having large no. of turns. Primary is connected across the line (generally between on line
and earth). Hence, sometimes it is also called the parallel transformer. Secondary of P.T. is
having few turns and connected directly to a voltmeter. As the voltmeter is having large resistance.
Hence the secondary of a P.T. operates almost in open circuited condition. One terminal of
secondary of P.T. is earthed to maintain the secondary voltage with respect to earth. Which
assures the safety of operators.
Current Transformer
Sl. No. Potential Transformer (P.T.)
(C.T.)
Secondary is connected to
2 Secondary is connected to Voltmeter.
Ammeter.
A lightning arrester protects telecommunication and electrical power systems from damage
during a lightning strike. It accomplishes this by redirecting the current in the lightning to the
ground.
Lightning is caused by the movement of a large current from a region of high voltage to a
region of low voltage. Lightning finds the path of least resistance to reach the ground.
Telecommunications towers and electrical grids provide a path for lightning to travel, but the
high voltage of the lightning can damage the components of the system. Adding a lightning
arrester to the system redirects the charges in the lightning to the ground. One terminal of
the arrester is connected to the device and the other terminal is connected to a rod or wire of
low resistance that is buried in the ground. Between the two terminals is a gap of either air or
a material of high resistance. This material prevents the normal signals from the
telecommunication device from being redirected to the ground. Since lightning strikes have a
high voltage, only the electrons from the lightning can cross the region of high resistance,
thus diverting the strike away from sensitive devices such as televisions, radios and other
telecommunications technology.
The transformer oil (insulation oil) of voltage- and current-transformers fulfils the purpose of
insulating as well as cooling. Thus, the dielectric quality of transformer oil is essential to secure
operation of a transformer.
As transformer oil deteriorates through aging and moisture ingress, transformer oil should,
depending on economics, transformer duty and other factors, be tested periodically. Power utility
companies have a vested interest in periodic oil testing since transformers represent a large
proportion of their total assets. Through such testing, transformers' life can be substantially
increased, thus delaying new investment of replacement transformer assets.
Recently time-consuming testing procedures in test labs have been replaced by on-site oil
testing procedures. There are various manufacturers of portable oil testers. With low weight
devices in the range of 20 to 40 kg, tests up to 100 kV rms can be performed and reported on-
site automatically. Some of them are even battery-powered and come with accessories.
The transformer oil is filled in the vessel of the testing device. Two standard-compliant
test electrodes with a typical clearance of 2.5 mm are surrounded by the dielectric oil.
At a certain voltage level breakdown occurs in an electric arc, leading to a collapse of the
test voltage.
An instant after ignition of the arc, the test voltage is switched off automatically by the
testing device. Ultra fast switch off is highly desirable, as the carbonisation due to the electric
arc must be limited to keep the additional pollution as low as possible.
The transformer oil testing device measures and reports the root mean square value of
the breakdown voltage.
After the transformer oil test is completed, the insulation oil is stirred automatically and
the test sequence is performed repeatedly: typically 5 repetitions, depending on the
standard.
A utility can determine moisture content for steady-state conditions using a family of
curves that show moisture content in the paper as a function of relative oil saturation,
with temperature as a parameter.
The usual method for monitoring moisture has been to sample the oil at regular intervals
as part of a scheduled maintenance routine. However, this procedure is problematic;
since moisture content varies with the load, spot checks will rarely coincide with a worst-
case scenario in which maximum water content will be measured. For example, in tests
on a 10-MVA single-phase water-cooled transformer at a Hydro-Qubec generating
station, at full load, relative moisture saturation was measured with the Syprotec Aquaoil
33 monitoring device and found to be 83% at a temperature of 43C (109F). At no load,
the relative saturation was 30% at a temperature of 35C (95F). Although this
transformer can definitely be classified as wet, the measurements showing such large
variations make it difficult to establish a true value for the water content in the insulating
paper.
Moisture in Paper
The moisture in the paper wrapping of the windings is of interest, relative to the
potential breakdown of the insulation medium. A utility can determine moisture content
for steady-state conditions by using a family of curves that show moisture content in the
paper as a function of relative oil saturation, with temperature as a parameter. Under
steady-state conditions, so-called moisture partition curves determine the moisture in
the paper based on the amount of moisture measured in the oil. Because these relations
can be applied only when the transformer has been at a steady state for some time, the
utility must use an approximation to estimate the amount of water in the main
insulation.
Most of the water in the transformer is stored in the bulk insulation material, which
constitutes the dielectric insulation between the windings. Equilibrium conditions
between this insulation and the surrounding oil are difficult to achieve because of the
long thermal time constant in these thick cellulose components. Fortunately, the
insulation of greatest interest is the turn insulation within the windings, which is made
of thin materials and is well irrigated by the oil. This insulation is the component that
will be affected by thermal aging and is the site where gas may bubble under overload
conditions. Therefore, it is acceptable that calculations of moisture in the paper be
limited to the paper in the hottest part of the winding. Moreover, the utility should make
this calculation only when the transformer is hot, since errors in estimating the moisture
content at low temperatures are of little practical consequence.
Online Monitoring
The Faraday TMCS includes a moisture analysis model that continuously monitors the
water-condensation temperature, the moisture content of the insulation paper and the
bubbling inception temperatures. The model for the assessment of moisture content in
winding insulation paper is based on the analysis of historical data in connection with
the relative humidity in oil, the humidity sensor temperature, the top-oil temperature
and the load current. The model is executed in a predetermined sequence (Fig. 1), in
which the hot-spot temperature is computed from the oil temperature, load current and
transformer characteristics. If the hot-spot temperature lies below 80C (176F), no
further calculations are required, and the moisture content in the paper is assumed to be
unchanged from the last calculated value. If the hot spot is equal to or above 80C
(176F), the following parameters are averaged over the stability period:
These values provide the data to compute the relative humidity of the oil in contact with
the winding insulation at the hot-spot temperature. Oil/paper partition curves are then
applied to convert the relative humidity in oil to moisture content in solid insulation. In
addition, the calculated value of the moisture content in the insulation is used to update
a register where a default value is stored. This default value is used if the hot-spot
temperature and thermal stability do not lend themselves to the application of
equilibrium curves.
Conclusions
Using the GE Syprotec Aquaoil 300 relative humidity sensor, a utility can monitor the
water content in transformer oil online. It then can use the collected data to determine
the water-condensation temperature and relative humidity of the oil in contact with the
winding insulation, which is inferred from the relative saturation characteristics.
To assess the moisture content of the solid insulation, the utility needs to make some
compromises to deal with the difficult, dynamic pattern of moisture migration between
the paper and oil. It is reasonable to focus on the thin winding insulation paper and
disregard the bulk insulation that contains most of the water. Since the main concerns
with moisture in paper are accelerated aging and the risk of bubbling, whose detrimental
effects are to be feared only in the winding insulation at high temperatures, it is
sufficient to limit the accurate assessment of moisture content to the condition of high
hot-spot temperatures. Taking advantage of this simplification, the utility can apply
online monitoring to identify quasi-steady hot-spot temperatures that allow for the
assessment of moisture content in insulation paper at even the most critical operating
conditions.