Anda di halaman 1dari 48

Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

EP-MS-P4/S2-091

Specification for
Distribution Package
Substations (DPS)

Issue : 1 21-07-2010 unclassified Page 1 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Document Control
Department Document Type Document Title
EP-MS-P4/S2-091
Material
EP Specification Specification for Distribution
Package Substations (DPS)
Standards
Issue Approval
Prepared By Approved By

Consultant M/s. Ewbank Preece Limited Head of Design & Development


Member of the Mott Mac Donald Group,UK

Material Specification Engineer


Manager, EN Planning Dept.

Signature: Signature:

Issue Record
Issue No. Date Reason for re-issuing Document

0.0 30.04.2003 First issue of Materials Specification Standards

21.07.2010 Review of Materials Specification Standards


1.0
2.0
3.0
4.0
5.0

Key Words : Specification for Distribution Package Substations (DPS)

Review Frequency : Every 3 years

When this document is approved for publishing on the intranet, a copy of its Document Control page should be sent to
the QA section who is custodian of KM quality management system.

Issue : 1 21-07-2010 unclassified Page 2 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Main Sub
Description Page No
Clause Clause
1.0 SCOPE 5
2.0 APPLICABLE STANDARDS 5
3.0 ENVIRONMENTAL AND SYSTEM CONDITIONS 7
3.1 Environmental Conditions 7
3.2 System Conditions 8
4.0 GENERAL DESIGN FEATURES OF DPS 8
5.0 TRANSFORMER DETAILS 10
5.1 General Design Requirements 10
5.2 Rating & Characteristics 12
Transformer Operating Conditions & Temperature rise
5.3 12
limits
5.4 Fittings & Accessories 13
5.5 Corrosion protection & Paint Work 15
5.6 Transformer Tests 16
6.0 RING MAIN UNIT (NON-EXTENSIBLE) 17
6.1 General Design & Construction Features 17
6.2 Rating & Characteristics 21
6.3 Operational Features 22
6.4 Combined Rating & Data Plates 23
6.5 Cleaning & Painting 24
6.6 Tests 24
LOW VOLTAGE DISTRIBUTION BOARD
7.0 25
(FEEDER PILLAR)
7.1 General Design & Construction Features 25
Incomer Unit with Switch-Disconnector (for
7.2 27
transformer Control)
7.3 Outgoing Distributor Unit 27
7.4 Electrical Ratings & Characteristics 29
7.5 Cleaning & Painting 30
7.6 Accessories Fitted 30
7.7 Tests 32
8.0 THE HOUSING OF DPS 32
8.1 Construction 32
8.2 Corrosion Protection & Painting 34
8.3 Earth Fault Blinking device 34
8.4 Restricted Earth Fault (REF) Tripping Mechanism 35
8.5 Accessories to be supplied as spares (free of cost) 35
8.6 Test to be conducted on paint work of DPS 36
8.7 Tests on DPS 36
9.0 QUALITY STANDARDS 36
10.0 TESTING, INSPECTION & DELIVERY 37

Issue : 1 21-07-2010 unclassified Page 3 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

INFORMATION/DOCUMENTS TO BE SUBMITTED BY
11.0 38
BIDDERS/MANUFACTURER
12.0 LIST OF DEVIATION TO THE SPECIFICATION 39
13.0 WARRANTY 40
14.0 RESTRICTIONS ON OUT SOURCING 40
DRAWING STD-EQP-63 RATING PLATE & CONNECTION DIAGRAM 41
DRAWING STD-EQP-64 EARTHING TERMINAL & LIFTING LUGS 42

Issue : 1 21-07-2010 unclassified Page 4 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

1.0 SCOPE

This specification details about requirements for design, manufacture, testing, packing, transport and
supply of 11KV Distribution Package Substation Units (DPS) with housing intended for use on public
electricity 11KV/433V distribution network in the state of Qatar.

Distribution Package Substation Unit comprises of an Enclosure, Transformer, 11kV Ring main
unit(RMU) and LV Sub-station cable distribution board (SCDB) (also known as FEEDER PILLAR),
HV & LV inter-connections, auxiliary equipment and circuits, in a single transportable unit ready for
operation on being placed in position and jointed into the network.

The DPS shall be able to provide a minimum service life of 30 years under the specified environmental,
climatic, system and service conditions specified, with minimum maintenance requirements.

DPS are intended to install, outdoor, exposed to direct sunlight. However, each component or
compartment of DPS (i.e., transformer, HV & LV S/G units) shall also individually be capable of
withstanding these conditions in outdoor.

Different Power ratings of the DPS are: 315, 500, 1000, and 1600KVA.

KAHRAMAA preferred Physical size of enclosures of different ratings of DPS are mentioned IN below
table
DPS Rated Overall size of Enclosure Clearance between Clearance Clearance
Capacity Width (W), x Depth (D) x the equipment (FP - between left between Right
Height (H) RMU) side wall of wall* of DPS
DPS to FP to RMU
kVA mm mm mm mm
315 1800 x 1800 x 1800 500 100 200
500 3000 x 2300 x 2800 500 100 200
1000 3000 x 2300 x 2800 500 100 200
1600 3000 x 2300 x 2800 500 100 200
* The portion of wall of DPS at RMU side equivalent to RMU dimensions, shall be removable from
inner side bolts which never be accessed from outer side. This is to facilitate easy connection or testing
of cables on RMU. The RMU and Feeder Pillar should be at different horizontal level.

2.0 APPLICABLE STANDARDS


The specification refers to the current issues of IEC and BS Standards as listed below

Package Sub-station Units


IEC 62271-202 High-voltage/low voltage prefabricated substations
IEC 60404-8-7:2008 Specification for CRGO Electrical steel strips & sheets
Transformers
IEC 60076 Power Transformers
IEC 60296/BS 148 Insulating oil for transformers and switchgear.

IEC 60076-7 Loading Guide for Oil immersed power transformers


IEC 60076-10 Method of Measurement of Sound levels in Transformers
IEC 60404-8-7:2008 Specification for CRGO Electrical steel strips & sheets
IEC/TR 60616 Terminal and tapping markings for power transformers
BS 2562 Specification for Cable boxes for Transformers and reactors
IEC 60214-1 Off Load Tap changer

Ring Main Unit

Issue : 1 21-07-2010 unclassified Page 5 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

IEC 62271-1 High Voltage Switchgear & Control gear Common specifications
IEC 62271-100 High-voltage switchgear and control gear AC circuit-breakers
High Voltage AC metal-enclosed switchgear and control gear for rated voltages
IEC 62271-200
above 1 kV and less than 52 kV
AC disconnectors & earthing switches for voltages above 1 kV and up to and
IEC 62271-102
including 52 kV
IEC 60265-1 High-voltages switches for rated voltages above 1 kV and less than 52 kV
High-voltages AC switch-fuse combinations for rated voltages above 1 kV and
IEC 62271-105
less than 52 kV
BS 2562 Specification for Cable boxes for Transformers & Wiping glands
IEC 61243-5 Live working Voltage detective systems
ESI 12-6 TLF Fuse-links

LV Feeder Pillar
IEC 60439-1 & 5 Low voltage switchgear and control gear assemblies.
IEC 60947-1 & 3 Low voltage switchgear and control-gear
BS 88-5 Cartridge fuses for voltages up to and including 1000V AC and 1500V DC
BS 1363 Specification for 13A plugs, switched and un-switched socket outlet.
BS 1361 Specification for cartridge fuses for AC circuits in domestic and similar premises.
ENATS 37-2 Low voltage Distribution boards

Other Common Standards


IEC 60529 Degrees of Protection (IP code)
IEC 62262 Degrees of Protection (IK code)
ISO 3864 Graphical symbols, Safety labels, Safety colours & Safety signs
IEC 60044-1 Current Transformers
BS 6480:1997 Paper Insulated Cables
BS 6231 PVC insulated cables for switchgear and control gear wiring.
IEC 60502 XLPE Cables

Fasteners
ISO 272/4759-1 ISO Metric Precision Hexagonal Bolts, Screws and Nuts
BS 7371-1 to 12 Coatings on metal fasteners
ISO 272/885/888/ ISO Metric black hexagonal bolts, screws and nuts.
4759/1
Surface preparation, coating & painting work
BS 381C 1996 Specification for colours for identification, coding and special purposes.
Hot dip galvanized coating on ferrous materials Gravimetric determination of the
ISO 1460
mass per unit area
Hot dip galvanized coatings on fabricated Iron and steel Articles specification
BS EN ISO 1461
and test methods
ISO 2081 Electroplated coatings of zinc on iron or steel
Chemical conversion coatings Black oxide coating on iron and steel
ISO 11408
Specification and test methods
Sprayed Metal Coatings- Protection of Iron and Steel Against Corrosion and
BS2569-2
Oxidation at Elevated Temperatures
Issue : 1 21-07-2010 unclassified Page 6 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

General introduction to standards for preparation of steel substrates before


BS7079
application of paints and related products
ISO 12944-1 to 8 Corrosion Protection of Steel Structures by Protective Paint Systems
ISO 8501-part - 1 Preparation of steel substrates before application of paints and related products.
to 4
ISO 8502-part 1 to Preparation of steel substrates before application of paints and related products -
12 Tests for the assessment of surface cleanliness.
ISO 8503-part 1 to Preparation of Steel Substrates Before Application of Paints and Related Products
5 - Surface Roughness Characteristics of Blast-Cleaned Steel Substrates
Thermal spraying Metallic and other inorganic coatings Zinc, aluminium and their
ISO 2063
alloys
ISO 9227 Corrosion tests in artificial atmospheres Salt spray test
ISO 4628-1 to 5 Paints & varnishes Evaluation of degradation of paint coatings
Protection against Iron & Steel Structures Zinc and Aluminium Coating
ISO 14713
Guidelines.
ISO 1519 Paints & varnishes Bend Test
ISO 2808 Paints & Varnishes Determination of Film thickness
ISO 2409 Paints & Varnishes Cross cut test
ISO 1520 Paints & Varnishes Cupping test
ISO 6272 Paints & Varnishes Rapid deformation (Impact resistance) test
ISO 2812-1 to 2 Paints & Varnishes Determination of resistance to liquids
ISO 6270 Paints & Varnishes Determination of resistance to humidity
ISO 11997 Paints & Varnishes Determination of resistance to cyclic corrosion conditions
ISO 7784 Paints & Varnishes Determination of resistance to abrasion

3.0 ENVIRONMENTAL AND SYSTEM CONDITIONS

3.1 Environmental conditions


The following conditions prevail throughout in the State of Qatar:-
1. Altitude - low lying, generally close to sea level, no part exceeding 100m above sea level.
2. Maximum air temperature 50o C( 46oC).
3. Minimum air temperature 0oC ( 10oC typical)
4. Mean maximum summer air temperature, 45oC typical.
5. Mean maximum exposed sunlight temperature, 75oC
6. Solar radiation- peak, 1030 Watts/sq.m.
7. Humidity - 100% humidity is common throughout the year and may occur at air temperature of
30oC or more.
8. Rainfall - very low on average. The winter season may bring infrequent very heavy rainfall.
9. General atmospheric conditions: A hot atmosphere containing very fine, highly penetrating
dust particles. In parts the atmosphere contains a highly corrosive salt laden sea mist.
Prevailing winds generally from the north west, mostly light but occasionally gusting in excess
of 30 knots

Issue : 1 21-07-2010 unclassified Page 7 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

3.2 System conditions


The 11kV system has three phase and earth

a) Nominal Voltage ....................................................................11kV


b) Maximum Voltage ............................................................... 12kV
c) Maximum Symmetrical fault level ....................................... 25KA
d) Limited earth fault current through earthing transformer.....4.5KA
e) Impulse Voltage....................................................................75kV
f) Rated Frequency ..................................................................50 Hz

The LV System has 5 wires i.e. 3 Phase + Neutral + Earth. Neutral and earth is directly shorted at
the Distribution Substation end. A consumer earth terminal is provided.

g) Nominal Voltage.................................................................. 415/240V


h) Highest Symmetrical fault level............................................44kA
i) The highest fuse rating..........................................................400 A
j) Fault duration is limited by HRC fuses, Type J to BS 88.

4.0 GENERAL DESIGN FEATURES OF DPS


1. The Distribution Package Substation (DPS) units with housing are intended to be installed in
residential areas in which the general public has the access. As such the housing shall have high
level of personal safety and vandal proof design to protect from un-authorized access.

2. The DPS shall be operated from outside (non-walk-in type) at ground level (on concrete plinth),
and shall be suitable for mounting on concrete plinth.

3. Operator access shall be only from front side. Side access for operation is not acceptable. Sufficient
clearance shall be provided, for safe and easy access to transformer tap-changer, oil-level indicator
& temperature gauge, from the front in between FP & RMU. (Refer clause 1.0 physical sizes of
enclosure.)

