Anda di halaman 1dari 159

Addendum

Specification No. 1001 (June 2008)

Substation Equipment

Addendum No.3

Clause Article Action

1001.81 1001-3 1001-3.16.1.1 a Revise the article to be read as follows:

"Fixture. The fixture shall be provided for


outdoor wide-beam floodlight with build-in
controlgear (ballast, capacitor, ignitor etc.).
The housing shall be corrosion resistant
aluminum alloy and the reflector shall be
anodized high purity aluminum. The front
glass shall be thermal shock resistant safety
glass with the silicone rubber gasket. All metal
parts shall be made of non-corrosive material.
The fixture shall be jetproof, dustproof and
shall conform to IP55, DrN, VDE, lEe class!."

1001.86 1001 -3 1001-3.18.1.1 b Revise the article to be read as follows:

Paragraph I "Cap and Pin. The cap and pin shall be of such
design that it will not yield or distort under·~e
specified mechanical load in such a manner as
to change the relative spacing of the insulators
or add other stresses to the shells and shall be
made of a good commercial grade of malleable
iron, ductile iron or steel. The insulator caps
shall be of the socket type, provided with
stainless steel cotter key. The cap shall be truly
circular, with the inner and outer surfaces
concentric, and shall be free from cracks,
shrinks, air holes, burrs and rough edges, to
minImIZe field concentrations and radio.
disturbances. The insulator pins shall be free
from cracks and air-holes. All bearing surfaces
shall be smooth and uniform so as to distribute
the loading stresses evenly:'

1001.93 1001-3 1001-3.19.1.2 a Revise the article to be read as follows:

Paragraph 2 "Bus support clamp bolted type shall be


furnished with first melting aluminum aHoy
2024-T4 or 7075-T73 bolts. 6061-T6 or 7075­
T73 nuts, and 7075-T6 or 7075-T73 split
lockwashers and are finished with an anodic
coating and lubricated, or shall be furnished

- 1001.156- (May 2010)


with stainless steel. manufactured of 18-8
materials, bolts, nuts and split lockwashers."

1001.93 1001-3 1001 .19.1.2b Revise the article to be read as follows:

Paragraph 2 "Bolted type connectors shall be furnished with


first melting aluminum alloy 2024-T4 or 7075­
T73 boits, 6061-T6 or 7075-T73 nuts, and
7075-T6 or 7075-T73 split lock washers and are
finished with an anodic coating and lubricated,
or shall be furnished with stainless steel,
manufactured of 18-8 materials, bolts, nuts and
split lockwashers."

Paragraph 4 "All terminal pad drilling holes shall conform to


NEMA-CCI. Contact surface of terminal pad
shall be finished."

Last Paragraph "Flexible element of expansion terminal


connectors shall be laminated aluminum strap or
all aluminum conductors which has current
capacity equivalent to the tube:'

1001.94 1001-3 1001-3.19.1.3 b Revise the article to be read as follows:

Paragraph 1 "Compression Terminal. The compression


terminal shall be tubular and made of first
melting aluminum alloy 1100 or Alcan DIS.
The terminal shall have slip strength of not less
than 30% of ultimate strength of the conductor.
All terminal pads drilling holes shall conform to
NEMA-CCl."
Paragraph 2 "The position of compression shall be clearly
marked on the surface of each connectors.
Contact surface of terminal pad shall be
fi nished."

1001.110 1001-3 100 1-3.23.1.2 i Revise the article to be read as follows:

"Audible Noise. The charger audible noise


shall not exceed 60 dB(A) at any point I m from
the charger cabinet."

1001.111 1001-3 1001-3.23.1.3 a Revise the article to be read as follows.


(c)
"Potentiometers for adjustment of the 110at and
equalize charge voltage levels. The
potentiometers shall permit voltage level
adjustment to within a maximum of 0.01 V pcr

- 1001.157 (May 2010)


battery ce II."

1001.111 1001-3 1001-3.23.1.3 b Revise the article to be read as follows.

'"Instrumentation. Each charger shall be


furnished with the following instruments
mounted on the front of the cabinet:

- Output DC ammeter

- Output DC voltmeter (The change-over


switch to read rectifier voltage, battery voltage
and load voltage individually shall be proviqed
for 48 V DC chargee)"

1001.112 1001-3 1001-3.23.1.3 c Revise the article to be read as follows.

Last Paragraph "Each of the above alarm conditions shall also


cause a common or summary alarm relay to
operate for common remote alarm indication.
The rclay shall be completed with an operating
time delay adjustable from 0 to lOs, auto reset
and two electrically separate NO contacts. The
alarm contacts shall be wired to terminal block
points for connection to remote alarms by
EGAT."

1001.138 1001-4 1001-4.26.2 c Revise the article to be read as follows.

"Quality Conformance Tests. Number of


samples required, for each lot of station post
insulator, for the tests shall be performed in
accordance with ANSI C29.9 except that
specifically noted herein.

(a) Visual and dimension test.

(b) Porosity test.

(e) Galvanizing test.

(d) Cantilever strength test. Number of


samples shall be 0.5 % of the number of
insulators in the lot. If the percentage does not
give a whole number, then the next whole
number above shall be chosen.

(e) Tensile strength test. Number of samples


shall be 0.5 % of the number of insulators in
the lot. If the percentage does not give a

- 1001.158- (May 2010)


whole number, then the next whole number
above shall be chosen.

(f) Creepage distance measurement. One unit


of each rating and type shall be subject to this
test. The test shall be perfonncd on insulators
being supply."

1001.140 1001-4 1001-4.27.4 Add the following sub-clause:

Design Tests. These tests may be omitted if a


design test record can be submitted.

(a) Corona and RIV test (For 500 kV


miscellaneous hardware only).

1001.141 1001-4 1001.4.31 a Delete (c) Temperature rise test

1001.142 1001-4 1001.4.31 b Add (g) Temperature rise test. One unit of each
rating shall be subject to this test. The test shall
be perfonned on battery charger being supply.

1001.152 1001-3 1001-3.16.1.2 a Revise the article to be read as follows.

":I<'ixture. The fixture shall be provided .for


outdoor use with built-in control gear (balhist,
capacitor, ignitor, etc.) and shall be post-top
mounted bottom support with 76 mm fixing
diameter. The canopy and base shall be
corrosion resistant aluminum alloy. The
diffuser shall be made of UV -stabilized clear
poly-carbonate or heat shock resistant clear
glass. All metal parts shall be made of non­
corrosive material. The tixture shall be
weatherprooL dust-protected and shall confonn
to IP54. DIN, VDE. lEe class 1."

- 1001. 159 - (May 2010)

Anda mungkin juga menyukai