4. Design and construction of the housing shall have good aesthetic & pleasant appearance and blend
with the surrounding buildings

5. DPS shall comprise a Transformer, non-extensible Ring Main Unit (RMU) and LV feeder pillar.
RMU and LV Feeder Pillar are directly mounted on to the transformer on same side. (i.e one side of
transformer tank). Their Electrical connections to transformer are made through bus-bars and
mounted through steel trunking pieces having standard flange faces. The connections can also be
made through suitably rated flexible cables with heat shrinkable terminations. (plug in type
terminations are not acceptable).

6. RMU and Feeder Pillar should be at different horizontal level.

7. HV inter-connecting bus-bars shall be fully insulated. The HV & LV trunking pieces shall be flange
connected to transformer body, and their IP protection shall be not be less than IP65.

8. All main components of DPS shall be mounted on structural steel base frame through bolted joints
(welded joints not acceptable) to form a rigid distortion-free structure. DPS shall have completely
bolted enclosure for easy assembly and retrofit.

9. DPS shall be single transportable unit, and able to be lifted or transported without dismantling any
of its components or enclosure.

10. Design & construction of DPS shall primarily need to conform to the requirements of IEC 62271-
202. It is acceptable that part of the enclosure of a component becomes part of substation enclosure.
Issue : 1 21-07-2010 unclassified Page 8 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

In such case, this part shall comply with the applicable requirements of both this standard (IEC
62271-202) and relevant product standard of the component.

11. DPS shall withstand climatic & environmental conditions prevailing in the State of Qatar.

12. Internal arc rating of the DPS shall be IAC-AB, 20KA @ 1 sec. Pressure relief system/vent(s) shall
be on the top of enclosure to allow safe passage of gases released in the event of internal arc inside
DPS unit

13. Cooling of DPS unit shall be through natural ventilation. Exhaust fans are not allowed.

14. IP protection Class of DPS enclosure shall be IP23D, with all its ventilation apertures closed with
vermin-proof, non-corrosive metallic screens having not more than 1 mm size apertures. Even the
cable entry ducts at the bottom shall be closed with the vermin-proof screens.

15. Temperature class of the enclosure (refer clause 8.2 of IEC 62271-202) shall be class-5. The
manufacturer needs to produce evidence about its compliance to the designated temperature class
by conducting heat-run test.

16. 100% utilization of rated capacity mentioned on the name plate of DPS shall be possible without
de-rating the transformer locally. Capacity of the transformer shall be pre-designed in co-relation
with the temperature class of enclosure, and its IP protection class, to ensure no de-rating of
transformer.

17. All type tests as prescribed in latest IEC standards shall be conducted, on representative sample of
essentially same design and ratings, at reputed independent laboratories.

18. Plinth matrix and size of 500KVA, 1000KVA & 1600KVA DPS units shall be same, implying that
position of bottom cable entry ducts, of all these three sizes shall be identical. However, 315KVA
DPS may have different plinth size & matrix.

19. Earthing: Main earthing conductor system shall be provided with an earth bar of not less than
40mm by 2.5mm hard drawn high conductivity copper strip. The earth bar shall be bolted to the
main frame so as to provide convenient facilities for earthing all metallic bodies. The earth bar
shall be connected directly to the transformer body, the LV feeder pillar body and the feeder pillar
earth bus-bar, the enclosure of HV switchgear, cable sheaths, and earthing connections of automatic
controls and remote control devices. A suitable connection point shall be provided for connection of
the substation to the earthing rod. Joints shall be brazed, welded or tinned and bolted to ensure that
adequate electrical continuity exists between all stationary metalwork.

20. All covers, doors and other accessible metallic parts of the enclosure shall be designed to carry at
least 30ADC current from them-selves and to the main earthing point of DPS, with a voltage drop
of maximum 3V. This is a safety requirement.

21. Earth fault blinking device on top of the DPS shall be provided. The specification for the same is
given hereunder at clause 8.3.

22. Restricted earth fault (REF) tripping mechanism shall be provided as per the details given
hereunder at clause 8.4.

23. Name Plate: Each DPS unit shall be provided with durable and clearly legible name plate, made
from metallic plate. It shall contain the following details:

a) Manufacturers name
b) Type/model designation
c) KVA rating of DPS
d) Internal arc classification
e) Serial number
f) Month & Year of Manufacture
g) KM tender & Purchase Order number
Issue : 1 21-07-2010 unclassified Page 9 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Note: In addition to this, all main components (Transformer, LV & HV switchgear units) shall be fitted with
individual Rating Plates, in such a manner that they shall be easily visible from front.
24. Details of main components (Transformer, HV & LV Switchgear) are explained in following
sections.

5.0 TRANSFORMER DETAILS.

5.1 General Design Requirements

1. The transformers shall be hermetically sealed, oil-immersed radiator panel or


corrugated type. Pressure excursions in case of radiator type are absorbed by inert gas
(preferably by nitrogen gas) cushion placed above the oil surface in a sealed-tank
system. In case of corrugated fins type, pressure excursions are to be absorbed by fins
movement. Tank shall be filled with oil without any gas /air.

2. Applicable standards: Shall comply with the requirements of IEC 60076, except where
otherwise covered by this specification. Oil shall comply with IEC 60294/Class-II of BS148.
Other applicable standards are shown in the preceding sections.

3. Winding: Winding shall be Oil immersed and made of high conductivity electrolytic copper.
Insulating material of high quality shall be used. 11KV and LV windings shall be separate.

4. Thermal Insulation: Thermal insulation requirements of the windings shall not be less than
insulation system temperature of 1050 C (Thermal class-A), IEC 60085

5. HV & LV bushings and Terminations: These shall be mounted on the same side of the tank
(i.e on one side of the transformer), so that access to the substation shall be only via one side
(i.e facilitating front access). Top mounting of bushings on tank cover is not acceptable. HV
& LV Terminations & bushings, and flanges shall comply with BS 2562

6. Rated power: Transformer power capacities shall be 315, 500, 1000 and 1600 kVA. Design
of these ratings shall be arrived after duly taking in to account the de-rating factors required
due to all influencing factors such as special service conditions, DPS Enclosure thermal class,
IP rating and specified temperature rise limits.

7. Magnetic Core: The magnetic core shall be made of high permeability, low loss, non-
aging, grain oriented, cold- rolled silicon steel laminations. Each lamination shall be
insulated with high quality coating without burrs.

i. High grade CRGO steel laminations, having specific watt loss of not more than
0.95 w/kg at 1.7T and 50Hz, shall be used. It shall conform to IEC 60404-8-7:2008.
Details of actual grade used, name of manufacturer, country of origin, product
catalogue need to be submitted along with tender offer, or technical submittal for
approval against external projects.
ii. All limbs and yokes shall be designed for keeping noise levels, no load losses, and
hot spot temperature in core as low as possible.
iii. Core and its clamping plates shall form in to rigid unit structure, to withstand all
stresses caused by S/C conditions, shipment, transportation, and installation.
iv. Ensure to secure uniformly distributed mechanical pressure over all laminations, to
limit noise & vibrations to minimum level.
v. Complete core assembly shall be provided with suitable lifting eyes to facilitate its
removal from the tank.
8. Parameters of Tank Designs:

Issue : 1 21-07-2010 unclassified Page 10 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

i. The under-base of transformers shall be in the form of skids. The skid shall be
provided with 42 mm diameter holes on axle at each end, clear of the jacking
position.

ii. All the bolts used in the transformers for mounting/fixing tank cover, Cable box
mounting flanges, bushings, radiators, etc, shall have consistency in its size &
length, and the fixing shall be such that, at least 2 or 3 threads of the bolt shall
come out of nut outer face.

iii. All the nuts & bolts used for fixing HV & LV bushing Clamps, shall be accessible
from outside the tank for easy opening or tightening. They should be accessible
without opening the top tank cover.

iv. All welds are required to be tested for oil tightness. Oil pressure test to be
conducted on each transformer, at least at a pressure of not less than 0.3bar for a
period of 16 hours to verify effectiveness of all welded joints and gaskets against
oil leaks. The test results are to be included in the routine test reports being
submitted.

v. The welding work need to be carried out through automated or robotic welding
process to ensure consistency in quality of welding

9. Tap changer:

i) The tap changer design & its performance shall generally conform to IEC
60214-1

ii) Tap changing shall be carried out with the transformer off circuit, by means of an
externally operated self-positioning tapping switch, which shall be mounted on one end
of the transformer tank. . The moving contacts shall be spring loaded, self-aligning roller
type. The tap changer selector switch shall be easily accessible to the operator from
convenient height from floor/ground.

iii) Switch position No. 1 shall correspond to the maximum plus tapping.
Provision shall be made for locking of the tapping switch handle at any
position, such means incorporating a hole for accommodating a padlock
having a 7mm diameter shackle. The switch shall be retained in a safe
position if a padlock with a 7mm diameter shackle is used.

iv) The tap-changer assembly shall be of a robust construction and shall be


capable of carrying the same current as the windings when under conditions
of short circuit. Current ratings of contacts used in tap changers shall not be
less than 63 amps for 1000KVA, 1250KVA & 1600KVA transformers, and
not less than 30 amps for 500KVA, 800KVA transformers.

v) Numerical digits need to be used as indication of the tap positions, shall be


embossed or engraved permanently on the knob.

vi) Tap changer shall be of high quality product; type tested according to the
requirements of IEC 60214-1, and shall be sourced from internationally
reputed manufacturers only.

10. Tank: Hermetically sealed type tank with bolted and gasketted top cover, and
so designed that there is no deformation of the unit when lifted with oil, and
with the ring main unit and feeder pillar attached. The thickness of the side
Issue : 1 21-07-2010 unclassified Page 11 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

walls shall not be less than 5mm, and the top and bottom not less than 4.5mm.
Radiators shall be of the panel type or corrugated fins type. In case of
corrugated fins, fins wall thickness shall be 1.5 0.1 mm. All welds are required
to be tested for oil tightness.

11. Gaskets: All Gaskets (both nitrile rubber and rubberized cork) shall be heat and
oil-resistant, and do not contain any joints. They shall be of one piece
construction only. Rubberized cork sheets shall be 5mm thick (un-compressed).
Nitrile rubber seals and o-rings shall be placed in suitable grooves, in order not
to slip from their positions, when tightened. Hemp material or neoprene gaskets
are not acceptable.

12. Terminal Markings: Terminals shall be identified by characters of a type,


which cannot be obliterated, marked on plates of durable and non-corrodible
metal securely fastened to the tank. High Voltage terminals shall be marked as
(left to right): A.B.C., and Low voltage terminals shall be marked as (left to
right): c,b,a,n.

13. Oil: Mineral oil shall meet the requirements of BS 148/IEC 60296.

5.2 Ratings & Characteristics

a) Rated Power : 315/500/1000/1600KVA (as explained above)


b) Type of Cooling : ONAN-Outdoor application (in side enclosure)
c) Voltage ratio : 11,000/433V
d) No. Of phases : 3-Phase
e) Connections : Delta-Star, as per vector group Dyn11
f) Rated frequency : 50HZ
g) Thermal Insulation of winding : Not less than Class-A (1050 C)
h) Maximum Flux density : 1.6 Tesla at normal voltage & frequency
i) Taping range & steps : +5% to -5%, in 4-steps each of 2.5%
j) Rated insulation levels:
Parameter Name HV Side LV Side
Rated Voltage (U) 11KV 433/250V(at no load)
Rated Highest Withstand Voltage (Um) 12KV 1.1KV
Rated Lightning impulse withstand (peak) 75KV -
Rated power frequency withstand voltage 28KV 3KV

k) Guaranteed values of load & no-load losses, and percentage impedance, measured at principal
tap and corrected to reference temperature of 750 C.

KVA Rating Max. No-Load Losses Max. Load-Losses % impedance


(watts) (watts)
315 565 6,700 4.0010%
500 900 7,200 4.7510%
1000 1350 10,600 5.4510%
1600 1875 15,300 6.0010%

5.3 Transformer Operating Conditions & Temperature rise limits

Issue : 1 21-07-2010 unclassified Page 12 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

a) Temperature class of the DPS enclosureclass-5


b) Average Ambient Temperature outside the DPS unit30C
c) Maximum ambient Temperature out side the DPS unit.500C
d) Maximum top oil temperature rise above Ambient for continuous rated load. 40K
e) Maximum average winding temp. rise, above Ambient for rated continuous load...45K
f) Maximum hot spot temperature for Continuous rated load...98C
g) Oil temperature shall not exceed 105C under any conditions.
h) Hot spot temperature shall not exceed 118C under any conditions.

Note: In the event, the DPS enclosure is designed for class-10 enclosure, top oil temperature rise and winding
temperature rise shall be 350 k and 400 k respectively.

5.4 Fittings & Accessories

The following fittings & Accessories are required:

a) Sealed filler boss: The design shall be such that water cannot collect in the
vicinity of the boss.

b) Lifting fittings: These shall be provided suitable for lifting the whole unit
without the housing, by crane and chains. Fittings shall be so located that DPS
can be fitted without tilting. Lifting fittings shall be fitted to the sides of the tank
not the top.

c) Jacking lugs: Four to be fitted, one of each corner of the tank at 400+5mm
above ground level.

d) Skids: Designed to support the unit and attached switchgear as necessary. Skids
shall have four 42mm diameter axle holes.

e) Drain Valve and Sampling Device


Transformer shall be equipped with drain and filler valves. The nominal size of
drain valve shall be 1 inch. Good quality, non-corrosive, gate valve type, hand
wheel operated valves to be used for this purpose. There shall be separate outlets
for oil draining and sampling on the same device. The sampling outlet shall be
smaller in size and at right angle direction to the main drain outlet. The valve
handles should have locking arrangement. This device shall facilitate filling,
draining, sampling, and venting of oil. The location of the drain valve cum
sampling device shall be so selected that it is easily accessible, and its operation
shall not be hindered by any other component installed on transformer.

f) Earthing terminal: A stainless steel earthing flag, approximately 60 sq. mm


surface area, and not less than 6mm thick as shown in Drawing STD-EQP-64. A
central hole, 14mm diameter shall be included. It shall be provided on front side
of operator access.

g) Prismatic oil gauge: This will provide indication of the oil levels over the full
range of normal temperature excursions. It will be calibrated to show the normal
oil level at 35C. Markings for the maximum and minimum oil levels should be

Issue : 1 21-07-2010 unclassified Page 13 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

clearly marked on the instrument. [Note: Instruments with colour code


indications are not acceptable.]

h) Oil temperature indicator with alarm contacts: A dial type thermometer to


indicate the temperature of the oil at the top of the tank needs to be provided.
Its scale shall be graduated in degrees Centigrade and cover the range of 20C
to 120C with increment marks at not more than 5C intervals and following
features.

i) The dial shall be fitted with pointers to indicate the present oil temperature,
and its maximum value. The maximum temperature pointer, alarm & trip
contacts shall be manually re-settable type from the front. Alarm contacts
(2NO+1NC or 2C/O) rated @ 10A, 240VAC, for maximum setting, shall be
incorporated.
ii) The IP protection of alarm contacts and cable entry gland shall be IP67.
iii) A permanent wiring, with suitably rated cable, to be made to the junction box
mounted on side walls of transformer tank, through rain tight conduit &
conduit fittings. Cable/conduit entry to the thermometer alarm contacts shall
be from bottom.
iv) The winding oil temperature alarm & trip values shall be pre-set at 95oC and
1050C respectively, by default.
v) The Standard thermometer size as described below shall be used.

Nominal dial size: Approx 100mm


Sensing element type Bimetallic, stem type
Bezel & Casing material: Stainless steel (SS-316)
Dial & Pointer: Black pointer on white dial
Maximum Pointer Red Pointer
Measuring Range: 20-140oC.
Connection type: Radial bottom
Stem size & material: 120mm(L)x12mm(D), stainless steel.
Process Connection: G inch male nut, stainless steel fitting.
Thermometer pocket(thermo-well): Welded to tank, W/matching
thread.
O-Ring suitable size of O ring shall be used.

i) Additional Thermometer Pocket


An additional thermometer pocket (thermo-well without thermometer) of same
size shall be fitted in the tank, for the purpose of routine testing & measuring
with portable instruments. The thermo-well opening shall be closed with
matching cap/plug.

j) Pressure relief valve: With a fixed pressure setting, assigned by the


manufacturer to permit pressure relief when the transformer is subject to
abnormal operating conditions, or an internal fault.
The device shall be equipped with two re-settable auxiliary switches (which may
have a common pole), one of which is normally open, the other normally closed.
Operation of the switches shall coincide with operation of the pressure relief
device.
Issue : 1 21-07-2010 unclassified Page 14 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

The pressure relief valve shall also be fitted with 2 re-settable auxiliary switches,
one normally open, the other normally closed. Operation of the switches shall
coincide with operation of the pressure relief valve. The limit switch containing
these auxiliary switches shall be totally concealed under the PRV outer cover, or
a separate shade/cover shall be provided over the limit-switch to protect it from
the external environment and rain. The limit switch body & gland/conduit fitting
shall be conforming to IP67 requirements.
A permanent wiring from the limit-switch contacts to be made, with suitably
rated cable, to the junction box mounted on side walls of transformer tank,
through rain tight conduit & conduit fittings. Cable/conduit entry to the limit-
switch shall be from the bottom.

The device shall also be fitted with a prominent indicator, which shall remain in
place after an operation of the device. The indicator shall be readily visible from
the front of the substation. Any cable entry holes meant for wiring auxiliary
switch unit shall be closed with temporary plugs.
k) Junction Box (for control wiring)
A suitable junction box (control box) made of sheet steel body with protective
covering and painting, shall be fixed on suitable side wall of tank. It shall be
fitted with suitably rated terminal strip, cable gland/conduit fittings, front hinged
door and gaskets, etc. The location of the junction box is such that it facilities
easy access to its connections. The box shall not hinder functions of any
transformer operations or other components. IP rating of the box shall not be
less than IP65.

Two inlet and two outlet electrical cable entries shall be provided to the box
through rain-tight conduit fittings. All cable/conduit entries shall be from bottom
only. Inlet connections shall be wired from thermometer alarm contacts, and
PRV limit switch through conduits. Outgoing terminal connections shall be left
free, to make connections during installation. The outgoing cable/conduit entry
holes shall be closed individually with suitable caps/plugs. A permanent label
showing terminal wiring diagram, terminal markings, functions of all terminal
connections, shall be fixed inside the front door of the junction box. The front
door shall have provision for fixing KM standard pad-lock having 7mm shackle.

l) Pressure Gauge with Isolating Valve (Applicable for Radiator type


Transformers)

A pressure gauge capable of measuring negative and positive pressures of


nitrogen gas inside the tank, over the atmospheric pressure, shall be fitted on the
inlet oil pipe line of each transformer. The pressure gauge shall be along with an
isolating valve as a combination, capable of isolating the gauge in normal
conditions, and measure gas pressure only when required. Suitable manifold, if
required, to be used at the Oil inlet valve, to accommodate this pressure gauge
+ isolating valve combination.

Suitable gaskets/seals/O-rings, shall be used at all joints of the fittings to ensure


no gas leaks during their service life. There should not be any joints or openings
in the gaskets used.

Issue : 1 21-07-2010 unclassified Page 15 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

The gauge nominal diameter shall not be less than 100mm. The bezel & casing of
the gauge, isolating valve, and their fittings shall be made of stainless steel
(SS316). The dial of the gauge shall have linier graduated scale; with centre zero
reading, covering required measuring ranges on both negative and positive
pressures.

An additional pressure gauge (Master gauge) is to be supplied, free of cost, as


an accessory, for every 100 transformers supplied.

m) Connection plate: A connection plate shall be provided which shall give full
details of tap positions and winding connections as per vector group diagram.
The sequence of terminals shall be as per enclosed drawings.

n) Rating Plate: The rating plate shall be made of metal and shall be durable in the
arduous climate encountered in Qatar. It shall be fitted to the front of the unit. It
shall contain the following information as per STD-EQP-63.

Manufacturers Name
Specification Number
KM Tender number
Manufacturers serial Number
Month & Year of Manufacture
Rated Power
Rated Frequency
Rated Voltage
Rated Currents
Connection Symbol
Impedance voltage at rated current at 75C
Type of cooling
Total mass of the unit with oil, with and without RMU & feeder pillar
Mass of insulating oil
Temperature rise
Insulation level

5.5 Corrosion protection & Paint Work


1) The definitive guideline document is BS EN ISO 12944 Parts #1 to 8, & BS EN ISO
14713.

2) The atmospheric corrosive category of local environmental conditional is considered


to be close to C5-M (as per ISO 12944-2), and it is imperative for the manufacturer
to provide a painting system suitable for this classification.

3) It is the responsibility of the manufacturer to select suitable paint system, in


accordance with above referred standards withstanding the specified local climatic &
environmental conditions, and to give a service life of at least 15+ years.

4) The selection of surface preparation processes, protective paint systems, execution


and supervision of paint work shall be made in accordance with the requirements
specified above.

Issue : 1 21-07-2010 unclassified Page 16 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

5) The exact Specification & procedure of surface preparation and painting system
followed by the manufacturer shall be submitted at time of tender. The manufacturer
shall clearly justify the selected paint system meeting above mentioned requirements
(Refer tables of BS EN ISO 12944 and BS EN ISO 14713)

6) The final coat on the exterior shall be Dark Admiralty Grey, Colour conforming
to 632 of BS 381C, or a near equivalent.

7) The manufacturer should possess required testing equipment in their laboratory to


test the paint work in accordance with BS EN ISO 12944-6. These test reports
should be submitted along with each consignment of delivery.

8) KM Engineers shall have the option of witnessing the tests on painting work, before
delivery of each consignment.

The manufacturer may offer an alternative, provided that it is of no less quality than the
above. The colour is mandatory.

5.6 Transformer Tests


Type Tests
1. Temperature rise test(IEC 60076-2)
2. Dielectric type tests (IEC 60076-3)

Special Tests
1. Dielectric special tests
2. Short circuit withstand test
3. Determination of sound levels
4. Measurement of insulation resistance to earth of windings
5. Measurement of dissipation factor (tan delta) of the insulation system
capacitance

Routine Tests on Transformer


1. Measurement of winding resistance
2. Measurement of voltage ratio and check of phase displacement.
3. Measurement of short-circuit impedance and load losses
4. Measurement of no-load loss and current
5. Separate source AC withstand voltage test
6. Short duration induced AC withstand voltage test.
7. Main tank Oil pressure test at 0.3 bar for 16 hrs on each transformer.
8. Oil Breakdown voltage test (BDV) and oil acidity test.

A. TESTS ON PAINTING WORK

1) Measurement of thickness of protective coating (ISO 2808)


2) Specular gloss factor at 60 deg (ISO 2813): 905%
3) Falling weight test (ISO 6272): 1kg/50cm
4) Cross cut test (ISO 2409): classification: 0
5) Cupping test (ISO 1520): 08mm

Issue : 1 21-07-2010 unclassified Page 17 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

6) Bending test Cylindrical mandrel test (ISO 1519): 3.0mm


7) Salt spray (fog) test (ISO 7253): 1000hrs

Tests on accessories
1. All type tests to be carried out on off load tap changer, as per IEC 60214-1

6.0 THE RING MAIN UNIT(NON-EXTENSIBLE)

6.1 General Design & Constructional Features

Scope
1. The RMU comprises two ring switches (for feeder control) and one circuit
breaker (for transformer control) as integral parts, all stored in a single common
SF6 tank. The arc interruption medium shall be SF6 or vacuum. The insulation
medium with in the tank shall be SF6. The vacuum bottles used should be from
Europe, North American or Japan.

Compliance standards & Function


2. RMU shall generally conform to the requirements of IEC 62271-200, IEC
62271-1, IEC 62271-100. RMU will control DPS on 11KV side

Housing, body, components & materials


3. The switchgear shall be fully insulated and enclosed, including incoming and
outgoing cable boxes. No exposure to live parts. Its housing shall be made of
galvanized steel with highly durable protective coating & painting. All bus-bars
shall be made of high purity electrolytic copper with electro-tin plating.

4. All materials used, as far as possible, shall be non-hygroscopic, non-flammable.


All insulating materials shall have highest resistance to tracking.

5. All gaskets shall be of superior quality having long life, and capable of
withstanding sever climatic and operating conditions.

6. Steel pockets shall be provided on the inner walls of each door for keeping
drawings and operating instructions.

Gas pressure system


7. Gas tightness of the SF6 chamber shall conform to sealed pressure system as
defined in clause 5-15-3 of IEC 62271-1. Expected operating life of sealed
pressure system shall not be less than 20 years, and the leakage rate shall not be
more than 0.1% per year. No filing of gas required during its life time.

8. Facility to monitor the SF6 gas pressure shall be made available through gauge.
The gauge shall be able to be replaced, when required, without interfering with
gas medium. The gauge dial shall have graduated scale for indicating actual
pressure, and colour coding to indicate operating and non-operating zones.
Gauge shall be fitted with alarm contacts, as an integral part, to facilitate remote
indication of low pressure.

Issue : 1 21-07-2010 unclassified Page 18 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

9. The SF6 gas container shall be designed with automatic pressure relief in case of
pressure build up due to internal arcing.

Mounting & Connections


10. The RMU shall be directly mounted to transformer through flange connections,
conforming to Flange-E of BS 2562 with suitable steel trunkings. Electrical
connections (of CB unit) are made through bus-bars, without cable connections.
However, RMU bottom frame work shall be bolted to the DPS base frame.

Operation & Switching requirements


11. The C/B is capable of making and/or breaking rated short circuit currents
specified. The ring switches are fault-making and load-breaking type. Each ring
switch and C/B shall have 3 operating positions: ON, OFF, and EARTH.

12. RMU CB is independent manually operated with the help of operating handle,
through spring assisted mechanism. Its closing operation sequence shall be
TRIP/OFF-RESET-ON. CB opening shall be possible through a) manual
TRIP button, b) SHUNT-TRIP coil, and c) C/C & E/F trip coils of protection
circuit.

13. RMU Ring switches shall be capable of operated both manually & electrically.
Manual operation is done with the help of operating handle, capable of
independent manual operated spring assisted mechanism. Electrical operation is
accomplished through linear motor actuators, operated from external power
source (supply voltage 24VDC), fitted to the ring-switches. Mounting of electric
motor actuators on ring switches shall not become hindrance to their manual
operation.

14. Two cam operated selector switches shall be fitted on front of each ring-switch
panel to select LOCAL-OFF-REMOTE, and OPEN-OFF-CLOSE of
electrical operation. These switches shall have pad-locking facility. Selector
switch for LOCAL-OFF-REMOTE shall have stay put action, selector switch
for OPEN-OFF-CLOSE shall have momentary action.

15. All operations shall be possible from front of the unit. Mimic and position
indicators (mechanical type) shall be provided for operator guidance. Required
interlocks need to be provided, with padlocking facilities, to prohibit unintended
operations

16. The switchgear unit shall be fitted with operations counter.

17. If the switching operation is not successful, its mechanism should not get stuck-
up in intermediate position. The mechanism should automatically come back to
OFF position. The mechanism should never get stopped in intermediate position.

Protection, and control


18. The RMU CB unit shall be equipped with O/C and E/F protection unit (for
transformer protection), using CT operated (self energising type) trip coils with
provision for using TLF fuse links. The protection circuit shall include 3-trip
coils and one additional trip coil for REF (if required) out of which one shall be
Issue : 1 21-07-2010 unclassified Page 19 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

dedicated to earth-fault protection. The trip coil for REF shall be connected to
terminals in the control compartment. The protection system shall provide
correct discrimination with BS: 88 J-type fuses used on LV side.

19. The CT ratio for the protection circuit shall be 100/50/5A (dual ratio)

20. The unit shall be provided, on front of the panel, with TLF fuse link
port/compartment for easy replacement of fuses, and a CT ratio adjustable
port/compartment with shorting links for easy adjustment of CT ratio
depending up on the transformer capacity

21. The C/B shall be equipped with 30VDC/240VAC (dual rating) shunt trip coil.
There shall be a provision to connect alarm contacts of transformers temperature
indicator, auxiliary contacts of transformer PRV in the shunt trip circuit, through
inter-trip facility.

22. A chart showing details of TLF fuse-link ratings, corresponding to each CT ratio
verses different KVA ratings of transformer, shall be fixed on front of the panel.

23. A Circuit diagram for control shall be fixed permanently on the non removable
part of the control compartment.

Integral Cable Testing Facilities.


24. All test access shall be possible from front. Each ring switch, as well as
transformer control unit (CB) shall be provided with integral facilities, which
enable the testing of connected apparatus.
25. It should be possible to make testing of the cable without disconnection. The
bushings shall be built in and no portable equipment shall be required.

The testing facilities shall be insulated to withstand 50kV D.C. between phases
with the mid-point earthed and 32.5 kV D.C. to earth for 1 minute and shall be
capable of carrying 200A continuously.

The contact resistance measured from the terminals for connection of the main
outgoing cables shall not be greater than 500 microhm.

26. Test access covers shall be provided with padlocking facilities. Screws or nuts
used for securing such covers shall be captive and have hexagonal faces for
tightening only with a spanner. They shall not be slotted. Test access covers shall
be fitted with seals to prevent ingress of water and dust

Capacitive Voltage Detectors, Neon lamp indicators & Phase comparators


27. Each ring switch shall be equipped with Capacitive Voltage detective system
with capacitor coupling electrodes conforming to IEC 61243-5, neon indicators
(glow discharge lamps) for LIVE phase indication, and standard sockets for 11
kV phase comparison between ring switches. The glow discharge lamps are to be
located on the front of the panel.
28. The test jacks (probes) of portable Phase comparator instrument shall match with
test sockets mentioned above.
29. One portable Phase comparator set complete with all accessories and carrying
case, are required to be supplied with every 10 numbers of DPS units.
Issue : 1 21-07-2010 unclassified Page 20 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Earth-Fault Indicator
30. One-through-earth fault indicator with core-balance type CT, shall be installed
on left-hand side ring-switch of each RMU. Its flag shall be mechanical type. The
unit shall function without integral battery power. Both auto & manual resetting
options shall be available for the unit. Provision for auto resetting through
240Vac auxiliary supply (external source) shall also be made available.

31. Earth-Fault Indicator (EFI) unit shall be complete with all accessories including
relay unit, ZCT, connecting cables, full technical information concerning its
functioning, method of connections with CT location, instruction manual, etc.

32. The EFI unit shall be automation compatible, and have provision for remote
indication, and remote resetting facility.

33. EFI relay unit shall have IP65 rated housing, and capable of withstanding the
prevailing ambient conditions.

Cable boxes
34. All cable entries shall be from bottom, and the cable boxes are to be fitted with
un-insulated brass wiping gland of suitable size. All Cable terminals shall be
positioned not less than 800mm above ground level. A clearance of not less than
650mm shall be provided between bottom gland support plate and cable
bushings.

35. Cable boxes of ring switches shall be suitable for terminating cables up to
3Cx300sq.mm copper conductor, XLPE insulated, SWA cables conforming to
IEC 60502.

36. All cable boxes shall be fitted with insulated brass wiping glands with armour
clamp, conforming to size-Y, as per BS: 2562 figure 32. Each cable gland shall
be fitted with full fault rated copper earthing braid and connected to equipment
earth.

37. The cable termination shall be so arranged that any externally mounted CT, for
earth-fault indication purpose, shall have sufficient clearance for easy connection.

38. Suitably rated and type tested insulated bushings with required creepage
distances and anti-tracking properties shall be mounted for cable connection with
adequate clearances. The connecting terminals on bushings shall be integral male
stud type with nuts, and suitable for installing heat-shrink type terminations with
right angled boots.

39. Cable boxes will be designed to permit ventilation, but such openings shall have
protection to not less than IP54. Provision shall also be made to prevent a build
up of water within the box such as may arise from heat cycling and condensation.

40. Phasing of all primary terminals shall be positively marked on the main structure
and not on removable covers. The phasing shall be marked by characters of a
type which cannot easily be obliterated
Issue : 1 21-07-2010 unclassified Page 21 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Remote monitoring & Control


41. Each ring switch and CB unit need to be suitably wired to handle
outgoing/incoming signals of position indications, alarms, commands, and
24VDC auxiliary power lines from future RTUs. They shall include but not
limited to below mentioned details.

Type of Control Control Detail From To


ON, OFF,
Status Indications Ring switches RTU
EARTH
Status Indications ON, OFF Earth Switch RTU
Status Indications MAIN ON, OFF Circuit Breaker RTU
Alarm SHUNT TRIP Circuit Breaker RTU
Alarm O/C & E/F TRIP Circuit Breaker RTU
Status Indications ON C/B Earth Position Selected RTU
Alarm LOW GAS SF6 gauges RTU
Status Indications FAULT/RESET Earth fault relays RTU
Command CLOSE/OPEN RTU Motor Actuator
Alarm Trip REF RTU

42. A dedicated terminal box prewired with all outputs from auxiliary switches, limit
switches other sensors (if any), all meant for remote monitoring & control of the
unit, shall be mounted on the switchgear unit. All terminals shall be clearly
marked with proper identifications. A wiring diagram indelibly printed with all
details of incoming/outgoing terminals, on water-proof medium, shall be
permanently fixed inside the box cover.

Pad Locking facilities


43. All covers, doors, operating mechanisms/handles, mechanical interlocks, selector
switches, shall have facilities, as specified, for pad-locking.

44. Wherever padlocking facilities are specified, it shall be possible to fit a padlock
having the following description:

Pad lock: Body Height = 33.5 + 1mm


Body Width = 34 + 1mm
Body Thickness = 15.5 + 1mm
Shackle Diameter = 5mm
The receiving hole for the padlock shackle = 8mm in diameter
For operational locks: When closed the shackle should accommodate a
bar of up to 19mm diameter.
For Safety locks: When closed should have a minimum clearance
dimension to accommodate an elliptical bar having a major axis of 30mm
and a minor axis of 19mm.

Circuit Labels
Issue : 1 21-07-2010 unclassified Page 22 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

45. Each switch shall be provided with a circuit label size 150mm x 50mm secured to
the front of the equipment by four non-rusting screws. In addition each cable box
shall have affixed in close proximity to it a label for the purpose of circuit
identification. These labels shall be easily removable for engraving. Circuit labels
shall not be positioned on movable covers and must be close to the control point
to which they refer. All circuit labels shall be inscribed with black letters on a
white background; they shall be suitable for outdoor use and must have non-
fading properties.

6.2 Ratings & Characteristics

1. IP & IK Protection:
IP protection of Enclosure, Cable boxes, remote control box shall be at-least
IP54
IK protection of Enclosure, Cable boxes, remote control box shall be at-least
IK08 (5J)

2. Internal arc Protection


RMU shall be so designed and tested that an internal arc inside the tank shall not
result in risk of injury to an operator. The protection against internal arc shall at
least conform to the classification IAC-AF, 20KA for 1 sec. as per IEC 62271-
200. Type test report issued from reputed independent laboratory need to be
submitted.

3. Electrical Ratings - General:

Frequency.............................................................................. 50 Hz
No. of Phases......................................................................... 3
Nominal Voltage.....................................................................11kV
Maximum Voltage..................................................................12kV
Rated Voltage........................................................................ 12kV
Rated Impulse withstand voltage Level................................75kV (1.2/50)
Rated short duration power frequency withstand voltage...... 28kA

4. Electrical Ratings - Ring Switches


Rated normal current of Bus-bar.............................................630ARated short-
time withstand current of bus-bars....................................... 20kA, 3 seconds
Rated peak withstand current of bus-bars...............................50kA
Rated nominal current (switch to feeder)................................630A
Rated breaking capacity, feeder switch...................................630A
Rated short-time withstand current, feeder switch.................20kA, 3 seconds
Rated peak withstand current, feeder switch..........................50kA
Rated short circuit making current, feeder switch...................50kA (Peak)

Circuit Breakers
Rated normal current, Bus-bar................................................630A
Rated short-time withstand current of bus-bars....20kA, 3 sec
Rated nominal current, CB......................................................200A
Rated breaking capacity, CB...................................................20kA
Issue : 1 21-07-2010 unclassified Page 23 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Rated short-time withstand current, CB.................................20kA, 3 seconds


Rated peak withstand current, CB..........................................50kA
Rated short circuit making current, CB...................................50kA (peak)

Earth switches
Rated short time withstand current, earth switch....................20kA 3 seconds
Rated peak withstand current, earth switch............................50kA
Rated short circuit making capacity, earth switch...................50kA (peak)

6.3 Operational Features

1. Operations

Ring switches shall incorporate a switch or switches which enable the outgoing
feeder to be: ON - connected to the bus-bars : OFF - isolated in the tank: or
EARTHED - connected to the earthing system of the switchgear.

The circuit breaker shall incorporate a manually operated switch between the
bus-bars and the circuit breaker. This switch shall be capable of being operated
between the ON position (bus-bar connected to circuit breaker), or the EARTH
position (transformer HV winding connected to earth). It shall not be possible to
operate this isolator switch unless the circuit breaker is in the OFF position.

All the switches shall be of the independent manual type i.e. a stored energy
operation where the energy originates from manual power, is stored and released
in one continuous operation, such that the speed and force of the operation are
independent of the action of the operator. It shall not be possible for the
operating mechanism(s) to be left in such a condition that any energy stored in
the initial part of the operation remains in the spring when the switch is in the
'ON', 'OFF', and 'EARTH ON' positions. In addition movement of an operating
handle against an interlock shall not charge any spring to any significant extent.

Lockable storage facilities shall be provided for removable operating handles in a


position readily accessible from the front of the equipment.

It shall be possible to lock the operating mechanism(s) in any operating position


and independently to lock off the 'ON', 'OFF', and 'EARTH ON' positions. In
addition it shall be necessary, before it is possible to operate from 'OFF' to
'EARTH ON' to move a captive device which can be padlocked and which shall
be labelled 'MOVE BEFORE EARTHING'. The same device must prevent
operation from 'EARTH OFF' to 'ON' until the device is removed.

Mechanical indication of the operating positions of the switches and circuit


breaker shall be provided.

The indicators shall be positively driven in both directions so as to show whether


the switch circuit breaker contacts are in the ON, OFF or EARTH ON positions.
The positions shall be clearly indicated and the indicators shall be inscribed.

Status Letters Background


ON White Red
Issue : 1 21-07-2010 unclassified Page 24 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

OFF White Green


EARTH ON Black Yellow

The height of the letters shall be approximately 10mm. Indication of only one of
these three positions shall be visible at any one time.

The direction of movement of any operating handle to attain any position shall be
readily apparent. A label for this purpose shall be provided on the fixed portion
positioned close to the midpoint of the operating stroke and shall incorporate
arrows to indicate the direction of movement to achieve the final handle position
of the selected operation.

It shall not be possible to operate a non fault breaking switch from ON to OFF,
or an earth switch from EARTH ON to EARTH OFF for a minimum period of
three seconds subsequent to achievement of the ON or EARTH ON positions
respectively. The detachable handle concept considered adequate for this
purpose.

2. Interlocks

Interlocks shall be mechanical, positively driven and clearly labelled. They shall
be robust and designed and manufactured to minimise the possibility of
malfunction.

They shall prevent the following operations:

a) When testing entails the removal of an integral earth connection from built in
bushings, by the action of opening the access cover:

For Ring Switches:

i) The opening of the test access when the switch equipment is in any other
than the EARTH position.
ii) Movement from EARTH ON position with the test access open.

For circuit breaker transformer control:

i) Movement of the off, load selector from ON to EARTH ON, or from


EARTH ON to ON with the circuit breaker closed.
ii) Movement of the off load isolator from EARTH ON to ON with the test
access open.
iii) Opening of the access cover with the off-load selector not set to EARTH
ON position.

b) For Ring Switches:


The operation from ON to OFF or an earth switch from EARTH ON to
EARTH OFF for a minimum period of three seconds subsequent to
achievement of the ON or EARTH ON positions respectively. In addition it
shall be necessary, before it is possible to operate from OFF to EARTH ON
to move a captive device which can be padlocked and which shall be labelled
Issue : 1 21-07-2010 unclassified Page 25 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

MOVE BEFORE EARTHING. The same device must present operation


from EARTH OFF to ON until the device is removed.

6.4 Combined Rating and Data Plate


The rating plate shall be made of metal and shall be durable in the arduous
climate encountered in Qatar. It shall be fitted to the front of the unit. It shall
contain the following information:

a) Manufacturers Name and Address


b) Type/Model Reference of RMU
c) Serial No.
d) Month & Year of Manufacture
e) KM Tender number
f) Rated Voltage (Ur)
g) Rated short duration power frequency withstand voltage (Ud)
h) Rated lightning impulse withstand voltage (Up)
i) Rated frequency (fr)
j) Rated normal current (Ir), at ambient conditions of CB unit/Ring
switch/bus-bar
k) System Highest Voltage (Um)
l) Rated short time withstand current(Ik), at 3 Second duration of CB/Feeder
switch/bus-bar/Earth switch
m) Rated Peak withstand current (Ip)-of CB/Feeder switch/bus-bar/Earth switch
n) Testing Standard

6.5 Cleaning & Painting

The following represents the minimum acceptable quality:

All ferrous external surfaces shall be cleaned of scale and rust by shot blasting
and shall then be treated on the same day, without outdoor exposure with a zinc
spray. The zinc shall be applied by the flame gun process to thickness ZN4, in
accordance with BS EN 22063 : 1994.

External surfaces shall be taken to refer to all surfaces outside weatherproof


gasketed joints whether or not they are exposed to sun or rain.

The final coat of paint on all exterior surfaces shall be Dark Admiralty Grey matt
finish colour 632 of BS 381C.

The manufacturer may offer his own recommendations for the paint finish, but if
so, these details shall be provided at the time of tender. The colour is mandatory.

6.6 Tests

Type Tests:

Representative sample of RMU shall be type tested in reputed independent testing


laboratory in accordance with relevant latest IEC standards, including but not
limited to IEC 60060, 60265, 62271-100, 62271-200, and 60420. Copies of valid
type test reports shall be submitted for verification.
Issue : 1 21-07-2010 unclassified Page 26 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

1. Verification of Insulation Levels through:


-
Lighting Impulse withstand voltage test
-
Power frequency voltage withstand test
-
Partial discharge tests
2. Temperature Rise Tests:
3. Measurement of resistance of main circuit
4. Short time current withstand and peak withstand current
5. Verification of breaking and making capacities
6. Mechanical Operating test
7. Gas tightness test
8. Verification of Degree of protection
9. Arcing due to internal fault
10. Type testing of insulated bushings

Routine Tests:

The following tests shall be performed, on each unit of the switchgear (100%
quantity).

1. Power frequency voltage on the main circuit.


2. Dielectric tests on auxiliary and control circuits.
3. Measurement of Resistance of the main circuit.
4. Verification of protection against electrical shock (Electrical continuity of
earthed metallic parts)
5. Mechanical operating tests.
6. Functional tests
7. Tests on auxiliary devices.
8. Verification of correct wiring
9. Gas tightness test
10. Check of interlocks
11. Partial discharge measurements
12. Design & visual checks

7.0 THE LOW VOLTAGE DISTRIBUTION BOARD (FEEDER PILLAR)

7.1 General Design & Constructional Features

1. The substation distribution board (also known as FEEDER PILLAR-FP) is an


assembly, made of sheet steel enclosure, for direct connection to distribution
transformer (without intervening cable), consisting of incoming circuits (switch-
disconnector), outgoing functional units, instrument panel, secondary wiring &
accessories. Incomer unit is connected via bus-bars to outgoing functional units
(fuse disconnectors) so as to provide protection for, and means of isolating and
controlling, the outgoing circuits.

2. The design & construction shall generally conform to the latest versions of IEC
60439-1 and IEC 60439-5, and Technical specification # 37-2 of Energy
Network Association.

3. The feeder pillars shall be designed to take up the following arrangements:


Issue : 1 21-07-2010 unclassified Page 27 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Type A: 2500 A Busbars


2500 A incoming transformer unit:

Nominal size of cables up to 800 sq.mm.


Six 630A outgoing distribution units.
Instrument panel.

The framework shall be arranged to accommodate the equipment in the following order
reading from the front, left to right :

Distributor units
Transformer unit
Instrument panel

Type B: 2500 A Busbars


2 x 2500 A incoming transformer units:

Nominal size of cables up to 800 sq.mm.


Four 630 A outgoing distribution units.
Two Instrument panels.

The framework shall be so arranged to accommodate the equipment in the following


order reading from the front, left to right :

Instrument panel
Transformer unit
Distributor units
Transformer unit
Instrument panel

4. The FP shall be constructed only of materials capable of withstanding the


mechanical, electrical and thermal stresses as well as the effects of humidity
which are likely to be encountered in normal service. The insulating materials
used for barriers, and other insulating parts shall have resistance to thermal
stress and flame retardant properties in accordance with clause 8.2.102 of IEC
60439-5.

5. Protection against corrosion shall be ensured by the use of suitable materials or


by the application of equivalent protective coatings to the exposed surface,
taking into account of the intended conditions of use and maintenance. The
materials of coating shall pass the appropriate tests of clause 8.2.103 of IEC
60439-5.

6. The shell of the FP shall be robust construction, and manufactured from sheet
steel. Its mechanical properties shall comply with the requirements specified
under clause 8.2.101 of IEC 60439-5.

7. IP protection of FP enclosure shall not be less than be IP 41 in closed door


condition. However, adequate ventilation shall be provided to permit natural
circulation of air. The ventilation apertures shall be covered with corrosion-
proof metallic screens to prevent entry of vermin and other foreign bodies.
Issue : 1 21-07-2010 unclassified Page 28 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

8. Access to the front of the FP cabinet is to be via a double door, fitted with a
locking bar to secure them top and bottom. The locking bar shall be operated
by a single robust handle which shall be arranged to permit locking by a padlock
with a 52 x 49mm body, 8.5mm diameter shackle, having a clear inside width of
29mm and inside length of 41 to 55mm. The holes provided for the shackle
shall be not less than 10mm diameter. A heavy duty lamp with shall be provided
in the feeder pillar with limit switch interlocked with door open/close.

9. The FP cabinet shall be designed to ensure that adequate clearances shall be


provided to permit closing & locking of main doors, even when the incoming
transformer circuit isolators blades are fully left in an open or closed position,
and pad locked with its protection cover.

10. The front apron plate, along with any associated structural members, at cable
entry point of the cabinet, shall be removable type to facilitate easy installation
or reshuffling of outgoing units cables. Rear access to the cabinet shall not be
provided.

11. Provision shall be made for supporting the lower half of the cabinet by two
adjustable supports that shall bear against the tank of the transformer when the
cabinet is in position. These shall be adjustable in length from inside the cabinet
and shall have end caps to prevent damage to the transformer paintwork.
Alternatively, root frame work of the FP cabinet may be bolted to the PSU
bottom frame work.

12. The design shall be such that cables can be terminated from the front through
bottom entry. All Parts of equal size and rating shall be interchangeable. The
general design shall be such that the number of joints shall be kept to a
minimum. Corrosion proof (with electro-nickel plated) steel bolts shall be used
for electrical joints. All bolts and studs shall be plated to BS 3382 and shall be
corrosion proof.

13. Bus-bars shall be situated at the rear of the equipment. Bus-bars shall be of
made of nickel/tin-plated high conductivity electrolytic copper and un-insulated.
Phase bus-bars shall be colour marked (at least one inch width strip) in
sequence from top to bottom, red, yellow, blue and the neutral bus-bar shall be
marked black (at least one inch width strip) and the earth bus-bar mounted at
the bottom shall be unmarked.

14. A bolted link-bar of same rating as neutral bar, shall be provided between the
neutral and earth bus-bars. The metal framework of the fuse cabinet shall be
bonded to the earth bar.

15. Where live metal is adjacent to the framework a sheet of Bakelite or other
suitable low voltage insulating material shall be fixed to the inner side walls of
the fuse cabinet. It shall extend to at least 200mm above the red phase (upper
phase) top contact and an equal distance below the blue phase (lower phase
bottom contact). The thickness of the insulating material shall not be less than
2.0mm. The width of the insulating sheet shall approximate to that of the
sidewall of the fuse cabinet. The sheet of the insulating material shall be suitably
fixed. The fixing shall not incorporate metallic parts, which protrude towards
live metal work. If adhesives are used, the quality shall be such as to ensure

Issue : 1 21-07-2010 unclassified Page 29 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

proper adhesion under the temperature/humidity conditions stated in this


Specification.

16. Insulated dividing barriers shall be provided between incomer unit, outgoing
distributor units and instrument panels. The fixing of the insulated dividing
barriers shall be such that they shall not swing.

17. All CTs should be complied with thermal class insulation F

7.2 Incomer Unit with Switch-Disconnector (for transformer Control)

1. The mechanical connection between the transformer and the feeder pillar
cabinet shall be through flange connection conforming to Flange: F, fig 25 of
BS 2562 with suitable steel trunking. The electrical connections are made
through suitable bus-bar connecting-links to match LV mono-block type
bushing unit, conforming to BS 2562.

2. The incomer unit consists of 3 independent single pole switch-disconnectors,


each pole independently operated through operating handle. Each pole
corresponds to matching phase of the incoming transformer circuit.

3. The incomer switch-disconnetor unit shall be a type tested product conforming


to the requirements of IEC 60947-3 & IEC 60947-1. It shall be dependent
manual operated, with utilization category of AC21A. Making and breaking
capacities shall be at least 1.5 times its rated operational current. Product type
test certificates, issued from reputed independent laboratory shall be submitted
for verification.

4. The switch-disconnector contacts shall include a contact-tightening device on


both the top fixed contact, the bottom hinged contact, designed to obviate
slackening when subject to vibration, and good contact shall not depend upon
the neutral spring of the contact. Reasonably good contact shall be made on
closing the switch so that the full current can be safely carried in the interval
prior to the tightening of the contacts

5. The contact tightening device shall be operated by crank action using the
insulated operating handle; the same end of the operating handle shall be used
for tightening or slackening the contact tightening device as is used for opening
or closing the switch-disconnector blades. When the device is being tightened
or slackened the operating handle end shall remain in the device. The total
movement of the contact tightening device, from full slackness to full tightness,
shall not be more than 140 of angular rotation. ISOLATING MOVING
BLADES SHOULD REMAIN IN ITS POSSITION WITHOUT
DROPPING BY ITS OWN WEIGHT, EVEN IN OPEN POSITION.

6. Each switch-disconnector pole shall be equipped with transparent


polycarbonate safety barrier at front, with pad-locking facilities. Pad-locking
shall be possible when the switch contacts are either in fully open or closed
positions. When the switch contact blade is in fully opened condition, the blade
shall not touch the front safety barrier, and shall have at least 20mm clearance.
It shall be possible to close main door of the FP when the contact blade is fully
opened and pad-locked.

Issue : 1 21-07-2010 unclassified Page 30 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

7. Each phase and neutral of the incomer unit shall be colour marked to
correspond with the bus-bars to which they relate.

8. The insulated operating handle shall be kept in the slots of clips provided on the
framework to store this when not in use. The amount of bare metal on the pole
shall be kept to a minimum.

9. Each switch-disconnector pole shall be equipped with one current transformer


(details specified elsewhere). It shall be possible to easily change current
transformers, without dismantling any major components.

10. A bolted link of not less than 1250A rating shall be provided to disconnect the
neutral.

11. Robust and rigid insulated dividing barriers, of not less than 5mm thickness,
shall be provided between each pole of incomer unit. The fixing of these
insulating dividing barriers shall be such that under normal operating conditions
it is not possible for contact to be made between live metalwork of different
phases or between live and earthed metalwork.

7.3 Outgoing Distributor units


1. Each distributor unit shall be drilled for mounting at 145 +5mm centres apart. It
shall be possible to change any single bus-bar or cable connection without
affecting other phases.

2. Contact assemblies shall be supported from the steel frame-work by means of


strips, rods, bars or mouldings of insulating materials. The arrangement of
supports shall be such that mechanical stresses produced in service by the
temperature rise of connections shall not adversely affect the alignment of the
contact surfaces.

3. The fixed contact assembly shall be suitable for accommodating a fuse carrier
with a 92 mm terminal centre fuse-link type 'J' in accordance with BS 88. Fuse
carriers shall be supplied with the pillars. Each fuse carrier shall be suitable for
inserting in a phase of the unit by hinge action pivoted on the lower contact and
for withdrawing by snatch action. The contacts shall be arranged to permit
contact tightening and the contact surfaces shall be flat and accurately aligned
in pairs.

4. The phase cable side fuse contacts shall be designed with long and short reach
and shall be fitted with forward projecting M16 captive steel studs, one per
contact complete with a full nut. A lock washer, and plain washer with lock nut
shall be provided. The contacts shall be so designed that they provide adequate
spacing and are fully interchangeable to permit terminating the phase
conductors of a cable whatever their lay.

5. The phase cable side contact groove (for receiving the fuse) shall be centrally
and symmetrically placed, so that, even if this contact is fixed in reverse side, its
fixing centre shall not miss its alignment for fixing fuses. Further, if these
contacts are made in L-shape, the gap between adjacent contacts, when fitted
in reverse directions, shall be at least 25mm. Alternatively, if these contacts are
made in I shape, these contacts shall be fitted with additional copper spacer

Issue : 1 21-07-2010 unclassified Page 31 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

rings of 6mm thickness, so that the outgoing cable insulation will not touch the
hot bus-bars, when connected.

6. Insulated dividing barriers shall be provided between phase contact assemblies


and phase and neutral contact assemblies which shall make it impossible to
insert a fuse link between contacts of different phases.

7. There shall be no separate neutral isolating link on each outgoing unit. The
neutral conductor of each cable (of outgoing unit) shall be terminated on to a
contact bar, rated at 315A, mounted below the corresponding outgoing
distributor unit, between the neutral bus-bar and the insulated support strut.
The bottom fixing of the insulated support strut shall be mounted above the
neutral contact bar so as to allow the neutral core an unimpeded approach to
the desired fixing position. This neutral contact bar shall be drilled in two
positions and fitted with a high tensile M16 steel bolt, nut, and lock-washer or
plain washer with locknut shall be provided. The neutral bus-bar shall be fitted
460mm above the centre line of cable cleats at bottom.
8. Bottom plate of the feeder pillar with cable entry holes, shall be divided into
two portions. By removing the front portion, and front apron plate, it shall be
suitable to connect, disconnect, or interchange any cable connection. All holes
shall be closed with dummy plates which are removable at the time of
connections.

9. Cable support shall be provided by a suitable wooden-cleats mounted at the


bottom of the cabinet (inside cabinet) in such a manner that the cable entry to
the cabinet is sealed by the wooden cleat and that the cable is clear of any
adjacent metalwork with the help of suitable grommets. It shall comply with the
requirements of IP41, not allowing any vermin to enter.

10. The cleat shall clamp directly on to the PVC over sheath of the cable. The cable
cleat and its fixings shall be adequate to support the outgoing cable in normal
service and when subjected to the short circuit duty specified elsewhere.

11. Cable termination arrangement shall be suitable for accommodating up to and


including 300mm 4 core stranded copper conductor either I) paper insulated
lead sheathed double steel tape armoured PVC over sheathed cables to BS
6480 or ii) XLPE insulated steel wire armoured PVC over sheath of the cable
as per IEC 60502.

12. Required number of holes shall be drilled on earth bar and fixed with M16 bolts,
nuts & washers, for terminating Cable earths from each out going cable.

13. All cable connections shall be suitable for terminating using heat shrinkable
materials and crimping lugs. (Heat shrink terminations & cable lugs are not in
the scope of supply).

14. Provision shall be made on each outgoing feeder ways to affix and padlock a
suitable insulated device to prevent fuse links being installed or removed. Two
such devices shall be provided with each feeder pillar. The device shall not
obstruct the feeder pillar doors from closing when in position or when stored
within the feeder pillar. It is essential that the device can be safely fitted whilst
the pillar and each feeder is alive.

Issue : 1 21-07-2010 unclassified Page 32 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

15. The device shall be marked with the following wording in English and Arabic
and be clearly visible when viewed from the front with the feeder pillar doors
open:

"CAUTION -MEN WORKING - DO NOT INTERFERE WITH THIS


APPARATUS

16. Blank circuit labels suitable for engraving black letter on white background
shall be provided for all outgoing circuits. The support for the circuit labels
shall not be on any live part.

7.4 Electrical Ratings & Characteristics

1. Rated operational voltage (Ue) : 415/240Vac


2. Rated insulation Voltage (Ui) : 415/240Vac
3. Rated impulse withstand voltage (Uimp) : 6kV
4. Rated frequency : 50 Hz

5. Rated Normal currents


For PSU/ Rated normal
Rated normal current Rated normal current of No. of outgoing
Transformer Rating current rating of
of Incomer units * Phase Bus-bars * Ways in FP
(KVA) * each Outgoing unit *
315 800A 800A 2 630A
500 1600A 1600A 4 630A
1000 1600A 1600A 6 630A
1600 2500A 2500A 6 630A
*These ratings have reference to local ambient conditions stated in the Specification.

6. Rated short circuit withstand current and Peak withstand currents


For PSU/ Transformer Rated normal current of Rated Short circuit Rated peak withstand
Rating (KVA) Incomer units withstand current (Icw) current (Ipk)
315 800A 20kA @ 1 Sec 50kA
500 1600A 20kA @ 1 Sec 50kA
1000 1600A 35.5kA @ 1 Sec 88 kA
1600 2500A 40 kA @ 1 Sec 100kA

7. Clearances
For all connections in air the clearance and creepage distances shall be not less than 25mm
between conductors and 20mm from conductors to earth.

8. Temperature rise limits

The distribution fuse-board shall be so designed as to ensure that thermal interaction does
not unduly affect the performance of any of the components
Temperature rise test on the FP shall be conducted in accordance with clause 8.2.1.3 of IEC
60439-1 (by using current on all apparatus) with all its components, including fuse-links,
fitted, and all circuits are fully loaded. The test shall be carried out with the base closed,
door(s) shut and mouth of the throat piece through which pass the incoming connections,
shall be effectively blanked off.
All the measurements shall be taken with the help of thermocouples and thermometers. The
FP shall be capable of withstanding the guaranteed temperature rise limits specified in IEC
Issue : 1 21-07-2010 unclassified Page 33 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

60439-1/ cl# 7.3/Table-2. However actual temperatures rises of over ambient temperature
outside the FP shall not cross the limits as specified below.

Sr.
Part/component of the Assembly Temperature rise limits, K
No
1 All temporary incoming connections
2 Interconnecting point between Tx and FP
3 Top contacts of each phase of the isolator
45
4 Top contacts of each phase of O/G fuse units
5 All cable lugs/terminals
6 All bus-bars
7 All other built-in components In accordance with limits
specified in relevant
product standards
requirements, less 250K

Evidence shall be submitted that temperature rise tests have been carried out on a completed FP, to demonstrate
that it does comply with this Clause.

7.5 Cleaning and Painting


The following is the minimum standard. Manufacturers may offer an alternative, at the time of
tender.

A ferrous surface and edges shall be cleaned of scale and rust by shot blasting and shall then be
treated on the same day, without outdoor exposure, with a zinc spray.

The zinc shall be applied by flame gun process of a thickness ZN4 in accordance with BS EN
22063 : 1994.

The treatment shall be followed by application of one coat of zinc chromate base priming paint, an
undercoat and final coat of durable oil and weather resisting paint. The final coat shall be dark
admiralty grey colour 632 in BS 381 C.

7.6 Accessories Fitted

1. Fuse Carriers
Fuses for Distributor Circuits
Fuse Links : These will be supplied by the purchaser.

Fuse Carriers
A thorough grip shrouded fuse carrier of high quality non-inflammable and non-
hygroscopic, DMC insulating material approved by Kahramaa shall be provided
on each phase. Each carrier shall be complete with two insulated contact
tightening thumbscrews. Reasonably good contact shall be made by wedge
action on inserting the fuse carrier so that current can be safely carried in the
interval prior to the tightening of the contact tightening thumbscrews. Wedge
action material shall be of brass and screws shall be of anti corrosive material.
There shall be one standard size of fuse-carrier which shall carry a 92mm
terminal centre fuse-link to type 'J' BS 88.

2. Fuses For Auxiliary Supply


Fuse carriers for auxiliary circuits shall be of the withdraw-able handle insulated
type with a rating of 60A and shall accommodate cylindrical cartridge type fuse-
Issue : 1 21-07-2010 unclassified Page 34 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

links of 32A with dimensions 57x22 mm, in accordance with type 11a fuses in
BS 1361:1986.

3. Neutral and Earth Connections


Separate neutral and earth bars shall be provided. They shall be solidly bolted
together. The neutral bar shall be insulated from the shell, but the shell be bonded to
the earth bar. A sideways projecting M 12 x 50mm captive stud complete with
washer, nut, and lock nut connected to the earth bar shall project outwards from the
shell.

4. Current Transformers
The current transformers of ratio 800/5A, 1600/5A or 2400/5A as specified shall be
provided on the incoming circuit of respective Feeder Pillars and securely fixed. The
current transformers shall comply with the requirements of BS 7626 and IEC 60044
and shall be of 5VA output, Class 1 accuracy. They shall be suitable for the
operation of thermal demand ammeters. The current transformers shall be of epoxy
cast resin type capable of withstanding required temperature limits. The mounting
of CTs shall be such that, in the event of failure, they shall be easily replaceable
without the need for dismantling any major component. Only single ratio CTs are to
be used.

5. Instrument Panels And Auxiliary Supply Circuits

An instrument panel suitably wired shall be provided to accommodate three thermal


demand ammeters (96x96mm size) with instantaneous pointer having a twenty-
minute lag and with direct reading quadrant scales. The scales readings shall be in
one side. Measuring ranges shall be 0-960A, 0-1960A and 0-2880A for C.T. ratios
800/5A, 1600/5A, and 2400/5A respectively. The cable connections shall be of
sufficient length to allow for the removal of the indicators from the front panel.

The following additional equipment shall be supplied:-

13A switched socket outlet to BS 1363.

60A fuse base and carrier for socket, substation supplies and earth fault indicator
reset supply.

The instrument panel shall be mounted in such a position that neither cable
installation nor jointing is impeded. Where it is mounted in front of the cables it shall
be removable.

The substation supplies circuit shall be wired to terminals on the side of the fuse-
cabinet mounted below the level of the neutral bar. A 25 mm cable gland is to be
equipped at right front corner of bottom plate, to terminate an outgoing 2 core
16mm PVC insulated steel wire armoured cable. It shall be possible to safely
connect the outgoing cable with the remainder of the pillar live in normal service.
The terminal block shall be fully shrouded.

6. Small Wiring

Issue : 1 21-07-2010 unclassified Page 35 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Small wiring shall be carried out in PVC insulated cable coloured black to BS 6231 Type B with
7/0.67 mm conductors and with cores ferruled. The substation supplies circuit shall be wired to
the terminal block with 16mm PVC insulated conductors having Red & Black colour insulation.
The terminal block shall be identified with permanent labels.

The secondary wiring of the group of current transformers shall be connected to earth at a single
point on the terminal block, which shall be accessible from the front the pillar or fuse-cabinet. In
addition to this, all secondary wires of CT are to be routed through TB.

Wiring shall be fixed and where wiring cleats are used they shall be of the insulated limited
compression type. Both the main connection from the phase bus-bar to the fuse and the main
connection from the neutral bus-bar shall be hard drawn high conductivity copper not less than
75mm cross-section.
If necessary use heat resistant grade wires for the small wiring to withstand the required
temperature limits.

7. Circuit Labels & Permanent Wiring Diagrams

A circuit label 75x50mm made of insulating material shall be mounted on the barrier
between red and yellow phases of each circuit unit. This label shall be securely held
without the use of screws or other metallic fixings and it shall be possible to slot
into position and remove label from the front of the barrier. The labels shall be
suitable for engraving black letters on a white background. The supports of the
labels shall not be fixed to live parts.

A permanent, indelible schematic & wiring diagrams, clearly indicating all terminal
markings, components, shall be fixed inside the FP front door.

7.7 Tests
1. Type tests
The following type tests are to be conducted in reputed independent laboratory
and copies of test reports shall need to be submitted.
a) Verification of temperature rise limits (IEC 60439-5/8.2.1)
b) Verification of Dielectric properties (IEC 60439-5/8.2.2)
c) Verification of short circuit withstand strength (IEC 60439-5/8.2.3)
d) Verification of clearances and creepage distances (IEC 60439-5/8.2.5)
e) Verification of mechanical operation (IEC 60439-5/8.2.6)
f) Verification of degree of protection (IEC 60439-5/8.2.7)
g) Verification of mechanical strength (IEC 60439-5/8.2.101)
h) Verification of resistance to abnormal heat and flame (IEC 60439-5/8.2.102)
i) Verification of corrosion and aging resistance (IEC 60439-5/8.2.103)
2. Routine Tests

Routine tests are to be carried out on every new assembly after it has been
assembled at factory. One set of routine test reports of each FP shall be fixed
inside the FP cabinet in a strong water-proof envelope. The following routine
tests are to be carried out.
a) Inspection of assembly, including wiring, and electrical operation test(8.3.1)
Issue : 1 21-07-2010 unclassified Page 36 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

b) Dielectric test (IEC 60439-5/8.3.2)


c) Electrical continuity (IEC 60 439-5/8.3.3)
d) Insulation resistance (IEC 60439-5/8.3.4)

8.0 THE HOUSING OF DPS

8.1 Construction

1. Overall dimensions: Overall dimensions shall be as per the clause 1.0 above.
Manufacturer may propose a compact design with the same clearances between
the equipment mentioned in the clause, however, KAHRAMAA reserves the
right to accept or not.

2. The main components (Transformer, LV & HV Switchgear) shall be mounted


on robust base made of structural steel frame, through bolted joints. Welded
joints are not acceptable. This shall facilitate easy replacement of components
when required.

3. It shall be four sided, with walls having removable type panels on three sides,
and two access doors at the front, for HV & LV switchgear compartments
individually. Each front access shall be of double leaved hinged type doors. In
order to facilitate the cable connection, the portion of the wall at RMU side
equivalent to RMU dimensions shall be removable from inner side bolts which
never be accessed from outer side.

4. All main components of DPS shall be mounted on structural steel base frame
through bolted joints to form a rigid distortion-free structure. DPS shall have
completely bolted enclosure for easy assembly and retrofit.

5. The DPS shall be operated from outside at ground level (on concrete plinth),
and shall be suitable for mounting on concrete plinth.

6. Plinth matrix of 500KVA, 1000KVA & 1600KVA DPS units shall be same.
These units shall be designed to fit on the same size plinth. This implies the
position of bottom cable entry ducts, of all these three sizes shall align with the
common plinth matrix. This shall permit replacement of any unit by any other,
irrespective of rating, by disconnection and reconnection of 11kV and LV
cables only. However, 315KVA DPS may have different plinth size & matrix

7. Bottom cable entry openings of PSU shall align with respective cable ducts on
concrete plinth. The cable entry opening shall be closed with removable type
covers to maintain IP protection of the enclosure.

8. The walls, door and roof shall be made of sheet steel with reinforcement as may
be necessary. The sheet steel thickness before paint shall not be less than
2.0mm.

9. The roof of the enclosure shall have double roof-system, separated by large
volume of air, to serve as insulation against direct solar radiation.

10. Pressure relief system/vent(s) shall be provided on the top of enclosure to allow
safe passage of gases released in the event of internal arc inside DPS unit.

Issue : 1 21-07-2010 unclassified Page 37 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

11. The design and construction of the modules shall be such that when all modules
are assembled together on the steel base frame, it shall form a strong and
distortion-free structure.

12. Suitable lifting arrangements shall be provided such that DPS along with or
without the housing can be lifted or transported to site as a single unit. The
lifting fittings shall be suitable for lifting the PDS with crane and chains without
damaging the enclosure.

13. The roof shall be pitched in all directions, and shall include extensions over the
walls of approximately 100mm.

14. The enclosure shall be removable type, from its base, without dismantling any
of its components.

15. The enclosure shall withstand all mechanical stresses including roof-load, wind-
loads, and external mechanical impacts. Covers, doors, and ventilation openings
shall be able to withstand mechanical impacts corresponding to a degree of
protection IK10 (20J).

16. The door hinges shall be robust and made from stainless steel. All doors shall
have suitable mechanism to toggle its position when fully opened, as well as
through half way. A heavy duty lamp with shall be provided in the enclosure of
DPS with limit switch interlocked with door open/close.

17. The doors of the housing shall be so placed as to permit an operator to carry
out switching operations from outside of the unit, including cable fault testing,
operation of the tap changer etc

18. Each door shall be in two parts. Left hand door shall be fixed with two 178mm
brass tower bolts. Right hand side door shall be fixed with stainless steel
458mm L-Drop, spindle dia. 16mm and accessory.

19. The doors shall be lockable by a padlock with a 52mm x 49mm body, and
8.5mm diameter shackle having a clear inside width of 29mm and an inside
length of 41 to 55mm. The purchaser will supply this.

20. Earthing: Each of the modules of PSU shall be effectively electrically bonded
and an earthing terminal shall be provided. This earthing terminal shall be
connected to the main earthing on the transformer with a 70mm earthing
conductor. The main earthing terminal on the transformer will be connected to
the earth electrodes

8.2 Corrosion Protection & Painting


1. The definitive guideline documents are BS EN ISO 12944 Parts #1 to 8, & BS
EN ISO 14713. The procedure should clearly indicate its relationship to the
appropriate parts and tables of BS EN ISO 12944 and BS EN ISO 14713
2. It is the responsibility of the manufacturer to assess environmental classification,
select suitable surface preparation process, protective paint system, execution
and supervision process, in accordance with above referred standards and
requirements.

Issue : 1 21-07-2010 unclassified Page 38 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

3. The painting work should render a service life of at least 25 years to the
equipment, withstanding local ambient climatic & environmental conditions.
5. The exact Specification & painting procedure going to be followed by the
manufacturer shall be submitted at time of tender.
6. The process shall contain the following steps as minimum requirement:
a) Surface cleaning
b) Degreasing
c) Automated Zinc phosphate chemical treatment followed by chromatic
passivization
d) Surface drying at 130-1600C
e) 3 coats of electrostatic powder coating (normal spray painting not
acceptable)
f) Curing of paint work in oven at 180-2100C, as appropriate.(curing by natural
air drying process is not acceptable)
g) Final coat colour shall be light grey or beige
7. The manufacturer should posses required laboratory testing equipment, in their
factory, to test the samples in accordance with BS EN ISO 12944-6. These test
reports should be submitted along with each consignment of delivery.

8.3 Earth Fault Blinking Device


a) The Blinking lamps shall be fixed on the top of package unit with Provision
to adjust the angle of view by means of opening and fixing the device such a
way to view the indication lamp by sitting in the vehicle or standing
position, either from front side or lateral.
b) The blinking lamp shall have a view range from not less than 50m.
c) The Blinking lamp shall be incorporated in housing with highly solid material
(polycarbonate) proper weather proof and viewing glass with oval shaped
metallic cover on top (Similar to traffic signals). All the cables should be laid
through metallic weatherproof conduit with proper /cable trays with
covering.
d) The Earth Fault Indicator should consists of i) Reading Instrument (Surface
mounted), ii) Sensor with cable and iii) Blinking lamp. The power supply
shall be performed by lithium battery long life (Minimum 10 Years) and of
Auxiliary supply 240V, AC supply. Test button should also be provided.
e) The indicator shall have facility for i) Manual reset, ii) Self resets when the
240V,AC supply resumes, iii) Resets automatically after a pre-set time. This
pre-set reset time shall be adjustable and shall 0 to 8 hrs in steps and iv)
Provision for connection to reset from remote.
f) The impulse duration of blinking light shall be adjustable between 50 to
1000 milliseconds. The fault Indicator shall be provided with enough length
of cable to fix in appropriate location.
g) The Earth fault current sensor shall be suitable for mounting on 12kV various
types of HV cables in KAHRAMAA distribution system. Suitable belt with
self locking facility shall be provided on the sensor to hold it firmly on the
cable.
h) The earth fault operating current shall be able to set from 10,20,40,60 and
100 Amps. The sensitivity (operating current) of the EFI shall be set at 30
Amps
The indicators including the cables should be weather proof enclosed with
front side glass for proper view (IP65).
Issue : 1 21-07-2010 unclassified Page 39 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

8.4 Restricted Earth Fault (REF) Tripping Mechanism

a) The purpose of this mechanism is to trip the 11kV side of the Transformer
Switch (TX Switch) in RMU from the REF scheme on LV side of
Transformer, in which CTs are provided in the feeder pillar, which Protect an
earth fault within in the protected zone of the scheme, ie LV winding up to
the CT location.
b) The scheme shall have 4 Nos. of class X CTs (1 no. each for phase and 1 no.
for neutral) and shall be mounted inside the feeder pillar.
c) The secondary of all these CTs shall be connected in parallel (i.e. the same
polarity terminals connected together ) for the REF scheme, and the wires
from the these CTs (common terminals) shall be connected to a trip coil of
the transformer C.B. of the RMU.
d) All the CTs used for the REF scheme shall have same ratio, magnetization
characteristics, winding resistance, etc and shall be from same manufacturer.
The knee point voltage of CTs must be higher than the stabilization voltage
for maximum external fault current.
e) CT ratio and knee point voltage shall be depending up on TX capacity
Calculation shall be provided by the supplier with Transformer and CT
parameters (Resistance of CTs, TX % Impedance etc.
f) To achieve the stability during external fault proper short time rated variable
stabilizing resistor in series with the trip coil shall be provided. The stabilizing
resistor shall be easily accessible and shall be easily replaceable. Same
methodology for REF scheme calculation shall be adopted for the above.
g) PVC insulated, sheathed and armoured 2x 4 sq.mm copper cable shall be
used for interconnecting the CT wires between the feeder pillar and RMU.
The cable shall be properly glanced at both ends.
h) Terminal Blocks having isolating link and CT shorting facility shall be used at
feeder pillar and RMU for terminating secondary wires of CTs. The single
point earthing of CT secondary circuit shall be confirmed.
i) All wires shall be provided with ferrules for identification. For example, wires
at CT terminals shall be ferruled as S1 and S2. At TBs on RMU these shall
be REF-S1 and REF-S2.
j) The 2 leads from the REF CTs shall be connected to a dedicated TRIP coil.
k) Provision of dedicated Trip coil for REF trip shall be made in RMU (similar
to the one provided for putting TLF).
l) A very low burden current operated series Mechanical Flag relay should be
connected in series with CT output leads from REF CTs
m) The trip coil shall be connected in series with variable stabilizing resistor and
series mechanical current operated flag relay with minimum burden which is
to be fixed in the instrument panel of F.P.
n) The stabilizing resistor is selected in such a way that, during maximum
through fault condition, the voltage developed across the shunt trip coil (or
the current through the shunt trip coil) shall not trip the transformer switch.
o) The scheme shall be tested for, CTs to prove ratio, polarity, magnetization
curve and winding resistance, ratio checks for confirming that the installed
CTs are adequate for the REF scheme and also the stability checks and
Tripping shall be proved.
p) Sensitivity of the scheme shall be tested by Primary injection. Also the
stability of the scheme shall be tested for external faults.

Issue : 1 21-07-2010 unclassified Page 40 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

q) Certification with test results complying above requirements shall be


provided with each unit.
r) All the CT calculation is similar to high impedance Restricted Earth Fault
scheme. Only the difference is instead of relay in the REF scheme, the
dedicated coil for RMU TX switch is connected and direct tripping of
transformer switch is achieved, without auxiliary supply and REF relay

8.5 Accessories to be supplied as spares (free of cost)

a) In Case of cable connection Termination kits


for interconnecting HV & LV Cables.: 10% of total quantity of DPS.
b) In Case of connection through bus bar, HV & LV
trunking box with gaskets and identification labels: 1% of total quantity of
DPS.
c) Complete set of REF CTs.: 3% of total quantity of DPS.

8.6 Test to be conducted on paint work of DPS

The paint work shall pass following tests


a) Measurement of thickness of protective coating (ISO 2808)
b) Specular gloss factor at 60 deg (ISO 2813): 905%
c) Falling weight test (ISO 6272): 1kg/50cm
d) Cross cut test (ISO 2409): classification: 0
e) Cupping test (ISO 1520): 08mm
f) Bending test Cylindrical mandrel test (ISO 1519): 3.0mm
g) Salt spray (fog) test (ISO 7253): 1000hrs

8.7 Tests on DPS


In addition to the type tests conducted on individual components (Transformer,
RMU and Feeder Pillar), DPS as a whole unit need to be type tested in accordance
with the requirements of IEC 62271-202. Copy of type test reports issued from
reputed independent laboratories need to be submitted.

1. Type tests
a) Tests to verify the insulation levels of PSU (IEC 62271-202/6.2)
b) Tests to prove the temperature rise of main components in PSU (IEC
62271-202/6.3)
c) Test to prove the capability of main and earthing circuits to be subjected to
the rated peak and the rated short-time with stand currents (IEC 62271-
202/6.4)
d) Functional tests to prove satisfactory operation of the assembly (IEC 62271-
202/6.5)
e) Tests to verify the degree of protection (IEC 62271-202/6.6)
f) Test to verify the withstand of the enclosure of the PSU against mechanical
stress (IEC 62271-202/6.7)
g) For PSU substation class (IAC-AB @ 20kA-1 sec) tests to assess the effects
of arcing due to an internal fault (IEC 62271-202/6.8)
h) Tests to verify the sound level of the PSU (IEC 62271-202/Annexure-B)

Issue : 1 21-07-2010 unclassified Page 41 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

2. Routine tests on DPS


Routine tests are to be carried out on every new assembly after it has been
assembled at factory. One set of routine test reports of each PSU shall be fixed
inside the PSU cabinet in a strong water-proof envelope. The following routine
tests are to be carried out.
a) Dielectric test on HV interconnection (IEC 62271-202/7.1)
b) Test on auxiliary and control circuits (IEC 62271-202/7.2)
c) REF stability checks / tests.
d) Functional tests (IEC 62271-202/7.3)
e) Verification of correct wiring (IEC 62271-202/7.4)
f) Tests on paint work as specified above.

9.0 QUALITY STANDARDS

The manufacturers of the equipment specified shall possess certification issued by a


body authorised to do so, which indicates that the manufacturing unit operates to a
standard equivalent to ISO 9001. Copy of a valid certificate shall be submitted along
with the tender.

Submission shall include documents to indicate the quality control procedures


adopted by the manufacturer of the housing.

10 TESTING, INSPECTION & DELIVERY


1. Before commencing the production/manufacturing of 1st lot, against KM tenders,
the manufacturer is obliged to produce samples of DPS units and inform Kahramaa
for inspection and acceptance through witnessing factory acceptance tests, and
routine tests. KM reserves the right to choose option of inspecting these proto-type
samples either at KM workshop or at factory.
2. For every subsequent lot, the manufacturer is obliged to inform Kahramaa, at least
20 days before dispatch, and obtain clearance for dispatch. KM Engineers have the
option of inspecting & witnessing all factory acceptance tests, including routine
tests, at manufacturers factory premises for each lot.
3. Acceptance by KM Engineer(s)/Representative(s) of any DPS unit shall not relieve
the manufacturer from any of their responsibilities, guarantees, or from other
obligations, to comply with product requirements.
4. Type tests are to be carried out on specimen DPS unit, essentially of same design
and ratings, as being offered. Manufacturer is obliged to provide details of test
procedures being followed, to the KM inspection team before commencing factory
accepting tests.
5. Each DPS unit need to be subjected to all routine tests at factory before delivery.
One unit in each lot will be subjected to prescribed tests on paint work. Further,
each unit may be subjected to inspection on receiving them at DOHA to verify its
healthiness and its conformity with the guaranteed design data.
6. All tests should be performed in accordance with the latest issue of relevant IEC
standards
7. Three sets (copies) of routine tests & FAT reports to be prepared. One set to be
attached with the body of switchgear unit, in a strong water-proof envelope. Second
Issue : 1 21-07-2010 unclassified Page 42 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

copy to be sent along with delivery note. Third copy to be sent to the end-user
department.
8. A detailed function drawing shall be engraved on metal plate and fixed at inner side
suitable location of H.V compartment.
9. FAT report shall include copy of quality control report containing list of check
points verified/inspected at factory against each switchgear unit.
10. Each delivery note shall include the details of serial number and month/year of
production of each switchgear unit.
11. Both the manufacturing date (i.e month/year) and delivery date should be shown on
the rating plate of each transformer, and the time difference between these two dates
should not be more than 6-months.
12. The manufacturer needs to organize training workshops for KM technical staff, to
familiarize with installation, operation & Maintenance, trouble shooting guidelines.
13. The manufacturer need to submit 6 copies of:
a) Manuals for Operation, Maintenance & Condition Monitoring (Details of
condition monitoring parameters, its required data values, frequency of
monitoring of each parameter, etc.)
b) Installation Instructions,
c) Trouble shooting manual,
d) Technical data-sheets and product catalogues of all main equipment
(Transformer, feeder pillar & ring main unit) and accessories mounted on the
transformers [i.e, Magnetic core material, PRV assembly, Tap-changer
assembly, thermometer assembly, drain valve cum sampling device, LV
bushing assembly, HV bushings, pressure gauge & isolating valve assembly,
oil-level gauge, all gaskets, REF, CTs etc]

11.0 INFORMATION/DOCUMENTS TO BE SUBMITTED BY


BIDDERS/MANUFACTURER
Each manufacturer must supply the following information along with their offer:

A Distribution Package substation unit

1. Brief description of product being offered along with details of name of


manufacturer, product type / model, country of origin, quantity being offered,
mobilization period/execution plan.
2. Detailed layout drawing with all views including plan. Elevation, side elevation,
dimensions, components.
3. Complete set schematic diagrams for power & control protection system.
4. A plan showing the minimum clearances required around a DPS on site when
installed
5. Details of materials used in frame and cladding
Issue : 1 21-07-2010 unclassified Page 43 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

6. Detailed drawing of interconnection between transformer and RMU


7. Detailed drawing of interconnection between transformer and LV Feeder pillar
8. Details of ventilation arrangements
9. Details of arc pressure relief device in the housing
10. Details of door locking arrangements and lifting arrangements
11. Detailed technical data sheets containing rated values and characteristics.
12. Approximate envelope dimensions of the whole unit, without housing.
13. Approximate envelope dimensions including housing.
14. Centre of gravity (plan position and height).
15. Copies of Type test reports
16. Original Product catalogues (photo copies not acceptable)
17. Sourcing details of all main components
18. Copy of valid ISO 9001;2000 certificate to be submitted
19. Set of installation, operation and maintenance instructions/manuals
20. Set of instructions for storage, transport
21. Weight of the DPS without and with housing.
22. A set of assembly instructions
23. Previous sales history of related supplies made to the clients in GCC and other
countries. The details should include client name, equipment ratings, quantity
delivered, year etc.
24. Compliance statement against each clause of this specification document
25. List of Deviations against each clause of the KM technical specification

B Transformer
1) Technical data-sheets, containing all technical details including, ratings, parameters,
vector group, connections symbols, losses, max. flux density, cooling, tank details,
winding details, oil details, temperature rise limits, % impedance values, insulation
levels, efficiency, regulation, etc, of the transformer
2) All technical details, parameters, data-sheets belong to each of the accessories fitted
to the transformer, including tap-changer, thermometer, PRV, HV & LV bushings,
Oil level indicator, gas pressure gauge with isolating valve, drain valve with
sampling device, etc.
3) All Type tests & Special test certificates of the transformer
4) Type test certificates of tap-changer
5) Type test certificates of HV & LV bushings
6) Specific Product catalogues of the transformer, tap-changer, Oil-level indicator,
PRV, Thermometer, HV & LV Bushings, various gaskets used, gas pressure gauge
etc.
7) Details of Painting system applied to the transformer
8) Detailed Operation & maintenance manuals of transformer.
9) Valid proof of documents showing the sourcing of tap-changer, magnetic core
laminations, HV & LV bushings from internationally reputed manufacturers.
Issue : 1 21-07-2010 unclassified Page 44 of 48
Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

10) Valid ISO 9001 certification of the Transformer manufacturer


11) Compliance/deviation statement against each clause of this specification document.
12) Two sets of Complete drawings, as stated below
13) Complete sales history of the proposed product, indicating details of the
Transformer rating, Client name, Year of supply, quantity supplied etc. The list
should highlight the supplies made to clients in GCC countries.

C Ring Main Unit (RMU)


1. Detailed layout drawing with all views, dimensions, components
2. Detailed technical data sheets containing rated values and characteristics
3. Pictorial views of gas pressure system, explaining how the gas medium is isolated
with the gas pressure gauge, and its replacement procedure.
4. Single line diagrams, controls circuits, wiring diagrams, list of inputs/outputs for
remote monitoring & control (where applicable), for each switchgear unit described
in the specification, need to be submitted.
5. Linear Motor Drive Actuators: Details of Motor characteristic, arrangements of
actuators, wiring diagrams of Motors and Control Box shall be submitted to
Kahramaa for prior approval
6. O/C & E/F protection: Details of tripping mechanism, tripping characteristics and
applicable setting shall be submitted with the Bid.
7. Earth fault relay: Product technical details, catalogues, installation instructions &
manuals should be submitted.
8. Type test reports, belong to all CTs & VTs, Vacuum bottles
9. Sourcing details of all components like vacuum bottles, CTs, VTs, shall be
furnished.
10. Latest type test certificates and reports
11. Copy of valid ISO 9001;2000 certificate to be submitted
12. Original Product catalogues (photo copies not acceptable)

D L.V Feeder Pillar


1. A full set of type test certificates as specified
2. As built construction drawing with all views and sections, containing all dimensions,
details of components, Size and arrangement of busbars, neutral bar, earth bar and
neutral/earth link, Dimensions of cabinet gauge of metal used.

3. Technical data-sheets of main feeder pillar, and its components


4. Paint work specification
5. Installation, operation & maintenance instructions.

Issue : 1 21-07-2010 unclassified Page 45 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

12.0 LIST OF DEVIATION TO THE SPECIFICATION.


The Tenderers are required to attach a separate deviation list to their Technical Offer
and include it in the Technical Package if the offered equipments do not meet the
requirements of any clause of the Specification.

Offers without any deviation list attached to the Technical Offer and included in the
Technical Package shall mean that the offer meets the requirements of the
Specifications on all the clauses.

Offers with deviations listed out shall mean that the offer meets the requirements of the
Specification on all the other clauses not included in the deviation list.

13.0 WARRANTY
Manufacturer need to provide a warranty of minimum 3 years from the date of delivery,
or 2 years from the date of installation (whichever is earlier) against each unit supplied
against any design, manufacture, and material defects. Manufacturer shall also provide
20 years guarantee against SF6 gas leaks.
Any switchgear unit failed during service, with in the warranty period, need to be
replaced with new unit free of cost. Further, the faulty units(s) need (s) to be get
analyzed with reputed independent agencies and fault-analysis reports to be submitted.
Further, it is the responsibility of the manufacturer to arrange for investigation of any
abnormalities/defects observed during service period, even if it is out of warranty period.

14.0 RESTRICTIONS ON OUT-SOURCING

1) Once the DPS is pre-qualified or short listed for tenders, based on manufacturer
approval for the main equipment (Transformer, Ring Main Unit & L.V. feeder pillar)
and manufacturing facilities for major components (DPS enclosure, transformer tank
body, radiators, paint work, magnetic core assembly, winding coils etc), outsourcing
of the same is not permitted.
2) Out sourcing of any of the main components or work need to be declared in the
beginning it- self, before the DPS is pre-qualified or short listed for tenders. In such
case, the manufacturer is responsible for quality of work for the main equipment &
components. Further, the manufacturer should arrange accessing the manufacturing
facilities of out-sourced components to KAHRAMAA Engineers, to verify their
quality parameters.

Issue : 1 21-07-2010 unclassified Page 46 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Issue : 1 21-07-2010 unclassified Page 47 of 48


Specification for Distribution Package Substations(DPS) EP-MS-P4/S2-091

Issue : 1 21-07-2010 unclassified Page 48 of 48

Anda mungkin juga menyukai